CUMMINS DSKAA, DSKAB, DSKBA, DSKCA Installation Manual

Page 1
Installation Manual
Generator Set
with PowerCommandR 1.1 Controller
DSKAA DSKAB DSKBA
DSKCA
English 04-2008 961-0620 (Issue 2)
Page 2
Page 3
Table of Contents
SECTION TITLE PAGE
IMPORTANT SAFETY INSTRUCTIONS iii. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1. INTRODUCTION 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About this Manual 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Overview 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2. SPECIFICATIONS 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3. MOUNTING THE GENERATOR SET 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Location 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Access to Set 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vibration Isolators 3-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4. MECHANICAL CONNECTIONS 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fuel System 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exhaust System 4-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ventilation and Cooling 4-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5. DC CONTROL WIRING 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Wiring 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TB1 Remote Monitor/Control Connections 5-2. . . . . . . . . . . . . . . . . . . . . . . .
Switched B+ 5-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O Module 5-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Run Relays (K10, K11) 5-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
California
Proposition 65 Warning
Diesel engine exhaust and some of its constituents are known to the State of California to cause cancer, birth defects, and other reproductive harm.
Page 4
SECTION TITLE PAGE
6. AC ELECTRICAL CONNECTIONS 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transfer Switch 6-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AC Wiring 6-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Heater (Optional) 6-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Coolant Heater (Optional) 6-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generator Heater (Optional) 6-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7. PRESTART PREPARATION 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
InPower Service Tool General Information 7-1. . . . . . . . . . . . . . . . . . . . . . . .
Electrical System 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PCC Options Prestart Checks 7-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Screen Adjust Menu 7-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting 7-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8. INSTALLATION CHECKLIST 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generator Set Support 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cooling Air Flow 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diesel Fuel System 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exhaust System 8-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AC and DC Wiring 8-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generator Set Prestart 8-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9. WIRING DIAGRAMS 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii
Page 5
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS This manual contains
important instructions that should be followed during installation and maintenance of the generator and batter­ies.
Before operating the generator set (genset), read the Operators Manual and become familiar with it and the equipment. Safe and efficient operation can be
achieved only if the equipment is properly operated and maintained. Many accidents are caused by failure
to follow fundamental rules and precautions.
The following symbols, found throughout this manual, alert you to potentially dangerous conditions to the op- erator, service personnel, or the equipment.
This symbol warns of immediate hazards which will result in severe personal in- jury or death.
WARNING
This symbol refers to a hazard or un- safe practice which can result in severe per- sonal injury or death.
CAUTION
This symbol refers to a hazard or un- safe practice which can result in personal injury or product or property damage.
FUEL AND FUMES ARE FLAMMABLE
Fire, explosion, and personal injury or death can result from improper practices.
DO NOT fill fuel tanks while engine is running, un-
less tanks are outside the engine compartment. Fuel contact with hot engine or exhaust is a potential fire hazard.
DO NOT permit any flame, cigarette, pilot light,
spark, arcing equipment, or other ignition source near the generator set or fuel tank.
Fuel lines must be adequately secured and free of
leaks. Fuel connection at the engine should be made with an approved flexible line. Do not use zinc coated or copper fuel lines with diesel fuel.
Be sure all fuel supplies have a positive shutoff
valve.
Be sure battery area has been well-ventilated prior
to servicing near it. Lead-acid batteries emit a highly explosive hydrogen gas that can be ignited by arc­ing, sparking, smoking, etc.
EXHAUST GASES ARE DEADLY
Provide an adequate exhaust system to properly
expel discharged gases away from enclosed or sheltered areas and areas where individuals are likely to congregate. Visually and audibly inspect the exhaust daily for leaks per the maintenance schedule. Make sure that exhaust manifolds are se- cured and not warped. Do not use exhaust gases to heat a compartment.
Be sure the unit is well ventilated.
Engine exhaust and some of its constituents are
known to the state of California to cause cancer, birth defects, and other reproductive harm.
MOVING PARTS CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
Keep your hands, clothing, and jewelry away from
moving parts.
Before starting work on the generator set, discon-
nect battery charger from its AC source, then dis- connect starting batteries, negative () cable first. This will prevent accidental starting.
Make sure that fasteners on the generator set are
secure. Tighten supports and clamps, keep guards in position over fans, drive belts, etc.
Do not wear loose clothing or jewelry in the vicinity of
moving parts, or while working on electrical equip- ment. Loose clothing and jewelry can become caught in moving parts.
If adjustment must be made while the unit is run-
ning, use extreme caution around hot manifolds, moving parts, etc.
DO NOT OPERATE IN FLAMMABLE AND EXPLOSIVE ENVIRONMENTS
Flammable vapor can cause an engine to overspeed and become difficult to stop, resulting in possible fire, explo- sion, severe personal injury and death. Do not operate a genset where a flammable vapor environment can be created by fuel spill, leak, etc., unless the genset is equipped with an automatic safety device to block the air intake and stop the engine. The owners and operators of the genset are solely responsible for operating the gen­set safely. Contact your authorized Cummins Power Generation distributor for more information.
LS-16L
iii
Page 6
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
Remove electric power before removing protective
shields or touching electrical equipment. Use rub­ber insulative mats placed on dry wood platforms over floors that are metal or concrete when around electrical equipment. Do not wear damp clothing (particularly wet shoes) or allow skin surface to be damp when handling electrical equipment. Do not wear jewelry. Jewelry can short out electrical con- tacts and cause shock or burning.
Use extreme caution when working on electrical
components. High voltages can cause injury or death. DO NOT tamper with interlocks.
Follow all applicable state and local electrical
codes. Have all electrical installations performed by a qualified licensed electrician. Tag and lock open switches to avoid accidental closure.
DO NOT CONNECT GENERATOR SET DI-
RECTLY TO ANY BUILDING ELECTRICAL SYS- TEM. Hazardous voltages can flow from the gen- erator set into the utility line. This creates a potential for electrocution or property damage. Connect only through an approved isolation switch or an ap- proved paralleling device.
GENERAL SAFETY PRECAUTIONS
Coolants under pressure have a higher boiling point
than water. DO NOT open a radiator or heat ex- changer pressure cap while the engine is running. To prevent severe scalding, let engine cool down before removing coolant pressure cap. Turn cap slowly, and do not open it fully until the pressure has been relieved.
Used engine oils have been identified by some state
or federal agencies as causing cancer or reproduc- tive toxicity. When checking or changing engine oil, take care not to ingest, breathe the fumes, or con- tact used oil.
Keep multi-class ABC fire extinguishers handy.
Class A fires involve ordinary combustible materials such as wood and cloth; Class B fires, combustible and flammable liquid fuels and gaseous fuels; Class C fires, live electrical equipment. (ref. NFPA No. 10).
Make sure that rags or combustible material are not
left on or near the generator set.
Make sure generator set is mounted in a manner to
prevent combustible materials from accumulating under or near the unit.
Remove all unnecessary grease and oil from the
unit. Accumulated grease and oil can cause over- heating and engine damage which present a poten- tial fire hazard.
Keep the generator set and the surrounding area
clean and free from obstructions. Remove any de- bris from the set and keep the floor clean and dry.
Do not work on this equipment when mentally or
physically fatigued, or after consuming any alcohol or drug that makes the operation of equipment un- safe.
Substances in exhaust gases have been identified
by some state or federal agencies as causing can- cer or reproductive toxicity. Take care not to breath or ingest or come into contact with exhaust gases.
Do not store any flammable liquids, such as fuel,
cleaners, oil, etc., near the generator set. A fire or explosion could result.
