CUMMINS DFBF, DFAC, DFAB, DFCC, DFCE Installation Manual

...
Page 1
Caution: This document contains mixed page sizes (8.5 x 11 or 11 x
17), which may affect printing. Please adjust your printer settings according to the size of each page you wish to print.
Page 2
Installation Manual
Redistribution or publication of this document,
by any means, is strictly prohibited.
PowerCommand Control
2100 Series
Generator Sets
Printed in U.S.A.
Models
DFAB, DFAC, DFBF, DFCB, DFCC, DFCE
960-0634C 02-2004
Page 3

Table of Contents

Redistribution or publication of this document,
by any means, is strictly prohibited.
SECTION TITLE PAGE
IMPORTANT SAFETY INSTRUCTIONS iii. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 INTRODUCTION
About this Manual 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation Overview 1-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 SPECIFICATIONS 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 MOUNTING THE GENERATOR SET
General 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Location 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Access to Set 3-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vibration Isolators 3-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Aligning Generator with Engine (750 kW Gensets and Larger) 3-5. . . . . . . . .
4 MECHANICAL CONNECTIONS
General 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fuel System 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exhaust System 4-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ventilation and Cooling 4-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 DC CONTROL WIRING
Control Wiring 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TB1 Remote Monitor/Control Connections 5-2. . . . . . . . . . . . . . . . . . . . . . . . . .
TB2 Power Transfer Control (PTC) Connections (Optional) 5-2. . . . . . . . . . . .
Control Relays (K11, K12, K13) 5-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diesel engine exhaust and some of its constituents are known to the State of California to cause cancer, birth defects, and other reproductive harm.
California
Proposition 65 Warning
i
Page 4
SECTION TITLE PAGE
Redistribution or publication of this document,
by any means, is strictly prohibited.
6 AC ELECTRICAL CONNECTIONS
General 6-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Transfer Switch 6-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AC Wiring 6-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Heater (Optional) 6-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Coolant Heater (Optional) 6-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generator Heater (Optional) 6-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fuel Transfer Pump (Optional) 6-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Ground Fault Alarm Relay (Optional) 6-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 ENCLOSURE ELECTRICAL CONNECTIONS
General 7-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional AC Distribution Panel 7-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Motorized Inlet/Outlet Louvers 7-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Optional Transfer Fuel Pump 7-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8 PRESTART PREPARATION
General 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical System 8-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PCC Options Prestart Checks 8-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Starting 8-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9 INSTALLATION CHECKLIST
General 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generator Set Support 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Cooling Air Flow 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diesel Fuel System 9-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Exhaust System 9-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
AC and DC Wiring 9-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Generator Set Prestart 9-2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10 WIRING DIAGRAMS
General 10-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii
Page 5

IMPORTANT SAFETY INSTRUCTIONS

Redistribution or publication of this document,
by any means, is strictly prohibited.
SAVE THESE INSTRUCTIONS − This manual contains important instructions that should be followed during installation and maintenance of the generator and batter­ies.
Before operating the generator set (genset), read the Operator’s Manual and become familiar with it and the equipment. Safe and efficient operation can be
achieved only if the equipment is properly operated and maintained. Many accidents are caused by failure
to follow fundamental rules and precautions. The following symbols, found throughout this manual,
alert you to potentially dangerous conditions to the oper­ator, service personnel, or the equipment.
This symbol warns of immediate hazards which will result in severe personal in­jury or death.
WARNING
This symbol refers to a hazard or un­safe practice which can result in severe person­al injury or death.
CAUTION
This symbol refers to a hazard or un­safe practice which can result in personal injury or product or property damage.
FUEL AND FUMES ARE FLAMMABLE
Fire, explosion, and personal injury or death can result from improper practices.
DO NOT fill fuel tanks while engine is running, un-
less tanks are outside the engine compartment. Fuel contact with hot engine or exhaust is a potential fire hazard.
DO NOT permit any flame, cigarette, pilot light,
spark, arcing equipment, or other ignition source near the generator set or fuel tank.
Fuel lines must be adequately secured and free of
leaks. Fuel connection at the engine should be made with an approved flexible line. Do not use zinc coated or copper fuel lines with diesel fuel.
Be sure all fuel supplies have a positive shutoff
valve.
Be sure battery area has been well-ventilated prior
to servicing near it. Lead-acid batteries emit a highly explosive hydrogen gas that can be ignited by arc­ing, sparking, smoking, etc.
EXHAUST GASES ARE DEADLY
Provide an adequate exhaust system to properly
expel discharged gases away from enclosed or sheltered areas and areas where individuals are likely to congregate. Visually and audibly inspect the exhaust daily for leaks per the maintenance schedule. Make sure that exhaust manifolds are se­cured and not warped. Do not use exhaust gases to heat a compartment.
Be sure the unit is well ventilated.
Engine exhaust and some of its constituents are
known to the state of California to cause cancer, birth defects, and other reproductive harm.
MOVING PARTS CAN CAUSE SEVERE PERSONAL INJURY OR DEATH
Keep your hands, clothing, and jewelry away from moving parts.
Before starting work on the generator set, discon-
nect battery charger from its AC source, then dis­connect starting batteries, negative () cable first. This will prevent accidental starting.
Make sure that fasteners on the generator set are
secure. Tighten supports and clamps, keep guards in position over fans, drive belts, etc.
