Redistribution or publication of this documentby any means, is strictly prohibited.
SAVE THESE INSTRUCTIONS − This manual contains
important instructions that should be followed during
installation and maintenance of the generator and batteries.
Before operating the generator set (genset), read the
Operator’s Manual and become familiar with it and the
equipment. Safe and efficient operation can be
achieved only if the equipment is properly operated
and maintained. Many accidents are caused by failure
to follow fundamental rules and precautions.
The following symbols, found throughout this manual,
alert you to potentially dangerous conditions to the operator, service personnel, or the equipment.
This symbol warns of immediate
hazards which will result in severe personal injury or death.
WARNING
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
CAUTION
This symbol refers to a hazard or unsafe practice which can result in personal injury
or product or property damage.
FUEL AND FUMES ARE FLAMMABLE
Fire, explosion, and personal injury or death can result
from improper practices.
• DO NOT fill fuel tanks while engine is running, un-
less tanks are outside the engine compartment.
Fuel contact with hot engine or exhaust is a potential
fire hazard.
• DO NOT permit any flame, cigarette, pilot light,
spark, arcing equipment, or other ignition source
near the generator set or fuel tank.
• Fuel lines must be adequately secured and free of
leaks. Fuel connection at the engine should be
made with an approved flexible line. Do not use zinc
coated or copper fuel lines with diesel fuel.
• Be sure all fuel supplies have a positive shutoff
valve.
• Be sure battery area has been well-ventilated prior
to servicing near it. Lead-acid batteries emit a highly
explosive hydrogen gas that can be ignited by arcing, sparking, smoking, etc.
EXHAUST GASES ARE DEADLY
Provide an adequate exhaust system to properly
•
expel discharged gases away from enclosed or
sheltered areas and areas where individuals are
likely to congregate. Visually and audibly inspect
the exhaust daily for leaks per the maintenance
schedule. Make sure that exhaust manifolds are secured and not warped. Do not use exhaust gases to
heat a compartment.
• Be sure the unit is well ventilated.
• Engine exhaust and some of its constituents are
known to the state of California to cause cancer,
birth defects, and other reproductive harm.
MOVING PARTS CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH
•
Keep your hands, clothing, and jewelry away from
moving parts.
• Before starting work on the generator set, discon-
nect battery charger from its AC source, then disconnect starting batteries, negative (−) cable first.
This will prevent accidental starting.
• Make sure that fasteners on the generator set are
secure. Tighten supports and clamps, keep guards
in position over fans, drive belts, etc.
• Do not wear loose clothing or jewelry in the vicinity of
moving parts, or while working on electrical equipment. Loose clothing and jewelry can become
caught in moving parts.
• If adjustment must be made while the unit is run-
ning, use extreme caution around hot manifolds,
moving parts, etc.
DO NOT OPERATE IN FLAMMABLE AND
EXPLOSIVE ENVIRONMENTS
Flammable vapor can cause an engine to overspeed and
become difficult to stop, resulting in possible fire, explosion, severe personal injury and death. Do not operate a
genset where a flammable vapor environment can be
created by fuel spill, leak, etc., unless the genset is
equipped with an automatic safety device to block the air
intake and stop the engine. The owners and operators of
the genset are solely responsible for operating the genset safely. Contact your authorized Cummins Power
Generation distributor for more information.
LS-15M
iii
Page 6
ELECTRICAL SHOCK CAN CAUSE
Redistribution or publication of this documentby any means, is strictly prohibited.
SEVERE PERSONAL INJURY OR DEATH
•
Remove electric power before removing protective
shields or touching electrical equipment. Use rubber insulative mats placed on dry wood platforms
over floors that are metal or concrete when around
electrical equipment. Do not wear damp clothing
(particularly wet shoes) or allow skin surface to be
damp when handling electrical equipment. Do not
wear jewelry. Jewelry can short out electrical contacts and cause shock or burning.
• Use extreme caution when working on electrical
components. High voltages can cause injury or
death. DO NOT tamper with interlocks.
• Follow all applicable state and local electrical
codes. Have all electrical installations performed by
a qualified licensed electrician. Tag and lock open
switches to avoid accidental closure.
• DO NOT CONNECT GENERATOR SET DI-
RECTLY TO ANY BUILDING ELECTRICAL SYSTEM. Hazardous voltages can flow from the generator set into the utility line. This creates a potential
for electrocution or property damage. Connect only
through an approved isolation switch or an approved paralleling device.
MEDIUM VOLTAGE GENERATOR SETS
(601V to 15kV)
•
Medium voltage acts differently than low voltage.
Special equipment and training is required to work
on or around medium voltage equipment. Operation
and maintenance must be done only by persons
trained and qualified to work on such devices. Improper use or procedures will result in severe personal injury or death.
• Do not work on energized equipment. Unauthorized
personnel must not be permitted near energized
equipment. Due to the nature of medium voltage
electrical equipment, induced voltage remains even
after the equipment is disconnected from the power
source. Plan the time for maintenance with authorized personnel so that the equipment can be de-energized and safely grounded.
GENERAL SAFETY PRECAUTIONS
Coolants under pressure have a higher boiling point
•
than water. DO NOT open a radiator or heat ex-
changer pressure cap while the engine is running.
To prevent severe scalding, let engine cool down
before removing coolant pressure cap. Turn cap
slowly, and do not open it fully until the pressure has
been relieved.
•Used engine oils have been identified by some state
or federal agencies as causing cancer or reproductive toxicity . When checking or changing engine oil,
take care not to ingest, breathe the fumes, or contact used oil.
•Keep multi-class ABC fire extinguishers handy.
Class A fires involve ordinary combustible materials
such as wood and cloth; Class B fires, combustible
and flammable liquid fuels and gaseous fuels; Class
C fires, live electrical equipment. (ref. NFP A No. 10).
•Make sure that rags are not left on or near the gener-
ator set.
•Make sure generator set is mounted in a manner to
prevent combustible materials from accumulating
under or near the unit.
•Remove all unnecessary grease and oil from the
unit. Accumulated grease and oil can cause overheating and engine damage which present a potential fire hazard.
•Keep the generator set and the surrounding area
clean and free from obstructions. Remove any debris from the set and keep the floor clean and dry.
•Do not work on this equipment when mentally or
physically fatigued, or after consuming any alcohol
or drug that makes the operation of equipment unsafe.
•Substances in exhaust gases have been identified
by some state or federal agencies as causing cancer or reproductive toxicity. Take care not to breath
or ingest or come into contact with exhaust gases.
•Do not store any flammable liquids, such as fuel,
cleaners, oil, etc., near the generator set. A fire or
explosion could result.
•Wear hearing protection when going near an oper-
ating generator set.
•To prevent serious burns, avoid contact with hot
metal parts such as radiator system, turbo charger
system and exhaust system.
KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE
iv
Page 7
1. Introduction
Redistribution or publication of this documentby any means, is strictly prohibited.
ABOUT THIS MANUAL
This manual provides troubleshooting and repair
information regarding the PowerCommand
Control 3100 (PCC) and generators for the
generator set (genset) models listed on the front
cover. Engine service instructions are in the
applicable engine service manual. Operating and
maintenance instructions are in the applicable
Operator’s Manual.
This manual does not have instructions for
servicing printed circuit board assemblies. After
determining that a printed circuit board assembly is
faulty, replace it. Do not repair it. Attempts to repair a
printed circuit board can lead to costly damage to
the equipment.
This manual contains basic (generic) wiring
diagrams and schematics that are included to help
in troubleshooting. Service personnel must use the
actual wiring diagram and schematic shipped with
each unit. The wiring diagrams and schematics that
are maintained with the unit should be updated
when modifications are made to the unit.
Read
Safety Precautions
instructions and precautions in this manual.
and carefully observe all
TEST EQUIPMENT
To perform the test procedures in this manual, the
following test equipment must be available
• True RMS meter for accurate measurement of
small AC and DC voltages. Fluke models 87 or
8060A are good choices.
• Grounding wrist strap to prevent circuit board
damage due to electrostatic discharge (ESD).
• Battery Hydrometer
• Jumper Leads
• Tachometer or Frequency Meter
• Wheatstone Bridge or Digital Ohmmeter
• Variac
• Load Test Panel
• Megger or Insulation Resistance Meter
• PCC Service Tool Kit (Harness Tool and Sen-
sor Tool)
HOW TO OBTAIN SERVICE
Always give the complete Model, Specification and
Serial number of the generator set as shown on the
nameplate when seeking additional service
information or replacement parts. The nameplate is
located on the side of the generator output box.
WARNING
parts can result in severe personal injury or
death, and/or equipment damage. Service personnel must be trained and experienced to perform electrical and mechanical service. Read
and follow Safety Precautions, on pages iii and
iv.
Incorrect service or replacement of
Copyright2001 Cummins Power Generation. All rights reserved.
Cummins and PowerCommand are registered trademarks of Cummins Inc.
1-1
Page 8
SYSTEM OVERVIEW
Redistribution or publication of this documentby any means, is strictly prohibited.
The PCC is a microprocessor-based control for
Cummins generator sets. It provides fuel control
and engine speed governing, main alternator
voltage output regulation, and complete generator
set control and monitoring. It also provides controls
for automatic and semi-automatic synchronizing
and automatic load sharing controls for both
isolated bus or utility (mains) paralleling
applications.
The operating software provides control of the
generator set and its performance characteristics,
and displays performance information on a digital
display panel. It accepts menu-driven control and
setup input from the push button switches on the
front panel.
GENERATOR SET CONTROL FUNCTION
Figure1-1 shows some of the control functions. A
more complete block diagram is provided in Section
3. A system schematic is provided in
Section 9
.
The PCC monitors frequency from both the
magnetic pick-up (MPU) and the main stator inputs.
The control sends a low power pulse-width
modulated (PWM) signal to the governor output
module, which then sends an amplified signal to the
engine fuel control.
The Bus PT module reduces the bus voltage to
approximately 18 VAC and provides a signal to the
control for reference in synchronizing the generator
set to the system bus.
The external PT/CT module reduces generator
voltage to approximately 18 VAC, and produces a
representative AC voltage from CT output current.
The voltage regulation function sends a low power
PWM signal to the voltage regulator output module,
which then sends an amplified signal to the exciter
stator.
Oil, coolant, and exhaust temperatures are sensed
by variable resistance element sensors. Oil
pressure is sensed by a capacitive element active
sensor.
Governor
Output
Regulator
Output
PMG
•
Fuel
Control
NS
•
•
2
3
4
11234
MPU
Bus PT
Module
•
•
Sensors
Battery
BT1
To
•
Load
FIGURE 1-1. GENERATOR SET CONTROL FUNCTIONS
1-2
Page 9
2. Control Operation
Redistribution or publication of this documentby any means, is strictly prohibited.
GENERAL
The following describes the function and operation
of the PowerCommand generator set control. All indicators, displays, meters and control switches are
located on the face of the control panel as illustrated
in Figure 2-1.
The PCC control cabinet must be opened only by
technically qualified personnel.
Normally, generator set configuration options are
set at the factory . When a new control is installed on
a generator set or when parts are replaced, the control must be configured for that generator set with
the use of the “Initial Start Setup” portion of the internal software. Setup and calibration procedures are
described in
The automatic voltage regulator (AVR) and governor operation characteristic adjustments are also
described in
Section 5
Section 5
.
.
SAFETY CONSIDERATIONS
AC power is present when the set is running. Do not
open the generator output box while the set is running.
WARNING
nents can cause electrocution, resulting in severe personal injury or death. Do not open the
generator output box while the set is running.
Read and observe all WARNINGS and CAUTIONS in your generator set manuals.
CAUTION
opened only by technically qualified personnel.
Lower level voltages (18 VAC to 24 VDC) are
present in PCC control cabinet. These voltages
can cause electrical shock, resulting in personal injury.
Even with power removed, improper handling
of components can cause electrostatic discharge and damage to circuit components.
Contacting high voltage compo-
The PCC control cabinet must be
2-1
Page 10
SEQUENCE OF OPERATION
Redistribution or publication of this documentby any means, is strictly prohibited.
When the PowerCommand control is in the AUTO
mode, it will cause the generator set to start on receiving a signal from a remote device. The PowerCommand control will initiate a starter cranking signal and verify that the engine is rotating. The PowerCommand control will provide sufficient fuel to the
engine to accelerate to start disconnect speed. On
reaching that speed, the control will ramp the generator set to rated speed and voltage.
On reaching rated speed and voltage, the PowerCommand control checks the system bus voltage. If
no bus voltage is present, it will wait for a pulse from
a remote Master First Start Sensor. On receiving
that pulse, the control will signal the paralleling
breaker to close.
If bus voltage is present, the PowerCommand control will check for proper phase rotation, adjust the
generator set to the bus voltage and frequency level, and then synchronize the generator set to the
system bus. When a synchronous condition is
achieved, the control will send a signal to close the
paralleling breaker.
When the paralleling breaker is closed, the generator set will assume it’s proportional share of the total
load on the system bus.
PCC POWER ON / STANDBY MODE
Standby Mode
In the Standby (sleep) mode (selector switch S5 on
the Digital Board is set to the right and the generator
set is not running), the control’s operating software
is inactive and the LEDs and displays on front panel
are all off.
The operating software is initialized and the front
panel is turned on in response to a run signal or any
one of eight “wake up” inputs from remote sensing
switches.
The wake up signals are:
• Emergency Stop
• Low Coolant Level
• Low Coolant Temperature
• Low Fuel
• Customer Fault Inputs 2 and 3
• Run Selected on Run/Off/Auto Switch
• Remote Start Signal in Auto Mode
• Self Test switch
To activate and view the menu displays, press and
release the Self Test switch. The PCC will initialize
the operating software and permit operation of the
menu display panel. If no menu selections are
made, the power to the control panel will shut down
after 30 seconds.
Power On Mode
In the Power On (awake) mode (selector switch S5
on the Digital Board is set to the left), the PCC will
initialize the operating software and permit operation of the menu display panel. (See Figure 3-1 for
S5 location.) Power will stay on until switch (S5) is
set to the Standby mode. It is recommended that
switch S5 be left in the Power On mode in all applications, except those where auxiliary battery
charging is not available.
CAUTION
circuit boards. Always wear a grounding wrist
strap when touching or handling circuit boards
or socket-mounted ICs and when disconnecting or connecting harness connectors.
Electrostatic discharge will damage
2-2
Page 11
KILOWATT
Redistribution or publication of this documentby any means, is strictly prohibited.
METER
(PERCENT LOAD)
FREQUENCY
METER
AC
VOLTMETER
(DUAL SCALE)
AC AMMETER
(PERCENT AMPS)
MENU
SELECTION
SWITCH
(1 of 4)
ACTIVE SWITCH
INDICATOR
(1 of 6)
ALPHANUMERIC
DISPLAY
UPPER AND LOWER
SCALE INDICATOR
PCC 3100
LABEL
PARALLELING
BREAKER
SWITCHES AND
INDICATORS
RUN/OFF/AUTO
SWITCH
RESET
SWITCH
SELF TEST
SWITCH
NON-AUTOMATIC
WARNING
SHUTDOWN
STATUS INDICATORS
MENU
SWITCH
PANEL LAMP
SWITCH
PHASE SELECTOR
FIGURE 2-1. FRONT PANEL (PCC 3100)
2-3
EMERGENCY
STOP PUSH
BUTTON
SWITCH AND
INDICATORS
Page 12
FRONT PANEL
Redistribution or publication of this documentby any means, is strictly prohibited.
Figure 2-1 shows the features of the front panel.
AC Voltmeter:
voltage. Measurement scale in use is shown on
scale indicator lamp.
AC Ammeter:
maximum rated current. (Percent current is based
on .8 PF.)
Kilowatt Meter:
put as percent of rated load.
Dual scale instrument indicates AC
Indicates current output in percent of
Indicates 3-phase AC power out-
Reset Switch:
Press this switch to reset warning
and shutdown messages after the condition has
been corrected. To reset a shutdown message with
the Reset switch, the Run/Off/Auto switch must be
in the Off position.
With the Run/Off/Auto switch in the Auto mode,
shutdown faults can be reset by removing the remote start input and then cycling the remote reset
input.
Self T est Switch:
Press and hold this switch to light
all front panel LEDs and cycle through all shutdown
and warning messages.
Frequency Meter:
Indicates generator output fre-
quency in hertz.
Upper and Lower Scale Indicator Lamps:
Indi-
cate AC voltmeter scale.
Digital Display:
This two-line, 16-character per line
alphanumeric display is used in the menu-driven
operating system, in conjunction with the display
menu selection switches and the Menu switch. Refer to the menu trees later in this section. The display is also used to show warning and shutdown
messages.
Display Menu Selection Switches:
Four momentary switches—two on each side of the digital display window—are used to step through the various
menu options and to adjust generator set parameters. The green arrow adjacent to the switch is lit
when the switch can be used (switch is “active”).
Menu Switch:
Press this switch to return the digital
display to the MAIN MENU. Refer to the menu trees
later in this section.
In the Standby (sleep) mode, with the generator set
not running, the control’s operating software is inactive and the LEDs and displays on front panel are all
off.
To activate and view the menu displays without
starting the generator set, press and hold the Self
Test switch until the front panel LEDs light. The
PCC will initialize the operating software and permit
operation of the menu display panel. If no menu
selections are made, a software timer will shut
down the power after 30 seconds.
Panel Lights Switch:
Press this switch to turn control panel illumination on and off. The illumination
will shut off after about eight minutes.
Phase Selector Switch and Indicators:
Press this
momentary switch to select phases of generator
output to be measured by the analog AC voltmeter
and ammeter. LEDs indicate the selected phase.
Run/Off/Auto Switch:
This switch starts and stops
the set locally, or enables start/stop control of the
engine from a remote location. (Ground to start.)
2-4
Page 13
Emergency Stop Button:
Redistribution or publication of this documentby any means, is strictly prohibited.
Push the button in for
emergency shutdown of the engine.
Remote Reset switch will not reset emergency stop.
Can only be reset at the PCC front panel.
To reset:
1. Pull the button out or turn the button clockwise
(button with arrow) and allow it to pop out.
2. Move the Run/Off/Auto switch to Off.
3. Press the front panel Reset switch.
4. Select Run or Auto, as required.
Shutdown Status Indicator:
This red lamp is lit
whenever the control detects a shutdown condition.
