important instructions that should be followed during
installation and maintenance of the generator and batteries.
Beforeoperating the generator set (genset), read theOperator’s Manual and become familiar with it and theequipment.Safe and efficient operation can be
achieved only if the equipment is properly operatedand maintained. Many accidents are caused by failure
to follow fundamental rules and precautions.
Thefollowing symbols, found throughout this manual,alert you to potentially dangerous conditions to the op-erator, service personnel, or the equipment.
This symbol warns of immediatehazards which will result in severe personal in-jury or death.
WARNING
This symbol refers to a hazard or un-safepractice which can result in severe per-sonal injury or death.
CAUTION
This symbol refers to a hazard or un-safe practice which can result in personal injuryor product or property damage.
FUEL AND FUMES ARE FLAMMABLE
Fire, explosion, and personal injury or death can resultfrom improper practices.
•DO NOT fill fuel tanks while engine is running, un-
less tanks are outside the engine compartment.Fuelcontact with hot engine or exhaust is a potentialfire hazard.
•DO NOT permit any flame, cigarette, pilot light,
spark, arcing equipment, or other ignition sourcenear the generator set or fuel tank.
•Fuellines must be adequately secured and free of
leaks. Fuel connection at the engine should bemadewith an approved flexible line. Do not use zinccoated or copper fuel lines with diesel fuel.
•Be sure all fuel supplies have a positive shutoff
valve.
• Be sure battery area has been well-ventilated prior
to servicing near it. Lead-acid batteries emit a highly
explosive hydrogen gas that can be ignited by arcing, sparking, smoking, etc.
EXHAUST GASES ARE DEADLY
Provide an adequate exhaust system to properly
•
expel discharged gases away from enclosed orsheltered areas and areas where individuals arelikely to congregate. Visually and audibly inspectthe exhaust daily for leaks per the maintenanceschedule.Make sure that exhaust manifolds are se-curedand not warped. Do not use exhaust gases toheat a compartment.
•Be sure the unit is well ventilated.
•Engine exhaust and some of its constituents are
known to the state of California to cause cancer,birth defects, and other reproductive harm.
MOVING PARTS CAN CAUSE SEVEREPERSONAL INJURY OR DEATH
•Keep your hands, clothing, and jewelry away from
moving parts.
•Before starting work on the generator set, discon-
nect battery charger from its AC source, then dis-connectstarting batteries, negative (−) cable first.This will prevent accidental starting.
•Makesure that fasteners on the generator set are
secure. Tighten supports and clamps, keep guardsin position over fans, drive belts, etc.
•Do not wear loose clothing or jewelry in the vicinity of
movingparts, or while working on electrical equip-ment. Loose clothing and jewelry can becomecaught in moving parts.
•If adjustment must be made while the unit is run-
ning, use extreme caution around hot manifolds,moving parts, etc.
DO NOT OPERATE IN FLAMMABLE ANDEXPLOSIVE ENVIRONMENTS
Flammablevapor can cause an engine to overspeed andbecome difficult to stop, resulting in possible fire, explo-sion,severe personal injury and death. Do not operate agenset where a flammable vapor environment can becreated by fuel spill, leak, etc., unless the genset isequippedwith an automatic safety device to block the air
intake and stop the engine. The owners and operators of
the genset are solely responsible for operating the genset safely. Contact your authorized Cummins Power
Generation distributor for more information.
LS-16L
iii
Page 6
ELECTRICAL SHOCK CAN CAUSE
SEVERE PERSONAL INJURY OR DEATH
• Remove electric power before removing protective
shields or touching electrical equipment. Use rubber insulative mats placed on dry wood platforms
over floors that are metal or concrete when around
electrical equipment. Do not wear damp clothing
(particularly wet shoes) or allow skin surface to bedampwhen handling electrical equipment. Do notwearjewelry. Jewelry can short out electrical con-tacts and cause shock or burning.
•Use extreme caution when working on electrical
components. High voltages can cause injury ordeath. DO NOT tamper with interlocks.
•Follow all applicable state and local electrical
codes.Have all electrical installations performed bya qualified licensed electrician. Tag and lock openswitches to avoid accidental closure.
•DO NOT CONNECT GENERATOR SET DI-
RECTLYTO ANY BUILDING ELECTRICAL SYS-TEM. Hazardous voltages can flow from the gen-eratorset into the utility line. This creates a potentialfor electrocution or property damage. Connect onlythroughan approved isolation switch or an ap-proved paralleling device.
GENERAL SAFETY PRECAUTIONS
•Coolantsunder pressure have a higher boiling point
thanwater. DO NOT open a radiator or heat ex-changer pressure cap while the engine is running.To prevent severe scalding, let engine cool downbeforeremoving coolant pressure cap. Turn capslowly, and donot open it fully until the pressure hasbeen relieved.
•Usedengine oils have been identified by some state
or federal agencies as causing cancer or reproduc-tive toxicity.When checking or changing engine oil,take care not to ingest, breathe the fumes, or con-tact used oil.
•Keep multi-class ABC fire extinguishers handy.
Class A fires involve ordinary combustible materials
such as wood and cloth; Class B fires, combustible
and flammable liquid fuels and gaseous fuels; Class
C fires, live electrical equipment. (ref. NFPA No. 10).
•Make sure that rags or combustible material are not
left on or near the generator set.
•Make sure generator set is mounted in amanner to
prevent combustible materials from accumulatingunder or near the unit.
•Remove all unnecessary grease and oil from the
unit. Accumulated grease and oil can cause over-heatingand engine damage which present a poten-tial fire hazard.
•Keep the generator set and the surrounding area
clean and free from obstructions. Remove any de-bris from the set and keep the floor clean and dry.
•Do not work on this equipment when mentally or
physically fatigued, or after consuming any alcoholor drug that makes the operation of equipment un-safe.
•Substances in exhaust gases have been identified
by some state or federal agencies as causing can-cer or reproductive toxicity. Take care not to breathor ingest or come into contact with exhaust gases.
•Donot store any flammable liquids, such as fuel,
cleaners, oil, etc., near the generator set. A fire orexplosion could result.
•Wear hearing protection when near an operating
generator set.
•To prevent serious burns, avoid contact with hot
metal parts such as radiator system, turbo chargersystem and exhaust system.
KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE
iv
Page 7
1. Introduction
ABOUT THIS MANUAL
This manual provides installation instructions for
the generator set models listed on the front cover.This includes the following information:
Mounting Recommendations- for fasteninggenerator set to base and space requirementsfor normal operation and service.
Mechanical and Electrical Connections -coversmost aspects of the generator set instal-lation.
Prestart− checklist of items or proceduresneeded toprepare generator set for operation.
Initial Startup− test complete system to en-sure proper installation, satisfactory perfor-mance,and safe operation. Refer to OperatorsManual for troubleshooting information.
Installation Checklist− reference checksupon completion of installation.
This manual DOES NOT provide application infor-mationfor selecting a generator set or designing thecompleteinstallation. If it is necessary to design thevarious integrated systems (fuel, exhaust, cooling,etc.), additional information is required. Reviewstandard installation practices. For engineeringdataspecific to the generator set, refer to the Speci-ficationSheet and Data Sheet. For application infor-mation,refer to Application Manual T-030, “LiquidCooledGenerator Sets”. To find this manual online:
1.Go to http://www.cumminspower.com
2.Click on “Application Engineering” under head-ing Technical Information
3.Click on “Liquid Cooled Genset ApplicationManual.