Wear hearing protection when near an operating
generator set.
To prevent serious burns, avoid contact with hot
metal parts such as radiator system, turbo charger system and exhaust system.
KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE
iv
Page 7
1. Introduction
ABOUT THIS MANUAL
This manual provides installation instructions for the generator set models listed on the front cover. This includes the following information:
Mounting Recommendations - for fastening generator set to base and space requirements for normal operation and service.
Mechanical and Electrical Connections - covers most aspects of the generator set instal- lation.
Prestart checklist of items or procedures needed to prepare generator set for operation.
Initial Startup test complete system to en- sure proper installation, satisfactory perfor- mance, and safe operation. Refer to Operators Manual for troubleshooting information.
Installation Checklist reference checks upon completion of installation.
This manual DOES NOT provide application infor- mation for selecting a generator set or designing the complete installation. If it is necessary to design the various integrated systems (fuel, exhaust, cooling, etc.), additional information is required. Review standard installation practices. For engineering data specific to the generator set, refer to the Speci- fication Sheet and Data Sheet. For application infor- mation, refer to Application Manual T-030, “Liquid Cooled Generator Sets”. To find this manual online:
1. Go to http://www.cumminspower.com
2. Click onApplication Engineering” under head- ing Technical Information
3. Click on “Liquid Cooled Genset Application Manual.
INSTALLATION OVERVIEW
These installation recommendations apply to typi­cal installations with standard model generator sets. Whenever possible, these recommendations also cover factory designed options or modifica- tions. However, because of the many variables in any installation, it is not possible to provide specific recommendations for every situation. If there are any questions not answered by this manual, contact your nearest Cummins Power Generation distribu- tor for assistance.
Application and Installation
A power system must be carefully planned and cor- rectly installed for proper operation. This involves two essential elements: application and installa- tion.
Application (as it applies to generator set installa- tions) refers to the design of the complete power system that usually includes power distribution equipment, transfer switches, ventilation equip- ment, mounting pads, and cooling, exhaust, and fuel systems. Each component must be correctly designed so the complete system will function as in- tended. Application and design is an engineering function generally done by specifying engineers or other trained specialists. Specifying engineers or other trained specialists are responsible for the de- sign of the complete power system and for selecting the materials and products required.
Installation refers to the actual set-up and assem- bly of the power system. The installers set up and connect the various components of the system as specified in the system design plan. The complexity of the system normally requires the special skills of qualified electricians, plumbers, sheetmetal work- ers, etc. to complete the various segments of the installation. This is necessary so all components are assembled using standard methods and prac- tices.
1-1
Page 8
Safety Considerations
The generator set has been carefully designed to provide safe and efficient service when properly installed, maintained, and operated. However, the overall safety and reliability of the complete system is dependent on many factors outside the control of the generator set manufacturer. To avoid possible safety hazards, make all mechanical and electrical connections to the generator set exactly as speci- fied in this manual. All systems external to the gen- erator (fuel, exhaust, electrical, etc.) must comply with all applicable codes. Make certain all required inspections and tests have been completed and all code requirements have been satisfied before certi- fying the installation is complete and ready for ser- vice.
Heating Devices for Standby Applications
In accordance with NFPA 110, Cummins Power Generation recommends installing standby gener- ator sets (life safety systems) equipped with engine jacket water coolant heaters in locations where the minimum ambient temperature is above 40
(4
°C). NFPA also requires that the engine be
heated as necessary to maintain the water jacket temperature determined by the manufacturer for cold start and load acceptance for the type of sys- tem.
Although Cummins Power Generation generator sets may start in temperatures below 40 when equipped with engine jacket water coolant
°F (4°C)
°F
heaters, it might take more than 10 seconds to warm the engine before a load can be applied and may also require other supplemental starting aids. Refer to engine manual for specific engine require­ments.
On generator sets equipped with a graphic display, the Low Coolant Temperature (Code 1435) mes- sage, in conjunction with illumination of the Warning LED, is provided to meet the requirements of NFPA
110. The engine cold sensing logic initiates a warn- ing when the engine jacket water coolant tempera- ture falls below 70 the ambient temperature falls below 40 cold engine may be indicated even though the cool- ant heaters are connected and operating correctly. Under these conditions, although the generator set may start, it may not be able to accept load within 10 seconds. When this condition occurs, check the coolant heaters for proper operation. If the coolant heaters are operating properly, other precautions may be necessary to warm the engine before apply- ing a load.
°F (21°C). In applications where
°F (4°C), a
Product Modifications
Agency certified products purchased from Cum- mins Power Generation comply only with those specific requirements and as noted on company product specification sheets. Subsequent modifica- tions must meet commonly accepted engineering practices and/or local and national codes and stan- dards. Product modifications must be submitted to the local authority having jurisdiction for approval.
Copyright© 2008 Cummins Power Generation. All rights reserved.
Cummins and PowerCommand are registered trademarks of Cummins Inc.
1-2
Page 9
2. Specifications
MODEL DSKAA DSKAB DSKBA DSKCA
Engine
Kubota Diesel Series D1703-M-E3 BG
3 Cylinder
Generator kW Rating See Genset Nameplate for rating information
Electrical System
Battery Charging Starting Voltage Battery
Group Number CCA (minimum)
Cold Soak @ 32° F (0° C)
Cooling System
Capacity with Standard Radiator 2.0 Gal (7.7 L)* 2.0 Gal (7.7 L)* 2.5 Gal (9.4 L)* 2.5 Gal (9.5 L)*
Lubricating System
Oil Capacity with Filters 7.4 Qts (7.0 L) 7.4 Qts (7.0 L) 10.0 Qts (9.5 L) 13.9 Qts (13.2 L)
Oil Type
Above 75° F (25° C) 32° F (0° C) to 75° F (25° C) Below 32° F (0° C)
Oil Grade
D1703-M-E3 BG
3 Cylinder
40A Alternator
12 Volts DC
One, 12 Volt
G24
350 Amps
SAE 30 or SAE 10W30 SAE 20 or SAE 10W30
SAE 10W or SAE 10W30
API CF or better
V2203-M-E3 BG
4 Cylinder
V3300-E3 BG
4 Cylinder
40A Alternator
12 Volts DC
One, 12 Volt
G31
450 Amps
Exhaust
Outlet Size @ Standby:
Maximum Allowable Back Pres-
sure
Exhaust Flow at Rated Load Exhaust Temperature
Fuel Pump
Fuel Supply Fuel Return Maximum Fuel Lift
**Fuel Consumption
Standby/Full Load/60Hz GPH
(L/HR)
* Use 50/50 antifreeze (ethylene glycol and water) mixture.
** Refer to generator set Specifications Sheet for other applications.
Normal Oil Pressure
Warning Limit Shutdown Limit
2 inch NPT
40 in H2O (10
kPa)
99 cfm (2.8
m3/min)
630° F (332° C)
0.95 (3.6) 1.37 (5.2) 1.93 (7.3) 2.43 (9.2)
OIL PRESSURE WARNING AND
SHUTDOWN LIMITS
2 inch NPT
40 in H2O (10
kPa)
126 cfm (3.6
m3/min)
919° F (493° C)
3/8 inch Hose Barb
3/16 inch Hose Barb
31.5 inches (800 mm)
40-70 psi (276-483 kPa)
20 psi (138 kPa) 15 psi (103 kPa)
40 in H2O (10
174 cfm (4.9
970° F (521° C)
2 inch NPT
kPa)
m3/min)
2 inch NPT
40 in H2O (10
kPa)
219 cfm (6.2
m3/min)
735° F (391° C)
2-1
Page 10
THIS PAGE LEFT INTENTIONALLY BLANK
2-2
Page 11
3. Mounting the Generator Set
GENERAL
Generator set installations must be engineered so the generator set will function properly under the ex- pected load conditions. Use these instructions as a general guide only. Follow the instructions of the consulting engineer when locating or installing any components. The complete installation must com- ply with all local and state building codes, fire ordi- nances, and other applicable regulations. A typical generator set installation is shown in Figure 3-1.