After the condition is corrected, shutdown indicators can be reset by turning the Run/Off/Auto switch
to the Off position, and pressing the Reset switch.
In Auto mode, shutdowns can be reset by removing
the remote start input and then cycling the remote
reset input.
Emergency Stop shutdown status (Code 102) can be
reset only at the PCC front panel.
Non-Automatic Status Indicator:
This red lamp
flashes continuously when the Run/Off/Auto switch
is not in the Auto position.
Warning Status Indicator:
This yellow lamp is lit
whenever the control detects a warning condition.
After the condition is corrected, warning indicators
can be reset by pressing the Reset switch. (It is not
necessary to stop the generator set.)
With the Run/Off/Auto switch in the Auto mode,
warnings can also be reset by cycling the remote reset input after the condition is corrected.
Paralleling Breaker Switches and Indicators:
These two switches are used to manually open or
close the paralleling breaker of the generator set.
The lamps are used to indicate the opened or
closed position of the paralleling breaker.
The Breaker Operation switches are operational only
when the Run/Off/Auto switch is in the Run position.
The breaker will close when the generator set is synchronized with the system bus, or if the system bus
is de-energized.
2-5
Page 14
FIGURE 2-2. DIGITAL DISPLAY AND MENU SELECTION SWITCHES
Redistribution or publication of this documentby any means, is strictly prohibited.
MENU DISPLAY AND SWITCHES
Figure 2-2 shows the digital display and the menu
selection switches. Refer to heading “
which describes the menu display and switches.
In the Standby Mode, to activate and view the menu
displays without starting the generator set, press
and release the Self Test switch. This will initialize
the PCC operating software and permit operation of
the menu display panel. If no menu selections are
made, a software timer will shut down the power after 30 seconds. In the Power On Mode, power is
continuously supplied to the control panel. Display
will always remain on.
In the digital display, the “>>” symbol indicates that
selecting the adjacent button causes the operating
program to branch to the next menu display—as
shown in the menu diagrams.
In the digital display, the “<<” symbol indicates that
selecting the adjacent button causes the operating
program to go back to the previous menu display.
Front Pane
MAIN MENU
The facing page shows the main menu and a block
representation of the available submenus.
l”
As shown in the diagram, the main menu can
branch into one of four directions.
To display engine parameters, such as oil pressure
and temperature, water temperature, engine speed
(RPM), and exhaust temperature, press the button
next to the word “ENGINE” in the display. Refer to
ENGINE MENU
in this section.
To display generator parameters, such as volts,
amps, power (kW), and frequency, press the button
next to the word “GEN” in the display. Bus voltage,
frequency and a digital synchroscope can also be
viewed from this menu branch. Turn to the
MENU
in this section.
GEN
To adjust output voltage and frequency, or start and
stop delays, press the button next to the word “ADJUST” in the display. Refer to
Section 5
.
ADJUST MENU
in
To display the selected generator set model and the
resident version software, press the button next to
the “>>” in the display. Refer to
PLAYS MENUS
in
Section 5
VERSION & DIS-
.
2-6
Page 15
MAIN MENU
Redistribution or publication of this documentby any means, is strictly prohibited.
PAGES 2-8 & 2-9
RPM<<
EXHAUST
BATTERY<<
HOURS>>
OIL<<
COOLANT>>
PAGES 2-10 & 2-11
%GOV / REG<<
FREQUENCY
POWER<<
KW HRS>>
VOLTS<<
AMPS>>
ENGINEGEN
<>
ADJUST>>
<>
RESET MENU>
CLEAR WARNING AND
SHUTDOWN MESSAGES
RETURN TO
MAIN MENU
⇑ VOLTAGE
⇓ _______>>
⇑ FREQUENCY
⇓ _______>>
⇑ START DELAY
⇓ _______ SEC >>
⇑ STOP DELAY
⇓ _______SEC>>
⇑ IDLE SPEED
⇓ _______RPM >>
SECTION 5
INACTIVE BUTTON
< ACTIVE BUTTON
<ACTIVE BUTTON SELECTED
SECTION 5
SECTION 5
SECTION 5
VERSION
SETUP / CAL
HISTORY
(ACCESS CODE)
DISPLAY CAL<<
METERS>>
GOV / REG<<
PARALLELSETUP
2-7
Page 16
ENGINE MENU
Redistribution or publication of this documentby any means, is strictly prohibited.
The facing page shows a block representation of
the ENGINE menu. If you press the button next to
the word “ENGINE” in the display, the first ENGINE
submenu will appear.
As shown in the diagram, the ENGINE menu has
three submenus.
OIL/COOLANT submenu:
This is the first submenu. Select OIL for a display of oil pressure and oil
temperature. Select COOLANT for a display of
coolant temperature. When oil or coolant parameters are displayed, pressing the button next to the
“<<” will return the display (“BACK”) to the OIL/
COOLANT submenu.
BATTERY/HOURS submenu:
From the OIL/
COOLANT submenu, press the button next to the
“>>” in the display to move to the BATTERY/
HOURS submenu. Select BATTERY for a display
of battery voltage. Select HOURS for a display of
the number of starts and the running hours. When
battery or hours parameters are displayed, pressing the button next to the “<<” will return the display
(“BACK”) to the BATTERY/HOURS submenu.
RPM/EXHAUST submenu:
From the BATTERY/
HOURS submenu, press the button next to the “>>”
in the display to move to the RPM/EXHAUST submenu. Select RPM for a display of engine RPM.
Select EXHAUST for a display of the (optional) exhaust temperature. When RPM or exhaust parameters are displayed, pressing the button next to the
“<<” will return the display (“BACK”) to the RPM/EXHAUST submenu.
2-8
Page 17
ENGINE
Redistribution or publication of this documentby any means, is strictly prohibited.
<>
ENGINEGEN
ADJUST>>
<>
<>
OIL<<
<>
COOLANT>>
<>
OIL<<
<>
COOLANT>>
___PSI / KPA<<
°F / °C
___
L___
°F / °C<<
°F / °C (or N/A)
R___
BACK
>
BACK
>
<>
OIL<<
<>
COOLANT>>
<>
OIL<<
<>
COOLANT>>
<>
BATTERY<<
<>
HOURS>>
<>
BATTERY<<
<>
HOURS>>
<>
BATTERY<<
<>
HOURS>>
<>
BATTERY<<
<>
HOURS>>
<>
ENGINEGEN
<>
ADJUST>>
BATTERY<<
___VDC
STARTS ___<<
HOURS ___
<>
OIL<<
<>
COOLANT>>
BACK
>
BACK
>
<>
RPM<<
<
EXHAUST
<>
RPM<<
<
EXHAUST
<>
RPM<<
<
EXHAUST
RPM<<
___
L___°F/°C (or N/A) <<
°F/°C (or N/A)
R___
<>
BATTERY<<
<>
HOURS>>
Indicates OR" Condition
2-9
BACK
>
BACK
>
Page 18
GEN MENU
Redistribution or publication of this documentby any means, is strictly prohibited.
The facing page shows a block representation of
the GEN menu. If you press the button next to the
word “GEN” in the display, the first GEN submenu
will appear.
As shown in the diagram, the GEN menu has three
submenus.
VOLTS/AMPS submenu:
This is the first submenu. Select VOLTS for a display of a line-to-line or
line-to-neutral selection, or for viewing of the system bus line-to-line voltage. Select line-line or lineneutral for the desired voltage display. Select
AMPS for a display of L1, L2, and L3 current in
amps. When voltage or current parameters are displayed, pressing the button next to the “<<” will return the display (“BACK”) to the L-L/L-N submenu.
If DELTA is selected in the Initial Start Setup submenu, when selecting VOLTS, the “line-line” or “lineneutral” submenus will not be displayed, only the
L12, L23, L31 submenu will be displayed.
POWER / KW HOURS submenu:
From the
VOLTS/AMPS submenu, press the button next to
the “>>” in the display to move to the POWER/KW
HOURS submenu. Select POWER for a display of
power output in kilowatts and a power factor value.
Select KW HOURS for a display of kilowatt hours.
When power or kW hours parameters are displayed, pressing the button next to the “<<” will re-
turn the display (“BACK”) to the POWER/KW
HOURS submenu.
The PF reading will contain an asterisk if the power
factor is leading (for example, *.3PF).
Beginning Version 1.06, N/A is displayed in the PF
field when the generator set is not running.
%GOV/REG/FREQUENCY submenu:
From the
POWER/KW HOURS submenu, press the button
next to the “>>” in the display to move to the %GOV/
REG/FREQUENCY submenu. Select %GOV/REG
for a display of voltage regulator and governor duty
cycle (drive) levels in percentage of maximum. Select FREQUENCY for a display of the generator
output frequency the bus frequency, or the digital
synchroscope. When voltage regulator and governor or frequency parameters are displayed, pressing the button next to the “<<” will return the display
(“BACK”) to the %GOV/REG/FREQUENCY submenu.
Bus Frequency (Digital Synchroscope) submenu:
When the bus frequency (digital synchroscope)
information is displayed, the operator can observe
the generator set synchronizing with the system
bus. The display indicates bus frequency and number of degrees from synchronous condition (+ indicates faster, − indicates slower). When the generator set is operating within the sync-check window,
an asterisk will indicate that the paralleling breaker
can be closed.
2-10
Page 19
<>
Redistribution or publication of this documentby any means, is strictly prohibited.
ENGINEGEN
ADJUST>>
<>
<>
VOLTS<<
AMPS>>
<>
VOLTS<<
<>
AMPS>>
L − L<<
L − NBUS
<<>
<>
L − L<<
L − NBUS
<
L − L<<
L − NBUS
<
L − L<<
<>
L − NBUS
<
L1 L2 L3<<
___ ___ ___
GEN
BACK
BACK
>
L12 L23 L31<<
___ ___ ___
L1N L2N L3N<<
___ ___ ___
L12 L23 L31<<
___ ___ ___
BACK
><>
BACK
>
BACK
><>
<>
VOLTS<<
<>
AMPS>>
<>
VOLTS<<
<>
AMPS>>
<>
ENGINEGEN
ADJUST>>
<>
<>
POWER<<
KW HRS>>
<>
<>
POWER<<
KW HRS>>
<>
<>
POWER<<
KW HRS>>
<>
<>
POWER<<
KW HRS>>
<>
<>
%GOV / REG<<
FREQUENCY
<
<>
%GOV / REG<<
FREQUENCY
<
BACK
BACK
___ KW<<
___ PF
KW HRS <<
____________
<>
%GOV / REG<<
FREQUENCY
<
GOV__ %<<
REG__ %
FREQUENCY<<
___ HZBUS
>
BACK
>
BACK
BACK
>
BACK
>
Indicates OR" Condition
2-11
FREQUENCY<<
___ HZBUS
BUS FREQUENCY<<
___ HZ___ DEG
>
BACK
>
Page 20
THIS PAGE LEFT INTENTIONALLY BLANK
Redistribution or publication of this documentby any means, is strictly prohibited.
2-12
Page 21
3. Circuit Boards and Modules
Redistribution or publication of this documentby any means, is strictly prohibited.
GENERAL
This section describes the function of the PCC circuit boards and modules that are contained in the
control panel (Figure 3-1) and the accessory box.
The block diagram in Figure 3-2, shows both internal and external components of the PCC system.
STANDBY SWITCH
DISPLAY BOARD
A35
The system schematics are provided in
this manual.
CAUTION
circuit boards. Always wear a grounding wrist
strap when touching or handling circuit boards
or socket-mounted ICs.
S5 POWER ON/
Section 9
of
Electrostatic discharge will damage
J1 (FOR INPOWER
SERVICE TOOL)
DIGITAL BOARD
A32
GENSET
COMM.
BOARD
A41
ANALOG
BOARD
A33
RUN/OFF/AUTO
SWITCH S12
BUS PT MODULE
A39
VOLTAGE REGULATOR
OUTPUT MODULE
A37
ENGINE INTERFACE
A31
ACCESSORY BOX
(HC 4/5)
FIGURE 3-1. CIRCUIT BOARD LOCATIONS
CUSTOMER INTERFACE
A34
GOVERNOR
OUTPUT MODULE
A38
PT/CT
BOARD
A36
3-1
Page 22
Redistribution or publication of this documentby any means, is strictly prohibited.
FIGURE 3-2. BLOCK DIAGRAM
3-2
Page 23
DIGITAL BOARD (A32)
Redistribution or publication of this documentby any means, is strictly prohibited.
Connectors
The digital circuit board (Figure 3-3) contains the
microprocessor and the operational software for the
control. It connects to all other boards inside the
control. This board also provides the analog-to-digital conversions for the PCC.
Switch
S5Slide the switch to the left to select the Power
On (awake) mode. Control panel power/operating software will remain on until the switch is
reset to the Standby mode. It is recommended that switch S5 be left in the Power On
mode in all applications, except those where
auxiliary battery charging is not available.
Slide right to put the PCC in the Standby
(“sleep”) mode. In this mode, the PCC operating software will be initiated by selection of
Run on the front panel, by pressing the Self
Test switch, by a remote start input (in Auto
mode), or by any one of several “wake-up”
signals from external switches.
The digital board has five connectors. They are:
J1For InPower Service Tool
J2Connects to J4 on A34 Customer Interface
board
J3Connects to J2 on A33 Analog board
J4Connects to J1 on A31 Engine Interface
board
J5Connects to J5 o n A35 Digital Display assem-
bly
LEDs
The digital board has seven LED’s that indicate the
following conditions:
DS1 Spare (Green)
DS2 Spare (Green)
DS3 +18 VDC supply OK (Green)
DS4 +5 VDC supply OK (Green)
DS5 Run (Flashes once per second if software
is running) (Green)
DS6 +24 VDC B+ supply OK (Green)
DS7 +12 VDC supply OK (Green)
DS1
DS2
DS3
DS4
DS7
DS6
DS5
FIGURE 3-3. DIGITAL BOARD
3-3
Page 24
ENGINE INTERFACE BOARD (A31)
Redistribution or publication of this documentby any means, is strictly prohibited.
The engine interface board (Figure 3-4) reads user
control inputs, monitors engine, generator and system status, and initiates the appropriate action for
normal operating and fault conditions (warning or
shutdown).
J4Connects to customer connections and to en-
gine harness which includes magnetic pick-
up.
J5Connects to engine sensors.
J6Connects to Genset Control module (GCM).
J7Connects to Genset Control module (GCM).
This board is connected to the engine sensors, battery , starter, governor output module, voltage regulator output module, and the magnetic pick-up
(MPU).
The engine interface board can also be connected
to an optional network interface module for network
access.
During a typical start sequence the LED’s light as
follows:
1. DS11 lights when a remote run signal is re-
ceived and S12 is in the Auto possition, or S12
is moved to the Run position.
2. DS12 lights when the magnetic pick-up voltage
is sensed (engine is cranking). (When the engine is cranking, the mag pickup output should
be a minimum of 1 volt.)
3. DS11 extinguishes, DS9 lights and DS10 is
dimly lit when the generator is running.
Connectors
The engine interface board has seven connectors
and one terminal strip. They are:
J1Connects to J4 on A32 Digital board.
J2Connects to J1 on A33 Analog board.
J3Connects to display board, front panel
switches and meters.
Fuses
The engine interface board has two replaceable
fuses. They are:
The engine interface board has 10 LED’s that indicate the following conditions:
DS1Low Fuel Alarm input (Red)
DS2Low Coolant Level Alarm input (Red)
DS3Low Engine Temperature Alarm input (Red)
DS4S12 in Run position (Green). S12 is the Run/
Off/Auto switch.
DS5S12 in Auto position (Green)
DS6Emergency Stop (Red)
DS7Not configured.
DS8Not configured.
DS9Automatic voltage regulator duty cycle
(Green). Brighter indicates larger duty
cycle.
DS10 Governor duty cycle (Green). Brighter indi-
cates larger duty cycle.
DS11 Start pilot relay output (Red)
DS12 Run pilot relay output (Red)
3-4
Page 25
DS1 - LOW FUEL
Redistribution or publication of this documentby any means, is strictly prohibited.
DS2 - LO COOL
DS3 - LET
DS4 - RUN SW
DS5 - AUTO
DS6 - E-STOP
DS9 - REG
DS10 - GOV
DS11 - START
DS12 - RUN RLY
5A CNTRL B+
5A AUX B+
FIGURE 3-4. ENGINE INTERFACE BOARD
3-5
Page 26
ANALOG BOARD (A33)
Redistribution or publication of this documentby any means, is strictly prohibited.
Connectors
The analog board (Figure 3-5) is the only circuit
board inside the control that has no LED’s. There
are two versions of the analog board that are used
for paralleling and non-paralleling systems.
This board interprets all analog input signals and
converts the analog signals to 0−5 VDC for the digital board.
The analog board has four connectors with ribbon
cables permanently soldered to them. They are:
J1Connects to J2 on A31 Engine Interface
board
J2Connects to J3 on A32 Digital board
J3Spare analog inputs
J4Connects to J1 on A34 Customer Interface
board
FIGURE 3-5. ANALOG BOARD
3-6
Page 27
DIGITAL DISPLAY BOARD (A35)
Redistribution or publication of this documentby any means, is strictly prohibited.
The digital board (Figure 3-6) connects to all meters
and the LED display.
Connectors
The digital board has three connectors. They are:
J1Connects to front panel membrane switches
J5Connects to J2 on A32 Digital board. (With J5
disconnected, the display will be non-functional, but the PCC will continue to operate.)
J6Connects to meters, Run/Off/Auto switch, J3
on A31 Engine Interface board
LEDs
The digital board has 18 LED’s that are used to indicate operational status of the generator set and
control panel mode/switch selections.
DS9Not In Auto (Red)
DS10 Upper Scale (Green)
DS11 Left Top Arrow (Green)
DS12 Right Top Arrow (Green)
DS13 Warning (Amber)
DS14 Lower Scale (Green)
DS15 Shutdown (Red)
DS20 Left Bottom Arrow (Green)
DS21 Right Bottom Arrow (Green)
DS22 Automatic mains failure (AMF) or paralleling
application only: Breaker Closed (Red)
DS23 Phase A (Green)
DS24 Reset Arrow (Green)
DS25 Menu Arrow (Green)
DS26 AMF application only: Breaker Open
(Green)
DS27 Phase B (Green)
DS29 Phase C (Green)
DS36 AMF application: Breaker Closed (Red) − or
− paralleling application: Breaker Open
(Green)
DS37 AMF application only: Breaker Open
(Green)
DS9
DS13
DS15
DS22
DS26
DS36
DS37
DS11
DS20
DS24
FIGURE 3-6. DIGITAL DISPLAY BOARD
DS12
DS21
DS25
DS10
DS14
DS23
DS27
DS29
3-7
Page 28
CUSTOMER INTERFACE BOARD (A34)
Redistribution or publication of this documentby any means, is strictly prohibited.