INSTALLATION OVERVIEW
These installation recommendations apply to typical installations with standard model generatorsets. Whenever possible, these recommendationsalso cover factory designed options or modifica-tions.However, because of the many variables inany installation, it is not possible to provide specificrecommendations for every situation. If there areany questions not answered by this manual, contactyour nearest Cummins Power Generation distribu-tor for assistance.
Application and Installation
A power system must be carefully planned and cor-rectly installed for proper operation. This involvestwo essential elements: application and installa-tion.
Application (as it applies to generator set installa-tions) refers to the design of the complete powersystem that usually includes power distributionequipment, transfer switches, ventilation equip-ment, mounting pads, and cooling, exhaust, andfuel systems. Each component must be correctlydesigned sothe complete system will function as in-tended. Application and design is an engineeringfunction generally done by specifying engineers orothertrained specialists. Specifying engineers orother trained specialists are responsible for the de-sign ofthe complete power system and for selectingthe materials and products required.
Installation refers to the actual set-up and assem-bly of the power system. The installers set up andconnect the various components of the system asspecified inthe system design plan. The complexityof the system normally requires the special skills ofqualifiedelectricians, plumbers, sheetmetal work-ers, etc. to complete the various segments of theinstallation. This is necessary so all componentsare assembled using standard methods and prac-tices.
1-1
Page 8
Safety Considerations
The generator set has been carefully designed to
provide safe and efficient service when properly
installed, maintained, and operated. However, the
overall safety and reliability of the complete system
is dependent on many factors outside the control of
the generator set manufacturer. To avoid possible
safety hazards, make all mechanical and electricalconnections to the generator set exactly as speci-fied in this manual. All systems external tothe gen-erator (fuel, exhaust, electrical, etc.) must complywith all applicable codes. Make certain all requiredinspections and tests have been completed and allcode requirements have been satisfied before certi-fying the installation is complete and ready for ser-vice.
Heating Devices for Standby Applications
In accordance with NFPA 110, Cummins PowerGeneration recommends installing standby gener-atorsets (life safety systems) equipped with enginejacket water coolant heaters in locations where theminimum ambient temperature is above 40
(4
°C). NFPA also requires that the engine be
heated as necessary to maintain the water jackettemperature determined by the manufacturer forcold start and load acceptance for the type of sys-tem.
Although Cummins Power Generation generatorsets may start in temperatures below 40when equipped with engine jacket water coolant
°F (4°C)
°F
heaters, it might take more than 10 seconds to
warm the engine before a load can be applied and
may also require other supplemental starting aids.
Refer to engine manual for specific engine requirements.
On generator sets equipped with a graphic display,
the Low Coolant Temperature (Code 1435) mes-sage, inconjunction with illumination of the WarningLED, isprovided to meet the requirements of NFPA
110. The engine cold sensing logic initiates a warn-ing when the engine jacket water coolant tempera-ture falls below 70the ambient temperature falls below 40cold engine may be indicated even though the cool-ant heaters are connected and operating correctly.Under these conditions, although the generator setmaystart, it may not be able to accept load within 10seconds. When this condition occurs, check thecoolant heaters for proper operation. If the coolantheaters are operating properly, other precautionsmay be necessary to warm the engine before apply-ing a load.
°F (21°C). In applications where
°F (4°C), a
Product Modifications
Agency certified products purchased from Cum-mins Power Generation comply only with thosespecific requirements and as noted on companyproductspecification sheets. Subsequent modifica-tions must meet commonly accepted engineeringpracticesand/or local and national codes and stan-dards. Product modifications must be submitted tothe local authority having jurisdiction for approval.
Above 75° F (25° C)32° F (0° C) to 75° F (25° C)Below 32° F (0° C)
Oil Grade
D1703-M-E3 BG
3 Cylinder
40A Alternator
12 Volts DC
One, 12 Volt
G24
350 Amps
SAE 30 or SAE 10W30SAE 20 or SAE 10W30
SAE 10W or SAE 10W30
API CF or better
V2203-M-E3 BG
4 Cylinder
V3300-E3 BG
4 Cylinder
40A Alternator
12 Volts DC
One, 12 Volt
G31
450 Amps
Exhaust
Outlet Size@ Standby:
Maximum Allowable Back Pres-
sure
Exhaust Flow at Rated LoadExhaust Temperature
Fuel Pump
Fuel SupplyFuel ReturnMaximum Fuel Lift
**Fuel Consumption
Standby/Full Load/60Hz GPH
(L/HR)
*Use 50/50 antifreeze (ethylene glycol and water) mixture.
**Refer to generator set Specifications Sheet for other applications.
Normal Oil Pressure
Warning Limit
Shutdown Limit
2 inch NPT
40 in H2O (10
kPa)
99 cfm (2.8
m3/min)
630° F (332° C)
0.95 (3.6)1.37 (5.2)1.93 (7.3)2.43 (9.2)
OIL PRESSURE WARNING AND
SHUTDOWN LIMITS
2 inch NPT
40 in H2O (10
kPa)
126 cfm (3.6
m3/min)
919° F (493° C)
3/8 inch Hose Barb
3/16 inch Hose Barb
31.5 inches (800 mm)
40-70 psi (276-483 kPa)
20 psi (138 kPa)
15 psi (103 kPa)
40 in H2O (10
174 cfm (4.9
970° F (521° C)
2 inch NPT
kPa)
m3/min)
2 inch NPT
40 in H2O (10
kPa)
219 cfm (6.2
m3/min)
735° F (391° C)
2-1
Page 10
THIS PAGE LEFT INTENTIONALLY BLANK
2-2
Page 11
3. Mounting the Generator Set
GENERAL
Generator set installations must be engineered so
the generator set will function properly under the ex-pectedload conditions. Use these instructions as ageneral guide only. Follow the instructions of theconsulting engineer when locating or installing anycomponents. The complete installation must com-ply with all local and state building codes, fire ordi-nances, and other applicable regulations. A typicalgenerator set installation is shown in Figure 3-1.
Requirements tobe considered prior to installation:
•Level mounting surface
•Adequate cooling air
•Adequate fresh induction air
•Discharge of generator set air
•Non-combustible mounting surface
• Discharge of exhaust gases
• Electrical connections
•Accessibility for operation and servicing
•Noise levels
•Vibration isolation
LOCATION
Generatorset location is decided mainly by relatedsystems such as ventilation, wiring, fuel, and ex-haust. The set should be located as near as pos-sible to the main power service entrance. Exhaustmust not be able to enter or accumulate around in-habited areas.
Provide alocation away from extreme ambient tem-peratures and protect the generator set from ad-verse weather conditions. An optional housing isavailable for outdoor operation.
WARNING
INCORRECT INSTALLATION, SERVICE OR PARTS REPLACEMENT CAN RESULTIN SEVEREPERSONAL INJURY,DEATH, AND/OR EQUIPMENT DAMAGE. SERVICE PERSONNEL MUSTBE TRAINED AND EXPERIENCED TO PERFORM ELECTRICAL AND MECHANICAL COM-PONENT INSTALLATION.