Requirements to be considered prior to installation:
Level mounting surface
Adequate cooling air
Adequate fresh induction air
Discharge of generator set air
Non-combustible mounting surface
Discharge of exhaust gases
Electrical connections
Accessibility for operation and servicing
Noise levels
Vibration isolation
LOCATION
Generator set location is decided mainly by related systems such as ventilation, wiring, fuel, and ex- haust. The set should be located as near as pos- sible to the main power service entrance. Exhaust must not be able to enter or accumulate around in- habited areas.
Provide a location away from extreme ambient tem- peratures and protect the generator set from ad- verse weather conditions. An optional housing is available for outdoor operation.
WARNING
INCORRECT INSTALLATION, SERVICE OR PARTS REPLACEMENT CAN RESULT IN SEVERE PERSONAL INJURY, DEATH, AND/OR EQUIPMENT DAMAGE. SERVICE PERSONNEL MUST BE TRAINED AND EXPERIENCED TO PERFORM ELECTRICAL AND MECHANICAL COM- PONENT INSTALLATION.
IMPORTANT
DEPENDING ON YOUR LOCATION AND INTENDED USE, FEDERAL, STATE OR LOCAL LAWS AND REGULATIONS MAY REQUIRE YOU TO OBTAIN AN AIR QUALITY EMISSIONS PERMIT BEFORE BEGINNING INSTALLATION OF YOUR GENSET. BE SURE TO CONSULT LOCAL POLLUTION CONTROL OR AIR QUALITY AUTHORITIES BEFORE COMPLETING YOUR CONSTRUCTION PLANS.
3-1
Page 12
SWEEPING
ELBOW
MUFFLER
THIMBLE
AC POWER WIRING
DC
CONTROL
WIRING
FLEXIBLE SECTION
AIR OUT
AIR
IN
FLEXIBLE
BELLOWS
COOLING
AIR
IN
CONCRETE
IMPORTANT!
COOLING AIR INLET MUST BE AT LEAST 1-1/2 TIMES LARGER
THAN RADIATOR DUCT OUTLET AREA ON RADIATOR-COOLED
MODELS.
FLOW OF COOLING AIR AND HEATED AIR MAY BE
CONTROLLED BY AUTOMATICALLY OPERATED LOUVRES.
FIGURE 3-1. TYPICAL GENERATOR SET (WITH RADIATOR) INSTALLATION
3-2
BASE
Page 13
MOUNTING
Generator sets are mounted on a steel skid that pro­vides proper support. The engine-generator as­sembly is isolated from the skid frame by rubber mounts that provide adequate vibration isolation for normal installations. Where required by building codes or special isolation needs, generator sets may be mounted on rubber pads or mechanical spring isolators. The use of unapproved isolators may result in harmful resonances and may void the genset warranty.
Mount the generator set on a substantial and level base such as a concrete pad. A non-combustible material must be used for the pad.
Use 5/8 inch or 16 mm anchored mounting bolts to secure the vibration isolators to the base. Secure the vibration isolators to the skid using a flat washer and hexagonal nut for each bolt (see Figure 3-2). The 1-1/2 x 6 inch pipe inserted over the mounting bolts allows minor adjustment of the bolts to align them to the holes in the subbase or vibration isola- tor.
Locate the isolators as shown on the generator set Outline Drawing referenced in the Data Sheet.
MOUNTING
BASE
MOUNTING
BOLT
SUBBASE OR
VIBRATION
ISOLATOR
FLANGE
HEX NUT
FLAT WASHER
1-1/2 x 6 INCH
PIPE
12 IN.
(305 mm)
CONCRETE
ACCESS TO SET
Generally, at least 1 meter (3 feet) of clearance should be provided on all sides of the generator set for maintenance and service access. (Increase clearance by width of door if optional housing is used.) A raised foundation or slab of 150 mm (6 inches) or more above floor level will make servic- ing easier.
Lighting should be adequate for operation, mainte- nance and service operations and should be con- nected on the load side of the transfer switch so that it is available at all times.
FIGURE 3-2. BOLT DIAGRAM
3-3
Page 14
VIBRATION ISOLATORS
Installation and Adjustment Procedure
1. Place the vibration isolators (Figure 3-3) on the genset support structure. The isolators should be shimmed or grouted to ensure that all of the isolator bases are within 0.25 inch (6 mm) elevation of each other. The surface that the isolator bases rest on must also be flat and lev- el.
2. Loosen the side snubber lock nuts so that the top plate of the isolator is free to move vertically and horizontally. Be sure that the top plate is correctly aligned with the base and springs.
3. Place the genset onto the isolators while align- ing the skid’s mounting with the threaded isola- tor hole. The top plates will move down and ap- proach the base of the isolator as load is ap- plied.
4. Once the genset is in position, the isolators may require adjusting so that the set is level.
The isolators are adjusted by inserting the lev­eling bolt through the skid and into the isolator (the leveling bolt’s locking nut should be threaded up towards the bolt head).
The leveling bolt will adjust the clearance be­tween the top plate and the isolator base. A nominal clearance of 0.25 inch (6 mm) or great­er is desired. This will provide sufficient clear- ance for the rocking that occurs during startup and shutdown. If the 0.25 inch (6 mm) clear- ance is not present, turn the leveling bolt until the desired clearance is achieved.
5. The genset may not be level yet; therefore, ad- just the leveling bolts until the set is level and sufficient clearance still remains. (Clearance on all isolators should be roughly equal). Once all isolators have been set, lock the leveling bolt in place with the lock nut.
6. The snubber nuts may remain loose and there- fore provide better isolation between the gen- set and support structure.
GENSET SKID
LEVELING BOLT
LOCK NUT
CLEARANCE
SNUBBER
BASE
FIGURE 3-3. VIBRATION ISOLATORS
3-4
Page 15
4. Mechanical Connections
GENERAL
The generator set mechanical system installation includes connecting the fuel, exhaust, ventilation and cooling systems. Before starting any type of fuel installation, all pertinent state and local codes must be complied with and the installation must be inspected before the unit is put in service.
FUEL SYSTEM
Engines used on these generator sets normally use ASTM No. 2 Diesel fuel. They will, however, operate on alternate diesel fuels within the specifications shown in the engine manual.
In all fuel system installations, cleanliness is of the upmost importance. Make every effort to prevent entrance of moisture, dirt or contaminants of any kind into the fuel system. Clean all fuel system com- ponents before installing.
A fuel filter/strainer/water separator of 100-120 mesh or equivalent (approximately 150 microns nominal) must be fitted between either the main tank and day tank or between the main tank and the engine.
Use only compatible metal fuel lines to avoid elec- trolysis when fuel lines must be buried. Buried fuel lines must be protected from corrosion.
CAUTION
lines, fittings or fuel tanks. Condensation in the tank and lines combines with the sulfur in diesel fuel to produce sulfuric acid. The molecular structure of the copper or galvanized lines or tanks reacts with the acid and contaminates the fuel.
An electric solenoid valve in the supply line is rec- ommended for all installations and required for in- door automatic or remote starting installations. Connect the solenoid wires to the genset “Switched B+” circuit to open the valve during generator set operation.