The customer interface board (Figure 3-7) connects
to the PT/CT board to bring in voltage and current. It
also connects to customer inputs and outputs. Note
that there are two versions of this board, for parallel
and non-parallel generator sets.
Connectors
The customer interface board has five connectors.
They are:
J1Customer connections
J2Customer connections
J3A36 PT/CT Board and customer connections
J4Connects to J2 on A32 Digital board
J5Connects to J4 on A33 Analog board
LEDs
The customer interface board has 27 LED’s that indicate the following conditions:
Redistribution or publication of this documentby any means, is strictly prohibited.
The PT/CT board (Figure 3-8) is mounted inside the
accessory box. This board converts generator output voltage to approximately 18 VAC levels for the
analog board. It also converts CT .55 amp (at full
load) output to approximately 1.65 VAC (at full load)
input for the analog board.
There are three versions of this board. For proper
operation, the PT/CT board must be correctly
matched to the generator set.
In addition, there is a specific set of CTs for each
genset. For proper operation, the CTs must also be
correctly matched to the genset output current.
Connectors
The PT/CT board has two connectors. They are:
J8Connects to J3 on A34 Customer Interface
board
J9Connects to AC harness (generator output
voltage and CTs)
J9 wiring connections:
YellowGen. A In
Orange Gen. B In
RedGen. C In
BrownGen. Common In
WhiteCT21 (+) In
GrayCT21 (common) In
Grn/Ylw CT22 (+) In
BlackCT22 (common) In
PurpleCT23 (+) In
BlueCT23 (common) In
J9
J8
FIGURE 3-8. PT/CT BOARD
3-10
Page 31
BUS PT MODULE (A39)
Redistribution or publication of this documentby any means, is strictly prohibited.
The bus PT module (Figure 3-9) is mounted inside
the accessory box. This module converts the bus
output voltage (from the load side of the paralleling
breaker) to 18 VAC and provides this to the analog
board. It provides a reference signal to the PowerCommand Control for synchronizing the generator
set output to a system bus. There are four versions
of this module, for primary voltages of 69, 120, 240
or 346 volts AC line to neutral. For proper operation,
the correct bus PT module must be installed in the
generator set. Correct phasing is also important as
the system uses the bus PT module output for both
protection and control of the generator set.
Connectors
The bus PT module has two terminal blocks. They
are:
TB1 Bus voltage connections.
N bus neutral
A bus A phase (U)
B bus B phase (V)
C bus C phase (W)
TB2 Bus PT output for PowerCommand control.
FIGURE 3-9. BUS PT MODULE
3-11
Page 32
GENSET COMMUNICATIONS MODULE
Redistribution or publication of this documentby any means, is strictly prohibited.
(A41)
The genset communications module (GCM) is required to connect the PCC to a PowerCommand
(LonWorks) network, and communicate with other
network modules. The GCM module is an optional
feature, and it is available as a field upgrade kit for
applications where the feature must be added in the
field. The PCC must be operating with firmware version 1.06 or later. For model DFH gensets only, firmware must be version 1.04 or later.)
The GCM provides an interface for data transfer between the PowerCommand control and other modules on the network. It communicates with the PCC
through a serial port on the PCC, as well as monitoring various PCC inputs to determine the operating
state of the control. For example, the GCM monitors
PCC data such as voltage, oil pressure, current, engine speed, and not in auto status; and provides
that information to the network.
The GCM also facilitates remote monitoring and
limited remote control of the genset that PCC controls. Outputs from the GCM can ’wake up’ the PCC
when needed, or issue start commands to the genset. The GCM also includes a terminate circuit for
use at the end of a network data bus.
The GCM module is powered from the genset starting batteries. It is operational at all times when powered, even if the PCC is asleep.
The GCM module is mounted on stand-off mounting legs above the analog board (A33).
Refer to the Power Command Network Installation
and Operator’s Manual (900-0366) for information
on installation and use of the GCM module.
J6
J7
TERMINATE
SWITCH S3
BATTERY
VOLTAGE
SWITCH S4
SERVICE
SWITCH S1
FIGURE 3-10. GENSET COMMUNICATIONS MODULE
SWITCH S2
3-12
RESET
Page 33
VOLTAGE REGULATOR OUTPUT MODULE
Redistribution or publication of this documentby any means, is strictly prohibited.
(A37)
The voltage regulator output module (Figure 3-11)
is a power amplifier. This board is used to amplify
the pulse-width modulated (PWM) signal from the
PCC to drive the exciter windings. Power from the
PMG is used by this board to amplify the PWM signal.
J10Connects to engine harness (power)
J10 wiring connections:
GreenPhase A PMG power
YellowPhase B PMG power
Orange Phase C PMG power
RedX (Field +) Output
BrownXX (Field −) Output
Connectors
The voltage regulator output module has two connectors. They are:
The voltage regulator output module has 3 LED’s
that indicate the following conditions.
DS1 On when voltage regulator isolated supply is
operating (Green)
DS2 Output Duty Cycle − Brighter when load in-
creases − larger duty cycle (Amber). The duty
cycle range of the PWM signal is 0 - 60%. Because the normal duty cycle is less than 10%,
the output duty cycle LED, DS2 will normally
be very dimly lit.
DS3 Backup start disconnect − On when start dis-
connect is true (Green). The backup start disconnect is initiated at about 850 RPM, when
sensed PMG voltage is greater than 105 volts
RMS.
DS1 - ISOLATED SUPPLY
DS2 - OUTPUT DUTY CYCLE
DS3 - BACKUP START DISCONNECT
J10J7
FIGURE 3-11. VOLTAGE REGULATOR OUTPUT MODULE (A37)
3-13
Page 34
GOVERNOR OUTPUT MODULE (A38)
Redistribution or publication of this documentby any means, is strictly prohibited.
Fuses
The governor output module (Figure 3-12) receives
a low power pulse−width modulated (PWM) signal
from the engine interface board and then sends an
amplified signal to drive the governor actuator. The
PCC monitors frequency from both the magnetic
pick-up (MPU) and the main stator inputs.
Connectors
The governor output module has one connector:
J6Connects to Governor Actuator, Governor
Drive (from Engine Interface), B+, T26
The governor output module has three fuses to protect it from overloads and groundfaults. They are:
The governor output module has two LED’s that indicate the following conditions:
DS1 Output Duty Cycle: brighter = longer duty
cycle (Amber). The duty cycle range of the
PWM signal is 0 - 90%. Normal duty cycle is
about 30%.
DS2 Run signal to Governor Controller (Green)
DS1 - OUTPUT DUTY CYCLE
DS2 - GENSET RUN
Network B+Switched B+Governor B+
J6
FIGURE 3-12. GOVERNOR OUTPUT MODULE (A38)
3-14
Page 35
MASTER FIRST START SENSOR
Redistribution or publication of this documentby any means, is strictly prohibited.
The First Start Sensor System is an Onan control
sub-system which is used to sense when a generator set is ready to close to a de-energized system
bus and to prevent more than one generator set
from closing to a dead bus on automatic system
starting. The First Start Sensor System for PowerCommand generator sets is composed of control algorithms within the PowerCommand control and a
Master First Start Sensor , which is usually mounted
in a remote master control panel.
The sequence of operation of the control system is
as follows:
On a signal to start, all generator sets in a system
simultaneously start, and accelerate to rated speed
and voltage. The Master First Start Sensor continuously provides pulses to each PowerCommand
control. When the PowerCommand control receives the pulse from the Master First Start Sensor,
if it is ready to close to the bus, an interlock signal is
sent to all other controls to prevent their respective
paralleling breakers from closing. A close signal is
then provided to the generator set paralleling breaker.
3-15
Page 36
THIS PAGE LEFT INTENTIONALLY BLANK
Redistribution or publication of this documentby any means, is strictly prohibited.
3-16
Page 37
4. Troubleshooting
Redistribution or publication of this documentby any means, is strictly prohibited.
GENERAL
The PowerCommand Control 3100 (PCC) continuously monitors engine sensors for abnormal conditions, such as low oil pressure and high coolant
temperature. If any of these conditions occur, the
PCC will light a yellow Warning lamp or a red Shutdown lamp and display a message on the digital display panel.
In the event of a shutdown fault (red Shutdown
lamp), the PCC will stop the generator set (genset)
and close a set of contacts that can be wired to trip a
circuit breaker. If the genset is stopped for this reason, the operator can restart the genset after making adjustments or corrections.
This section contains the following information:
• T able 4 - 1 : Contains a list of all status codes, in-
cluding the displayed message and status indicator. Also references the page number that
contains a description of each code.
• Table 4-2: Describes each warning and shut-
down code, warning and shutdown limits
where applicable, and basic corrective actions,
such as, checking fluid levels, control reset
functions, battery connections, etc.
• Table 4-3: Lists the PCC oil pressure warning
and shutdown limits.
• Tables 4-4 through 4-35: Provide detailed
troubleshooting procedures.
• T able 4-36: Describes the analog circuit board
inputs and outputs.
• Table 4-37: Describes the location and func-
tion of each fuse.
SAFETY CONSIDERATIONS
WARNING
nents can cause electrocution, resulting in severe personal injury or death. Keep the output
box covers in place during troubleshooting.
Contacting high voltage compo-
High voltages are present when the genset is running. Do not open the generator output box while
the genset is running.
WARNING
Ignition of explosive battery gases
can cause severe personal injury or death. Arcing at battery terminals, light switch or other
equipment, flame, pilot lights and sparks can ignite battery gas. Do not smoke, or switch
trouble light ON or OFF near battery . Discharge
static electricity from body before touching batteries by first touching a grounded metal surface.
Ventilate battery area before working on or near
battery—Wear goggles—Stop genset and disconnect charger before disconnecting battery
cables—Disconnect negative (−) cable first and
reconnect last.
CAUTION
Disconnect battery charger from AC
source before disconnecting battery cables.
Otherwise, disconnecting cables can result in
voltage spikes damaging to DC control circuits
of the genset.
WARNING
Accidental starting of the generator
set can cause severe personal injury or death.
Prevent accidental starting by disconnecting
the negative (−) cable from the battery terminal.
When troubleshooting a generator set that is shut
down, make certain the generator set cannot be accidentally restarted as follows:
1. Move the Run/Off/Auto switch on the control
panel to the OFF position.
2. Turn off or remove AC power from the battery
charger.
3. Remove the negative (−) battery cable from the
generator set starting battery.
4-1
Page 38
STATUS INDICATORS
Redistribution or publication of this documentby any means, is strictly prohibited.
Non-Automatic Status Indicator:
flashes continuously when the Run/Off/Auto switch
is in the Off position.
Warning Status Indicator:
This yellow lamp is lit
whenever the control detects a warning condition.
After the condition is corrected, warning indicators
can be reset by pressing the Reset switch. (It is not
necessary to stop the generator set.) In auto mode,
warning indicators can also be reset by cycling the
remote reset input after the condition is corrected.
Shutdown Status Indicator:
whenever the control detects a shutdown condition.
Shutdown faults are latched. After the condition is
corrected, shutdown indicators can be reset by
turning the Run/Off/Auto switch to the Off position,
and pressing the Reset switch. In the Auto position,
shutdown faults can be reset by removing the remote start input and then cycling the remote reset
input.
This red lamp
This red lamp is lit
Emergency Stop shutdown status (Code 102) can be
reset only at the PCC front panel.
Digital Display:
This two-line, 16-character per line
alphanumeric display is used in the menu-driven
operating system and to show shutdown and warning messages. Refer to Tables 4-1 and 4-2.
RESETTING THE CONTROL
Press the momentary
ing and shutdown messages after the condition has
been corrected. To reset a shutdown message with
the Reset switch, the Run/Off/Auto switch must be
in the Off Position. (The control cannot go into
Standby (sleep) mode until all faults have been
reset.)
In Auto mode, warning indicators can also be reset
by cycling the remote reset input after the condition
is corrected. Shutdown faults can be reset by removing the remote start input and then cycling the
remote reset input.
Reset Switch
to reset warn-
WARNING AND
SHUTDOWN
STATUS INDICATORS
RESET
SWITCH
FIGURE 4-1. CONTROL PANEL
4-2
ALPHANUMERIC
FAULT MESSAGE
DISPLAY
Page 39
TABLE 4-1. WARNING AND SHUTDOWN CODES
Redistribution or publication of this documentby any means, is strictly prohibited.
* Default message. Editable for customer site requirements. It is recommended that the bell alarm contacts of the
paralleling breaker be brought back to the control and indicate “Parallel CB Trip” as one customer fault.
4-4
Page 41
TABLE 4-2. WARNING AND SHUTDOWN CODES
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Hazards present in troubleshooting can cause equipment damage, severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Read Safety Precautions page
and observe all instructions and precautions in this manual.
SYMPTOMCORRECTIVE ACTION
MESSAGE:
LOAD DEMAND
MESSAGE:
IDLE MODE
101 − WARNING
The PowerCommand control has received a signal to shut down from a
remote device. This is a normal operation mode, which is typically used in
automatic control system to minimize generator set operation hours and
system fuel consumption. When the load demand signal is removed, the
generator set will automatically start, synchronize, and close to the system bus.
Indicates that the engine is operating in idle mode. When the genset is operating in the RUN mode, grounding the engine idle input causes generator build-up to be inhibited and the engine to be governed at 800 RPM.
When ground is removed from this input, the genset returns to normal
speed and voltage.When the engine idle function is enabled, the control
automatically gensets lower oil pressure warning and shutdown trip
points to reflect the lower operating speed. When the engine idle function
is removed and the genset reverts to normal operating speed, the control
automatically resets oil pressure warning and shutdown trip points to the
normal settings.
Shutdown lamp lights.
MESSAGE:
EMERGENCY STOP
102 − SHUTDOWN
Warning lamp lights.
MESSAGE:
LOW OIL PRESSURE
200 − WARNING
Shutdown lamp lights.
MESSAGE:
LOW OIL PRESSURE
201 − SHUTDOWN
Warning lamp lights.
MESSAGE:
OIL PRES SENDER
204 − WARNING
Indicates local or remote Emergency Stop.
To reset the local/remote Emergency Stop button:
Pull the button out (button with arrow − turn clockwise to allow it to pop
out).
Move the Run/Off/Auto switch to Off.
Press the Reset switch.
Select Run or Auto, as required.
Indicates engine oil pressure has dropped to an unacceptable level. If generator is powering critical loads and cannot be shut down,
wait until next shutdown period and then follow 201-SHUTDOWN
procedure.
T o check oil pressure, access the Oil Pressure menu prior to clearing the fault.
Indicates engine oil pressure has dropped below the shutdown trip point.
Check oil level, lines and filters. If oil system is OK but oil level is low, re plenish. Reset control and restart. Oil pressure limits are listed in Table
4-3.
Indicates that the control has sensed that the engine oil pressure sender is
out of its working range. Check that the engine oil pressure sender is properly connected.
4-5
Page 42
TABLE 4-2. WARNING AND SHUTDOWN CODES (CONT.)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Hazards present in troubleshooting can cause equipment damage, severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Read Safety Precautions page
and observe all instructions and precautions in this manual.
SYMPTOMCORRECTIVE ACTION
Warning lamp lights.
MESSAGE:
LOW COOLANT TEMP
210 − WARNING
Set is not operating. Warning occurs
when engine coolant temperature is
° F (21° C) or lower.
70
NOTE: In applications where the
ambient temperature falls below
40
°F (4°C), Low Coolant Temp
may be indicated even though the
coolant heaters are operating.
Warning lamp lights.
MESSAGE:
HIGH COOLANT TEMP
211 − WARNING
Indicates engine coolant heater is not operating or is not circulating coolant. Check for the following conditions:
a. Coolant heater not connected to power supply. Check for blown fuse
or disconnected heater cord and correct as required.
b. Check for low coolant level and replenish if required. Look for pos-
sible coolant leakage points and repair as required.
c. Open heater element. Check current draw of heater.
Indicates the engine coolant temperature is getting close to the recommended maximum temperature limit:
215°
F (102°C) − standby or 207°F (97°C) − prime.
If generator is powering non-critical and critical loads and cannot be shut
down, use the following:
a. Reduce load if possible by turning off non-critical loads.
b. Check air inlets and outlets and remove any obstructions to airflow.
If engine can be stopped, follow HIGH COOLANT TEMP 212 − SHUT-
DOWN procedure.
Shutdown lamp lights.
MESSAGE:
HIGH COOLANT TEMP
212 − SHUTDOWN
Warning lamp lights.
MESSAGE:
COOLANT SENDER
213 − WARNING
To check coolant temperature, access the coolant temperature
menu prior to clearing the fault.
Indicates engine has overheated (coolant temperature has risen above
the shutdown trip point:
223°F (106°C) − standby or 215°F (102°C) − prime. Allow engine to
cool down completely before proceeding with the following checks:
a. Check for obstructions to cooling airflow and correct as necessary.
b. Check fan belt and repair or tighten if necessary.
c. Check coolant mixture.
d. Check blower fan and circulation pumps on remote radiator installa-
tions.
e. Reset control and restart after locating and correcting problem.
Indicates that the resistance of the coolant temperature sender is out of
range. Check the resistance of the sender. Resistance should be 500 to
2k ohms.
4-6
Page 43
TABLE 4-2. WARNING AND SHUTDOWN CODES (CONT.)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Hazards present in troubleshooting can cause equipment damage, severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Read Safety Precautions page
and observe all instructions and precautions in this manual.
Indicates engine coolant level has fallen below the trip point. Allow engine
to cool down completely before proceeding.
a. Check coolant level in both radiator and coolant recovery bottle and
replenish if l o w. Look for possible coolant leakage points and repair if
necessary.
b. If radiator level is low and coolant bottle level is correct, defective
coolant bottle hose or radiator cap.
c. Reset control and restart after locating and correcting problem.
LOW COOLANT LVL Shutdown will not occur if genset is in Idle
mode (low coolant warning only).
Indicates mag pickup speed indication is not being sensed or does not
match generator set output frequency.
a. Restart and check RPM on the digital display.