Do not wear loose clothing or jewelry in the vicinity of
moving parts, or while working on electrical equip­ment. Loose clothing and jewelry can become caught in moving parts.
If adjustment must be made while the unit is run-
ning, use extreme caution around hot manifolds, moving parts, etc.
DO NOT OPERATE IN FLAMMABLE AND EXPLOSIVE ENVIRONMENTS
Flammable vapor can cause an engine to overspeed and become difficult to stop, resulting in possible fire, explo­sion, severe personal injury and death. Do not operate a genset where a flammable vapor environment can be created by fuel spill, leak, etc., unless the genset is equipped with an automatic safety device to block the air intake and stop the engine. The owners and operators of the genset are solely responsible for operating the gen­set safely. Contact your authorized Cummins Power Generation distributor for more information.
LS-14L
iii
Page 6
ELECTRICAL SHOCK CAN CAUSE
Redistribution or publication of this document,
by any means, is strictly prohibited.
SEVERE PERSONAL INJURY OR DEATH
Remove electric power before removing protective
shields or touching electrical equipment. Use rub­ber insulative mats placed on dry wood platforms over floors that are metal or concrete when around electrical equipment. Do not wear damp clothing (particularly wet shoes) or allow skin surface to be damp when handling electrical equipment. Do not wear jewelry. Jewelry can short out electrical con­tacts and cause shock or burning.
Use extreme caution when working on electrical
components. High voltages can cause injury or death. DO NOT tamper with interlocks.
Follow all applicable state and local electrical
codes. Have all electrical installations performed by a qualified licensed electrician. Tag and lock open switches to avoid accidental closure.
DO NOT CONNECT GENERATOR SET DIRECT-
LY TO ANY BUILDING ELECTRICAL SYSTEM. Hazardous voltages can flow from the generator set into the utility line. This creates a potential for elec­trocution or property damage. Connect only through an approved isolation switch or an ap­proved paralleling device.
GENERAL SAFETY PRECAUTIONS
Coolants under pressure have a higher boiling point
than water. DO NOT open a radiator or heat ex­changer pressure cap while the engine is running. Allow the generator set to cool and bleed the system pressure first.
Used engine oils have been identified by some state
or federal agencies as causing cancer or reproduc­tive toxicity . When checking or changing engine oil, take care not to ingest, breathe the fumes, or con­tact used oil.
Keep multi-class ABC fire extinguishers handy.
Class A fires involve ordinary combustible materials such as wood and cloth; Class B fires, combustible and flammable liquid fuels and gaseous fuels; Class C fires, live electrical equipment. (ref. NFP A No. 10).
Make sure that rags are not left on or near the en-
gine.
Make sure generator set is mounted in a manner to
prevent combustible materials from accumulating under the unit.
Remove all unnecessary grease and oil from the
unit. Accumulated grease and oil can cause over­heating and engine damage which present a poten­tial fire hazard.
Keep the generator set and the surrounding area
clean and free from obstructions. Remove any de­bris from the set and keep the floor clean and dry.
Do not work on this equipment when mentally or
physically fatigued, or after consuming any alcohol or drug that makes the operation of equipment un­safe.
Substances in exhaust gases have been identified
by some state or federal agencies as causing can­cer or reproductive toxicity. Take care not to breath or ingest or come into contact with exhaust gases.
Do not store any flammable liquids, such as fuel,
cleaners, oil, etc., near the generator set. A fire or explosion could result.
Wear hearing protection when going near an oper-
ating generator set.
To prevent serious burns, avoid contact with hot
metal parts such as radiator, turbo charger and ex­haust system.
KEEP THIS MANUAL NEAR THE GENSET FOR EASY REFERENCE
iv
Page 7

1. Introduction

Redistribution or publication of this document,
by any means, is strictly prohibited.
ABOUT THIS MANUAL
This manual provides installation instructions for the generator set models listed on the front cover. This includes the following information:
Mounting Recommendations - for fastening generator set to base and space requirements for normal operation and service.
Mechanical and Electrical Connections ­covers most aspects of the generator set instal­lation.
Prestart − checklist of items or procedures needed to prepare generator set for operation.
Initial Startup − test complete system to en­sure proper installation, satisfactory perfor-
mance, and safe operation. Refer to Operators Manual for troubleshooting information.
Installation Checklist − reference checks upon completion of installation.
This manual DOES NOT provide application infor­mation for selecting a generator set or designing the complete installation. If it is necessary to design the various integrated systems (fuel, exhaust, cooling, etc.), additional information is required. Review standard installation practices. For engineering data specific to the generator set, refer to the
fication
tion, refer to Application Manual T-030, “Liquid Cooled Generator Sets”.
and
Data Sheets
. For application informa-
Speci-
1-1
Page 8
INSTALLATION OVERVIEW
Redistribution or publication of this document,
by any means, is strictly prohibited.
These installation recommendations apply to typi­cal installations with standard model generator sets. Whenever possible, these recommendations also cover factory designed options or modifica­tions. However, because of the many variables in any installation, it is not possible to provide specific recommendations for every situation. If there are any questions not answered by this manual, contact your nearest Cummins Power Generation distribu­tor for assistance.
Application and Installation
installed, maintained, and operated. However, the overall safety and reliability of the complete system is dependent on many factors outside the control of the generator set manufacturer. To avoid possible safety hazards, make all mechanical and electrical connections to the generator set exactly as speci­fied in this manual. All systems external to the gen­erator (fuel, exhaust, electrical, etc.) must comply with all applicable codes. Make certain all required inspections and tests have been completed and all code requirements have been satisfied before certi­fying the installation is complete and ready for ser­vice.