Separate fuel return lines to the day tank or supply tank must be provided for each generator set in a multiple-set installation to prevent the return lines of idle sets from being pressurized. Fuel return lines must not contain a shutoff device. Engine damage will occur if the engine is run with the return fuel lines blocked or restricted.
CAUTION
return line(s). If fuel return line(s) is blocked or exceeds fuel restriction limit, engine damage will occur.
Fuel Return Restriction (or Pressure) Limit: Fuel return drain restriction (consisting of friction head and static head) between the engine injector return line connection and the fuel tank must not exceed the limit stated in the model-specific genset Specifi- cation Sheet.
Never use galvanized or copper fuel
Never install shutoff device in fuel
4-1
Page 16
Fuel Lines − Routing
A flexible fuel hose(s) or section of flexible fuel hose(s) must be used between the engine’s fuel system and fuel supply and return line(s) to protect the fuel system from damage caused by vibration, expansion and contraction. Flexible lines for con­necting between the engine and the stationary fuel lines are supplied as standard equipment.
WARNING
hazards which can result in severe personal in- jury or death. Always use flexible tubing be- tween engine and fuel supply to avoid line fail- ure and leaks due to vibration. The fuel system must meet all applicable codes.
Installation of the fuel hose must be done according to all applicable codes and standards, and installa-
Fuel leaks create fire and explosion
tion recommendations provided by the manufactur­er. The supplied flexible hose is approved by the hose manufacture for use with the genset fuel type and product application.
Support fuel lines to restrain movement and prevent chaffing or contact with sharp edges, electrical wir­ing and hot exhaust parts.
WARNING
Sparks and hot surfaces can ignite fuel, leading to severe personal injury or death. Do not route fuel lines near electrical wiring or hot exhaust parts.
Fuel lines must be routed and secured to maintain a 1/2 inch (12.7 mm) minimum clearance from electri- cal wiring and a 2 inch (51 mm) minimum clearance from hot exhaust parts.
Engine Fuel Connections
Identification tags are attached to the fuel supply line and fuel return line connections.
Supply Tank
Locate the fuel tank as close as possible to the gen- erator set and within the restriction limitations of the fuel pump.
Install a fuel tank that has sufficient capacity to sup- ply the genset operating continuously at full rated load for the planned period of operation or power outage. Refer to Specification Sheet for fuel con- sumption data.
If the fuel inlet restriction exceeds the defined limit due to the distance/customer-supplied plumbing between the genset and the main fuel tank, a trans- fer tank (sometimes referred to as a day tank) and auxiliary pump will also be required. If an overhead
main fuel tank is installed, a transfer tank and float valve will be required to prevent fuel head pres- sures from being placed on the fuel system compo- nents.
For critical start applications, where generator sets are paralleled or must satisfy emergency start-time requirements, it is recommended that a fuel tank or reservoir be located such that the lowest possible fuel level is not less than 6 inches (150 mm) above the fuel pump inlet. This will prevent air from accu- mulating in the fuel line while the set is in not run- ning, eliminating the period during startup when it has to be purged.
Fuel Inlet Pressure/Restriction Limit: Engine
performance and fuel system durability will be com- promised if the fuel inlet pressure or restriction limits are not adhered to. Fuel inlet pressure or restriction must not exceed the limits stated in the model-spe- cific genset Specification Sheet.
4-2
Page 17
Day Tank (If Used)
Fuel day tanks are used when fuel inlet restriction limits can not be met, or the supply tank is overhead and presents problems of high fuel head pressure for the fuel inlet and return lines.
Supply Tank Lower Than Engine: With this instal­lation, the day tank is installed near the generator set, below the fuel injection system and within the fuel inlet restriction limit. Install a fuel transfer pump, to pump fuel from the supply tank to the day tank. A float switch in the day tank controls operation of the fuel transfer pump.
When using a fuel transfer pump, the supply tank top must be below the day tank top to prevent siphoning from the fuel supply to the day tank.
Provide a return line from the engine injection sys- tem return connection to the day tank. Plumb the re- turn line to the bottom of day tank as shown in Fig-
ure 4-1. Provide a day tank overflow line to the sup­ply tank in case the float switch fails to shut off the fuel transfer pump.
WARNING
Spilled fuel presents the hazard of fire or explosion which can result in severe per­sonal injury or death. Provide an overflow line to the supply tank from the day tank.
Supply Tank Higher Than Engine: With this
installation, the day tank is installed near the gener- ator set, below the fuel injection system and within the fuel inlet restriction limit. Include an automatic fuel shutoff valve in the fuel line between the fuel supply tank and the day tank to stop fuel flow when the generator set is off.
Provide a return line from the engine injection sys- tem return connection to the day tank. Plumb the re- turn line to the bottom of day tank as shown in Fig- ure 4-1.
WARNING
Spilled fuel can create environmental hazards. Check local requirements for containment
and prevention of draining to sewer and ground water.
ENGINE
FUEL
PUMP
DAY TANK
FUEL TRANSFER PUMP ELECTRIC
MOTOR DRIVEN
VENTED FILL CAP
SHUTOFF
VALVE
1 INCH
BAFFLE
FLOAT
SWITCH
120 MESH FUEL
STRAINER
INJECTOR FUEL
RETURN LINE
CONNECT TO
AC OUTPUT
SUPPLY
LINE
FUEL TANK
All models require a fuel return line from injectors to tank.
VENT LINE
FILL PIPE
LARGER OVER-
FLOW LINE
FIGURE 4-1. TYPICAL FUEL SUPPLY INSTALLATION
4-3
Page 18
EXHAUST SYSTEM
Pipe exhaust gases to the outside of any enclosure. Locate the exhaust outlets away from any air inlets to avoid gases re-entering the enclosure. Exhaust installations are subject to various detrimental con­ditions such as extreme heat, infrequent operation and light loads. Regularly inspect the exhaust sys­tem both visually and audibly to see that the entire system remains fume tight and safe for operation.
WARNING
sult in severe personal injury or death. Use ex- treme care during installation to provide a tight exhaust system. Terminate exhaust pipe away from enclosed or sheltered areas, windows, doors and vents.
For indoor installation, the exhaust system must use sealed joint type fittings, (for example NPT fit- tings) to provide a tight exhaust system. Use of slip type fittings (secured with a muffler clamp) may al- low leakage of exhaust gases into the building.
WARNING
sult in severe personal injury or death. Use ex- treme care during installation to provide a tight exhaust system. Use NPT or equivalent type fit- tings for all indoor installations.
Use an approved thimble (Figure 4-2) where ex- haust pipes pass through wall or partitions. Insu- lated wall/roof thimbles are used where exhaust pipes pass through a combustible roof or wall. This includes structures, such as wood framing or insu- lated steel decking, etc. Uninsulated wall/roof thimbles are used where exhaust pipes pass through a non-combustible wall or roof, such as concrete. Refer to NFPA 37, Section 6-3. “Station- ary Combustion Engines and Gas Turbines” for ac-
Inhalation of exhaust gases can re-
Inhalation of exhaust gases can re-
cepted design practices. Build according to the code requirements in effect at the installation site.
WARNING
Hot exhaust pipes can start a fire and cause severe injury or death if improperly routed through walls. Use an approved thimble where exhaust pipes pass through walls or partitions.
WARNING
Inhalation of exhaust gases can re- sult in severe personal injury or death. Do not use exhaust heat to warm a room, compartment or storage area.