Engine will not crank.
Shutdown lamp lights.
MESSAGE:
FAIL TO CRANK
221 − SHUTDOWN
Shutdown lamp lights.
Engine stops cranking.
MESSAGE:
OVERCRANK
222 − SHUTDOWN
Engine runs and then shuts down.
Shutdown lamp lights.
MESSAGE:
OVERSPEED
223 − SHUTDOWN
Indicates possible fault with control or starting system. Check for the following conditions:
a. Check fuse F3 on the Engine Interface board.
b. Poor battery cable connections. Clean the battery cable terminals
and tighten all connections.
c. Discharged or defective battery. Recharge or replace the battery.
Indicates possible fuel system problem.
a. Check for empty fuel tank, fuel leaks, or plugged fuel lines and cor-
rect as required.
b. Check for dirty fuel filter and replace if necessary.
c. Check for dirty or plugged air filter and replace if necessary.
d. Reset the control and restart after correcting the problem.
Indicates engine has exceeded normal operating speed. (115% ±1% of
nominal).
4-7
Page 44
TABLE 4-2. WARNING AND SHUTDOWN CODES (CONT.)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Hazards present in troubleshooting can cause equipment damage, severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Read Safety Precautions page
and observe all instructions and precautions in this manual.
SYMPTOMCORRECTIVE ACTION
Warning (or Shutdown) lamp
lights.
MESSAGE:
FAIL TO SYNCHRONIZE
224 − WARNING
or
FAIL TO SYNCHRONIZE
224
Warning lamp lights.
MESSAGE:
FAIL TO CLOSE
226 − SHUTDOWN
The generator set has not synchronized to the system bus within the allowable time frame.
a. Check the governor system stability. Adjust governing and synchro-
nizer parameters as required.
b. Check for fuel system problems which can cause engine instability.
Synchronizing time can be improved by widening the synchronizing
window and reducing the acceptance time delay.
Indicates that the paralleling breaker has been given a signal to close, but
has not closed properly.
a. Verify that the charging mechanism of the paralleling breaker is func-
tioning properly.
b. Check the close signal to the breaker.
c. Verify that the auxiliary contact signals from the breaker to the Pow-
erCommand control are operational.
Warning lamp lights.
MESSAGE:
LOW DC VOLTAGE
230 − WARNING
Warning lamp lights.
MESSAGE:
HIGH DC VOLTAGE
231 − WARNING
Warning lamp lights.
MESSAGE:
WEAK BATTERY
232 − WARNING
Indicates battery voltage is below 10 VDC.
a. Discharged or defective battery.
Check the battery charger fuse.
Recharge or replace the battery.
b. Poor battery cable connections. Clean the battery cable terminals
and tighten all connections.
c. Check engine DC alternator. Replace engine DC alternator if normal
battery charging voltage is not obtained.
d. Check battery charge voltage float level if applicable (raise float lev-
el).
Indicates battery voltage exceeds 32 VDC.
Check voltage float level on battery charger if applicable (lower float lev-
el).
Check engine DC alternator. Replace engine DC alternator if normal bat-
tery charging voltage is not obtained.
Indicates battery voltage drops below 60% of nominal for two seconds,
during starting.
Discharged or defective battery.
See Warning message 230, LOW DC VOLTAGE.
4-8
Page 45
TABLE 4-2. WARNING AND SHUTDOWN CODES (CONT.)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Hazards present in troubleshooting can cause equipment damage, severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Read Safety Precautions page
and observe all instructions and precautions in this manual.
SYMPTOMCORRECTIVE ACTION
Warning lamp lights.
MESSAGE:
LOW FUEL−DAY
240 − WARNING
or
LOW FUEL
241 − WARNING
Shutdown lamp lights.
MESSAGE:
EEPROM ERROR
250 − SHUTDOWN
Warning lamp lights.
MESSAGE:
EEPROM ERROR
251 − WARNING
or
252 − WARNING
Indicates day tank fuel supply is running low. Check fuel supply and replenish as required.
Indicates PCC memory error. Data corruption of critical operating parameters.
Indicates PCC memory error. Data corruption of noncritical operating parameters.
When any one of these customer defined inputs is closed to ground, the
corresponding fault message is displayed. The nature of the fault is an optional customer selection. These fault functions can be programmed to
initiate a shutdown or a warning.
As indicated by the Shutdown lamp, a shutdown response has been preselected.
Note: Customer fault messages are editable. The message displayed for
the code shown (260 thru 263) may have been edited and may not appear
as shown in this table.
4-9
Page 46
TABLE 4-2. WARNING AND SHUTDOWN CODES (CONT.)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Hazards present in troubleshooting can cause equipment damage, severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Read Safety Precautions page
and observe all instructions and precautions in this manual.
When any one of these customer defined inputs is closed to ground, the
corresponding fault message is displayed. The nature of the fault is an optional customer selection. These fault functions can be programmed to
initiate a shutdown or a warning.
As indicated by the Warning lamp, a warning response has been preselected.
Note: Customer fault messages are editable. The message displayed for
the code shown (260 thru 263) may have been edited and may not appear
as shown in this table.
The phase relationship between the generator set and the system bus is
not matched.
a. Using a phase rotation checker, verify that the generator set phase
rotation matches the phase orientation of the system bus.
b. Verify that control wiring to the bus PT module on the PowerCom-
mand control is properly connected.
Shutdown lamp lights.
MESSAGE:
FIRST START
272 − WARNING
Shutdown lamp lights.
MESSAGE:
HIGH AC VOLTAGE
301 − SHUTDOWN
Shutdown lamp lights.
MESSAGE:
LOW AC VOLTAGE
303 − SHUTDOWN
Shutdown lamp lights.
MESSAGE:
UNDER FREQUENCY
313 − SHUTDOWN
The PowerCommand control is not receiving a proper signal from the system master first start sensor . When this occurs, the control reverts to a fallback mode in which breaker closure is automatically allowed if bus is deenergized. If bus voltage is sensed, the control will force the generator set
to synchronize to the system bus before breaker close signal is initiated.
Indicates that one or more of the phase voltages has exceeded 130% of
nominal, or has exceeded 110% of nominal for 10 seconds.
Indicates that one or more of the phase voltages has dropped below 85%
of nominal for 10 seconds.
Indicates that engine speed has dropped below 90% of nominal for 10
seconds.
Note: Five seconds before shutdown, a Load Dump signal is initiated.
Check fuel supply, intake air supply and load.
4-10
Page 47
TABLE 4-2. WARNING AND SHUTDOWN CODES (CONT.)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Hazards present in troubleshooting can cause equipment damage, severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Read Safety Precautions page
and observe all instructions and precautions in this manual.
SYMPTOMCORRECTIVE ACTION
Warning lamp lights.
MESSAGE:
OVERCURRENT
320 − WARNING
Shutdown lamp lights.
MESSAGE:
OVERCURRENT
321 − SHUTDOWN
Shutdown lamp lights.
MESSAGE:
SHORT CIRCUIT
322 − SHUTDOWN
Indicates that generator output current has exceeded 1 10% of rated for 60
seconds.
Check load and load lead connections.
Indicates that generator output current has exceeded 110% of rated, and
that a PCC time/current calculation has initiated an overcurrent shutdown.
Check load and load lead connections.
Indicates that generator output current has exceeded 175% of rated.
Check load and load lead connections.
Warning lamp lights.
MESSAGE:
OVERLOAD
330 − WARNING
Indicates that three-phase power output exceeds 105% of standby (or
115% of prime) rating. After five seconds, the Load Dump output is activated. After 60 seconds, the OVERLOAD warning is activated.
Check load and load lead connections.
4-11
Page 48
TABLE 4-2. WARNING AND SHUTDOWN CODES (CONT.)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Hazards present in troubleshooting can cause equipment damage, severe personal
injury or death. Only trained and experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Read Safety Precautions page
and observe all instructions and precautions in this manual.
SYMPTOMCORRECTIVE ACTION
Shutdown lamp lights.
MESSAGE:
REVERSE POWER
335 − SHUTDOWN
Shutdown lamp lights.
MESSAGE:
LOSS OF EXCITATION
337 − SHUTDOWN
Indicates that power is flowing into the generator set, rather than out from
the unit. This can be caused by engine failure, or inability to carry load, or
by a number of control or interconnection problems.
a. If problem occurs at initial startup, verify connection of generator set
CT’s, by applying load to the generator set while it is operating alone
while connected to bus.
b. Verify proper connection of load sharing lines.
c. Verify that the generator set is operating at the correct frequency and
voltage. The no-load voltage of the generator set and other generator sets should all be the same.
Indicates that t he a lternator e xcitation s ystem i s i mproperly a djusted o r h as
failed. Loss of Excitation failure may also b e c aused b y o peration of f ilters
and power factor c orrection capacitors in the generator s et l oads w hen t he
kW load level on the g enset i s l ow. The capacitors in the f ilters and p ower
factor correction equipment can p resent a l eading power factor load to the
generator set, which (correctly) shuts down the generator set through the
loss of e xcitation f ault. L eading p ower f actor l oads c an c ause t he g enerator
set to lose control of the output voltage of the genset and can cause kVar
load sharing p roblems. T herefore, i t i s n ecessary t o p rotect t he g enset f rom
excessive leading power factor and reverse Var conditions.
a. Start the generator set in the RUN mode and check output voltage
with both the control digital meter set and a calibrated meter. Calibrate voltage if necessary . Output voltage should be adjusted to t h e
same level as all other generator sets at no load. Make adjustments
as necessary to correct.
b. Check load sharing lines for proper interconnections.
c. See
Section 6
tifier, and exciter Rotor.
of this manual “Servicing the Generator”, Exciter Rec-
35 psi(241 kPa) shutdown limit - run mode value
40 psi(276 kPa) warning limit - run mode value
10 psi(69 kPa)shutdown limit - idle mode value
15 psi(103 kPa) warning limit- idle mode value
To check oil pressure or engine temperature during a warning, access the oil pressure
or engine temperature menu prior to clearing the fault.
4-13
Page 50
TROUBLESHOOTING PROCEDURE
Redistribution or publication of this documentby any means, is strictly prohibited.
The following tables are a guide to help you evaluate problems with the generator set. You can save
time if you read through the manual ahead of time
and understand the system.
To determine the appropriate troubleshooting
procedure for the specific problem at hand, be
sure to refer to the “Indicators” column provided in each troubleshooting table.
Try to think through the problem. Go over what was
done during the last service call. The problem could
be as simple as a loose wire, an opened fuse or a
tripped circuit breaker. (Table 4-32 describes the
location and function of each fuse.)
Figure 4-2 shows the location of the components
within the control panel that are referenced in the
following troubleshooting procedures. Connector,
LED and switch locations for each circuit board and
module are provided in
and circuit board connections are shown in
9
.
CAUTION
Always set the Run/Off/Auto (S12)
Section 3
. The control wiring
Section
switch to the Off position and the Power On/
Standby (S5) switch to the Standby position before disconnecting or connecting harness connectors. Otherwise, disconnecting the harness
connectors can result in voltage spikes high
enough to damage the DC control circuits of the
set.
CAUTION
Electrostatic discharge will damage
circuit boards. Always wear a wrist strap when
handling circuit boards or socket-mounted IC’s
and when disconnecting or connecting harness
connectors.
4-14
Page 51
DISPLAY BOARD
Redistribution or publication of this documentby any means, is strictly prohibited.
A35
S5 POWER ON/
STANDBY SWITCH
DIGITAL BOARD
A32
ANALOG BOARD
A33
OPTIONAL
THERMISTOR
RELAY 160
OPTIONAL RUN
RELAYS K11, K12 &
°/140° C
TB1-1
K13
TB1-60
RUN/OFF/AUTO
SWITCH S12
ENGINE INTERFACE
A31
CUSTOMER INTERFACE
A34
BUS PT MODULE
A39
GOVERNOR
OUTPUT MODULE
A38
OPTIONAL
COMMON ALARM
RELAY K14
PT/CT BOARD A36
OPTIONAL RTD
RELAY
VOLTAGE
REGULATOR
OUTPUT MODULE
A37
ACCESSORY BOX
FIGURE 4-2. CIRCUIT BOARD LOCATIONS
4-15
Page 52
TABLE 4-4. ENGINE DOES NOT CRANK—LOCAL OR REMOTE RUN
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“FAIL TO
CRANK”
(221)
message
Reset and
attempt to
start:
Start LED
DS11 on the
engine
interface board
turns on.
NOTE:
These two
indications
suggest that
the PCC has
received a
start signal
and has sent a
start command
to the start
output (J4-2)
on the engine
interface
board.
1. Insufficient battery voltage. Check the
following conditions:
a. Batteries not charged.
b. Battery connections loose or
dirty.
c. Insufficient battery charging volt-
age.
d. Engine DC alternator could be
bad.
2. Starter could be bad.
3. If there is no B+ at the starter, start solenoid K4 could be bad.
4. If there is no B+ at the start solenoid
coil (K4), the backup start disconnect
contacts in the regulator output module (A37) could be open (indicating
that A37 is bad).
1a. Recharge or replace the battery. Specific gravi-
ty for a fully charged battery is approximately
1.260 at 80° F (27° C).
1b. Clean and tighten or replace the battery cable
connectors and cables at the battery and the
set.
1c. Adjust charge rate of battery charging circuit.
1d. Replace engine DC alternator if normal battery
charging voltage is not obtained.
2. Reset the control. Attempt to start, and test for
B+ at the starter. If there is B+ at the starter, the
starter could be bad. Test starter (see engine
service manual). Replace the starter.
3. Reset the control. Attempt to start, and test for
B+ into and out of start solenoid contacts. If
there is B+ in, but not out, check for B+ at the
start solenoid coil. If there is B+ at the coil,
check ground connection. If ground connection
is good, the start solenoid is bad. Replace the
start solenoid.
If there is B+ into and out of the start solenoid
contacts, check for an open between the start
solenoid contacts and the starter. If there is no
B+, go to the next step.
*4. Disconnect J7/P7 at the regulator output mod-
ule. Test for continuity at A37 J7-5/J7-6. If there
is no continuity, the regulator output module is
bad. Replace A37.
5. If there is continuity at A37 J7-5/J7-6,
there may be an open between A37
and A31, an open between A37 and
K4, or A31 may be bad.
6. The mag pickup signal is not being
sensed.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
*5. If there is continuity at A37 J7-5/J7-6, reset the
control, attempt to start, and check for B+ at
A37 P7-5.
If there is B+ at P7-5, there may be an open be-
tween start solenoid coil (K4) and A37. If there
is no B+ at P7-5, check for B+ at J4-2 on the engine interface board (A31) while attempting to
start.
If there is B+ at A31 J4-2, check for an open between A37 and A31.
If there is no B+ at A31 J4-2, (and DS11 is on)
the engine interface board is bad. Replace A31.
6. Refer to the mag pickup shutdown message
(220).
4-16
Page 53
TABLE 4-5. ENGINE DOES NOT CRANK—LOCAL OR REMOTE RUN
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“FAIL TO
CRANK”
(221)
message
Reset and
attempt to
start:
Start LED
DS11 on the
engine
interface board
does NOT
turn on.
NOTE:
These two
indications
suggest that
the PCC has
received a
start signal
and has NOT
sent a start
command to
the start output
(J4-2) on the
engine
interface
board.
1. Fuse F3 on the engine interface board
(A31) may be open, or B+ may not be
getting to F3.
2. Emergency Stop switch S13 or the
PCC door harness may be bad.
3. Digital board (A32) may be bad.
4. Engine interface board (A31) may be
bad.
*1. Install harness tool between A31 J4/P4. Reset
the control. Attempt to start and check for B+ at
J4-2. If no B+, remove F3 and check continuity.
If open, replace the fuse with one of the same
type and amp rating (5 Amps). If F3 is OK,
check the B+ supply from the wiring harness.
2. To isolate:
• Check for B+ at S13-1 and S13-2.
If there is B+ at S13-2, but not at S13-1
(and S13 is NOT in the emergency stop
position), then S13 is bad. Replace S13.
• If there is no B+ at S13-2, disconnect
J3/P3, and check for B+ at A31 J3-2. If
there is no B+, replace A31.
• If there is B+ at A31 J3-2, check continuity
from P3-2 to P3-6. If no continuity, repair
or replace as necessary.
*3. Install harness tool between A32 J4/P4. Reset
the control. Attempt to start, and test for ground
output at A32 J4-3. If there is no ground output,
A32 is bad. Replace A32.
*4. If there is a ground output at A32 J4-3, and yet
there is no B+ output at A31 J4-2; then A31 is
bad. Replace A31.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-17
Page 54
TABLE 4-6. ENGINE DOES NOT CRANK—REMOTE RUN
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“FAIL TO
CRANK”
(221)
message
DOES NOT
appear on
digital display
−and:
Auto LED DS5
on the engine
interface board
(A31) is on −
RMT Start
LED DS14 on
the customer
interface board
(A34) is on −
NOTE:
This condition
suggests that
the PCC
processor
(digital board
−A32) has
NOT received
or recognized
a remote start
start signal.
1. The Auto mode signal is not getting
from engine interface board A31 to
digital board A32, indicating that A31 is
bad.
2. The Remote run signal is not getting
from customer interface board A34 to
A32, indicating that A34 is bad.
3. Digital board (A32) may be bad.
*1. Install harness tool between A32 J4/P4. Check
for ground output at A32 J4-18.
If there is no ground output (but A31 DS5 is on)
engine interface board A31 is bad. Replace
A31.
If there is a ground output at A31 J1-18, proceed to the next step.
*2. Install harness tool between A32 J4/P4. Reset
the control. Attempt to remote start, and check
for ground output at A32 J2-26. If no ground output (but A34 DS14 is on) customer interface
board A34 is bad. Replace A34.
If there is a ground output at A32 J2-26, proceed to the next step.
*3. If, when attempting remote start, there is a
ground input at A32 J2-26, and a ground input
at A32 J4-18—and there is no “FAIL TO
CRANK” message—and the set does not
crank; A32 is bad. Replace, A32.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-18
Page 55
TABLE 4-7. ENGINE DOES NOT CRANK—REMOTE RUN
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“FAIL TO
CRANK”
(221)
message
DOES NOT
appear on
digital display
−and:
Auto LED DS5
on the engine
interface board
(A31) is off −
RMT Start
LED DS14 on
the customer
interface board
(A34) is on −
The Auto mode input is not getting from the
Auto select switch (S12) to engine interface
board A31 (indicating that S12, A31, or the
harness is bad.