IMPORTANT
DEPENDING ONYOUR LOCATION AND INTENDED USE, FEDERAL, STATE OR LOCAL LAWSAND REGULATIONS MAY REQUIRE YOU TO OBTAIN AN AIR QUALITY EMISSIONS PERMITBEFORE BEGINNING INSTALLATION OF YOUR GENSET. BE SURE TO CONSULT LOCALPOLLUTION CONTROL OR AIR QUALITY AUTHORITIES BEFORE COMPLETING YOURCONSTRUCTION PLANS.
3-1
Page 12
SWEEPING
ELBOW
MUFFLER
THIMBLE
AC POWER WIRING
DC
CONTROL
WIRING
FLEXIBLE SECTION
AIR OUT
AIR
IN
FLEXIBLE
BELLOWS
COOLING
AIR
IN
CONCRETE
IMPORTANT!
COOLING AIR INLET MUST BE AT LEAST 1-1/2 TIMES LARGER
THAN RADIATOR DUCT OUTLET AREA ON RADIATOR-COOLED
MODELS.
FLOW OF COOLING AIR AND HEATED AIR MAY BE
CONTROLLED BY AUTOMATICALLY OPERATED LOUVRES.
FIGURE 3-1. TYPICAL GENERATOR SET (WITH RADIATOR) INSTALLATION
3-2
BASE
Page 13
MOUNTING
Generator sets are mounted on a steel skid that provides proper support. The engine-generator assembly is isolated from the skid frame by rubber
mounts that provide adequate vibration isolation for
normal installations. Where required by building
codes or special isolation needs, generator sets
may be mounted on rubber pads or mechanicalspring isolators. The use of unapproved isolatorsmay result in harmful resonances and may void thegenset warranty.
Mountthe generator set on a substantial and levelbase such as a concrete pad. A non-combustiblematerial must be used for the pad.
Use 5/8 inch or 16 mm anchored mounting bolts tosecure the vibration isolators to the base. Securethe vibration isolators to the skid using a flat washerand hexagonal nut for each bolt (see Figure 3-2).The 1-1/2 x 6 inch pipe inserted over the mountingbolts allows minor adjustment of the bolts to alignthem to the holes in the subbase or vibration isola-tor.
Locate the isolators as shown on the generator setOutline Drawing referenced in the Data Sheet.
MOUNTING
BASE
MOUNTING
BOLT
SUBBASE OR
VIBRATION
ISOLATOR
FLANGE
HEX NUT
FLAT WASHER
1-1/2 x 6 INCH
PIPE
12 IN.
(305 mm)
CONCRETE
ACCESS TOSET
Generally, at least 1 meter (3 feet) of clearanceshould beprovided on all sides of the generator setfor maintenance and service access. (Increaseclearance by width of door if optional housing isused.) A raised foundation or slab of 150 mm (6inches)or more above floor level will make servic-ing easier.
Lighting should be adequate for operation, mainte-nance and service operations and should be con-nected onthe load side of the transfer switch so thatit is available at all times.
FIGURE 3-2. BOLT DIAGRAM
3-3
Page 14
VIBRATION ISOLATORS
Installation and Adjustment Procedure
1. Place the vibration isolators (Figure 3-3) on the
genset support structure. The isolators should
be shimmed or grouted to ensure that all of the
isolator bases are within 0.25 inch (6 mm)
elevation of each other. The surface that theisolatorbases rest on must also be flat and lev-el.
2.Loosen the side snubber lock nuts so that thetop plate of the isolator is free to move verticallyand horizontally. Be sure that the top plate iscorrectly aligned with the base and springs.
3.Place the genset onto the isolators while align-ing the skid’s mounting with the threaded isola-tor hole. The top plates will move down and ap-proach the base of the isolator as load is ap-plied.
4.Once the genset is in position, the isolatorsmay require adjusting so that the set is level.
The isolators are adjusted by inserting the leveling bolt through the skid and into the isolator
(the leveling bolt’s locking nut should be
threaded up towards the bolt head).
The leveling bolt will adjust the clearance between the top plate and the isolator base. A
nominal clearance of 0.25 inch (6 mm) or greater is desired. This will provide sufficient clear-ance for the rocking that occurs during startupand shutdown. If the 0.25 inch (6 mm) clear-ance is not present, turn the leveling bolt untilthe desired clearance is achieved.
5.The genset may not be level yet; therefore, ad-just the leveling bolts until the set is level andsufficientclearance still remains. (Clearanceon all isolators should be roughly equal). Onceall isolators have been set, lock the leveling boltin place with the lock nut.
6.The snubber nuts may remain loose and there-fore provide better isolation between the gen-set and support structure.
GENSET SKID
LEVELING BOLT
LOCK NUT
CLEARANCE
SNUBBER
BASE
FIGURE 3-3. VIBRATION ISOLATORS
3-4
Page 15
4. Mechanical Connections
GENERAL
The generator set mechanical system installationincludes connecting the fuel, exhaust, ventilationand cooling systems. Before starting any type offuel installation, all pertinent state and local codesmust be complied with and the installation must beinspected before the unit is put in service.
FUEL SYSTEM
Engines used on these generator sets normally useASTM No. 2 Diesel fuel. They will, however,operateon alternate diesel fuels within the specificationsshown in the engine manual.
In all fuel system installations, cleanliness is of theupmost importance. Make every effort to prevententrance of moisture, dirt or contaminants of anykind into the fuel system. Clean all fuel system com-ponents before installing.
A fuel filter/strainer/water separator of 100-120 meshor equivalent (approximately 150 microns nominal)must be fitted between either the main tank and daytank or between the main tank and the engine.
Use only compatible metal fuel lines to avoid elec-trolysis when fuel lines must be buried. Buried fuellines must be protected from corrosion.
CAUTION
lines, fittings or fuel tanks. Condensation in the
tank and lines combines with the sulfur in diesel
fuel to produce sulfuric acid. The molecularstructure of the copper or galvanized lines ortanksreacts with the acid and contaminates thefuel.
An electric solenoid valve in the supply line is rec-ommendedfor all installations and required for in-door automatic or remote starting installations.Connectthe solenoid wires to the genset “SwitchedB+” circuit to open the valve during generator setoperation.
Separate fuel return lines to the day tank or supplytankmust be provided for each generator set in amultiple-setinstallation to prevent the return lines ofidle sets from being pressurized. Fuel return linesmust not contain a shutoff device. Engine damagewilloccur if the engine is run with the return fuel linesblocked or restricted.
CAUTION
return line(s). If fuel return line(s) is blocked orexceeds fuel restriction limit, engine damagewill occur.
FuelReturn Restriction (or Pressure) Limit: Fuelreturn drain restriction (consisting of friction headand static head) between the engine injector returnline connection and the fuel tank must not exceedthe limit stated in the model-specific genset Specifi-cation Sheet.
Never use galvanized or copper fuel
Never install shutoff device in fuel
4-1
Page 16
Fuel Lines − Routing
A flexible fuel hose(s) or section of flexible fuel
hose(s) must be used between the engine’s fuel
system and fuel supply and return line(s) to protect
the fuel system from damage caused by vibration,
expansion and contraction. Flexible lines for connecting between the engine and the stationary fuel
lines are supplied as standard equipment.
WARNING
hazardswhich can result in severe personal in-jury or death. Always use flexible tubing be-tween engine and fuel supply to avoid line fail-ure and leaks due to vibration. The fuel systemmust meet all applicable codes.