Rain caps are available for the discharge end of ver- tical exhaust pipes. The rain cap clamps onto the end of the pipe and opens due to exhaust discharge force from the generator set. When the generator set is stopped, the rain cap automatically closes, protecting the exhaust system from rain, snow, etc.
Use a section of flexible exhaust pipe between the engine and remainder of exhaust system. Support exhaust system to prevent weight from being ap- plied to engine exhaust outlet.
CAUTION
Weight applied to the engine man- ifold can result in damage. Support the muffler and exhaust piping so no weight or stress is ap- plied to engine exhaust elbow.
The exhaust system design should meet local code requirements.
Liability for injury, death, damage, and warranty ex- pense due to use of unapproved mufflers or modifi- cations to the exhaust system becomes the respon- sibility of the person installing the unapproved muf- fler or performing the modification. Contact a Cum- mins Power Generation distributor for approved ex- haust system parts.
4-4
Page 19
Avoid sharp bends by using sweeping, long radius elbows and provide adequate support for muffler and tailpipe. Pitch a horizontal run of exhaust pipe DOWNWARD (away from engine) to allow any moisture condensation to drain away from the en­gine. If an exhaust pipe must be turned upward, install a condensation trap at the point where the rise begins (Figure 4-3).
Shield or insulate exhaust lines if there is danger of personal contact. Allow at least 12 inches (305 mm) of clearance if the pipes pass close to a combustible wall or partition. Before installing insulation on ex- haust system components, check the exhaust sys- tem for leaks while operating the genset under full load and correct all leaks.
RAIN CAP
9 INCH
(230 mm)
VERTICAL
DRIP CAP
HOLES IN
END OF INNER
SLEEVE
ROOF
9 INCH
(230 mm)
WARNING
Exhaust pipes are very hot and they can cause severe personal injury or death from direct contact or from fire hazard. Shield or in- sulate exhaust pipes if there is danger of per- sonal contact or when routed through walls or near other combustible materials.
HORIZONTAL
WALL OR PARTITION
FIGURE 4-2. MOUNTING EXHAUST THIMBLE
IF EXHAUST LINE MUST BE
PITCHED UPWARD, CONSTRUCT
A TRAP AT POINT OF RISE
4-5
AVOID SHARP BENDS
DRAIN CONDENSATION
TRAP PERIODICALLY
FIGURE 4-3. CONDENSATION TRAP
Page 20
VENTILATION AND COOLING
Generator sets create considerable heat that must be removed by proper ventilation. Outdoor installa­tions normally rely on natural air circulation but in­door installations need properly sized and posi­tioned vents for required airflow.
Vents and Ducts
For indoor installations, locate vents so incoming air passes through the immediate area of the installa- tion before exhausting. Install the air outlet higher than the air inlet to allow for convection air move- ment.
Size the vents and ducts so they are large enough to allow the required flow rate of air. The ”free area” of ducts must be as large as the exposed area of the radiator. Refer to the genset Specification Sheet for the airflow requirements and allowed airflow restric- tion.
Wind will restrict free airflow if it blows directly into the air outlet vent. Locate the outlet vent so the ef- fects of wind are eliminated, or if outlet vent cannot be located as mentioned, install wind barrier. See Figure 4-4.
PREVAILING WINDS PREVAILING WINDS
WIND
BARRIER
FIGURE 4-4. WIND BARRIER
4-6
Page 21
Dampers
Dampers or louvres protect the generator set and equipment room from the outside environment. Their operation of opening and closing should be controlled by operation of the generator set.
In cold climates, the radiator exhaust air can be re­circulated to modulate the ambient air temperature in the generator set room. This will help the genera- tor set warm up faster, and help to keep fuel temper- atures higher than the cloud point of the fuel. If recir- culation dampers are used, they should be de- signed to “fail closed”, with the main exhaust damp- ers open, so that the generator set can continue to operate when required. Designers should be aware that the generator set room operating temperature will be very close to the outdoor temperature, and either not route water piping through the generator set room, or protect it from freezing.
Radiator Set Requirements
Louvers and screens over air inlet and outlet open- ings restrict air flow and vary widely in performance.
A louver assembly with narrow vanes, for example, tends to be more restrictive than one with wide vanes. The effective open area specified by the lou­ver or screen manufacturer should be used.
Radiator set cooling air is drawn past the control end of the set by a pusher fan that blows air through the radiator. Locate the air inlet to the rear of the set. Make the inlet vent opening 1-1/2 times larger than the radiator area.
Locate the cooling air outlet directly in front of the ra- diator and as close as possible. The outlet opening must be at least as large as the radiator area. Length and shape of the air outlet duct should offer minimum restriction to airflow.
Attach a canvas or sheet metal duct to the air outlet opening using screws and nuts so duct can be re- moved for maintenance purposes. The duct pre- vents recirculation of heated air. Before installing the duct, remove the radiator core guard.
ENGINE-DRIVEN
FAN
DAMPER
COOL
AIR
INLET
AIR
RADIATOR
THERMOSTATICALLY
CONTROLLED
RECIRCULATING DAMPER
FLEXIBLE
DUCT
CONNECTOR
OUTLET AIR
DAMPER
WIND/
NOISE
BARRIER
HOT
AIR
D
DISTANCE SHOULD
NOT BE LESS THAN
HEIGHT OF RADIATOR
FIGURE 4-5. TYPICAL RADIATOR SET INSTALLATION
4-7
Page 22
THIS PAGE LEFT INTENTIONALLY BLANK
4-8
Page 23
5. DC Control Wiring
CONTROL WIRING
The generator set control box contains connection points for remote control and monitor options. These connection points are located inside of the control box (Figure 5-1).
Use flexible conduit for all wiring connections to the generator set.
CAUTION
for all customer connections to the control pan- el. Solid copper wire may break due to genset vibration.
Stranded copper wire must be used
K11
K10
TB10
WARNING
HAZARDOUS VOLTAGE Touching uninsulated high voltage parts inside the con­trol box can result in severe personal injury or death. Control wire installation must be done with care to avoid touching uninsulated live parts.
Stand on a clean dry wooden platform or clean rubber insulating mat, make sure your clothing and shoes are dry, remove jewelry and use tools with insulated handles.
BASE
BOARD
CUSTOMER WIRING
FIGURE 5-1. CONTROL BOX
TB1
ACCESS HOLE
5-1
Page 24
TB1 REMOTE MONITOR/CONTROL
CONNECTIONS
Customer monitor/control connections are at­tached to terminal block TB1 (Figure 5-1). Optional equipment, such as sensing devices used to moni­tor genset operation, remote start/stop switches, etc. are attached to TB1. Refer to Customer Con­nections diagram in Section 9.
TB1 Wiring
CAUTION
a separate metal conduit from AC power cables to avoid inducing currents that could cause problems within the control.
Digital Connections: Connection points, other than relayed outputs and network are considered digital connections to terminal strip TB1. The type/ gauge wire to use for these connections are:
Always run control circuit wiring in
Less than 1000 feet (305m), use 20 gauge
stranded copper wire.
1000 to 2000 feet (305 to 610m), use 18 gauge
stranded copper wire.
Relay Connections: Due to the wide variety of de- vices that can be attached to the relay outputs of TB1, the electrical contractor must determine the gauge of the stranded copper wire that is used at this installation site.
TB1 Customer Inputs
Refer to Page 9-1 for typical connections to TB1.
Remote Start: When the control is in Auto/Remote mode, grounding this input initiates the engine cranking and start sequence. This circuit must be opened to permit resetting a shutdown condition with the Reset input. (The remote stop is actually the removal of the remote start signal to the control.)