1. S12 or the wiring harness may be bad.
2. Engine interface board A31 may be
bad.
*1. Disconnect A31 J3/P3. Check continuity to
ground at A31 J3-11. (J3-11 is ground out to
S12. If ground is not present, replace A31. If
ground is present, place S12 in Auto and check
continuity from P3-11 to P3-13. If no continuity ,
isolate to switch or wiring harness. Repair as
necessary. If there is continuity, A31 may be
bad. Reconnect J3/P3.
*2. Install harness tool between A32 J4/P4. Check
the 16 volt (nominal) supply at A32 J4-16.
NOTE:
This condition
suggests that
the engine
interface board
(A31) is NOT
enabling the
remote start
logic on the
digital board.
3. Digital board A32 may be bad.
If the voltage is present at A32 J4-16, and
ground is present at A31 P3-13—and yet A31
DS5 is off; then A31 is bad. Replace A31.
3. If there is no +16 volt supply voltage at A32
J4-16, A32 is bad. Replace A32.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-19
Page 56
TABLE 4-8. ENGINE DOES NOT CRANK—REMOTE RUN
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“FAIL TO
CRANK”
(221)
message
DOES NOT
appear on
digital display
−and:
Auto LED DS5
on the engine
interface board
(A31) is on −
RMT Start
LED DS14 on
the customer
interface board
(A34) is off
NOTE:
This condition
suggests that
the remote
start input is
NOT passing
through the
customer
interface board
(A34) to
enable the
remote start
logic on the
digital board.
The remote start input is not getting from the
remote start switch to the output of the customer interface board (A34) (indicating that
the switch, A34, or the harness is bad.
1. The remote start switch or the
wiring harness may be bad.
2. Customer interface board A34
may be bad.
*1. Install harness tool between A34 J1/P1. Reset
the control. Attempt remote start and check for
ground at A34 J1-13. If ground level is not present, isolate to the switch or the wiring harness
by checking for a start signal at TB1-5. Repair
as necessary.
2. If ground is present at A34 J1-13—and yet A34
DS14 is off, replace A34.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-20
Page 57
TABLE 4-9. ENGINE DOES NOT CRANK—LOCAL RUN
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“FAIL TO
CRANK”
(221)
message
DOES NOT
appear on
digital display
−and:
Run LED DS4
on the engine
interface board
(A31) is off−
NOTE:
This condition
suggests that
the start input
is NOT getting
from the
Run/Off/ Auto
switch (S12) to
the engine
interface board
(A31) to
enable the
remote start
logic on the
digital board.
The start input is not getting from the Run/
Off/ Auto select switch (S12) to A31 (indicating that S12, A31, or the harness is bad.
1. Run/Off/ Auto select switch S12 or the
wiring harness may be bad.
2. Engine interface board A31
may be bad.
3. Digital board A32 may be bad.
*1. Check continuity to ground at A31 J3-11. If
ground is not present, replace A31. If ground is
present, place S12 in Run and check continuity
from P3-11 to P3-12. If no continuity, isolate to
switch or wiring harness. Repair as necessary .
If there is continuity, A31 may be bad.
*2. Install harness tool between A32 J4/P4. Check
the 16 volt (nominal) supply at A32 J4-16.
If the voltage is present at A32 J4-16, and
ground is present at A31 J3-12—and yet A31
DS5 is off, replace A31.
3. If there is no +16 volt supply voltage at A32
J4-16, replace A32.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-21
Page 58
TABLE 4-10. ENGINE CRANKS BUT DOES NOT START
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“OVERCRANK”
(222)
message
−and
While cranking,
Run LED DS12
on the
engine interface
board (A31)
is on.
and
While cranking,
Run LED DS2
on the
governor output
module (A38)
is on.
NOTE:
These
indications
suggest that the
PCC has sent a
run signal to the
fuel solenoid.
Fuel supply or fuel delivery.
1. Restricted fuel supply due to:
a. Fuel level below pickup tube in
tank.
b. Closed shutoff valve in supply
line.
c. Fuel injectors clogged.
d. Air in fuel system.
2. The mechanical fuel linkage could be
binding, loose, or damaged.
3. Fuel solenoid (K1) on the injection
pump not energized due to:
a. Open in fuel solenoid circuit or
defective governor module.
b. Defective fuel solenoid.
1a. Add fuel if low. Prime the fuel system.
1b. Open any closed shutoff valve in the fuel line
supplying the engine.
1c. Refer to engine service manual.
1d. Bleed air from fuel system. Refer to engine ser-
vice manual.
2. Inspect the mechanical fuel linkage, and repair
or replace as necessary.
Follow the procedure in the engine repair
manual to check the EFC for binding or damage.
Disconnect the actuator connector, and connect +12 VDC from the battery to the actuator.
The actuator should click upon application and
removal of the voltage.
If the actuator does not click, refer to the engine
manual.
If the actuator clicks, reconnect the wires to the
actuator.
3a. Reset the control. Attempt to start and check for
B+ at the K1 fuel solenoid coil on the injection
pump and at output of governor module. Check
continuity from J6-20 and 21 to J6-19.
3b. Check wiring continuity of fuel solenoid circuit.
Test fuel solenoid.
Repair or replace as necessary.
4. Fuel tank solenoid not energized due
to:
5. Engine fuel injection or other engine
problem.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
a. Open in fuel tank solenoid circuit.
b. Defective fuel tank solenoid.
4-22
4a. Check wiring continuity of fuel tank solenoid cir-
cuit.
4b. Test fuel tank solenoid.
Repair or replace as necessary.
5. Refer to the engine service manual.
Page 59
TABLE 4-11. ENGINE CRANKS BUT DOES NOT START
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“OVERCRANK”
(222)
message
−and
While cranking,
Run LED DS12
on the
engine interface
board (A31)
is on.
and
While cranking,
Run LED DS2
on the
governor output
module (A38)
is off.
The run signal is not getting through the
governor module to the fuel solenoid.
1. The run signal is not getting out of the
engine interface board (A31). A31
may be bad.
2. There is an open between the engine
interface board (A31) and the governor output module (A38).
3. The run signal is not getting through
the governor output module (A38).
A38 may be bad.
Reset the control. Attempt to start and check for B+
at A31 J4-1.
*1. Install harness tool between A31 J4/P4. Reset
the control. Attempt to start and check for B+ at
A31 J4-1. If there is no B+ at A31 J4-1, replace
A31.
*2. If there is B+ at A31 J4-1, install harness tool be-
tween A38 J6/P6. Check for B+ at
A38 J6-19, while attempting to crank. If there is
no B+ at A38 J6-19, isolate to connectors and
wiring. Repair or replace as necessary.
3. If there is B+ at A31 J4-1, and there is B+ at A38
J6-19, check continuity from A38 J6-15 to battery ground, if not continuity replace harness, if
continuity, replace A38.
NOTE:
These
indications
suggest that the
PCC has sent a
run signal to the
governor
module, but the
signal is not
getting through
the governor
module to the
fuel solenoid.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-23
Page 60
TABLE 4-12. ENGINE CRANKS BUT DOES NOT START
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“OVERCRANK”
(222)
message
−and
Run LED DS12
on the
engine interface
board (A31)
is off.
NOTE:
These
indications
suggest that the
PCC has NOT
sent a run
signal −
(fuel solenoid
enable signal)
out to the
governor
module and the
fuel solenoid.
The run signal from the digital board (A32)
is not being processed by the engine interface board (A31).
1. The run signal is not getting out of the
digital board (A32). A32 may be bad.
2. The run signal is not being processed
by the engine interface board (A31).
A31 may be bad.
*Install harness tool between A32 J4/P4. Attempt to
start and check for ground signal at A32 J4−8.
1. If there is no ground signal at A32 J4−8, replace
A32.
2. If there is a ground signal at A32 J4−8, replace
A31.
“FAIL TO
CRANK”
(221)
message
NOTE:
The engine is
cranking but
shutting down
on a 221 fault.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
The mag pickup signal is not being
sensed.
Refer to the mag pickup shutdown message
(220).
4-24
Page 61
TABLE 4-13. LOW OIL PRESSURE WARNING (200) OR SHUTDOWN (201)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“LOW OIL
PRESSURE”
warning
(200) or
shutdown
(201)
message.
1. Low oil level. Clogged lines or filters.
2a. Sender or oil pump could be bad. Or
the generator set may be shutting
down on another fault.
1. Check oil level, lines and filters. If oil system is
OK but oil level is low, replenish. Oil pressure
limits are listed in
2. Disconnect the oil pressure sender leads, and
connect an oil pressure sender simulator to the
harness.
a. If the control responds to the simulator, recon-
nect the sender, disconnect the run signal wire
at the fuel solenoid, and crank the engine.
Check the oil pressure reading on the digital
display.
• If the display shows an acceptable oil pressure, the problem may not be in the oil or oil
sensing system. The generator set may
be shutting down on another fault (out of
fuel, blown governor fuse, intermittent
connector). Restart the generator set and
monitor the PCC display panel for other
faults.
• If the display does not show an acceptable
oil pressure, replace the sender. If the
PCC still doesn’t display an oil pressure
while cranking, the oil pump may be faulty .
Refer to the engine service manual.
Table 4-3.
2b. Harness or PCC circuit board could be
bad.
Isolate to the harness, engine inter-
face board (A31), analog board (A33),
or digital board (A32).
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-25
*b. If the control does not respond to the simulator,
the PCC or the harness is bad. Install harness
tool between A31 J2/P2.
Check for +5 VDC at the sender (lead marked
E1-B). If there is no 5 VDC at the sender
• Check for 5 VDC at A31 J5-18.
• If yes, harness is bad. If no, check for 5
VDC at A31 J2-24.
• If yes, A31 is bad. If no, A33 is bad.
If there is 5 VDC at the sender, use the sender
simulator to generate a signal to A31 J2-23. If
the pressure signal (.5 to 4.5 VDC) does not get
to A31 J2-23, isolate to the harness or A31. If
the pressure signal does get to A31 J2-23, refer
to the analog/digital troubleshooting procedure
(
Table 4-35a/b
).
Page 62
TABLE 4-14. SENDER WARNINGS (204 or 213)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“OIL
PRESSURE
SENDER”
warning
(204)
message.
1. The sender connections could be bad.
2. The sender, the harness, engine interface board (A31), digital board (A32),
or analog board (A33) could be faulty.
1. Check the sender connections.
*2. Isolate to the sender, harness, engine interface
board (A31), analog board (A33), or digital
board (A32).
Disconnect the oil pressure sender leads, and
connect an oil pressure sender simulator to the
harness.
“OIL PRES SENDER” warning is displayed
after the fault condition is sensed for 10 seconds.
a. If the control responds to the simulator, r e -
place the sender.
*b. If the control does not respond to the simulator,
the PCC or the harness is bad. Install harness
tool between A31 J2/P2.
Check for +5 VDC at the sender (lead marked
E1-B). If there is no 5 VDC at the sender
• Check for 5 VDC at A31 J5-18.
• If yes, harness is bad. If no, check for 5
VDC at A31 J2-24.
• If yes, A31 is bad. If no, A33 is bad.
If there is 5 VDC at the sender, use the sender
simulator to generate a signal to A31 J2-23. If
the pressure signal (.5 to 4.5 VDC) does not get
to A31 J2-23, isolate to the harness or A31. If
the pressure signal does get to A31 J2-23, refer
to the analog/digital troubleshooting procedure
(
Table 4-35a/b
).
“COOLANT
SENDER”
warning
(213)
message.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
1. The sender connections could be bad.
2. The sender, the harness, engine interface board (A31), digital board (A32),
or analog board (A33) could be faulty.
1. Check the sender connections.
*2. Isolate to the sender, harness, engine interface
board (A31), analog board (A33), or digital
board (A32).
Disconnect the sender, and plug in a resistive
sender simulator to isolate the fault.
a. If the control responds to the simulator, r e -
place the sender.
b. If the control does not respond to the simu-
lator, refer to the high coolant temp troubleshooting procedure.
4-26
Page 63
TABLE 4-15. LOW ENGINE TEMPERATURE WARNING (210)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“LOW
COOLANT
TEMP”
warning
(210)
message.
Coolant level
is normal.
Heater is OK.
Coolant temp
on front panel
display is OK.
DS3 on the
engine
interface
board, A31,
is on.
DS3 / A31 is on, indicating that engine interface board A31 is receiving a low coolant temp from the sender.
The sender, the harness or A31 could be
bad.
Isolate the source of the signal.
Unplug the coolant temperature switch (S1) and re-
set the control.
1. If the 210 warning message drops out and does
not reappear, replace the sender.
*2. If the 210 warning message reappears and re-
mains after control reset, disconnect A31 J4
and check continuity from P4−13 to GND.
• If there is continuity, replace the harness.
• If there is no continuity, replace circuit
board A31.
“LOW
COOLANT
TEMP”
warning
(210)
message.
Coolant level
is normal.
Heater is OK.
Coolant temp
on front panel
display is OK.
DS3 on the
engine
interface
board, A31,
is off.
DS3 / A31 is off, indicating that engine interface board A31 is not receiving a low en gine temp signal from the sender—but the
210 message indicates that A32, the digital
board, is responding to a false low engine
temp signal.
A31, the engine interface board, or A32,
the digital board, could be bad.
Isolate the source of the signal.
Check J4−6/P4−6 on A32.
*1. Install harness tool between A32 J4/P4.
2. Open J4−6 and reset the control.
• If fault drops out and does not return, replace A31.
• If fault returns after resetting the control,
replace A32.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-27
Page 64
TABLE 4-16. HIGH ENGINE TEMPERATURE WARNING (211) OR SHUTDOWN (212)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“HIGH
COOLANT
TEMP”
warning
(211) or
shutdown
(212)
message.
Coolant
mixture and
level is normal.
No airflow
obstructions.
Fan belt is OK.
1. Engine problem:
• Coolant pump could be faulty.
• Thermostat could be faulty.
• There could be an obstruction in
the coolant flow.
• External coolant pump (with remote radiator) could be faulty.
• External radiator fan motor (with
remote radiator) could be faulty.
2. The generator set may have been
overloaded.
3. Sender, harness or PCC circuit board
could be bad.
1. Refer to the engine service manual if there are
any physical indications of overheating.
2. Correct any overload condition.
3. If there are no physical indications of overheating, check to see if the PCC accurately displays
ambient engine temperature.
• If the PCC ambient coolant temperature
reading is accurate, the engine may be
overheating. Refer to the engine service
manual.
• If the PCC ambient coolant temperature
reading is not accurate, isolate to the
sender, harness, engine interface board
(A31), analog board, or digital board.
Disconnect the coolant temperature sender
leads, and connect a coolant temperature
sender simulator to the harness.
a. If the control responds to the simulator, re-
place the sender.
*b. If the control does not respond to the simu-
lator, install harness tool between A31
J5/P5. Connect the coolant temperature
sender simulator (and B+) to A31 J5.
• If the control displays the correct simulated
temperature, replace the harness.
• If the control does not display the correct
simulated temperature, install harness
tool at A31 J2/P2, and open lines 18/19
(and 14/15, if applicable). Check for continuity between A31 J2-18 to 19 (for coolant
temp L), and A31 J2-14 to 15 (for coolant
temp R).
• If no continuity, then A31 is bad.
• If continuity is OK, then send a simu-
lated temperature signal and measure the voltage out of A31 (A31
J2-18 to 19, and A31 J2-14 to 15).
If voltage is not OK (refer to the analog board inputs and outputs,
), replace A33.
4-36
If voltage is OK, refer to the analog/
digital troubleshooting procedure
Table 4-35a/b
(
).
Table
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-28
Page 65
TABLE 4-17. LOW COOLANT WARNING OR SHUTDOWN (214 / 215)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“LOW
COOLANT
LVL” warning
(214) or
shutdown
(215) message
Coolant level
is normal.
DS2 on the
engine
interface
board, A31,
is on.
DS2 on A31 is on, indicating that A31 is receiving a low coolant signal from the sender.
The sender, the harness or the A31 circuit
board could be bad.
If the coolant level is normal, isolate the source of the
low coolant signal. (This is a ground signal.)
Disconnect the signal lead at the sender and reset
the control.
1. If the 215 shutdown message drops out and
does not reappear, replace the sender.
*2. If the 215 shutdown message reappears and
remains after control reset, disconnect J4/A31
and check continuity from P4−7 to GND.
• If there is continuity, replace the harness.
• If there is no continuity, replace circuit
board A31.
“LOW
COOLANT
LVL” warning
(214) or
shutdown
(215) message
Coolant level
is normal.
DS2 on the
engine
interface
board, A31,
is off.
DS2 on A31 is off, indicating that A31 is not
receiving a low coolant signal from the
sender—but the 215 message indicates
that A32, the digital board, is responding to
a false low coolant signal.
A31, the engine interface board, or A32, the
digital board, could be bad.
If the coolant level is normal, isolate the source of the
low coolant signal.
Check J4−4/P4−4 on A32.
*1. Install harness tool between A32 J4/P4.
2. Open the J4-4 circuit and reset the control.
• If the fault drops out and does not return,
replace A31.
• If the fault returns after resetting the control, replace A32.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-29
Page 66
TABLE 4-18. MAG PICKUP SHUTDOWN (220)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“MAG
PICKUP”
shutdown
message (220)
This indicates that the PCC is not sensing
the mag pickup signal, or the mag pickup
frequency does not correspond (in proportion) to the genset output frequency.
1. The PCC may not be set for the correct
generator set.
2. Loose or damaged mag pickup wire.
3. Damaged mag pickup (MPU).
4. The harness, the engine interface
board (A31), the analog board (A33) o r
the digital board (A32) could be bad.
1. Check and correct setting if necessary.
2. Inspect the wires, and repair or replace as necessary.
*3/4 To isolate the problem, reset the control and at-
tempt to start the set in idle mode.
a. If the engine displays a “FAIL TO CRANK” shut-
down message, or if the engine starts and idles,
but then shuts down on a MAG PICKUP fault,
the MPU sender could be bad. Remove the
MPU connectors and check for 3.5 to 15 VAC at
the MPU while cranking.
• If no output, check for damage or debris.
Also check for improper adjustment of the
MPU. (Refer to
no output, replace the MPU sender.