A standby power system must be carefully planned and correctly installed for proper operation. This in­volves two essential elements: application and installation.
Application (as it applies to generator set installa­tions) refers to the design of the complete standby power system that usually includes power distribu­tion equipment, transfer switches, ventilation equip­ment, mounting pads, and cooling, exhaust, and fuel systems. Each component must be correctly designed so the complete system will function as in­tended. Application and design is an engineering function generally done by specifying engineers or other trained specialists. Specifying engineers or other trained specialists are responsible for the de­sign of the complete standby system and for select­ing the materials and products required.
Installation refers to the actual set-up and assem­bly of the standby power system. The installers set up and connect the various components of the sys­tem as specified in the system design plan. The complexity of the standby system normally requires the special skills of qualified electricians, plumbers, sheetmetal workers, etc. to complete the various segments of the installation. This is necessary so all components are assembled using standard meth­ods and practices.
Safety Considerations
The generator set has been carefully designed to provide safe and efficient service when properly
Standby Heating Devices
In accordance with NFPA 110, Cummins Power Generation recommends installing diesel standby generator sets (life safety systems) equipped with engine jacket water coolant heaters in locations where the minimum ambient temperature is above 40
°F (4°C). NFPA also requires that the engine
jacket water coolant be maintained at a minimum of
°F (32°C) and, for most applications, accept the
90 emergency load in 10 seconds or less. Although most Cummins Power Generation generator sets will start in temperatures down to −25 when equipped with engine jacket water coolant heaters, it might take more than 10 seconds to warm the engine up before a load can be applied when ambient temperatures are below 40
The Engine Cold (Code 1435) message, in con- junction with illumination of the Warning LED, is pro­vided to meet the requirements of NFPA 110. The engine cold sensing logic initiates a warning when the engine jacket water coolant temperature falls below 70
ent temperature falls below 40
°F (21°C). In applications where the ambi-
°F (4°C), a cold en-
gine may be indicated even though the coolant heaters are connected. Under these conditions, al­though the generator set may start, it may not be able to accept load within 10 seconds. When this condition occurs, check the coolant heaters for proper operation. If the coolant heaters are operat­ing properly, other precautions may be necessary to warm the engine before applying a load.
°F (−32°C)
°F (4°C).
Copyright2003 Cummins Power Generation. All rights reserved. Cummins and PowerCommand are registered trademarks of Cummins Inc.
1-2
Page 9

2. Specifications

Redistribution or publication of this document,
by any means, is strictly prohibited.
MODEL DFAB/DFAC DFBF DFCB/DFCC DFCE
Cummins Diesel Series LTA10 NT855 NTA855 NTA855 Generator kW Rating See Genset Nameplate for rating information. Cooling System
Capacity with Standard Radiator 13 Gal (49 L) 13.5 Gal (51 L) 13.5 Gal (51 L) 15 Gal (57 L)
Oil Capacity* 9.5 Gal (36 L) 10.5 Gal (40 L) 10.5 Gal (40 L) 10 Gal (38 L) Engine Fuel Connection
Inlet/Oultet Thread Size
Fuel Flow
Max. Fuel Inlet Restriction Max. Fuel Return Restriction
Exhaust
Outlet Size Max. Allowable Back Pressure
H20 kPa
Electrical System
Starting Voltage Battery
Group number CCA (minimum)
Cold Soak @ 0° F (-18° C)
* Refer to Cummins engine
Operation and Maintenance Manual
4 in. Hg. (13.5 kPa)
6.5 in. Hg. (22 kPa)
4 in. NPT
41
10.2
for lubricating oil recommendations/specifications.
Refer to Generator Outline Drawing
4 in. Hg. (13.5 kPa) 6 in. Hg. (20.3 kPa)
5 in. NPT
41
10.2
24 Volts DC
Two, 12 Volt
8D
1400
6 in. NPT
41
10.2
6 in. NPT
41
10.2
FUEL CONSUMPTION (STANDBY/FULL LOAD/60HZ)
MODEL DFAB DFAC DFBF DFCB DFCC DFCE
US gph (L/hr) 15.6 (59) 16.8 (63.7) 20.4 (77.3) 22.5 (85.3) 24.4 (92.5) 29.1 (110.3)
2-1
Page 10
THIS PAGE LEFT INTENTIONALLY BLANK
Redistribution or publication of this document,
by any means, is strictly prohibited.
2-2
Page 11

3. Mounting the Generator Set

Redistribution or publication of this document,
by any means, is strictly prohibited.
GENERAL
Discharge of exhaust gases
Electrical connections
Generator set installations must be engineered so the generator set will function properly under the ex­pected load conditions. Use these instructions as a general guide only. Follow the instructions of the consulting engineer when locating or installing any components. The complete installation must com­ply with all local and state building codes, fire ordi­nances, and other applicable regulations.
Requirements to be considered prior to installation:
Level mounting surface
Adequate cooling air
Adequate fresh induction air
Discharge of generator set air
Non-combustible mounting surface.
Accessibility for operation and servicing
Noise levels
Vibration isolation
LOCATION
Generator set location is decided mainly by related systems such as ventilation, wiring, fuel, and ex­haust. The set should be located as near as pos­sible to the main power service entrance. Exhaust must not be able to enter or accumulate around in­habited areas.