Installation ofthe fuel hose must be done accordingto all applicable codes and standards, and installa-
Fuel leaks create fire and explosion
tion recommendations provided by the manufacturer. The supplied flexible hose is approved by the
hose manufacture for use with the genset fuel type
and product application.
Support fuel lines to restrain movement and prevent
chaffing or contact with sharp edges, electrical wiring and hot exhaust parts.
WARNING
Sparks and hot surfaces can ignitefuel,leading to severe personal injury or death.Do not route fuel lines near electrical wiring orhot exhaust parts.
Fuel lines must be routed and secured to maintain a1/2 inch (12.7 mm) minimum clearance from electri-cal wiring and a 2 inch (51 mm) minimum clearancefrom hot exhaust parts.
Engine Fuel Connections
Identification tags are attached to the fuel supplyline and fuel return line connections.
Supply Tank
Locatethe fuel tank as close as possible to the gen-erator set and within the restriction limitations of thefuel pump.
Install afuel tank that has sufficient capacity to sup-ply the genset operating continuously at full ratedload for the planned period of operation or poweroutage. Refer to Specification Sheet for fuel con-sumption data.
If the fuel inlet restriction exceeds the defined limitdue to the distance/customer-supplied plumbingbetween the genset and the main fuel tank, a trans-fer tank (sometimes referred to as a day tank) andauxiliary pump will also be required. If an overhead
main fuel tank is installed, a transfer tank and floatvalve will be required to prevent fuel head pres-suresfrom being placed on the fuel system compo-nents.
For critical start applications, where generator setsare paralleled or must satisfy emergency start-timerequirements, it is recommended that a fuel tank orreservoirbe located such that the lowest possiblefuel level is not less than 6 inches (150 mm) abovethe fuel pump inlet. This will prevent air from accu-mulating in the fuel line while the set is in not run-ning, eliminating the period during startup when ithas to be purged.
Fuel Inlet Pressure/Restriction Limit: Engine
performance and fuel system durability will be com-promised ifthe fuel inlet pressure or restriction limitsare not adhered to. Fuel inlet pressure or restrictionmustnot exceed the limits stated in the model-spe-cific genset Specification Sheet.
4-2
Page 17
Day Tank (If Used)
Fuel day tanks are used when fuel inlet restriction
limits can not be met, or the supply tank is overhead
and presents problems of high fuel head pressure
for the fuel inlet and return lines.
Supply Tank Lower Than Engine: With this installation, the day tank is installed near the generatorset, below the fuel injection system and within thefuel inlet restriction limit. Install a fuel transfer pump,to pump fuel from the supply tank to the day tank. Afloat switch in the day tank controls operation of thefuel transfer pump.
Whenusing a fuel transfer pump, the supply tank topmust bebelow the day tank top to prevent siphoningfrom the fuel supply to the day tank.
Provide a return line from the engine injection sys-tem return connection to the day tank. Plumb the re-turn line to the bottom of day tank as shown in Fig-
ure 4-1. Provide a day tank overflow line to the supply tank in case the float switch fails to shut off the
fuel transfer pump.
WARNING
Spilled fuel presents the hazard of
fire or explosion which can result in severe personal injury or death. Provide an overflow line
to the supply tank from the day tank.
Supply Tank Higher Than Engine: With this
installation, the day tank is installednear the gener-ator set, below the fuel injection system and withinthe fuel inlet restriction limit. Include an automaticfuel shutoff valve in the fuel line between the fuelsupply tank and the day tank to stop fuel flow whenthe generator set is off.
Provide a return line from the engine injection sys-tem return connection to the day tank. Plumb the re-turn line to the bottom of day tank as shown in Fig-ure 4-1.
WARNING
Spilled fuel can create environmental hazards. Check local requirements for containment
and prevention of draining to sewer and ground water.
ENGINE
FUEL
PUMP
DAY TANK
FUEL TRANSFERPUMP ELECTRIC
MOTOR DRIVEN
VENTEDFILL CAP
SHUTOFF
VALVE
1 INCH
BAFFLE
FLOAT
SWITCH
120 MESH FUEL
STRAINER
INJECTOR FUEL
RETURN LINE
CONNECT TO
AC OUTPUT
SUPPLY
LINE
FUEL TANK
All models require a fuel returnline from injectors to tank.
VENT LINE
FILL PIPE
LARGER OVER-
FLOW LINE
FIGURE 4-1. TYPICAL FUEL SUPPLY INSTALLATION
4-3
Page 18
EXHAUST SYSTEM
Pipe exhaust gases to the outside of any enclosure.
Locate the exhaust outlets away from any air inlets
to avoid gases re-entering the enclosure. Exhaust
installations are subject to various detrimental conditions such as extreme heat, infrequent operation
and light loads. Regularly inspect the exhaust system both visually and audibly to see that the entiresystem remains fume tight and safe for operation.
WARNING
sult in severe personal injury or death. Use ex-treme care during installation to provide a tightexhaustsystem. Terminate exhaust pipe awayfrom enclosed or sheltered areas, windows,doors and vents.
For indoor installation, the exhaust system mustuse sealed joint type fittings, (for example NPT fit-tings)to provide a tight exhaust system. Use of sliptype fittings (secured with a muffler clamp) may al-low leakage of exhaust gases into the building.
WARNING
sult in severe personal injury or death. Use ex-treme care during installation to provide a tightexhaustsystem. Use NPT or equivalent type fit-tings for all indoor installations.
Use an approved thimble (Figure 4-2) where ex-haust pipes pass through wall or partitions. Insu-lated wall/roof thimbles are used where exhaustpipes pass through a combustible roof or wall. Thisincludes structures, such as wood framing or insu-lated steel decking, etc. Uninsulated wall/roofthimbles are used where exhaust pipes passthrough a non-combustible wall or roof, such asconcrete. Refer to NFPA 37, Section 6-3. “Station-ary Combustion Engines and Gas Turbines” for ac-
Inhalation of exhaust gases can re-
Inhalation of exhaust gases can re-
cepted design practices. Build according to the
code requirements in effect at the installation site.
WARNING
Hot exhaust pipes can start a fire
and cause severe injury or death if improperly
routed through walls. Use an approved thimble
where exhaust pipes pass through walls or
partitions.
WARNING
Inhalation of exhaust gases can re-sult in severe personal injury or death. Do notuse exhaust heat to warm a room, compartmentor storage area.
Raincaps are available for the discharge end of ver-tical exhaust pipes. The rain cap clamps onto theend of the pipe and opens due to exhaust dischargeforce from the generator set. When the generatorset is stopped, the rain cap automatically closes,protectingthe exhaust system from rain, snow, etc.
Use a section of flexible exhaust pipe between theengine and remainder of exhaust system. Supportexhaust system to prevent weight from being ap-plied to engine exhaust outlet.
CAUTION
Weight applied to the engine man-ifold can result in damage. Support the mufflerand exhaust piping so no weight or stress is ap-plied to engine exhaust elbow.
The exhaust system design should meet local coderequirements.
Liability for injury, death, damage, and warranty ex-pense due to use of unapproved mufflers or modifi-cations to the exhaust system becomes the respon-sibility of the person installing the unapproved muf-fler or performing the modification. Contact a Cum-mins Power Generation distributor for approved ex-haust system parts.