Remote Emergency Stop: Opening this input causes an immediate shutdown. Emergency stop must be reset at the front panel.
Customer Fault Inputs 1 and 2: Grounding any one of these inputs activates the corresponding warning or shutdown sequence.
External sensing equipment must be connected to the designated digital input.
The nature of the fault is an optional customer selection. Example inputs: Low Coolant Level, Low Fuel Level, Ground Fault, etc.
Each of the two fault functions can be programmed as follows:
Status, Warning or Shutdown. Default = Warn­ing.
Enter a brief description of the event (up to 32 characters).
The InPower service tool or access to the Setup Sub- menus is required to modify the customer fault in- puts. Contact an authorized service center for assis- tance.
TB1 Customer Outputs
Refer to Page 9-1 for typical connections to TB1.
Customer Outputs 1 and 2: One set of normally open (NO) contacts, rated for 2 amps at 30 VDC for each of the two output signals. The relays can be used to control small devices and indicator lamps.
The nature of the customer output signal (contacts closed) is an optional customer selection. Example outputs: Genset running (event), common warning, common shutdown, etc. (Refer to Operators manu- al for warning and shutdown code listing and the Service manual for event code listing.)
Each relay can be independently programmed to energize by entering a code number (0 through 255, default = 0) for the desired event.
The InPower service tool or access to the Setup Sub- menus is required to modify the customer outputs. Contact an authorized service center for assistance.
Ready To Load: Operates when the generator set has reached 90% of rated speed and voltage and latches until generator set is switched to off mode (B+ signal output).
SWITCHED B+
Switched B+ is fused at 15 amps. Wiring is the same as Relay Connection description.
Switched B+ quick connect terminal is located on the right side of the engine (facing the control) near the flywheel housing. Wire color is Red/Orange stripe.
5-2
Page 25
I/O MODULE
The optional I/O module(s) provides additional cus­tomer inputs and outputs for control and monitoring of the power system. Up to sixteen relay outputs and twelve discrete analog inputs are available when the control contains both the Base I/O Module (AUX101) and the Expansion I/O Module (AUX102).
RUN RELAYS (K10, K11)
The optional run relays (Figure 5-1 and Figure 5-2) are mounted inside the control box. The single­pole, double-throw run relays are used to control auxiliary equipment such as fans, pumps and mo­torized air dampers. The run relays are energized when the generator set control receives a start sig­nal.
The contacts are rated:
Refer to Instruction Sheet C693 for I/O module con- figuration/wiring information.
K10
TB1
K11
BASE
BOARD
20 amps resistive @ 30VDC
15 amps inductive @ 30VDC
TB10
CUSTOMER
CONNECTIONS
FIGURE 5-2. OPTIONAL RUN RELAYS (K10, K11)
5-3
Page 26
THIS PAGE LEFT INTENTIONALLY BLANK
5-4
Page 27
6. AC Electrical Connections
GENERAL
This section provides the procedure that is used to connect the AC electrical system of the genset.
Before making any AC electrical connections, make certain the generator set cannot be accidentally started. Place the control panel run switch in the OFF position. Turn off or remove AC power from the battery charger and then remove the negative () battery cable from the set starting battery.
WARNING
can cause severe personal injury or death. Arc- ing at battery terminals, light switch or other equipment, flame, pilot lights and sparks can ig- nite battery gas. Do not smoke, or switch trouble light ON or OFF near battery. Discharge static electricity from body before touching bat- teries by first touching a grounded metal sur- face.
Ventilate battery area before working on or near battery—Wear goggles—Stop genset and dis- connect charger before disconnecting battery cables—Disconnect negative () cable first and reconnect last.
CAUTION
source before disconnecting battery cables. Otherwise, disconnecting cables can result in voltage spikes damaging to DC control circuits of the set.
WARNING
set can cause severe personal injury or death. Prevent accidental starting by disconnecting the negative () cable from the battery terminal.
Ignition of explosive battery gases
Disconnect battery charger from AC
Accidental starting of the generator
WARNING
this section should be done only by persons trained and experienced in electrical mainte­nance. Improper procedures may result in prop- erty damage, bodily injury or death.
Connecting the genset AC electrical system in- volves:
Each of the operations described in
Installation of transfer switch
Generator output voltage selection
Load cable connection
Standard and optional AC equipment connec-
tions (e.g., control box heater, coolant heater, etc.).
Local regulations often require that wiring connec- tions be made by a licensed electrician, and that the installation be inspected and approved before op- eration. All connections, wire sizes, materials used, etc. must conform to the requirements of electrical codes in effect at the installation site.
WARNING
electrical hazard, resulting in severe personal injury or death and/or property and equipment damage.
Before starting the genset, check to make sure that all electrical connections are secure, and that all wiring is complete. Replace and secure any access panels that have been removed during installation. Check that the load cables from the genset are properly connected.
WARNING
cause electrocution or property damage. Do not connect to any building electrical system ex- cept through an approved device and after building main switch is opened.
Improper wiring can cause a fire or
Backfeed to utility system can
6-1
Page 28
TRANSFER SWITCH
If the installation is for standby service, a transfer switch must be used for switching the load from the normal power source to the genset (see Figure 6-1). Follow the installation instructions provided with the transfer switch when connecting the load and con­trol wiring.
LOAD
NORMAL SOURCE
FIGURE 6-1. TYPICAL LOAD TRANSFER FUNCTION
GENSET
6-2
Page 29
AC WIRING
Generator Voltage Connections
The available generator output voltages and maxi­mum current ratings are specified on the generator set nameplate. Line-to-neutral voltage is always the lower voltage shown and line-to-line voltage is the higher rating.
CAUTION
lower voltages can reduce generator set rat­ings, and also increase line current, rendering line circuit breakers too small. Consult with your distributor before performing reconnec­tion for a different voltage.
Reconfiguring generator sets to
Load Connections
These generators can be configured to the name- plate voltages as shown on the Reconnection Dia- gram located on the side access cover of the power output box. Many of the voltages listed will require reconfiguration of the generator output leads on the connection terminal block. This reconfiguration must only be done by service personnel that are trained and experienced to perform electrical instal- lation. The generator set was adjusted to produce a specified voltage during production verification test- ing prior to shipment. The installer must always check the stator lead terminal block connections and perform any necessary reconnect to obtain the voltage required.
Some generator sets are capable of producing a wide range of voltages and connection configura- tions, others have specific limited capabilities. Re- fer to wiring diagram and generator voltages (from the nameplate) when reviewing the voltage connec- tion information and use the wiring diagram sup- plied with your generator set when actually perform- ing load connections.
CAUTION
higher voltages can exceed the voltage capabil- ity of the specific generator windings and dam- age the generator and also decrease line cur- rent, rendering line circuit breakers too large. Consult with your distributor before performing reconnection for a different voltage.
Reconfiguring generator sets to
Load wires are brought into the stub-up space in the lower left corner of the power output box (Figure 6-2).
Flexible conduit and stranded conductors must be used for connections to take up movement of the generator set.
All loads are connected to the generator by bolting stranded load wires to the appropriate terminals on the generator reconnection terminal block or circuit breaker lugs.
Load Balancing
When connecting loads to the generator set, bal- ance the loads so the current flow from each line ter- minal (L1, L2 and L3) is about the same. This is es- pecially important if both single phase and three phase loads are connected. Any combination of single phase and three phase loading can be used as long as each line current is about the same, with- in 10 percent of median value and no line current ex- ceeds the nameplate rating of the generator. After all load wires are connected, check the current flow from each line, by observing the control panel am- meter. If the control panel does not contain a graphi- cal display, use of a multimeter will be required to check current flow.