Provide a location away from extreme ambient tem­peratures and protect the generator set from ad­verse weather conditions. An optional housing is available for outside operation.
WARNING
INCORRECT INSTALLATION, SERVICE OR PARTS REPLACEMENT CAN RESULT IN SEVERE PERSONAL INJURY, DEATH, AND/OR EQUIPMENT DAMAGE. SERVICE PERSONNEL MUST BE TRAINED AND EXPERIENCED TO PERFORM ELECTRICAL AND MECHANICAL COM­PONENT INSTALLATION.
DEPENDING ON Y O U R L O C ATION AND INTENDED USE, FEDERAL, STATE OR LOCAL LA WS AND REGULATIONS MAY REQUIRE YOU TO OBTAIN AN AIR QUALITY EMISSIONS PERMIT BEFORE BEGINNING INSTALLATION OF YOUR GENSET. BE SURE TO CONSULT LOCAL POLLUTION CONTROL OR AIR QUALITY AUTHORITIES BEFORE COMPLETING YOUR CONSTRUCTION PLANS.
IMPORTANT
3-1
Page 12
MOUNTING
Redistribution or publication of this document,
by any means, is strictly prohibited.
Generator sets are mounted on a steel skid or fuel tank that provides proper support. The engine-gen­erator assembly is isolated from the skid frame by rubber mounts that provide adequate vibration isolation for normal installations. Where required by building codes or special isolation needs, generator sets may be mounted on rubber pads or mechanical spring isolators. The use of unapproved isolators may result in harmful resonances and may void the genset warranty.
For fuel tank mounted generator sets, it is required that the tank be mounted such that an air space is provided between the bottom of the tank and the floor underneath to reduce corrosion and permit visual inspections for leaks.
Mount the generator set on a substantial and level base such as a concrete pad. A non-combustible material must be used for the pad.
Use 5/8 inch or 16 mm anchored mounting bolts to secure the vibration isolators to the base. Secure the vibration isolators using flat or bevel washer and hexagonal nut for each bolt (see Figure 3-1). The 1-1/2 x 6 inch pipe inserted over the mounting bolts allows minor adjustment of the bolts to align them to the holes in the subbase or vibration isolator.
Locate the isolators as shown on the generator set
Outline Drawing
referenced in the
Data Sheet
.
MOUNTING
BASE
MOUNTING
BOLT
SUBBASE OR
VIBRATION
ISOLATOR
FLANGE
HEX NUT
FLAT OR BEVEL
WASHER
1-1/2 x 6 INCH
PIPE
12 IN.
(305 mm)
CONCRETE
FIGURE 3-1. BOLT DIAGRAM
ACCESS TO SET
Generally, at least 1 meter (3 feet) of clearance should be provided on all sides of the generator set for maintenance and service access. (Increase clearance by width of door if optional housing is used.) A raised foundation or slab of 150 mm (6 inches) or more above floor level will make servic­ing easier.
Lighting should be adequate for operation, mainte­nance and service operations and should be con­nected on the load side of the transfer switch so that it is available at all times.
3-2
Page 13
MUFFLER
Redistribution or publication of this document,
by any means, is strictly prohibited.
THIMBLE
FLEXIBLE SECTION
DC CONTROL
WIRING
CONDENSATION
DRAIN TRAP
SWEEPING
ELBOW
AC POWER
WIRING
AIR
IN
AIR OUTLET
DUCT
SHIPPING SCREW
(DFCE ONLY) EACH SIDE
VIBRATION
ISOLATORS
COOLING AIR INLET MUST BE AT LEAST 1-1/2
TIMES LARGER THAN RADIATOR DUCT OUTLET
AREA ON RADIATOR COOLED MODELS
FLOW OR COOLING AIR AND HEATED AIR CAN
BE CONTROLLED BY AUTOMATICALLY
FIGURE 3-2. TYPICAL INSTALLATION
3-3
CONCRETE
BASE
IMPORTANT!
OPERATED LOUVRES
Page 14
VIBRATION ISOLATORS
Redistribution or publication of this document,
by any means, is strictly prohibited.
Installation and Adjustment Procedure
1. Place the vibration isolators (Figure 3-3) on the genset support structure. The isolators should be shimmed or grouted to ensure that all of the isolator bases are within 0.25 inch (6 mm) elevation of each other. The surface that the isolator bases rest on must also be flat and lev­el.
2. Loosen the side snubber lock nuts so that the top plate of the isolator is free to move vertically and horizontally. Be sure that the top plate is correctly aligned with the base and springs.
3. Place the genset onto the isolators while align­ing the skid’s mounting with the threaded isola­tor hole. The top plates will move down and ap­proach the base of the isolator as load is ap­plied.
4. Once the genset is in position, the isolators may require adjusting so that the set is level. The isolators are adjusted by inserting the lev­eling bolt through the skid and into the isolator (the leveling bolt’s locking nut should be threaded up towards the bolt head).
The leveling bolt will adjust the clearance be­tween the top plate and the isolator base. A nominal clearance of 0.25 inch (6 mm) or great­er is desired. This will provide sufficient clear­ance for the rocking that occurs during startup and shutdown. If the 0.25 inch (6 mm) clear­ance is not present, turn the leveling bolt until the desired clearance is achieved.
5. The genset may not be level yet; therefore, ad­just the leveling bolts until the set is level and sufficient clearance still remains. (Clearance on all isolators should be roughly equal). Once all isolators have been set, lock the leveling bolt in place with the lock nut.