4-4
Page 19
Avoid sharp bends by using sweeping, long radius
elbows and provide adequate support for muffler
and tailpipe. Pitch a horizontal run of exhaust pipe
DOWNWARD (away from engine) to allow any
moisture condensation to drain away from the engine. If an exhaust pipe must be turned upward,
install a condensation trap at the point where the
rise begins (Figure 4-3).
Shield or insulate exhaust lines if there is danger ofpersonal contact. Allow at least 12 inches (305 mm)of clearance if the pipes pass close to a combustiblewall or partition. Before installing insulation on ex-haust system components, check the exhaust sys-tem for leaks while operating the genset under fullload and correct all leaks.
RAIN CAP
9 INCH
(230 mm)
VERTICAL
DRIP CAP
HOLES IN
END OF INNER
SLEEVE
ROOF
9 INCH
(230 mm)
WARNING
Exhaust pipes are very hot and theycan cause severe personal injury or death fromdirect contact or from fire hazard. Shield or in-sulateexhaust pipes if there is danger of per-sonal contact or when routed through walls ornear other combustible materials.
HORIZONTAL
WALL OR PARTITION
FIGURE 4-2. MOUNTING EXHAUST THIMBLE
IF EXHAUST LINE MUST BE
PITCHED UPWARD, CONSTRUCT
A TRAP AT POINT OF RISE
4-5
AVOIDSHARPBENDS
DRAIN CONDENSATION
TRAP PERIODICALLY
FIGURE 4-3. CONDENSATION TRAP
Page 20
VENTILATION AND COOLING
Generator sets create considerable heat that must
be removed by proper ventilation. Outdoor installations normally rely on natural air circulation but indoor installations need properly sized and positioned vents for required airflow.
Vents and Ducts
For indoor installations, locate vents so incoming airpasses through the immediate area of the installa-tion before exhausting. Install the air outlet higherthan the air inlet to allow for convection air move-ment.
Size the vents and ducts so they are large enough toallowthe required flow rate of air. The ”free area” ofducts must be as large as the exposed area of theradiator.Refer to the genset Specification Sheet forthe airflow requirements and allowed airflow restric-tion.
Wind will restrict free airflow if it blows directly intothe air outlet vent. Locate the outlet vent so the ef-fects of wind are eliminated, or if outlet vent cannotbe located as mentioned, install wind barrier.SeeFigure 4-4.
PREVAILING WINDSPREVAILING WINDS
WIND
BARRIER
FIGURE 4-4. WIND BARRIER
4-6
Page 21
Dampers
Dampers or louvres protect the generator set and
equipment room from the outside environment.
Their operation of opening and closing should be
controlled by operation of the generator set.
In cold climates, the radiator exhaust air can be recirculated to modulate the ambient air temperaturein the generator set room. This will help the genera-tor set warm up faster, and help to keep fuel temper-atures higher than the cloud point of the fuel. If recir-culation dampers are used, they should be de-signed to“fail closed”, with the main exhaust damp-ers open, so that the generator set can continue tooperatewhen required. Designers should be awarethat the generator set room operating temperaturewill be very close to the outdoor temperature, andeither not route water piping through the generatorset room, or protect it from freezing.
Radiator Set Requirements
Louvers and screens over air inlet and outlet open-ings restrict air flow and vary widely in performance.
A louver assembly with narrow vanes, for example,
tends to be more restrictive than one with wide
vanes. The effective open area specified by the louver or screen manufacturer should be used.
Radiator set cooling air is drawn past the control
end of the set by a pusher fan that blows air through
the radiator. Locate the air inlet to the rear of the set.Make the inlet vent opening 1-1/2 times larger thanthe radiator area.
Locatethe cooling air outlet directly in front of the ra-diatorand as close as possible. The outlet openingmust be at least as large as the radiator area.Lengthand shape of the air outlet duct should offerminimum restriction to airflow.
Attach acanvas or sheet metal duct to the air outletopening using screws and nuts so duct can be re-moved for maintenance purposes. The duct pre-vents recirculation of heated air. Before installingthe duct, remove the radiator core guard.
ENGINE-DRIVEN
FAN
DAMPER
COOL
AIR
INLET
AIR
RADIATOR
THERMOSTATICALLY
CONTROLLED
RECIRCULATING DAMPER
FLEXIBLE
DUCT
CONNECTOR
OUTLET AIR
DAMPER
WIND/
NOISE
BARRIER
HOT
AIR
D
DISTANCE SHOULD
NOT BE LESS THAN
HEIGHT OF RADIATOR
FIGURE 4-5. TYPICAL RADIATOR SET INSTALLATION
4-7
Page 22
THIS PAGE LEFT INTENTIONALLY BLANK
4-8
Page 23
5. DC Control Wiring
CONTROL WIRING
The generator set control box contains connection
points for remote control and monitor options.These connection points are located inside of thecontrol box (Figure 5-1).
Use flexible conduit for all wiring connections to thegenerator set.
CAUTION
for all customer connections to the control pan-el.Solid copper wire may break due to gensetvibration.
Stranded copper wire must be used
K11
K10
TB10
WARNING
HAZARDOUS VOLTAGE Touching
uninsulated high voltage parts inside the control box can result in severe personal injury or
death. Control wire installation must be donewith care to avoid touching uninsulated liveparts.
Stand on a clean dry wooden platform or cleanrubber insulating mat, make sure your clothingand shoes are dry,remove jewelry and use toolswith insulated handles.
BASE
BOARD
CUSTOMER WIRING
FIGURE 5-1. CONTROL BOX
TB1
ACCESS HOLE
5-1
Page 24
TB1 REMOTE MONITOR/CONTROL
CONNECTIONS
Customer monitor/control connections are attached to terminal block TB1 (Figure 5-1). Optional
equipment, such as sensing devices used to monitor genset operation, remote start/stop switches,
etc. are attached to TB1. Refer to Customer Connections diagram in Section 9.
TB1 Wiring
CAUTION
a separate metal conduit from AC power cablesto avoid inducing currents that could causeproblems within the control.
Digital Connections: Connection points, otherthan relayed outputs and network are considereddigital connections to terminal strip TB1. The type/gauge wire to use for these connections are:
Always run control circuit wiring in
•Less than 1000 feet (305m), use 20 gauge
stranded copper wire.
•1000 to2000 feet (305 to 610m), use 18 gauge
stranded copper wire.
Relay Connections: Due to the wide variety of de-vices that can be attached to the relay outputs ofTB1, the electrical contractor must determine thegauge of the stranded copper wire that is used atthis installation site.
TB1 Customer Inputs
Refer to Page 9-1 for typical connections to TB1.
RemoteStart: When the control is in Auto/Remotemode, grounding this input initiates the enginecranking and start sequence. This circuit must beopened to permit resetting a shutdown conditionwith the Reset input. (The remote stop is actuallythe removal of the remote start signal to the control.)
Remote Emergency Stop: Opening this inputcauses an immediate shutdown. Emergency stopmust be reset at the front panel.
Customer Fault Inputs 1 and 2: Grounding anyone of these inputs activates the correspondingwarning or shutdown sequence.
External sensing equipment must be connected to
the designated digital input.
The nature of the fault is an optional customer
selection. Example inputs: Low Coolant Level, Low
Fuel Level, Ground Fault, etc.
Each of the two fault functions can be programmed
as follows:
• Status, Warning or Shutdown. Default = Warning.
•Enter a brief description of the event (up to 32characters).