• If the MPU output is OK, install harness
tool between A32 J4/P4. Check for MPU
voltage at A32 J4-10 to 11, while cranking.
If OK, replace A32. If not OK, use continuity checks to isolate to A31 or harness.
b. If the engine starts and idles, and does not dis-
play a fault, then there could be a frequency
mismatch problem.
• Measure generator output frequency with
a digital multimeter and compare to the frequency on the PCC display.
• If they do match, multiply the frequency by
30 and compare this number to the RPM
on the PCC display. If these are not the
same, the MPU sender may be bad. Replace the MPU sender
• If the multimeter and PCC frequencies do
not match, there is a frequency sensing
problem. Verify the accuracy of the PCC
L1N voltage, and then refer to the analog/
digital troubleshooting procedure (
4-35a/b
).
Section 5
.) If there is still
Table
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-30
Page 67
TABLE 4-19. OVERSPEED SHUTDOWN (223)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“OVERSPEED”
shutdown
message (223)
1. The mechanical fuel linkage could be
binding, loose, or damaged.
2. The governor output module (A38) or
the digital board (A32) could be bad.
1. Inspect the mechanical fuel linkage, and repair
or replace as necessary.
• Follow the procedure in the engine repair
manual to check the EFC for binding or
damage.
• Disconnect the actuator connector, and
connect +12 VDC from the battery to the
actuator. The actuator should click upon
application and removal of the voltage.
If the actuator does not click, refer to the
engine manual.
If the actuator clicks, reconnect the wires
to the actuator.
*2. Reset the control, and start the set while moni-
toring the PCC duty cycle display.
• If the duty cycle goes high (above 40%) and the
set shuts down on overspeed, replace A32.
• If the duty cycle goes to zero and the set shuts
down on overspeed, replace A38.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-31
Page 68
TABLE 4-20a. FAIL TO SYNCHRONIZE (224)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“FAIL TO
SYNCHRONIZE” warning
(224) or
shutdown
(224)
message.
1. Improper adjustment of bus or generator set voltage.
2. Generator set hunting due to improper
synchronizing adjustments.
1. Verify that the bus voltage is within plus or minus 5% of the value which is programmed into
the PowerCommand control, and verify that the
generator set is operating at proper voltage and
frequency. Verify that the bus PT module is
properly calibrated. (Refer to
in
age Calibration
TO SYNCHRONIZE time delay. I t should be set
for approximately 120 seconds. Check paralleling setup adjustments, particularly PERM WIN PHASE and PERM WIN - TIME. They are typically adjusted to 20 degrees and 0.5 seconds.
2. Check synchronizer adjustments in the PowerCommand control set−up. If you are unsure of
proper adjustment procedure, returning the unit
to it’s default values should result in proper operation. The default values are shown in the test
report which is shipped with the generator set.
In particular, check values for paralleling functions, governing and voltage regulation.
Section 5
Digital Bus Volt-
). Check the FAIL
3. Unstable or hunting generator set due
to governor component failure or misadjustment.
Continued On Next Page...
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
3. Inspect generator set governing system for evidence of binding or sticking linkages or other
components which are not operating correctly.
Verify that water jacket heaters are operational
and properly functioning. Check and adjust
governor settings as required.
4-32
Page 69
TABLE 4-20b. FAIL TO SYNCHRONIZE (224)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“FAIL TO
SYNCHRONIZE” warning
(224) or
shutdown
(224)
message.
4. Unstable or hunting generator set due
to air entrained in the fuel system.
4. This problem is indicated in situations where
the generator set performs properly after the
generator set is up and running with load, but
experiences ”FAIL TO SYNCHRONIZE” alarms
after it has been shut down for several days.
Check the generator set fuel system for leaks or
cracks. If fuel filters have recently been
changed, air may be trapped in the fuel filter
heads. Check to be sure that there is a fuel head
on the engine fuel pump. Check fuel line routing
for overhead loops which could result in the
trapping of air in the system if the system sits
idle for some period of time. Parallel systems
should use option C174, the fuel pump feature
option. This feature is available as an aftermarket accessory kit.
Note: The generator set will synchronize
faster as the synchronize acceptance window is widened (i.e., the value in the PERM
WIN−PHASE is increased) and as the acceptance time is minimized (the value in the
PERM WIN−TIME is minimized). Caution
should be taken in utility (mains) paralleling
applications to avoid damage to the generator set by inappropriate setting of these parameters.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-33
Page 70
TABLE 4-21a. FAIL TO CLOSE (226)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“FAIL TO
CLOSE”
warning (226)
or shutdown
(226)
message.
1. Check the paralleling breaker for indication that the breaker is tripped and
locked out from a signal issued from
it’s internal trip unit
2. Breaker charge circuit is not operating
properly. (Power circuit breakers only .)
Continued On Next Page...
1. If the breaker has tripped due to operation of it’s
internal trip unit, the alternator and electrical
distribution system connected to the alternator
should be carefully inspected for evidence of
burning or tracking, which might indicate that an
electrical fault has occurred. If no evidence of a
fault is found, reset the trip unit and verify that
the trip settings of the breaker are appropriate
for the application. Reset the fault on the PowerCommand control and check the system operation to verify that the failure to close fault
problem has been eliminated.
2. Check the circuit breaker status indicators and
verify that the breaker status indicates that the
breaker is properly charged. If it is, go on to step
3. If it is not charged, check the charge circuit for
proper operation. Switch the PowerCommand
control RUN/OFF/AUTO switch to OFF and
then manually recharge the paralleling breaker
according to the manufacturer’s instructions.
Switch the PowerCommand control RUN/OFF/
AUTO switch back to RUN. The generator set
should start and accelerate to rated speed and
voltage and the operator should be able to
manually control the circuit breaker from the
pushbuttons on the front panel of the PowerCommand control. In most cases the breaker
should automatically recharge on closing to the
system bus. If this does not occur , problem may
be in the control wiring to the breaker, or the
control power source.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
NOTE: Some breakers are not able to be set
up to charge on closing (they will recharge
on opening). If this is the case with your
installation, it is critical that the generator
set be allowed to operate for a cooldown period which is long enough for the breaker to
completely charge before the generator set
is shut down. If the generator set is shut
down on a fault condition, the breaker may
require manual recharge before the system
can be put back into automatic operation.
4-34
Page 71
TABLE 4-21b. FAIL TO CLOSE (226)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“FAIL TO
CLOSE”
warning (226)
or shutdown
(226)
message.
3. Breaker close signal has been issued
from the PowerCommand control, but
has not reached the breaker.
4. Breaker status (open/close) signals
are not properly connected to the PowerCommand control, or are not operating properly.
3. Disconnect breaker control wiring and verify
that the control is sending a close signal to the
breaker. If the breaker signal is present at the
generator set control, reconnect the control wiring at the set, verify that it is present at the
breaker terminals.
Note that in Onan paralleling systems, DC power for operation of the relay comes from the generator control. Verify that the 20 amp customer
B+ fuse (F1 − engine harness assembly) is OK
and that the pilot relay operates properly.
4. Verify that the breaker auxiliary contact wiring is
properly connected to the generator set. Verify
that the breaker is sending proper condition signals to the generator set, by disconnecting the
control wiring at the breaker and verifying that
the breaker auxiliary contacts change state
when breaker condition changes. If they are
functioning properly, verify that the signals are
reaching the generator set by reconnecting the
wiring and the breaker and checking for condition change at the generator set control accessory box.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-35
Page 72
TABLE 4-22. DC (BATTERY) WARNINGS (230, 231, 232)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“LOW DC
VOLTAGE”
(230) or
“WEAK
BATTERY”
(232),
warning
message.
1. Weak or discharged battery.
2. Low electrolyte level in battery.
3. Battery connections loose or dirty.
4. Insufficient battery charging voltage.
5. Engine DC alternator could be bad.
6. If the batteries are OK, the problem
may be the harness, the engine interface board (A31), the digital board
(A32), or the analog board (A33).
1. Recharge or replace the battery. Specific gravity for a fully charged battery is approximately
1.260 at 80° F (27° C).
2. Replenish electrolyte and recharge battery.
3. Clean and tighten or replace the battery cable
connectors and cables at the battery and the
set.
4. Adjust charge rate of battery charging circuit,
according to manufacturers instructions.
5. Replace engine DC alternator if normal battery
charging voltage is not obtained.
*6. If the battery voltage, electrolyte, and connec-
tions are OK, check the battery voltage at A31
J5-17. If the voltage is not OK (same as battery
voltage), disconnect J5 and isolate to the harness or A31.
If the voltage is OK, check battery voltage at
A33 J1-31. If the voltage is not OK, replace
A31. If the voltage at A33 J1-31 is OK, isolate to
A33 or A32 using the analog input troubleshooting procedure (
Table 4-35a/b
).
“HIGH DC
VOLTAGE”
(231)
warning
message.
But battery
voltage is OK.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
1. Excessive battery charging voltage.
2. Engien DC alternator could be bad.
3. If the battery voltage is OK, the problem may be the engine interface board
(A31), the digital board (A32), or the
analog board (A33).
4-36
1. Adjust charge rate of battery charging circuit ac cording to manufacturers instructions.
2. Replace engine DC alternator if normal battery
charging voltage is not obtained.
*3. Check the battery voltage at A31 J5-17. If the
voltage is not OK (same as battery voltage), disconnect J5 and isolate to the harness or A31.
If the voltage is OK, check battery voltage at
A33 J1-31. If the voltage is not OK, replace
A31. If the voltage at A33 J1-31 is OK, isolate to
A33 or A32 using the analog input troubleshooting procedure (
Table 4-35a/b
).
Page 73
TABLE 4-23. LOW FUEL −DAY WARNING (240)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“LOW FUEL−
DAY”
warning
message (240)
Fuel level is
normal.
DS1 on the
engine
interface
board, A31,
is on.
“LOW FUEL−
DAY”
warning
message (240)
Fuel level is
normal.
DS1 (A31)
and DS13
(A34) are off.
DS1 on A31 is on, indicating that A31 is receiving a low fuel signal from the sender.
The sender, the harness or the A31 circuit
board could be bad.
DS1 on A31 is off, indicating that the PCC is
not receiving a low fuel signal from the
sender—but the 240 message indicates
that A32, the digital board, is responding to
a false low fuel signal.
A31, the engine interface board, or A32, the
digital board, could be bad.
If the fuel level is normal, isolate the source of the low
fuel signal.
Disconnect the signal lead at the sender and reset
the control.
1. If the 240 message drops out and does not reappear, replace the sender.
*2. If the 240 message reappears and remains af-
ter control reset, disconnect J4/A31 and check
continuity from P4−14 to GND.
• If there is continuity, replace the harness.
• If there is no continuity, replace circuit
board A31.
If the fuel level is normal, isolate the source of the low
fuel signal.
*1. Install a breakout connector at A32 J4.
2. Open the J4-15 circuit and reset the control.
• If the fault drops out and does not return,
replace A31.
• If the fault returns after resetting the control, go to step 3.
3. Install harness tool between A32 J2/P2.
4. Opern the J2-19 circuit and reset the control.
• If the fault drops out and does not return,
replace A31.
• If the fault returns after resetting the control, replace A32.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-37
Page 74
TABLE 4-24. LOW FUEL WARNING (241)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“LOW FUEL”
warning
message (241)
Fuel level is
normal.
DS13 on the
customer
interface
board, A34, is
on.
“LOW FUEL”
warning
message (241)
Fuel level is
normal.
DS13 (A34) is
off.
DS13 on A34 is on, indicating that A34 is receiving a low fuel signal from the customer
circuit.
If there is no actual fault, the problem may
be a short to ground in the external wiring or
a bad customer interface board (A34)
DS13 on A34 is of f, indicating that the PCC
is not receiving a low fuel signal from the
sender—but the 241 message indicates
that A32, the digital board, is responding to
a false low fuel signal.
A34, the customer interface board, or A32,
the digital board, could be bad.
.
If the fuel level is normal, isolate the source of the low
fuel signal.
Disconnect the signal lead near the control and reset
the control.
1. If the 241 message drops out and does not reappear, there is a short to ground in the external
wiring or a faulty sender.
*2. If the 241 message reappears and remains af-
ter control reset, disconnect J1/A34 and check
continuity from P1−5 to GND.
• If there is continuity, find and repair a short
to ground in the external wiring.
• If there is no continuity, replace circuit
board A34.
If the fuel level is normal, isolate the source of the low
fuel signal.
*1. Install harness tool between A32 J2/P2.
2. Open the J2-19 circuit and reset the control.
• If the fault drops out and does not return,
replace A34.
• If the fault returns after resetting the control, replace A32.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-38
Page 75
TABLE 4-25. EEPROM ERROR SHUTDOWN (250) OR WARNING (251, 252)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“EEPROM
ERROR”
shutdown
(250)
message.
“EEPROM
ERROR”
warning
(251)
message.
The EE memory on the digital board (A32)
may be bad.
The EE memory on the digital board (A32)
may be bad.
1. Perform the initial start setup procedure.
Turn the Run/Off/Auto switch to Off and reset
the control. Simultaneously press the RESET,
MENU, and PHASE SELECT keys to start the
setup.
Select the correct values, save your choices,
and attempt to start the set.
2. If the set shuts down on the same EEPROM
ERROR message, replace the digital board
(A32).
1. Perform the adjustment procedures (described
Section 5
in
Reset the control. Shut off and restart the set.
2. If the control generates the same EEPROM
ERROR message, perform the calibration procedures in
Reset the control. Shut off and restart the set.
3. If the control generates the same EEPROM
ERROR message, replace the digital board
(A32).
). Save the adjustments.
Section 5
.
“EEPROM
ERROR”
warning
(252)
message.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
The EE memory on the digital board (A32)
may be bad.
1. If this message occurred during an adjustment,
option selection, or calibration of the PCC,
verify the values or choices selected and repeat
the save operation.
Reset the control. Shut off and restart the set.
2. If the control generates the same EEPROM
ERROR message, replace the digital board
(A32).
4-39
Page 76
TABLE 4-26. CUSTOMER FAULTS (260, 261, 262 or 263)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“CUSTOMER
FAULT
(260, 261, 262
or 263)
message.
And
corresponding
LED on
customer
interface board
A34 is on.
If the corresponding LED on the customer
interface board (A34) is on, then A34 is receiving a signal from the customer circuit.
If there is no actual fault, the problem may
be a short to ground in the external wiring or
a bad customer interface board (A34).
Isolate the source of the false signal.
Disconnect the signal lead near the control and reset
the control.
1. If the message drops out, there is a short to
ground in the external wiring.
2. If the message remains, replace A34.
“CUSTOMER
FAULT
(260, 261, 262
or 263)
message.
And
corresponding
LED on
customer
interface board
A34 is off.
If the corresponding LED on the customer
interface board (A34) is off, then A34 is not
receiving a signal from the customer circuit.
The message indicates that A32, the digital
board, is responding to a false signal.
A34, the customer interface board, or A32,
the digital board, could be bad.
Isolate the source of the false signal.
Check J2/P2 on A32.
*1. Install harness tool between A32 J2/P2.
2. Open the appropriate circuit J2-3, J2-24, J2-9,
or J2-15 and reset the control.
• If the fault does not return, replace A34.
• If the fault reappears, replace A32.
A 34
LED
DS4
DS11
DS15
DS3
A32
CONNECTOR
J2-3
J2-24
J2-9
J2-15
CUSTOMER
FAULT #
1
2
3
4
FAULT
CODE
260
261
262
263
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-40
Page 77
TABLE 4-27a. PHASE ROTATION (270)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“PHASE
ROTATION”
shutdown
(270)
message.
1. Single phase bus condition.
2. Generator set output power feeders
are improperly connected.
1. Verify that bus voltage is proper and is not single
phased.
2. Verify phase rotation of the generator set output
relative to the system bus. Correct wiring of
power output conductors if required. The phase
relationship between the generator set and the
system bus can be checked by either using a
phase rotation checker, o r b y using synchronizing lamps or two voltmeters. The procedure for
using voltmeters for checking phase relationship is as follows:
Energize the system bus and start the generator set in question in the RUN mode, but do not
close the paralleling breaker. Connect each
voltmeter from the line to load side of a single
phase of the paralleling breaker (see Figure
8-1). If the generator set and bus have the same
phase rotation, the voltmeters should rise and
fall in voltage at the same time. If they are not in
phase, one will rise while the other falls.
Continued On Next Page...
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-41
Page 78
TABLE 4-27b. PHASE ROTATION (270)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“PHASE
ROTATION”
shutdown
(270)
message.
3. Wiring to bus PT module is not correct.
3. If power conductors are properly phased, check
the phase rotation of the wiring to the generator
set CT/PT module (A36) and Bus PT module
(A39). This is done using voltmeters connected
as shown in Figure 8-1. Energize the system
bus and start the generator set being tested in
the RUN mode. Operate the display screen on
the PowerCommand control to show the digital
synchroscope (bus frequency). Observe the
voltmeter(s) and the synchronized indicator (*)
on the PowerCommand screen. When the voltage of the meter(s) approaches zero, the *
should be displayed. If the * is on when the voltmeters are reading their highest value, the Bus
PT module or the genset CT/PT module is incorrectly wired. If incorrect wiring is indicated,
switch off the power supply to the system bus
and manually close the paralleling breaker by
pushing the breaker close switch on the front of
the PowerCommand control. Check the voltage
between phase L1 of the generator CT/PT module (J9-4 yellow) and phase L1 of the Bus PT
module (terminal TB1-1 on the module). If there
is voltage difference between these points, reverse the wiring between TB1-1 and TB1-3 on
the Bus PT module. Retest the system to be
certain that the phase relationship problem has
been corrected. If no voltage difference is
sensed at the input to the CT/PT module and
Bus PT module, the problem could be in the wiring between the Bus PT module and the PowerCommand control. Reverse the connections
between terminals TB2-1, 2 with TB2-5, 6. Retest the system to make sure that the phase
relationship problem has been corrected.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-42
Page 79
TABLE 4-28. FIRST START (272)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“FIRST
START”
warning (272)
message.
1. Master First Start Sensor has failed.
2. Interconnection between Master First
Start Sensor and the PowerCommand
control has failed.
1. Verify that the Master First Start Sensor is properly functioning. This can be accomplished by
connecting a DC voltmeter from ground to the
appropriate terminal on the Master First Start
Sensor to the PowerCommand Control. The
voltmeter should indicate a pulsing voltage
present on the terminal.