6. The snubber nuts may remain loose and there­fore provide better isolation between the gen­set and support structure.
7. Model DFCE only: With the genset in position and secured to the isolators, remove the two controller cabinet shipping screws (see Figure 3-2).
CAUTION
Remove shipping screws (two) prior to genset operation. Genset operation with shipping screws in place will damage control components.
GENSET SKID
LEVELING BOLT
LOCK NUT
CLEARANCE
SNUBBER
BASE
FIGURE 3-3. VIBRATION ISOLATORS
3-4
Page 15
ALIGNING GENERATOR WITH ENGINE
Redistribution or publication of this document,
by any means, is strictly prohibited.
(750 kW GENSETS AND LARGER)
Proper alignment of the generator and engine as­semblies is necessary to avoid premature wear and improper operation of the genset. Review the fol­lowing alignment conditions and procedures for aligning the generator assembly to engine flywheel housing.
Angular Misalignment
Angular misalignment is the result of the generator bearing center axis not aligning with axis of the en­gine crankshaft. This condition creates an angle between the generator shaft axis and the crank­shaft axis . The cause of this type of misalignment is usually shimming error.
Axial Misalignment
Axial misalignment is the result of the generator shaft axis not aligning with engine crankshaft axis. The tolerances in the bolted flywheel and drive disc connection may add up to displace the generator axially relative to the crankshaft axis.
Misalignment Symptoms
If the assembly is allowed to run under these condi­tions, the discs must flex in alternate directions twice for each engine revolution. It is important to minimize the amount of disc flexing since, if it is ex­cessive, the drive disc will crack. Although perfect bearing alignment is desirable, it is more important to keep disc deflection to the very minimum pos­sible. This procedure assumes that the pilot bore of the drive discs are in the exact center and the fly­wheel counterbore (pilot) has no practical runout. Under these conditions, perfect Angular alignment will be attained when no deflection of the discs is measured.
Excessive Axial alignment will cause more genera­tor vibration than Angular misalignment.
Axial misalignment needs to be checked only when an objectionable vibration is present.
Either type off misalignment may be present in a generator set assembly , with angular misalignment being the most common problem. Angular align­ment may also be effected by set installation condi­tions and/or mishandling during shipping of the gen­set.
GENERATOR AND ENGINE
CRANKSHAFT
CENTERLINE
SHIMS
SEE DETAIL A
CLAMP
MOUNTING BOLT
TO DISC
MEASUREMENT
FIGURE 3-4. ANGULAR ALIGNMENT MEASUREMENT
AXIAL
ALIGNMENT
DIAL INDICATOR
FLEX
DISCS
DETAIL A
3-5
Page 16
Angular Alignment Procedure
Redistribution or publication of this document,
by any means, is strictly prohibited.
WARNING
set during this procedure presents the hazard of severe personal injury or death. Make sure to disconnect the negative (-) battery cable(s) be­fore beginning.
Accidental starting of the generator
-.015”.) The indicator is closer to the top and further away at the bottom. This example indicates that the generator bearing is high. Since the side readings are equal, the generator is centered side to side. T o lower the generator, remove equal shims from un­der both generator mounting feet. To approximate the amount of shims to remove or add:
Fasten a dial indicator to either the generator shaft or the cooling fan with the sensing point resting on the capscrew head or the flat surface of the drive disc at the bolt circle diameter, see Figure 3-4. Bar the engine over in a clockwise rotation as viewed from engine flywheel. Do not allow it to roll back on compression at the end of the travel of each read­ing. It is unnecessary to zero the indicator since the total indicator reading (T.I.R.) of the deflection mea­surement to the bolt heads is what is required. T.I.R. will be the sum of the maximum positive and nega­tive dial indicator readings as the engine completes one revolution.
CAUTION
Do not bar engine over by prying on fan blade. This may damage the blade and result in premature, sudden blade failure.
Sample Generator Runout Readings: When taking the deflection readings described, make a diagram similar to the example shown in Figure 3-5, with a total indicator reading of .025”. (The highest posi­tive value of +.010” and the largest negative value of
1. Measure the distance between the center of the generator shaft to the point the indicator is measuring at. (For example; a SAE 18 Disc coupling distance is 10.7”).
2. Measure the distance from the generator side of the flex discs to the center of the generator mounting bolt, refer to Figure 3-4. (For exam­ple; a HC6 Frame’s distance is 28.4”.)
3. Compare the distance measured in steps 1 and
2. (28.4” vs 10.7” or a 2.65 to 1 ratio.) Multiply this ratio times one half the T.I.R. (In our exam­ple, .025” divided by 2 is .0125”. This, times
2.65 equals .033”. Therefore, remove .033” of shims from under both mounting feet.)
In general, the T.I.R. should not be more than .001” for each inch of radius (center of shaft to indicator axis). If w e use our example of 10.7 inches, then the maximum T.I.R. would be .011”. This would only re­quire a correction of .014” from the T.I.R. of .025”. (A reading of +.002 at the top and −.009 at the bottom would fall within the satisfactory range.)
FIGURE 3-5. ANGULAR ALIGNMENT MEASUREMENT READINGS (EXAMPLE)
−.004
−.010
+.010
MEASURED AT
BOLT CIRCLE
DIAMETER
−.015
−.015
3-6
+.010
−.002
10.7 IN.
−.010
Page 17
Axial Alignment Procedure
Redistribution or publication of this document,
by any means, is strictly prohibited.