6-3
Page 30
Current Transformers
The current transformers (CT’s) are used to display/ monitor genset load in kVA and alternator amper­age. The CT’s must be installed as noted in the fol­lowing CT Installation Requirements.
Refer to the Reconnection Diagram to identify the generator output leads/phase that must be routed through each CT, and also appropriate transformer post selection for control sensing leads. The trans- formers are labeled CT1, CT2 and CT3 on the re- connection wiring diagram. (The Reconnection Dia- gram is located on the power output box cover.)
CT Installation Requirements:
A. The CT has a dot on one side. This dot must be
facing toward the generator (conventional cur­rent flowing into the dot). A dot is also used to indicate pin 1 of the CT.
B. CT1 U load leads (A phase),
CT2 V load leads (B phase) CT3 W load leads (C phase)
C. Route the appropriate generator output lead
through each CT.
D. The CT’s have dual secondaries (3 pins). The
CT secondary wire marked 1 is connected to pin 1 of the CT. CT secondary wire marked 2/3 is connected to pin 2 for above 300 VAC gen- sets or to pin 3 for below 300 VAC gensets. (Re- fer to Reconnection Diagram.)
6-4
Page 31
GENERATOR
LEAD ENTRANCE
CURRENT TRANSFORMERS CT1,
CT2 AND CT3 (WHEN PROVIDED)
THE POLARITY DOTS MUST BE
TOWARDS ALTERNATOR.
LINE CIRCUIT
BREAKERS (WHEN
PROVIDED)
TERMINALS FOR CONNECTING
GENERATOR LEADS ON
OPTIONAL CIRCUIT BREAKER
120-240 VAC TERMINALS FOR GENERATOR HEATER (CONNECTED TO NORMAL
SOURCE)
THESE TERMINALS ARE
LIVE WHEN THE SET IS NOT
RUNNING—DISCONNECT
POWER BEFORE REMOVING
AC OUTPUT BOX COVER.
LOAD WIRING
STUB-UP SPACE
GENSET
GROUNDING
LUG
FIGURE 6-2. POWER OUTPUT BOX
AC CONTROL
WIRING HARNESS
TERMINAL BLOCKS
6-5
LOAD TERMINALS
ON OPTIONAL
CIRCUIT BREAKER
Page 32
Grounding
The following is a brief description of system and equipment grounding of permanently installed AC generators within a facility wiring system. It is impor­tant to follow the requirements of the local electrical code.
Figure 6-3 illustrates typical system grounding for a 3-pole and a 4-pole automatic transfer switch (ATS). In the 3-pole ATS, note that the generator neutral is connected to the ATS and is NOT bonded to ground at the generator. In the 4-pole ATS sys- tem, a grounding electrode conductor and a bond- ing jumper are used to connect the generator neu- tral to ground.
Make sure the genset is grounded to earth in one location only. Use the ground lug provided in the power output box.
WARNING
Electric current can cause severe personal injury or death. Bonding and ground­ing must be done properly. All metallic parts that could become energized under abnormal conditions must be properly grounded.
Typical requirements for bonding and grounding are given in the National Electrical Code, Article
250. All connections, wire sizes, etc. must conform to the requirements of the electrical codes in effect at the installation site.
SERVICE ENTRANCE
THREE-PHASE, FOUR-WIRE UTILITY, THREE-POLE ATS
SERVICE ENTRANCE
GENERATOR SET
3-POLE ATS
LOAD
GENERATOR SET
4-POLE ATS
LOAD
THREE-PHASE, FOUR-WIRE UTILITY, FOUR-POLE ATS
FIGURE 6-3. TYPICAL SYSTEM GROUNDING ONE-LINE DIAGRAMS
6-6
Page 33
CONTROL HEATER (OPTIONAL)
A control heater (Figure 6-4) provides a means of humidity / temperature control of the control box in­terior. It protects the components when the genera-
120V OR
240V PLUG
tor set is subjected to varying ambient air conditions during extended periods of non-use.
The heater is equipped with a power cord that termi­nates with a 120V or 240V NEMA plug.
HEATER
BOTTOM VIEW OF
CONTROL BOX
FIGURE 6-4. OPTIONAL CONTROL HEATER
6-7
Page 34
COOLANT HEATER (OPTIONAL)
A coolant heater keeps engine coolant warm when the engine is shut down. It heats and circulates the coolant within the engine. This reduces startup time and lessens engine wear caused by cold starts. It is electrically operated and thermostatically con­trolled.
OUTLET
TUBE
CAUTION
The coolant heater must not be op­erated while the cooling system is empty or damage to the heater will occur.
Figure 6-5 shows a typical coolant heater installa­tion. Connect the heater to a source of power that will be on during the time the engine is not running. Be sure the supply voltage and circuit amperage is correct for the heater element rating.
COOLANT
HEATER
INLET TUBE
POWER
PLUG
FIGURE 6-5. TYPICAL COOLANT HEATER
6-8
Page 35
GENERATOR HEATER (OPTIONAL)
A generator heater(s) is used to help keep the gen­erator free of condensation when the generator set is not running. During cool and humid conditions, condensation can form within a generator, creating flashing and shock hazards.
The generator heater is connected as shown in Fig­ure 6-6. Terminal strip is located inside of power out­put box (Figure 6-2). Connect 120 or 240 volt AC power to this terminal strip from an outside source so heater is on when genset is not running.
WARNING
Water or moisture inside a genera­tor increases the possibility of flashing and electrical shock, which can cause equipment damage and severe personal injury or death. Do not use a generator which is not dry inside and out.
GENERATOR HEATER
(VIEW AA)
LEADS FROM
GENERATOR HEATER
CONNECTION FOR 120V CONNECTION FOR 240V
CUSTOMER SUPPLIED
POWER LEADS
FIGURE 6-6. TYPICAL GENERATOR HEATER INSTALLATION
6-9
Page 36
THIS PAGE LEFT INTENTIONALLY BLANK
6-10
Page 37
7. Prestart Preparation
GENERAL
Before attempting the initial start of the generator set, be sure to complete the Installation Checklist in Section 8.
INPOWER SERVICE TOOL GENERAL
INFORMATION
InPower is a PC based service tool for the Power- Command
Make adjustments to the controls trims and set-
Perform diagnostics and monitoring.
Create a capture file of the controls trims and
Update control calibrations (InPower PRO ver-
Refer to INPOWER Users Guide for specifics.
®
tings.
settings.
sion).
1.1 controller (PCC). Use InPower to:
InPower Adjust Mode
The adjustment feature allows you to make adjust- ments to genset parameters, calibrations and set- tings. There are several groups of adjustment pa- rameters; note that not all gensets will have the same adjustments available.
InPower Capture File Description
InPower provides a method of extracting (captur- ing) a device’s parameter values. Capturing saves device information in a file that is identified with a .CAP extension.
Capture files are used to store a copy of the gen- set’s parameter values. During genset installation, it is suggested that a capture file be made before and after changes are made to the genset operating parameters. This information can be a very useful
when troubleshooting the genset (determine if pa­rameters/settings have been modified after installa­tion) and when replacement of the Base board is necessary. The capture file can be used as a tem- plate to write the previous settings to the new Base board software.
ELECTRICAL SYSTEM
Verify all electrical connections are secure and all wiring is complete and inspected. Replace and se- cure any access panels that may have been re- moved during installation.
Battery Connections
WARNING
set can cause severe personal injury or death. Make sure that the PCC is in the OFF mode be- fore connecting the battery cables.
Starting the unit requires a 12 volt battery. Connect positive battery cable before connecting negative battery cable to prevent arcing.