The InPower service tool or access to the Setup Sub-menus is required to modify the customer fault in-puts. Contact an authorized service center for assis-tance.
TB1 Customer Outputs
Refer to Page 9-1 for typical connections to TB1.
Customer Outputs 1 and 2: One set of normallyopen (NO) contacts, rated for 2 amps at 30 VDC foreach of the two output signals. The relays can beused to control small devices and indicator lamps.
The nature of the customer output signal (contactsclosed) is an optional customer selection. Exampleoutputs:Genset running (event), common warning,commonshutdown, etc. (Refer to Operator’s manu-al for warning and shutdown code listing and theService manual for event code listing.)
Each relay can be independently programmed toenergize byentering a code number (0 through 255,default = 0) for the desired event.
The InPower service tool or access to the Setup Sub-menus is required to modify the customer outputs.Contact anauthorized service center for assistance.
Ready ToLoad: Operates when the generator sethas reached 90% of rated speed and voltage andlatches until generator set is switched to off mode(B+ signal output).
SWITCHED B+
Switched B+ is fused at 15 amps. Wiring is thesame as Relay Connection description.
Switched B+ quick connect terminal is located on
the right side of the engine (facing the control) near
the flywheel housing. Wire color is Red/Orange
stripe.
5-2
Page 25
I/O MODULE
The optional I/O module(s) provides additional customer inputs and outputs for control and monitoring
of the power system. Up to sixteen relay outputs
and twelve discrete analog inputs are available
when the control contains both the Base I/O Module
(AUX101) and the Expansion I/O Module(AUX102).
RUN RELAYS (K10, K11)
The optional run relays (Figure 5-1 and Figure 5-2)
are mounted inside the control box. The singlepole, double-throw run relays are used to control
auxiliary equipment such as fans, pumps and motorized air dampers. The run relays are energized
when the generator set control receives a start signal.
The contacts are rated:
Refer toInstruction Sheet C693 for I/O module con-figuration/wiring information.
K10
TB1
K11
BASE
BOARD
•20 amps resistive @ 30VDC
•15 amps inductive @ 30VDC
TB10
CUSTOMER
CONNECTIONS
FIGURE 5-2. OPTIONAL RUN RELAYS (K10, K11)
5-3
Page 26
THIS PAGE LEFT INTENTIONALLY BLANK
5-4
Page 27
6. AC Electrical Connections
GENERAL
This section provides the procedure that is used to
connect the AC electrical system of the genset.
Beforemaking any AC electrical connections, makecertain the generator set cannot be accidentallystarted. Place the control panel run switch in theOFF position. Turn off or remove AC power from thebattery charger and then remove the negative (−)battery cable from the set starting battery.
WARNING
can cause severe personal injury or death. Arc-ing at battery terminals, light switch or otherequipment,flame, pilot lights and sparks can ig-nite battery gas. Do not smoke, or switchtroublelight ON or OFF near battery. Dischargestatic electricity from body before touching bat-teries by first touching a grounded metal sur-face.
Ventilatebattery area before working on or nearbattery—Wear goggles—Stop genset and dis-connect charger before disconnecting batterycables—Disconnectnegative (−) cable first andreconnect last.
CAUTION
source before disconnecting battery cables.Otherwise, disconnecting cables can result involtage spikes damaging to DC control circuitsof the set.
WARNING
set can cause severe personal injury or death.Prevent accidental starting by disconnectingthe negative (−) cable from the battery terminal.
Ignition of explosive battery gases
Disconnect battery charger from AC
Accidental starting of the generator
WARNING
this section should be done only by persons
trained and experienced in electrical maintenance.Improper procedures may result in prop-erty damage, bodily injury or death.
Connecting the genset AC electrical system in-volves:
Each of the operations described in
•Installation of transfer switch
•Generator output voltage selection
•Load cable connection
•Standard and optional AC equipment connec-
tions (e.g., control box heater, coolant heater,etc.).
Local regulations often require that wiring connec-tions bemade by a licensed electrician, and that theinstallation be inspected and approved before op-eration.All connections, wire sizes, materials used,etc. must conform to the requirements of electricalcodes in effect at the installation site.
WARNING
electrical hazard, resulting in severe personalinjury or death and/or property and equipmentdamage.
Beforestarting the genset, check to make sure thatall electrical connections are secure, and that allwiring iscomplete. Replace and secure any accesspanels that have been removed during installation.Check that the load cables from the genset areproperly connected.
WARNING
cause electrocution or property damage. Do notconnect to any building electrical system ex-cept through an approved device and afterbuilding main switch is opened.
Improper wiring can cause a fire or
Backfeed to utility system can
6-1
Page 28
TRANSFER SWITCH
If the installation is for standby service, a transfer
switch must be used for switching the load from the
normal power source to the genset (see Figure 6-1).
Follow the installation instructions provided with the
transfer switch when connecting the load and control wiring.
LOAD
NORMAL
SOURCE
FIGURE 6-1. TYPICAL LOAD TRANSFER FUNCTION
GENSET
6-2
Page 29
AC WIRING
Generator Voltage Connections
The available generator output voltages and maximum current ratings are specified on the generator
set nameplate. Line-to-neutral voltage is always the
lower voltage shown and line-to-line voltage is the
higher rating.
CAUTION
lower voltages can reduce generator set ratings, and also increase line current, rendering
line circuit breakers too small. Consult with
your distributor before performing reconnection for a different voltage.
Reconfiguring generator sets to
Load Connections
These generators can be configured to the name-plate voltages as shown on the Reconnection Dia-gramlocated on the side access cover of the poweroutput box. Many of the voltages listed will requirereconfiguration ofthe generator output leads on theconnection terminal block. This reconfigurationmust only be done by service personnel that aretrainedand experienced to perform electrical instal-lation. The generator set was adjusted to produce aspecified voltage during production verification test-ing prior to shipment. The installer must alwayscheck the stator lead terminal block connectionsand perform any necessary reconnect to obtain thevoltage required.
Some generator sets are capable of producing awiderange of voltages and connection configura-tions, others have specific limited capabilities. Re-fer to wiring diagram and generator voltages (fromthe nameplate) when reviewing the voltage connec-tion information and use the wiring diagram sup-pliedwith your generator set when actually perform-ing load connections.
CAUTION
highervoltages can exceed the voltage capabil-ity of the specific generator windings and dam-age the generator and also decrease line cur-rent, rendering line circuit breakers too large.Consultwith your distributor before performingreconnection for a different voltage.
Reconfiguring generator sets to
Load wires are brought into the stub-up space in thelower left corner of the power output box (Figure6-2).
Flexible conduit and stranded conductors must beused for connections to take up movement of thegenerator set.
All loads are connected to the generator by boltingstranded load wires to the appropriate terminals onthe generator reconnection terminal block or circuitbreaker lugs.
Load Balancing
When connecting loads to the generator set, bal-ance the loads so the current flow from each line ter-minal (L1, L2 and L3) is about the same. This is es-pecially important if both single phase and threephase loads are connected. Any combination ofsingle phase and three phase loading can be usedas long as each line current is about the same, with-in 10 percent of median value and no line current ex-ceeds the nameplate rating of the generator. Afterall load wires are connected, check the current flowfrom each line, by observing the control panel am-meter. Ifthe control panel does not contain a graphi-cal display, use of a multimeter will be required tocheck current flow.