Axial misalignment needs to be checked only when an objectionable vibration is present.
If excessive vibration remains after the angular alignment, check for concentric alignment of the generator shaft/engine crankshaft axis.
to the varying surface quality of the generator shaft’s drive disc mounting hub.
The goal of the Axial alignment is to reduce the vibration level of the genset while it is operating. A small improvement in the T.I.R. runout may have dramatic effects in the mechanically measured or physically observed vibration levels.
Fasten dial indicator holding device to skid base, engine block, or generator shell with a magnetic base or clamp and position so the sensor point of in ­dicator rests on the generator shaft hub, see Figure 3-6. Bar the engine over in a clockwise rotation as viewed from engine flywheel, through a couple of rotations. Record indicator readings in eight equal­ly spaced points around the shaft diameter. This will provide a T.I.R. for Axial shaft misalignment.
The maximum allowable T.I.R. runout is subjective, the optimal T.I.R. for runout would be .000 inches, however that may not be attainable. The recom­mendation of this procedure will be to reduce the measured T.I.R. runout by one half. Specific out-of­tolerance runout levels are difficult to establish due
ANGULAR ALIGNMENT
To correct for an out-of-tolerance T.I.R. indication, remove the capscrews connecting drive discs and flywheel. Mark the drive discs and flywheel with re­spect to each other. Rotate either the engine or gen­erator so that drive discs holes are repositioned 180 degrees from their original location. Put the drive discs capscrews back in and retorque. Recheck shaft alignment as before. If shaft T.I.R. runout re­mains unchanged then discs should be rotated to either 30, 60 or 90 degrees from original location to correct the out-of-tolerance condition. If the T.I.R. does not improve after repositioning, a closer in­spection of the flywheel pilot and drive disc runouts is required. This will help determine the cause of the Axial misalignment.
SEE DETAIL A
GENERATOR AND ENGINE
CRANKSHAFT
CENTERLINE
GENERATOR
SHAFT
HUB
DIAL
INDICATOR
CLAMP
FAN HOUSING
DETAIL A
FIGURE 3-6. AXIAL ALIGNMENT MEASUREMENT
3-7
Page 18
THIS PAGE LEFT INTENTIONALLY BLANK
Redistribution or publication of this document,
by any means, is strictly prohibited.
3-8
Page 19

4. Mechanical Connections

Redistribution or publication of this document,
by any means, is strictly prohibited.
GENERAL
The generator set mechanical system installation includes connecting the fuel, exhaust, ventilation and cooling systems. Before starting any type of fuel installation, all pertinent state and local codes must be complied with and the installation must be inspected before the unit is put in service.
FUEL SYSTEM
Cummins engines normally use ASTM No. 2 diesel fuel. They will, however , operate on alternate diesel fuels within the specifications shown in the Cum­mins engine
In all fuel system installations, cleanliness is of the upmost importance. Make every effort to prevent entrance of moisture, dirt or contaminants of any kind into the fuel system. Clean all fuel system com­ponents before installing.
A fuel filter/strainer/water separator of 100-120 mesh or equivalent (approximately 150 microns nominal) must be fitted between either the main tank and day tank or between the main tank and the engine.
Use only compatible metal fuel lines to avoid elec­trolysis when fuel lines must be buried. Buried fuel lines must be protected from corrosion.
Operation and Maintenance Manual.
CAUTION
Never use galvanized or copper fuel lines, fittings or fuel tanks. Condensation in the tank and lines combines with the sulfur in diesel fuel to produce sulfuric acid. The molecular structure of the copper or galvanized lines or tanks reacts with the acid and contaminates the fuel.
An electric solenoid valve in the supply line is rec­ommended for all installations and required for in­door automatic or remote starting installations. Connect the solenoid wires to the genset “Switched B+” circuit to open the valve during generator set operation.
Separate fuel return lines to the day tank or supply tank must be provided for each generator set in a multiple-set installation to prevent the return lines of idle sets from being pressurized. Fuel return lines must not contain a shutoff device. Engine damage will occur if the engine is run with the return fuel lines blocked or restricted.
CAUTION
Never install shutoff device in fuel return line(s). If fuel return line(s) is blocked or exceeds fuel restriction limit, engine damage will occur.
Fuel Return Restriction (or Pressure) Limit: Fuel
return drain restriction (consisting of friction head and static head) between the engine injector return line connection and the fuel tank must not exceed the limit stated in the
Specification
section.
4-1
Page 20
Fuel Lines − Routing
Redistribution or publication of this document,
by any means, is strictly prohibited.
A flexible fuel hose(s) or section of flexible fuel hose(s) must be used between the engine’s fuel system and fuel supply and return line(s) to protect the fuel system from damage caused by vibration, expansion and contraction. Flexible lines for con­necting between the engine and the stationary fuel lines are supplied as standard equipment.
Installation of the fuel hose must be done according to all applicable codes and standards, and installa­tion recommendations provided by the manufactur­er. The supplied flexible hose is approved by the hose manufacture for use with the genset fuel type and product application.
Support fuel lines to restrain movement and prevent chaffing or contact with sharp edges, electrical wir­ing and hot exhaust parts.
WARNING
Sparks and hot surfaces can ignite fuel, leading to severe personal injury or death. Do not route fuel lines near electrical wiring or hot exhaust parts.