2. Verify that the voltage pulse is present at the
PowerCommand Control (terminal TB1−50).
Check and repair any problems in the interconnection wiring between the generator set and
the Master First Start Sensor.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-43
Page 80
TABLE 4-29a. HIGH AC VOLTAGE SHUTDOWN (301)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“HIGH AC
VOLTAGE ”
shutdown
(301)
message.
1. The problem may be in the PCC, the
alternator, or the interconnection between them.
Note 1: The PCC may indicate either
a low AC Voltage or High AC Voltage
shutdown due to the design of the
logic in the control.
You must first determine if the output voltage the control sees is low
or high.
Note 2: Residual voltage is normally
5 to 10% of nominal output voltage.
For example, a genset with a 480
volt outpu t , will have a residual voltage of 25 to 50 VAC at normal operating speed.
1. Set the display on the PCC to GEN, VOLTS,
L-N.
a. Start the genset and observe the voltage
displayed on the digital display.
b. If all phases of voltage are balanced and not
zero, but lower than normal, the alternator
and the input to the PCC are OK. The problem is in the excitation circuit for the alternator. Go to step 2.
c. If one or more phases of voltage are high or
the voltages are unbalanced, the PCC is not
measuring all phases of voltage and is responding to the low “average” of the three
phases of voltage. Go to step 3.
(Continued)
2. The problem may be the regulator
module (A37), the engine interface
board (A31), or the digital board (A32).
2. With DC power to the PCC and with the set not
running, check A31 DS9, the AVR duty cycle
LED. this LED should be off. If it si on, go to step
2d.
Isolate the genset output from the load. Disconnect A37 J10, and place the set in Idle mode. In
Idle mode the excitation circuit is disabled. Start
the set and monitor the AC output voltage with a
digital multimeter.
a. If output voltage is greater than residual (5%
of normal output), go to step 3.
b. If output voltage stays at 0 (or residual), and
DS2 on A37 is off, go to step 4.
c. If output voltage stays at 0 (or residual), and
DS2 on A37 is on, look at DS9 on A31.
If DS9 on A31 is off, replace A37.
d. If DS9 on A31 is on, connect a breakout con-
nector at A32 J4, and open J4-2.
If DS9 goes out, replace A32.
If DS9 stays on replace A31.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-44
Page 81
TABLE 4-29b. HIGH AC VOLTAGE SHUTDOWN (301)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“HIGH AC
VOLTAGE ”
shutdown
(301)
message.
3. The problem may be the PT/CT module (A36) or the interconnecting wiring
to the PT/CT module.
NOTE: To calculate the “expected A36
output” voltage range, do the following:
Determine the ratio between the measured voltage and the expected voltage. The output (18 VAC) of the PT/CT
module will also be reduced by this ratio.
4. The problem may be in the customer
interface board (A34) or the interconnecting wiring.
*3. Before starting the generator set, discon-
nect the harness connector from the PT/CT
module (A36) and connect the harness tool
between A36 and its harness connector.
Check the output voltage at the alternator
output terminals and record the voltages.
a. If the voltages are not balanced, go to step 5.
b. If the voltages are balanced, calculate the
expected output voltage from the PT/C mod-
ule (see Note to the left). Measure and re-
cord the outputs from A36 J8 pins 6−5, 4−3,
and 2−1.
If the output voltage is proportional to the
alternator output voltage the A36 module
is OK. Go on to step 4.
If the voltages are not balanced, replace
A36.
*4. Disconnect the plugs in the following steps
below with the set off then start the set in the
idle mode, and measure voltages with a digi-
tal multimeter.
a. Disconnect J3/P3 (blue) and insert the har-
ness tool. Check the voltage into the cus-
tomer interface board with the harness tool
at J3 terminals 4−6, 5−13, and 7−20. Re-
move the harness tool and reconnect J3 and
P3. These voltages should be the same val-
ues measured in step 3b.
If the voltages are balanced, continue in this
step. If the voltages are unbalanced, repair
the harness between the A36 module and
the A34 board.
b. Disconnect J5/P5 on the customer interface
board and insert the harness tool. Check the
voltage out of the customer interface board
at J5 terminals 24−28, 26−28, and 30−28.
These voltages should be the same values
measured in step 3b.
If the voltages are balanced, go to step 5. If
the voltages are unbalanced, replace the
customer interface board.
(Continued)
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-45
Page 82
TABLE 4-29c. HIGH AC VOLTAGE SHUTDOWN (301)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“HIGH AC
VOLTAGE ”
shutdown
(301)
message.
5. The problem may be the analog board
(A33).
NOTE: To determine the “3-phase
ave” signal voltage range for Step 3b,
use the following formula:
V
3-phase ave = Vin (2.9÷PT) ±5%
out
V
= Actual generator output voltage
in
(phase-to-neutral)
PT = PT primary (120, 240 or 346)
6. The problem may be in the generator
set itself.
*5. Using the harness tool, check the “3-phase
ave” signal at A33 J2-18.
If the voltage is within the expected range,
replace A32. If the voltage is not within the
expected range, replace A33. See Note.
6. Refer to the generator servicing procedures in
Section 6
.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-46
Page 83
TABLE 4-30a. LOW AC VOLTAGE SHUTDOWN (303)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“LOW AC
VOLTAGE ”
shutdown
(303)
message.
1. PMG or field wiring could be faulty.
2. The rotating rectifier assembly (diodes
CR1 through CR6) is faulty.
3. Overload.
4. There may be a loose connector in the
control loop.
5a. The problem may be the analog board
(A33) or the digital board (A32).
5b. The problem may be the regulator
module (A37), the engine interface
board (A31), or the digital board (A32).
1. If output voltage is low and both A37/DS2 and
A31/DS10 are on, check and repair the PMG or
field wiring.
2. Check each diode according to
Generator
3. Check the load and correct any overload.
4. Check connectors J8 and J9 on A36, J3 and J5
on A34, and J7 on A37.
*5. Isolate the genset output from the load. Reset
the control, restart the set, and measure AC
output voltage with a multimeter.
a. If output voltage is high, refer to the trouble-
shooting section for High AC Voltage Shutdown
(301).
If output voltage is normal, the problem must be
in the voltage sensing circuitry (A32 or A33).
Isolate, using the analog input troubleshooting
procedure (
that shows a low voltage on the PCC display.
*b. If output voltage is low, the control cannot drive
the output voltage high enough. The problem
could be A37, A31, or A32. Restart the set and
monitor isolated B+ supply LED A37/DS1,
output duty cycle LED A37/DS2, and
AVR duty cycle LED A31/DS10.
• If A37/DS1 is not on, disconnect A3 J7/P7
and check for B+ at P7-1. (Control must be in
Run mode for B+ reading.)
• If B+ is OK to A37, replace A37.
• If A37/DS1 is on, check A31/DS10 (with the
set running).
• If A31/DS10 is not on with set running, check
for continuity: A31 J1-2 to J4-10 and A31
J1-1 to J4-11 (270 ohms). If no continuity, r e place A31.
• If A31is OK, replace A32.
• If A31/DS10 is on with set running and
A37/DS2 is not on, check the harness.
• If the harness is OK, replace A37.
in
Section 6
Table 4-36a/b
. Service as necessary.
). Check the phase
Servicing the
(Continued)
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-47
Page 84
TABLE 4-30b. LOW AC VOLTAGE SHUTDOWN (303)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“LOW AC
VOLTAGE ”
shutdown
(303)
message.
5c. The problem may be the PT/CT mod-
ule (A36), the analog board (A33), the
customer interface board (A34), or the
digital board (A32).
c. If the measured AC voltage is high, the control
must have lost AC sensing. Check PTs (primary
1K−2.5K ohms; secondary 140−225 ohms),
sensing harness wires, generator output connections, and the customer interface board for
continuity . If these are OK, then check the analog and digital boards, using the analog input
troubleshooting procedure (
Table 4-36a/b
).
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-48
Page 85
TABLE 4-31. UNDER FREQUENCY SHUTDOWN (313)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“UNDER
FREQUENCY”
shutdown
(313)
message.
1. Improper setup.
2. Overload.
3. Fuel or air delivery problem.
4. The governor output module (A38),
the digital board (A32), or the engine
interface board (A31) could be bad.
1. Check Initial Setup (set size) and correct, if necessary.
2. Check the load and correct any overload, if necessary.
Disconnect the load. Reset the control and attempt to restart the generator set.
3. If the engine starts and runs, refer to the engine
fuel/air delivery service procedures.
*4. Disconnect the wire to the fuel solenoid, reset
the control, and crank the set. DS2 on the governor output module A38 should light.
If the duty cycle LED (DS1) on the governor output module (A38) slowly becomes bright, the
governor output module(A38), the digital board
(A32), and the engine interface board (A31) are
functioning properly.
If DS1 does not light or instantly becomes
bright, A31, A32 or A38 may be bad.
A38 - Crank the set, and check the governor duty cycle on the PCC display. If the
duty cycle is OK (60% max), replace governor output module (A38).
If the duty cycle is not OK, the digital board
(A32) or the engine interface board (A31)
may be bad.
• A31 - Check for continuity: A31 J1-13 to
A31 J4-19 and A31 J1-14 to A31 J4-12. If
no continuity, replace A31.
• A32 - If A31 is OK, replace A32
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-49
Page 86
TABLE 4-32. OVERCURRENT WARNING (320) OR SHUTDOWN (321),
Redistribution or publication of this documentby any means, is strictly prohibited.
SHORT CIRCUIT SHUTDOWN (322), OR OVERLOAD WARNING (330)
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“OVERCURRENT”
warning (320)
or shutdown
(321),
or
“SHORT
CIRCUIT”
shutdown
(322), or
OVERLOAD
warning (330)
message.
1. Short or Overload.
2. Incorrect CTs or CT connections.
3. The problem may be a bad PT/CT
module (A36).
4. The problem may be the customer interface board (A34) or connections.
5. The problem may be the analog board
(A33) or the digital board (A32).
1. Check the load and load cables. Repair if necessary.
2. Check CTs and CT connections. Correct if necessary . R efer to
Section 5
3. Disconnect the PT/CT module and check the
3-ohm resistors (J8-15 to 14, J8-22 to 23,
J8-7 to 8). Replace the module if necessary.
*4. Check continuity from A36—through A34—to
A33. Repair the connection or replace A34 if
necessary. Refer to
5. Isolate, using the analog input troubleshooting
procedure (
phase or phases.
Current Transfer Installation
.
Table 4-35a/b
Section 9
). Check the bad
in
for pin reference.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-50
Page 87
TABLE 4-33. REVERSE POWER (335)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
Indicator(s) Possible CauseCorrective Action
“REVERSE
POWER”
shutdown
(335)
message.
1. If this shutdown condition occurs
when a non-paralleled generator
set is loaded, it indicates that the
generator set output CT’s or PT’s
are incorrectly installed.
1. Verify proper CT orientation, wiring and
connections on the control system. Refer to
Current Transformer (CT) Installation
Section 5
. Make sure that the no load fre-
in
quency matches the bus frequency . Check
metering calibration for both generator set
and bus.
2. Verify that the generator set is operating at the correct frequency
2. Make adjustments as required for proper
operation.
and voltage. The bus voltage and
frequency should be the same as
the no-load generator set frequency and voltage.
3. The load sharing line connections
and orientation must be correctly
accomplished for proper load sharing.
3. Verify that load sharing connections are
made as noted in the drawings and that
there are no damaged or disconnected
wires.
4. If the alarm occurs when a large
load is added or shed, dissimilar
transient response of the generator sets in the system may cause
the reverse power condition.
5. Reverse power alarm can also indicate that the generator set is unable to carry load properly.
4. Apply various load steps to each generator
set in the system, noting the voltage and
frequency dips/surges and recovery times.
The generator sets should be adjusted so
that transient load performance is approximately the same in all machines in the system.
5. Verify that the generator set can pick up
and carry loads properly, up t o the rated capacity of the machine. Inability to carry load
can be related to engine misadjustments,
component failures, or poor fuel quality.
Check governing system for binding or
sticking. Check fuel filters and fuel lines for
cracks, leaks or dents. Check air cleaner(s)
for obstructions.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-51
Page 88
TABLE 4-34. LOSS OF EXCITATION (337)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained and experienced service personnel with knowledge of fuels, electricity, and
machinery hazards should perform service procedures. Review safety precautions on pages iii and iv .
Indicator(s) Possible CauseCorrective Action
“LOSS OF
EXCITATION”
shutdown
(337)
message.
1. Improper voltage adjustment of the
generator set relative to the system
bus.
2. Load sharing line mis-connection or
damage.
3. If condition occurs when the generator
set is lightly loaded, leading power factor loads may cause this condition.
1. Verify that the no load voltage of the generator
set matches the bus voltage. Check generator
set metering calibration for both generator set
and bus readings. If no problems are found,
check the paralleling adjustments in the PowerCommand control, to see if they match the default settings in the generator set test report.
2. Verify load sharing line connections and condition. Make corrections as required.
3. Loss of Excitation failure may also be caused by
operation of filters and power factor correction
capacitors in the generator set loads when the
kW load level on the genset is low. The capacitors in the filters and power factor correction
equipment can present a leading power factor
load to the generator set, which (correctly)
shuts down the generator set through the loss
of excitation fault. Leading power factor loads
can cause the generator set to lose control of
the output voltage of the genset, and can cause
kVar load sharing problems, so it is necessary
to protect the genset from excessive leading
power factor and reverse var conditions.
For generator sets prior to the release of
version 2.0 firmware:
Check the load for devices which may apply
leading power factor loads to the generator set.
These include power factor correction capacitors, input filter and some non-linear load devices with internal voltage waveform correction
provisions. These devices may need to be disconnected from the bus until other loads are
added to the system.
For generator sets with version 2.0 and
higher firmware:
(Continued)
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
If there is a loss of excitation fault that cannot be
explained by genset component failures or misadjustments, perform the following steps:
4-52
Page 89
TABLE 4-34. LOSS OF EXCITATION (337) (Continued)
Redistribution or publication of this documentby any means, is strictly prohibited.
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained and experienced service personnel with knowledge of fuels, electricity, and
machinery hazards should perform service procedures. Review safety precautions on pages iii and iv .
Indicator(s) Possible CauseCorrective Action
“LOSS OF
EXCITATION”
shutdown
(337)
message.
3. (continued)
a. Start the generator set and apply system
loads in their normal operation sequence.
Observe the output voltage, power factor,
and % voltage regulation of the generator
set as the loads are applied. (This may
take more than one test.)
b. If the voltage does not rise and the % volt-
age regulation is greater than 0 as the system loads are applied, extend the time
delay on loss of excitation shutdown and
repeat the load addition test.
c. If the increase in time delay does not re-
solve the shutdown condition, contact the
factory for the maximum permissible setting of the loss of excitation shutdown set
points.
d. If the voltage rises or the % voltage regula-
tion value drops to 0 and does not rise as
load is applied, investigate means to remove leading power factor loads from the
genset bus.
4. The generator set may be incapable of
carrying full reactive load due to component failures.
5. If transient conditions result in this
alarm condition, the PowerCommand
control internal set points may need
adjustment.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4. See section 6 of this manual, “Servicing the
Generator, Exciter Rectifier and Exciter Rotor”.
See also repair and diagnosis process for ”Low
AC Voltage” in this section.
5. Consult factory.
4-53
Page 90
TABLE 4-35a. TROUBLESHOOTING ANALOG SIGNALS BETWEEN ANALOG AND DIGITAL
Redistribution or publication of this documentby any means, is strictly prohibited.
BOARDS
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
NOTE: Perform this procedure after you have isolated the problem to either the analog
board (A33) or to the digital board (A32). You must have schematics and wiring
diagrams to identify the various inputs and outputs.
*1. Check that the input to the analog board is correct. There are a few signals (e.g.: 3PH Ave, Line Freq,
Phase Angle 1 to 3, Lead Lag) that are derived from one or more input signals.
1a. To check the sensor input voltages into the analog board, connect the sender simulator and test the
voltage across the + and − inputs at A33 J1 using harness tool. (This assumes that you have verified
that the harness and the engine interface board is good.)
• If the input voltage to the analog board is correct (refer to Table 4-36), go to step 2.
• If the input voltage to the analog board is incorrect, check for 12 VDC at A32 J3-20 and 5 VDC at
A32 J3-12. Do this with the analog board connected to the digital (A32).
If the 12 VDC and 5 VDC voltages are OK, replace the analog board.
If the 12 VDC and 5 VDC voltages are not OK, disconnect A32 J3 and recheck for 12 VDC at
A32 J3-20 and 5 VDC at A32 J3-12.
If the 12 VDC and 5 VDC voltages are now OK, replace the analog board.
If the 12 VDC and 5 VDC voltages are still not OK, replace the digital board.
1b. To check the AC inputs into the analog board, drive the PT/CT inputs (voltage or current) and verify
that the input is correct.
• If the input to the analog board is correct, go to step 2.
• If the input to the analog board is incorrect, disconnect the ribbon cable at A34 J5 and check the volt-
age at A34 J5 again (Customer Interface).
If the voltage is now correct, replace the analog board.
If the voltage is still not correct, the problem is not on the analog or digital boards.
2. If the input to the analog board is correct, determine whether the signal is multiplexed (refer to Table
4-36). If the signal is not multiplexed, go to step 2a. If the signal is multiplexed, go to step 2b.
2a. This step is for non-multiplexed AC signals. Drive the input to the analog board with an AC source,
and test the signal level out of the analog board. You must calculate what the analog output voltage
should be (Table 4-36), assuming the analog board transfer function is linear.
• If the signal level into the digital board is correct, the problem must be on the digital board. Replace
the digital board.
• If the signal level into the digital board is incorrect, remove the ribbon cable connector at A32 J3, and
check the front panel digital display of the bad analog value.
If the display reads 0, replace the analog board.
If the display reads a value other than 0, replace the digital board.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-54
Page 91
TABLE 4-35b. TROUBLESHOOTING ANALOG SIGNALS BETWEEN ANALOG AND
Redistribution or publication of this documentby any means, is strictly prohibited.
DIGITAL BOARDS
WARNING
Many troubleshooting procedures present hazards that can result in severe personal injury or death. Only trained experienced service personnel with knowledge of fuels, electricity, and machinery hazards should perform service procedures. Review safety precautions on pages iii and iv.