6-3
Page 30
Current Transformers
The current transformers (CT’s) are used to display/
monitor genset load in kVA and alternator amperage. The CT’s must be installed as noted in the following CT Installation Requirements.
Refer to the Reconnection Diagram to identify thegenerator output leads/phase that must be routedthrougheach CT, and also appropriate transformerpost selection for control sensing leads. The trans-formers are labeled CT1, CT2 and CT3 on the re-connectionwiring diagram. (The Reconnection Dia-gram is located on the power output box cover.)
CT Installation Requirements:
A. The CT has a dot on one side. This dot must be
facing toward the generator (conventional current flowing into the dot). A dot is also used to
indicate pin 1 of the CT.
B. CT1 − U load leads (A phase),
CT2 − V load leads (B phase)
CT3 − W load leads (C phase)
C.Route the appropriate generator output lead
through each CT.
D.The CT’s have dual secondaries (3 pins). The
CT secondary wire marked 1 is connected topin 1 of the CT. CT secondary wire marked 2/3is connected to pin 2 for above 300 VAC gen-sets or topin 3 for below 300 VACgensets. (Re-fer to Reconnection Diagram.)
6-4
Page 31
GENERATOR
LEAD ENTRANCE
CURRENT TRANSFORMERS CT1,
CT2 AND CT3 (WHEN PROVIDED)
THE POLARITY DOTS MUST BE
TOWARDS ALTERNATOR.
LINE CIRCUIT
BREAKERS (WHEN
PROVIDED)
TERMINALS FOR CONNECTING
GENERATOR LEADS ON
OPTIONAL CIRCUIT BREAKER
120-240 VAC TERMINALSFOR GENERATOR HEATER(CONNECTED TO NORMAL
SOURCE)
THESE TERMINALS ARE
LIVE WHEN THE SET IS NOT
RUNNING—DISCONNECT
POWER BEFORE REMOVING
AC OUTPUT BOX COVER.
LOAD WIRING
STUB-UP SPACE
GENSET
GROUNDING
LUG
FIGURE 6-2. POWER OUTPUT BOX
AC CONTROL
WIRING HARNESS
TERMINAL BLOCKS
6-5
LOAD TERMINALS
ON OPTIONAL
CIRCUIT BREAKER
Page 32
Grounding
The following is a brief description of system and
equipment grounding of permanently installed AC
generators within a facility wiring system. It is important to follow the requirements of the local electrical
code.
Figure 6-3 illustrates typical system grounding for a3-pole and a 4-pole automatic transfer switch(ATS). In the 3-pole ATS, note that the generatorneutral isconnected to the ATS and is NOT bondedtoground at the generator. In the 4-pole ATS sys-tem, a grounding electrode conductor and a bond-ing jumper are used to connect the generator neu-tral to ground.
Make sure the genset is grounded to earth in one
location only. Use the ground lug provided in the
power output box.
WARNING
Electric current can cause severe
personal injury or death. Bonding and grounding must be done properly. All metallic parts
that could become energized under abnormalconditions must be properly grounded.
Typical requirements for bonding and groundingare given in the National Electrical Code, Article
250. All connections, wire sizes, etc. must conformto the requirements of the electrical codes in effectat the installation site.
SERVICE ENTRANCE
THREE-PHASE, FOUR-WIRE UTILITY, THREE-POLE ATS
SERVICE ENTRANCE
GENERATOR SET
3-POLE ATS
LOAD
GENERATOR SET
4-POLE ATS
LOAD
THREE-PHASE, FOUR-WIRE UTILITY, FOUR-POLE ATS
FIGURE 6-3. TYPICAL SYSTEM GROUNDING ONE-LINE DIAGRAMS
6-6
Page 33
CONTROL HEATER (OPTIONAL)
A control heater (Figure 6-4) provides a means of
humidity / temperature control of the control box interior. It protects the components when the genera-
120V OR
240V PLUG
tor set is subjected to varying ambient air conditions
during extended periods of non-use.
The heater is equipped with a power cord that terminates with a 120V or 240V NEMA plug.
HEATER
BOTTOM VIEW OF
CONTROL BOX
FIGURE 6-4. OPTIONAL CONTROL HEATER
6-7
Page 34
COOLANT HEATER (OPTIONAL)
A coolant heater keeps engine coolant warm when
the engine is shut down. It heats and circulates the
coolant within the engine. This reduces startup time
and lessens engine wear caused by cold starts. It is
electrically operated and thermostatically controlled.
OUTLET
TUBE
CAUTION
The coolant heater must not be operated while the cooling system is empty or
damage to the heater will occur.
Figure 6-5 shows a typical coolant heater installation. Connect the heater to a source of power that
will be on during the time the engine is not running.
Be sure the supply voltage and circuit amperage is
correct for the heater element rating.
COOLANT
HEATER
INLETTUBE
POWER
PLUG
FIGURE 6-5. TYPICAL COOLANT HEATER
6-8
Page 35
GENERATOR HEATER (OPTIONAL)
A generator heater(s) is used to help keep the generator free of condensation when the generator set
is not running. During cool and humid conditions,
condensation can form within a generator, creating
flashing and shock hazards.
The generator heater is connected as shown in Figure 6-6. Terminal strip is located inside of power output box (Figure 6-2). Connect 120 or 240 volt AC
power to this terminal strip from an outside source
so heater is on when genset is not running.
WARNING
Water or moisture inside a generator increases the possibility of flashing andelectrical shock, which can cause equipmentdamageand severe personal injury or death. Donot use a generator which is not dry inside andout.
GENERATOR HEATER
(VIEW AA)
LEADS FROM
GENERATOR HEATER
CONNECTION FOR 120VCONNECTION FOR 240V
CUSTOMER SUPPLIED
POWER LEADS
FIGURE 6-6. TYPICAL GENERATOR HEATER INSTALLATION
6-9
Page 36
THIS PAGE LEFT INTENTIONALLY BLANK
6-10
Page 37
7. Prestart Preparation
GENERAL
Before attempting the initial start of the generator
set, besure to complete the Installation Checklist inSection 8.
INPOWER SERVICE TOOL GENERAL
INFORMATION
InPower is a PC based service tool for the Power-Command
•Makeadjustments to the controls trims and set-
•Perform diagnostics and monitoring.
•Create a capture file of the controls trims and
•Updatecontrol calibrations (InPower PRO ver-
Refer to INPOWER User’s Guide for specifics.
®
tings.
settings.
sion).
1.1 controller (PCC). Use InPower to:
InPower Adjust Mode
The adjustment feature allows you to make adjust-ments to genset parameters, calibrations and set-tings. There are several groups of adjustment pa-rameters; note that not all gensets will have thesame adjustments available.
InPower Capture File Description
InPower provides a method of extracting (captur-ing) a device’s parameter values. Capturing savesdevice information in a file that is identified with a.CAP extension.
Capture files are used to store a copy of the gen-set’s parameter values. During genset installation,it is suggested that a capture file be made beforeand after changes are made to the genset operatingparameters. This information can be a very useful
when troubleshooting the genset (determine if parameters/settings have been modified after installation) and when replacement of the Base board is
necessary. The capture file can be used as a tem-plate to write the previous settings to the new Baseboard software.
ELECTRICAL SYSTEM
Verify all electrical connections are secure and allwiring is complete and inspected. Replace and se-cure any access panels that may have been re-moved during installation.