Fuel lines must be routed and secured to maintain a 1/2 inch (12.7 mm) minimum clearance from electri­cal wiring and a 2 inch (51 mm) minimum clearance from hot exhaust parts.
Engine Fuel Connections
Identification tags are attached to the fuel supply line and fuel return line connections.
Supply Tank
Locate the f uel tank as close as possible to the gen­erator set and within the restriction limitations of the fuel pump.
Install a fuel tank that has sufficient capacity to sup­ply the genset operating continuously at full rated load for the planned period of operation or power outage. Refer to
Data Sheet
for fuel consumption
data.
WARNING
Fuel leaks create fire and explosion hazards which can result in severe personal in­jury or death. Always use flexible tubing be­tween engine and fuel supply and return to avoid line failure and leaks due to vibration. The fuel system must meet applicable codes.
If the fuel inlet restriction exceeds the defined limit due to the distance/customer-supplied plumbing between the genset and the main fuel tank, a trans­fer tank (referred to as a day tank) and auxiliary pump will also be required. If an overhead main fuel tank is installed, a transfer tank and float valve will be required to prevent fuel head pressures from be­ing placed on the fuel system components.
For critical start applications, where generator sets are paralleled or must satisfy emergency start-time requirements, it is recommended that a fuel tank or reservoir be located such that the lowest possible fuel level is not less than 6 inches (150 mm) above the fuel pump inlet. This will prevent air from accu­mulating in the fuel line while the set is in standby, eliminating the period during startup when it has to be purged.
Fuel Inlet Pressure/Restriction Limit:: Engine
performance and fuel system durability will be com­promised if the fuel inlet pressure or restriction limits are not adhered to. Fuel inlet pressure or restriction must not exceed the limits stated in the
tion
section.
Specifica-
4-2
Page 21
Day Tank (If Used)
Redistribution or publication of this document,
by any means, is strictly prohibited.
Fuel day tanks are used when fuel inlet restriction limits can not be met, or the supply tank is overhead and presents problems of high fuel head pressure for the fuel inlet and return lines.
Supply T ank Lower Than Engine:
lation, the day tank is installed near the generator set, below the fuel injection system and within the fuel inlet restriction limit. Install an auxiliary fuel pump, to pump fuel from the supply tank to the day tank. A float switch in the day tank controls opera­tion of the auxiliary fuel pump.
The supply tank top must be below the day tank top to prevent siphoning from the fuel supply to the day tank.
Provide a return line from the engine injection sys­tem return connection to the day tank. Plumb the re-
With this instal-
turn line to the bottom of day tank as shown in Fig­ure 4-1. Provide a day tank overflow line to the sup­ply tank in case the float switch fails to shut off the fuel transfer pump. Also, the overflow line should be one pipe diameter larger than the supply line.
WARNING
Spilled fuel presents the hazard of fire or explosion which can result in severe per­sonal injury or death. Provide an overflow line to the supply tank from the day tank.
Supply Tank Higher Than Engine:
Install the day tank near the generator set, but below the fuel injec­tion system. Use fuel line at least as large as the fuel pump inlet. The engine fuel return line must enter the day tank.
Include a shutoff valve in the fuel line between the fuel supply tank and the day tank to stop fuel flow when the generator set is off.
WARNING
Spilled fuel can create environmental hazards. Check local requirements for containment
and prevention of draining to sewer and ground water.
ENGINE
FUEL
PUMP
DAY TANK
FUEL TRANSFER PUMP ELECTRIC
MOTOR DRIVEN
VENTED FILL CAP
SHUTOFF
VALVE
1 INCH
BAFFLE
FLOAT
SWITCH
INJECTOR FUEL
RETURN LINE
CONNECT TO
AC OUTPUT
SUPPLY
LINE
All models require a fuel return line from injectors to tank.
VENT LINE
FILL PIPE
120 MESH FUEL
STRAINER
LARGER OVER-
FLOW LINE
FIGURE 4-1. TYPICAL FUEL SUPPLY INSTALLATION
FUEL TANK
4-3
Page 22
EXHAUST SYSTEM
Redistribution or publication of this document,
by any means, is strictly prohibited.
Pipe exhaust gases to the outside of any enclosure. Locate the exhaust outlets away from any air inlets to avoid gases re-entering the enclosure. Exhaust installations are subject to various detrimental con­ditions such as extreme heat, infrequent operation and light loads. Regularly inspect the exhaust sys­tem both visually and audibly to see that the entire system remains fume tight and safe for operation.
WARNING
sult in severe personal injury or death. Use ex­treme care during installation to provide a tight exhaust system. Terminate exhaust pipe away from enclosed or sheltered areas, windows, doors and vents.
For indoor installation, the exhaust system must use sealed joint type fittings, (for example NPT fit­tings) to provide a tighter exhaust system. Use of slip type fittings (secured with a muffler clamp) may allow leakage of exhaust gases into the building.
WARNING
sult in severe personal injury or death. Use ex­treme care during installation to provide a tight exhaust system. Use NPT or equivalent type fit­tings for all indoor installations.
Use an approved thimble (Figure 4-2) where ex­haust pipes pass through wall or partitions. Insu­lated wall/roof thimbles are used where exhaust pipes pass through a combustible roof or wall. This includes structures, such as wood framing or insu­lated steel decking, etc. Uninsulated wall/roof thimbles are used where exhaust pipes pass through a non-combustible wall or roof, such as concrete. Refer to NFPA 37, Section 6-3. “Station­ary Combustion Engines and Gas Turbines” for ac-
Inhalation of exhaust gases can re-
Inhalation of exhaust gases can re-
cepted design practices. Build according to the code requirements in effect at the installation site.