NOTE: Perform this procedure after you have isolated the problem to either the analog
board (A33) or to the digital board (A32). You must have schematics and wiring
diagrams to identify the various inputs and outputs.
2b. This step is for multiplexed signals. Is more than one multiplexed signal reading bad?
• No. If the input to the analog board is correct and only one multiplexed signal is reading bad, replace
the analog board.
• Yes. If more than one multiplexed signal reading is bad, remove the ribbon cable connector at
A32 J3 and check the front panel digital display of the bad inputs. It should read 0 for all inputs except the temperature inputs (which should read less than 32° F or less than 0° C) and power factor
(which should read “NA”).
If any values read incorrectly, replace the digital board.
If they all read correctly, measure voltages on the multiplexer control lines (with A32-J3 discon-
nected, measure from Digital board connector J3). Voltages should be:
A32-J3-34: 3.0 ±0.25 VDC
If these control (select) line voltages are not correct, replace the digital board.
If these control (select) line voltages are correct (and the input to the analog board is correct),
reconnect the ribbon cable connector (through harness tool) at A32 J3 and check the 5 VDC
reference at A32 J3-12 and the 12 VDC supply at A32 J3-20.
If the 5 VDC and the 12 VDC voltages are OK, replace the analog board.
If the 5 VDC and the 12 VDC voltages are not OK, disconnect A32 J3 and check the
voltages again (measured from Digital board side).
If the 5 VDC and the 12 VDC voltages are OK with A32 J3 disconnected, replace the
analog board.
If the 5 VDC and the 12 VDC voltages are not OK with A32 J3 disconnected, replace
the digital board.
*CAUTION: Wearing wrist strap, set S12 to Off and A32 S5 to Standby before connecting/disconnecting harness plugs.
4-55
Page 92
TABLE 4−36. ANALOG CIRCUIT BOARD (A33) INPUTS AND OUTPUTS
Redistribution or publication of this documentby any means, is strictly prohibited.
Input NameInput
Connection
L1 (0 to nominal)J4-24 to J4-280 to 18 VACL10 (ACH1)J2-40 to 3.0 VDC
L2 (0 to nominal)J4-26 to J4-280 to 18 VACL20 (ACH2)J2-130 to 3.0 VDC
L3 (0 to nominal)J4-30 to J4-280 to 18 VACL30 (ACH3)J2-10 to 3.0 VDC
CT21 (0 to full load)J4-33 to J4-340 to 1.65 VAC C1 fltrd (ACH4)J2-30 to 1.0 VDC
CT22 (0 to full load)J4-32 to J4-340 to 1.65 VAC C2 fltrd (ACH5)J2-90 to 1.0 VDC
CT23 (0 to full load)J4-31 to J4-340 to 1.65 VAC C3 fltrd (ACH6)J2-170 to 1.0 VDC
(1 to 0.8 pf)Phase angle 1 (ACH7)
(1 to 0.8 pf)Phase angle 2 (ACH7)
(1 to 0.8 pf)Phase angle 3 (ACH7)
(L1 vs CT21)Lead lag (P2A.1))
Bus L1 (0 to nominal)
Bus L2 (0 to nominal)
Bus L3 (0 to nominal)
6
6
6
J4-15 to J4-180 to 18 VACBus L1 (ACH7)J2-70 to 3.0 VDC
J4-16 to J4-180 to 18 VACBus L2 (ACH7)J2-70 to 3.0 VDC
J4-17 to J4-180 to 18 VACBus L3 (ACH7)J2-70 to 3.0 VDC
Input Signal
Range
Output Name
3PH ave (ACH0)J2-180 to 2.9 VDC
Line freq. (HSI.1)J2-210-5V sq wave @ L1 Hz
C1 (ACH7)J2-70 to 1.0 VDC
C2 (ACH7)J2-70 to 1.0 VDC
C3 (ACH7)J2-70 to 1.0 VDC
1
3
3
3
3
Output
Connection
J2-70 to 1.0 VDC
J2-70 to 1.0 VDC
J2-70 to 1.0 VDC
J2-290 or 5 VDC (digital)
2
Output
Signal Range
Bus freq (HS1.3)J2-220-5V sq wave @ Bus L1 Hz
Phase rot (P2A.0)
Bus/gen phase dif (ACH7)
Bus/gen phase (HS1.2)
Synch (ACH7)
Battery voltageJ1-31 (+) to J1-30(−)0 to 32 VDCBattery voltage (ACH7)J2-70 to 2.9 VDC
Oil press (0 to 100 psi)(See note
H2O 1 (6 to 230° F)J1-19/20 to J1-17/18700 to 1800 Ω H2O 1 (ACH7)J2-71.4 to 3.7 VDC
H2O 2 (6 to 230° F)J1-15/16 to J1-14/15700 to 1800 Ω H2O 2 (ACH7)J2-71.4 to 3.7 VDC
Oil temp (6 to 230° F)J1-11/12 to J1-9/10700 to 1800 Ω Oil temp (ACH7)J2-71.4 to 3.7 VDC
Exh temp 1 (32 to 1471° F)J1-7/8 to J1-5/6100 to 376 ΩExh temp 1 (ACH7)J2-70.8 to 3.0 VDC
Exh temp 2 (32 to 1471° F)J1-3/4 to J1-1/2100 to 376 ΩExh temp 2 (ACH7)J2-70.8 to 3.0 VDC
4 )
0.5 to 4.5 VDC Oil press (ACH7)J2-70.5 to 4.5 VDC
5
5
5
J2-260 or 5 VDC (digital)
5
J2-70 to 5.0 VDC
J2-190-5V 120 Hz 0 to 100% DC
J2-7
Notes:
1. All output signals on ACH7 are multiplexed.
2. All output voltages on A33 J2 are referenced to ground (J2-15 and J2-16).
3. Must have L1, L2, L3, CT21, CT22, and CT23 for these phase angle outputs.
4. J1-24 (5VDC), J1-23 (signal), J1-18 (return).
5. Must have L1, L2, L3, Bus L1, Bus L2, and Bus L3 for these outputs.
6. L1, L2, and L3 can be 0 to 180° out of phase with Bus L1, Bus L2, and Bus L3, respectively.
4-56
Page 93
TABLE 4-37. PCC FUSES
Redistribution or publication of this documentby any means, is strictly prohibited.
REFERENCE
LOCATION
Engine InterfaceA31-F15 AmpPCC control B+
Engine InterfaceA31-F35 AmpAuxiliary B+ (for panel lights, run and start relays)
Redistribution or publication of this documentby any means, is strictly prohibited.
TROUBLESHOOTING PROCEDURE
The generator set load sharing settings in the PowerCommand control are factory set and normally do
not require adjustment. The controls are designed
to cause generator sets in the paralleling system to
share load proportionally , based on the standby ratings of the generator sets in the system.
When the system is operating normally, the generator sets in an isolated bus (not utility/mains paralleled) paralleling system will share both real (kW)
and reactive (amps) load equally, within plus or minus 5%. For example, if two 1000 kW generator
sets are paralleled and serving a 2000 kW load, the
generator sets should each carry between 950 and
1050 kW.
If the generator set is not sharing load properly, the
following procedure can be used to diagnose and
solve the problem:
1. The no load speed and voltage of the generator
set must be the same as the system bus. Measure the bus voltage and frequency, and the
generator set voltage and frequency with a true
RMS digital meter. Calibrate the voltage and
current sensing circuits of the control, and
make required adjustments to voltage and frequency to match bus conditions. Adjusting the
voltage and frequency after the generator set is
paralleled to the bus will cause load sharing to
be unequal between generator sets.
2. Check to make sure that the load sharing control wiring is properly connected.
In actual practice, load sharing may be much more
precise than plus or minus 5%, but you should not
be concerned about operational problems unless
the load sharing is in error by more than 5%. If dissimilar generator sets are used in a system, there
may be load sharing inequities for a short time when
loads are applied, but the steady state load sharing
should perform to the plus or minus 5% standard.
If the generator set is paralleled to a utility (mains)
gird, the amount of load on the generator set is programmed into the control in the setup mode or set
from a remote device. It is NOT a function of the load
sharing control system. See
Section 5
for more information on load sharing set−up functions, and utility (mains) paralleling set−up.
3. Check to make sure that each generator set in
the system is capable of carrying its rated load.
4. Fine adjustment to the amount of load carried
by each generator set can be made by adjusting the KW BALANCE and KVAR BALANCE
settings under the paralleling setup menu
(
Section 5
).
5. If the generator sets share load approximately
equally , but there is an oscillating load circulating between the generator sets, the governor
gain may be set too high. Reduce the governor
gain (see
Setup Menu, Section 5
).
6. Consult factory for any other load sharing prob-
lems.
4-58
Page 95
5. Control Service and Calibration
Redistribution or publication of this documentby any means, is strictly prohibited.
GENERAL
This section contains circuit board removal and replacement procedures, calibration procedures for
the genset control and test procedures for the generator and engine components. Refer to the figures
included with this information and also the
Diagrams
Before servicing the PCC, all settings should be recorded. This will enable correct and complete readjustment of the PCC in the event that all previous entries are lost during servicing.
section when instructed.
CIRCUIT BOARD
Analog Board (A33)
TABLE 5-1. CONTROL PANEL RECALIBRATION
1. Voltage, Current and PF.
2. Coolant Temperature L & R
Wiring
ADJUSTMENTPROCEDURE / PAGE
CIRCUIT BOARD
REMOVAL/REPLACEMENT
No special tools (other than a grounding wrist strap)
are required to remove a circuit board from inside
the control panel or the accessory box.
There are several circuit boards that, when replaced, require you to recalibrate the control panel
functions. Table 5-1 lists the circuit boards and the
appropriate procedure to perform to recalibrate the
control panel. The circuit board locations are shown
in Figure 5-1.
Before you attempt to remove a circuit board, read
the
Circuit Board Removal Safety Precautions
this section.
Setup and Calibration Menus
(Page 5-8)
in
Digital Board (A32)Must recalibrate all values, starting with
the
Initial Start Setup
PT/CT Board (A36)Voltage, Current and PF.
Bus PT Module (A39)Voltage
procedure.
1.
Initial Start Setup
2.
Adjust Menu
3.
Setup and Calibration Menus
5-8).
Setup and Calibration Menus
Setup and Calibration Menus
(Page 5-4).
(Page 5-6).
(Page
(Page 5-8)
(Page 5-8)
5-1
Page 96
DISPLAY BOARD
Redistribution or publication of this documentby any means, is strictly prohibited.
A35
S5 POWER ON/
STANDBY SWITCH
DIGITAL BOARD
A32
ANALOG BOARD
A33
BUS PT MODULE
A39
VOLTAGE REGULATOR
OUTPUT MODULE
A37
ENGINE INTERFACE
A31
ACCESSORY BOX
(HC 4/5)
FIGURE 5-1. CIRCUIT BOARD LOCATIONS
CUSTOMER INTERFACE
A34
GOVERNOR
OUTPUT MODULE
A38
PT/CT BOARD
A36
5-2
Page 97
Circuit Board Removal Safety Precautions
Redistribution or publication of this documentby any means, is strictly prohibited.
To prevent circuit board damage due to electrostatic
discharge (ESD), a grounding wrist strap must be
worn when handling circuit boards or socketmounted IC’s. (The wrist strap does not provide a
direct short to ground, but is typically rated at
approximately 1 megohm to ground.)
Attach the clip to a non -painted surface of the control box and place the strap around your wrist before
handling a circuit board.
CAUTION
circuit boards. Always wear a grounding wrist
strap when handling circuit boards or socketmounted IC’s.
Turn off or remove AC power from the battery charger and then remove the negative (−) battery cable
from the set starting battery. This is to make sure
that the set will not start while working on it and to
avoid circuit board damage caused by voltage
spikes when removing and replacing circuit board
connectors.
Electrostatic discharge will damage
WARNING
Ignition of explosive battery gases
can cause severe personal injury or death. Arcing at battery terminals, light switch or other
equipment, flame, pilot lights and sparks can ignite battery gas. Do not smoke, or switch
trouble light ON or OFF near battery . Discharge
static electricity from body before touching batteries by first touching a grounded metal surface.
Ventilate battery area before working on or near
battery—Wear goggles—Stop genset and disconnect charger before disconnecting battery
cables—Disconnect negative (−) cable first and
reconnect last.
CAUTION
Disconnect battery charger from AC
source before disconnecting battery cables.
Otherwise, disconnecting cables can result in
voltage spikes damaging to DC control circuits
of the set.
WARNING
Accidental starting of the generator
set can cause severe personal injury or death.
Prevent accidental starting by disconnecting
the negative (−) cable from the battery terminal.
WRIST STRAP
NON-PAINTED
SURFACE
GROUND LEAD CLIP
FIGURE 5-2. WRIST STRAP
5-3
Page 98
INITIAL START SETUP MENU
Redistribution or publication of this documentby any means, is strictly prohibited.
The facing page shows a block representation of
the INITIAL START SETUP menu.
CAUTION
Selecting this menu resets all operating parameters to the default values for the
selected set. All previously selected setup and
adjustment settings will be lost. Therefore, this
procedure must be performed by technically
qualified personnel only.
This menu appears on the digital display when the
PCC has not been set up for use with a generator
set during factory test, or the digital board was replaced in the PCC.
When this display is showing, you must go through
the Initial Start Setup menu to select the operating
parameters for the generator set. These include
whether the set will be used for Prime Power or
Standby use, the Model Number of the generator
set, and its operating frequency and output voltage.
These choices must be saved into the PCC’s readonly memory before the PCC will accept changes
made to other menus.
STANDBY/PRIME submenu:
Use the buttons next
to the “⇑⇓” symbols to toggle the standby/prime option. Press the button next to the “>>” in the display
to move to the model select submenu.
MODEL select submenu:
the “
⇑” and “⇓” symbols to select the correct genera-
Use the buttons next to
tor set model number, frequency and power rating.
VOLTAGE SELECT submenu:
Use the buttons
next to the “⇑” and “⇓” symbols to select the correct
generator set nominal line-to-line output voltage.
If the PCC is already set up to operate with a specific
generator set, this menu will not appear when power
is applied. To reset the control and display the Initial
Start Setup menu, you can press RESET, MENU, and
PHASE SELECT buttons at the same time.
If you choose to do this, the governor/regulator adjustments and the setup options will be reset to the
default settings (including the editable customer
fault messages). Display calibrations (volts, amps,
PF and coolant temperature) are retained (not reset).
To ensure correct and complete readjustment of the
PCC, it is suggested that all settings be recorded before you perform the reset function.
CAUTION
Improper setup, calibration, or adjustments can cause equipment malfunction or
damage. Setup, calibration, and adjustment
must be performed by technically qualified personnel only.
DELTA / WYE submenu:
the “
⇑” and “⇓” symbols to select the delta or wye op-
Use the buttons next to
tion.
SAVE submenu:
From the model select submenu,
press the button next to the “>>” in the display to
move to the SAVE submenu. Select SAVE to save
your changes. The MAIN MENU will then be displayed.
5-4
Page 99
INITIAL START SETUP
Redistribution or publication of this documentby any means, is strictly prohibited.
(It can be invoked by simultaneously pressing
the Reset, Menu, and Phase Select keys.)
STANDBY/PRIME
⇓⇑ _______>>
<>
⇑ MODEL
<
⇓ (kw mod# freq) >>
<>
⇑ VOLTAGE SELECT
<
⇓ (vac) L-L VAC >>
<>
DELTA / WYE
⇓⇑ _______>>
<>
<>
TO LOOP BACK & CHECK:
<>
SAVE>>
SAVE>>
<>
ENGINEGEN
ADJUST>>
<>
STANDBY/PRIME
⇓⇑ _______>>
<>
Indicates OR" Condition
5-5
Page 100
ADJUST MENU
Redistribution or publication of this documentby any means, is strictly prohibited.
The ADJUST submenus permit adjustment of the
output voltage and frequency and the start and stop
delay times of the generator set.
The complete calibration procedure is described in
the
Calibration Procedure
in this section.
The facing page shows a block representation of
the ADJUST menu. If you press the button next to
the word “ADJUST” in the Main menu, the VOLTAGE ADJUST submenu will appear.
As shown in the diagram, the ADJUST menu has
five submenus, including a save/exit procedure.
Voltage and frequency can be adjusted only when
the generator set is running under normal operating
parameters (not in idle mode). For example, if voltage adjustment is selected when the set is in Idle
mode or not running, the digital display will be:
“⇑ VOLTAGE ”
⇓ N/A >>”
“
VOLTAGE submenu:
Use the buttons next to the “
adjust output voltage
FREQUENCY submenu:
This is the first submenu.
⇑” and “⇓” symbols to
± 5%.
From the VOL TAGE submenu, press the button next to the “>>” in the display to move to the FREQUENCY submenu. Use
the buttons next to the “
output frequency
START DELAY submenu:
⇑” and “⇓” symbols to adjust
± 5%.
This delay applies only
to remote starting in the Auto mode. From the FREQUENCY submenu, press the button next to the
“>>” in the display to move to the START DELAY
submenu. Use the buttons next to the “
⇑” and “⇓”
symbols to set the start delay. The start delay adjustment range is 0 to 300 seconds.
STOP DELAY submenu:
This delay applies only
to remote stopping in the Auto mode. From the
START DELAY submenu, press the button next to
the “>>” in the display to move to the STOP DELAY
submenu. Use the buttons next to the “
⇑” and “⇓”
symbols to set the stop delay. The stop delay adjustment range is 0 to 600 seconds.
IDLE SPEED submenu:
From the STOP DELAY
submenu, press the button next to the “>>” in the
display to move to the IDLE SPEED submenu. Use
the buttons next to the “
⇑” and “⇓” symbols to set the
idle speed. The idle speed adjustment range is 800
RPM
±100 RPM. (Default value is 800 RPM.)
The idle speed can be adjusted only when the gener-
.
ator set is running in the idle mode
mode, N/A is displayed in RPM field.
SAVE/EXIT submenu:
From the STOP DELAY
When not in idle
submenu, press the button next to the “>>” in the
display to move to the SAVE/EXIT submenu. Select
SAVE to save your changes. At the CHANGES
SAVED submenu, select EXIT to return to the main
menu.
If you select SAVE, the adjustments will be retained
after shutdown, and will be in effect when the set is
restarted. If you select EXIT without saving first, the
adjustments will remain in effect until the genset is
shut down, but will be reset (and will not be in effect)
when the set is restarted.
5-6
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.