Battery Connections
WARNING
set can cause severe personal injury or death.Make sure that the PCC is in the OFF mode be-fore connecting the battery cables.
Startingthe unit requires a 12 volt battery. Connectpositive battery cable before connecting negativebattery cable to prevent arcing.
Service the batteries as necessary. If an automatictransfer switch is installed without a built-in chargecircuit, connect a separate battery charger. Properselectionand maintenance of batteries and batterychargers is essential for system reliability.
WARNING
can cause severe personal injury or death. Al-ways connect negative (−) battery cable last toprevent arcing.
WARNING
ing on or near battery. Arcing at battery termi-nals, light switch or other equipment, flame, pi-lotlights and sparks can ignite battery gas. Donot smoke, or switch trouble light ON or OFFnear battery. Discharge static electricity frombody before touching batteries by firsttouchinga grounded metal surface.
Accidental starting of the generator
Ignition of explosive battery gases
Ventilate battery area before work-
7-1
Page 38
PCC OPTIONS PRESTART CHECKS
All generator set configuration options are set at the
factory except for site related options, (e.g., Start/
Stop Time Delays, Cycle Crank, Customer Fault 1
and 2, etc.
Adjustment of these options are divided into two
categories within the menu driven system. Thesetwo categories are Setup and Screen Adjust.
The Setup menus are intended for qualified servicepersonnel only and require a password to modifythese submenus (refer to Service manual). TheScreenAdjust menu is intended for service person-nel and site personnel.
SCREEN ADJUST MENU
Figure 7-1 shows a block representation of theScreen Adjust menu. The Screen Adjust menu isdisplayed when the (3) button is pressed in the firstService Menu.
From any of the Operator menus, simultaneouslypress the and selection buttons for two sec-onds to display the first Service menu.
Adjusting Values/Parameters
1.Press the ADJUST selection button to select
the first parameter or value to be changed.
2. Press the + or − selection buttons to adjust val-
ues or select parameters.
3. Press the arrow selection button
gate to the next or previous adjustable value or
parameter.
4. After adjusting values/selecting parameters,
press the SAVE button to save your settings.
NOTE:If the Previous Menu button
pressedbefore pressing the SAVEbut-ton, the changes are not saved.
5.Press the Menu.
button to return to the Service
to navi-
is
Screen Adjust Menu
This menu allows for adjusting the screen’s contrastand brightness and for selecting the units of mea-surement (SAE or SI) to be displayed.
•Contrast and Brightness: Press the + or −selection buttons to adjust the screen’s con-trast and brightness. Changing the bright-ness setting also affects the brightness of theLEDs on the control panel.
•Units: Press the + or − selection buttons toselect SAE (_F, PSI) or SI (C, kPa) units ofmeasurement to be displayed.
SCREEN ADJUST MENU
FIGURE 7-1. SCREEN ADJUST MENU
7-2
Page 39
STARTING
Refer to the generator set Operator’s manual for important safety precautions and recommended procedures for starting the genset and verifying proper
operation. Start the generator set and verify all engine and generator menus are displaying the correct values.
7-3
Page 40
THIS PAGE LEFT INTENTIONALLY BLANK
7-4
Page 41
8. Installation Checklist
GENERAL
j Generator set wattage capacity is sufficient to
handle maximum anticipated load.
jAt least 3 feet of clearance (or greater for hous-
ing door) is provided around entire generatorset for servicing and ventilation.
jGeneratorset is located in an area not subject
to flooding.
jAll operating personnel have read and are fa-
miliar with Operator’s manual.
jAll operators have been thoroughly briefed on
preventive maintenance procedures.
jAll operators have read and understand all Im-
portantSafety Instructions in Operator’s manu-al.
GENERATOR SET SUPPORT
jFloor, roof or earth on which the generator set
rests isstrong enough and will not allow shiftingor movement. Observe local codes on soilbearing capacity due to freezing and thawing.
jGenerator set is properly supported and re-
tained to approved base.
jSupportingbase is large enough and is of non-
combustible material − extends 6-inches allaround set.
COOLING AIR FLOW
jGenerator set air inlet is faced into direction of
strongest, prevailing winds.
j Air inlet openings are unrestricted and at least
1−1/2 times larger than air outlet area.
jCooling air outlet is on downwind side of build-
ing (if not, wind barrier is constructed).
jProper ducting material (sheet metal, canvas)
is used between radiator and air outlet.
DIESEL FUEL SYSTEM
jFuel tanks meet or exceed all Local, State or
National codes.
jFuel lines are properly installed, supported and
protected against damage.
jApprovedflexible fuel line is installed between
main fuel supply line and generator set’s fuelsystem, near the generator set, to protect thefuel system from damage caused by vibration,expansion and contraction.
jStrainer or fuel screen (100 to 120 mesh) is
installed in the fuel supply line to protect thefuel lift pump, day tank transfer pump or floatvalve seat from fuel supply tank debris.
jAutomaticfuel supply line shutoff valves are
installed to prevent fuel flow in case of leaks.
jNo shutoff valves are installed on engine fuel
return line.
jExternalfuel pumps are connected and opera-
tional at all times (generator set started or shutdown).
jFuel system is properly primed.jNo fuel leaks are found in supply line or engine
fuel system.
8-1
Page 42
EXHAUST SYSTEM
AC AND DC WIRING
j Operators are thoroughly briefed on the dan-
gers of carbon monoxide gas.
j Areas around set are well ventilated. No possi-
bility of exhaust fumes entering building doors,
windows, or intake fans.
jExhaust gases are piped safely out-of-doors
and away from building.
jThe correct length of approved rigid pipe is
connected tothe generator set flexible pipe us-ing approved securing methods with no weightresting on engine exhaust components. Thereare no bends in flex section.
jCondensation drain is provided in lowest sec-
tion of exhaust piping.
jExhaust piping is insulated to guard against
burns to personnel.
jExhaust piping passing through walls or ceil-
ings have approved fire-proof materials andare in compliance with all codes.
jExhaust piping is large enough in diameter to
prevent excessive back pressure on engine.
j Wire sizes, insulation, conduits and connection
methods all meet applicable codes.
j AC and DC wires are separated in their own
conduit to prevent electrical induction.
j All load, line and generator connections are
proper and correct.
jFlexible conduit between generator set and
building or surrounding structure.
GENERATOR SET PRESTART
jGenerator set engine is properly serviced with
oil and coolant.
jBatteries are properly installed, serviced and
charged.
jBattery charger and engine coolant heater are
connected and operational.
jAll generator set covers and safety shields are
installed properly.
jAll fuel and coolant shutoff valves are opera-
tional.
jCreatedcontrol capture file of the genset’spa-
rameter values before and after modifications.
8-2
Page 43
9. Wiring Diagrams
NOTES:
1.TORQUETERMINALS TO 4.4 IN/LBS (0.5 Nm).
2.WIRE SIZE, 30−12 AWG (0.14−2.5MM) (TB1).
3. WIRE TYPE, USE 60°C RATED MINIMUM. COPPER WIRE (TB1).
4. TERMINAL SCREWS ARE SLOTTED (0.6MM).
5. USE FLAT−BLADED SCREWDRIVER WITH 2.5MM BLADE.
6. STRIP WIRE LENGTH TO 6.0MM.
7. FAULT IN #2 USED FOR OPTIONAL RUPTURE BASIN INPUT.