Service the batteries as necessary. If an automatic transfer switch is installed without a built-in charge circuit, connect a separate battery charger. Proper selection and maintenance of batteries and battery chargers is essential for system reliability.
WARNING
can cause severe personal injury or death. Al- ways connect negative () battery cable last to prevent arcing.
WARNING
ing on or near battery. Arcing at battery termi- nals, light switch or other equipment, flame, pi- lot lights and sparks can ignite battery gas. Do not smoke, or switch trouble light ON or OFF near battery. Discharge static electricity from body before touching batteries by first touching a grounded metal surface.
Accidental starting of the generator
Ignition of explosive battery gases
Ventilate battery area before work-
7-1
Page 38
PCC OPTIONS PRESTART CHECKS
All generator set configuration options are set at the factory except for site related options, (e.g., Start/ Stop Time Delays, Cycle Crank, Customer Fault 1 and 2, etc.
Adjustment of these options are divided into two categories within the menu driven system. These two categories are Setup and Screen Adjust.
The Setup menus are intended for qualified service personnel only and require a password to modify these submenus (refer to Service manual). The Screen Adjust menu is intended for service person- nel and site personnel.
SCREEN ADJUST MENU
Figure 7-1 shows a block representation of the Screen Adjust menu. The Screen Adjust menu is displayed when the (3) button is pressed in the first Service Menu.
From any of the Operator menus, simultaneously press the and selection buttons for two sec- onds to display the first Service menu.
Adjusting Values/Parameters
1. Press the ADJUST selection button to select
the first parameter or value to be changed.
2. Press the + or selection buttons to adjust val-
ues or select parameters.
3. Press the arrow selection button gate to the next or previous adjustable value or parameter.
4. After adjusting values/selecting parameters, press the SAVE button to save your settings.
NOTE: If the Previous Menu button
pressed before pressing the SAVE but- ton, the changes are not saved.
5. Press the Menu.
button to return to the Service
to navi-
is
Screen Adjust Menu
This menu allows for adjusting the screen’s contrast and brightness and for selecting the units of mea- surement (SAE or SI) to be displayed.
Contrast and Brightness: Press the + or selection buttons to adjust the screen’s con- trast and brightness. Changing the bright- ness setting also affects the brightness of the LEDs on the control panel.
Units: Press the + or selection buttons to select SAE (_F, PSI) or SI (C, kPa) units of measurement to be displayed.
SCREEN ADJUST MENU
FIGURE 7-1. SCREEN ADJUST MENU
7-2
Page 39
STARTING
Refer to the generator set Operator’s manual for im­portant safety precautions and recommended pro­cedures for starting the genset and verifying proper operation. Start the generator set and verify all en­gine and generator menus are displaying the cor­rect values.
7-3
Page 40
THIS PAGE LEFT INTENTIONALLY BLANK
7-4
Page 41
8. Installation Checklist
GENERAL
j Generator set wattage capacity is sufficient to
handle maximum anticipated load.
j At least 3 feet of clearance (or greater for hous-
ing door) is provided around entire generator set for servicing and ventilation.
j Generator set is located in an area not subject
to flooding.
j All operating personnel have read and are fa-
miliar with Operators manual.
j All operators have been thoroughly briefed on
preventive maintenance procedures.
j All operators have read and understand all Im-
portant Safety Instructions in Operators manu- al.
GENERATOR SET SUPPORT
j Floor, roof or earth on which the generator set
rests is strong enough and will not allow shifting or movement. Observe local codes on soil bearing capacity due to freezing and thawing.
j Generator set is properly supported and re-
tained to approved base.
j Supporting base is large enough and is of non-
combustible material extends 6-inches all around set.
COOLING AIR FLOW
j Generator set air inlet is faced into direction of
strongest, prevailing winds.
j Air inlet openings are unrestricted and at least
11/2 times larger than air outlet area.
j Cooling air outlet is on downwind side of build-
ing (if not, wind barrier is constructed).
j Proper ducting material (sheet metal, canvas)
is used between radiator and air outlet.
DIESEL FUEL SYSTEM
j Fuel tanks meet or exceed all Local, State or
National codes.
j Fuel lines are properly installed, supported and
protected against damage.
j Approved flexible fuel line is installed between
main fuel supply line and generator set’s fuel system, near the generator set, to protect the fuel system from damage caused by vibration, expansion and contraction.
j Strainer or fuel screen (100 to 120 mesh) is
installed in the fuel supply line to protect the fuel lift pump, day tank transfer pump or float valve seat from fuel supply tank debris.
j Automatic fuel supply line shutoff valves are
installed to prevent fuel flow in case of leaks.
j No shutoff valves are installed on engine fuel
return line.
j External fuel pumps are connected and opera-
tional at all times (generator set started or shut down).
j Fuel system is properly primed. j No fuel leaks are found in supply line or engine
fuel system.
8-1
Page 42
EXHAUST SYSTEM
AC AND DC WIRING
j Operators are thoroughly briefed on the dan-
gers of carbon monoxide gas.
j Areas around set are well ventilated. No possi-
bility of exhaust fumes entering building doors, windows, or intake fans.
j Exhaust gases are piped safely out-of-doors
and away from building.
j The correct length of approved rigid pipe is
connected to the generator set flexible pipe us- ing approved securing methods with no weight resting on engine exhaust components. There are no bends in flex section.
j Condensation drain is provided in lowest sec-
tion of exhaust piping.
j Exhaust piping is insulated to guard against
burns to personnel.
j Exhaust piping passing through walls or ceil-
ings have approved fire-proof materials and are in compliance with all codes.
j Exhaust piping is large enough in diameter to
prevent excessive back pressure on engine.
j Wire sizes, insulation, conduits and connection
methods all meet applicable codes.
j AC and DC wires are separated in their own
conduit to prevent electrical induction.
j All load, line and generator connections are
proper and correct.
j Flexible conduit between generator set and
building or surrounding structure.
GENERATOR SET PRESTART
j Generator set engine is properly serviced with
oil and coolant.
j Batteries are properly installed, serviced and
charged.
j Battery charger and engine coolant heater are
connected and operational.
j All generator set covers and safety shields are
installed properly.
j All fuel and coolant shutoff valves are opera-
tional.
j Created control capture file of the genset’s pa-
rameter values before and after modifications.
8-2
Page 43
9. Wiring Diagrams
NOTES:
1. TORQUE TERMINALS TO 4.4 IN/LBS (0.5 Nm).
2. WIRE SIZE, 3012 AWG (0.142.5MM) (TB1).
3. WIRE TYPE, USE 60°C RATED MINIMUM. COPPER WIRE (TB1).
4. TERMINAL SCREWS ARE SLOTTED (0.6MM).
5. USE FLAT−BLADED SCREWDRIVER WITH 2.5MM BLADE.
6. STRIP WIRE LENGTH TO 6.0MM.
7. FAULT IN #2 USED FOR OPTIONAL RUPTURE BASIN INPUT.
CUSTOMER CONNECTION DIAGRAM
9-1
Page 44
THIS PAGE LEFT INTENTIONALLY BLANK
9-2
Page 45
Cummins Power Generation
1400 73rd Ave. NE Minneapolis, MN 55432 USA
Phone 1 763 574 5000 Toll-free 1 800 888 6626 Fax 1 763 574 5298 Email ask.powergen@cummins.com www.cumminspower.com
CumminsR, the “C” logo, and “Our energy working for you.” are trademarks of Cummins Inc.
E2008 Cummins Power Generation, Inc. All rights reserved.
Loading...