WARNING
Hot exhaust pipes can start a fire and cause severe injury or death if improperly routed through walls. Use an approved thimble where exhaust pipes pass through walls or partitions.
WARNING
Inhalation of exhaust gases can re­sult in severe personal injury or death. Do not use exhaust heat to warm a room, compartment or storage area.
Rain caps are available for the discharge end of ver­tical exhaust pipes. The rain cap clamps onto the end of the pipe and opens due to exhaust discharge force from the generator set. When the generator set is stopped, the rain cap automatically closes, protecting the exhaust system from rain, snow, etc.
Use a section of flexible exhaust pipe between the engine and remainder of exhaust system. Support exhaust system to prevent weight from being ap­plied to engine exhaust outlet elbow/turbocharger connection.
CAUTION
Weight applied to the engine man­ifold can result in turbocharger damage. Sup­port the muffler and exhaust piping so no weight or stress is applied to engine exhaust el ­bow.
The exhaust system design should meet local code requirements.
Liability for injury, death, damage, and warranty ex­pense due to use of unapproved mufflers or modifi­cations becomes the responsibility of the person installing the unapproved muffler or performing the modification. Contact a Cummins Power Generation distributor for approved exhaust system parts.
4-4
Page 23
Avoid sharp bends by using sweeping, long radius
Redistribution or publication of this document,
by any means, is strictly prohibited.
elbows and provide adequate support for muffler and tailpipe. Pitch a horizontal run of exhaust pipe DOWNWARD (away from engine) to allow any moisture condensation to drain away from the en­gine. If an exhaust pipe must be turned upward, install a condensation trap at the point where the rise begins (Figure 4-3).
Shield or insulate exhaust lines if there is danger of personal contact. Allow at least 12 inches (305 mm) of clearance if the pipes pass close to a combustible wall or partition. Before installing insulation on ex­haust system components, check the exhaust sys­tem for leaks while operating the genset under full load and correct all leaks.
RAIN CAP
9 INCH
(230 mm)
VERTICAL
DRIP CAP
HOLES IN
END OF INNER
SLEEVE
ROOF
9 INCH
(230 mm)
WARNING
Exhaust pipes are very hot and they can cause severe personal injury or death from direct contact or from fire hazard. Shield or in­sulate exhaust pipes if there is danger of per­sonal contact or when routed through walls or near other combustible materials.
HORIZONTAL
WALL OR PARTITION
FIGURE 4-2. MOUNTING EXHAUST THIMBLE
IF EXHAUST LINE MUST BE
PITCHED UPWARD, CONSTRUCT
A TRAP AT POINT OF RISE
AVOID SHARP BENDS
DRAIN CONDENSATION
TRAP PERIODICALLY
FIGURE 4-3. CONDENSATION TRAP
4-5
Page 24
VENTILATION AND COOLING
Redistribution or publication of this document,
by any means, is strictly prohibited.
Generator sets dissipate heat and fumes that must be removed by proper cooling and ventilation.
Generator sets in factory-mounted housings for outdoor installation are designed for proper cooling and ventilation.
Indoor installations require careful design with re­spect to cooling and ventilation. In an indoor instal­lation, all radiator cooling air must be discharged to the out-of-doors. Duct adapter kits are available. See Figure 4-5 for a typical indoor installation.
PREVAILING WINDS PREVAILING WINDS
WARNING
Engine or radiator cooling air may carry deadly carbon monoxide gas which can cause asphyxiation and death. All engine or ra­diator cooling air must be discharged to the out­of-doors. Do not use it for heating a room or compartment.
Vents and Ducts
For indoor installations, locate vents so incoming air passes through the immediate area of the installa­tion before exhausting. Install the air outlet higher than the air inlet to allow for convection air move­ment.
Size the vents and ducts so they are large enough to allow the required flow rate of air . The ”free area” of ducts must be as large as the exposed area of the radiator. Refer to the genset flow requirements and allowed airflow restriction.
Wind will restrict free airflow if it blows directly into the air outlet vent. Locate the outlet vent so the ef­fects of wind are eliminated. See Figure 4-4.
Data Sheet
for the air-
FIGURE 4-4. WIND BARRIER
4-6
Page 25
Dampers
Redistribution or publication of this document,
by any means, is strictly prohibited.
Dampers or louvres protect the genset and equip­ment room from the outside environment. Their op­eration of opening and closing should be controlled by operation of the genset.
In cooler climates movable or discharge dampers are used. These dampers allow the air to be recircu­lated back to the equipment room. This enables the equipment room to be heated while the genset en­gine is still cold, increasing the engine efficiency.
Radiator Set Requirements
Radiator set cooling air is drawn past the control end of the set by a pusher fan that blows air through the radiator (Figure 4-5). Locate the air inlet to the rear of the set. Make the inlet vent opening 1-1/2 to 2 times larger than the radiator area.
Louvers and screens over air inlet and outlet open­ings restrict air flow and vary widely in performance. A louver assembly with narrow vanes, for example, tends to be more restrictive than one with wide vanes. The effective open area specified by the lou­ver or screen manufacturer should be used.
Locate the cooling air outlet directly in front of the ra­diator and as close as possible. The outlet opening must be at least as large as the radiator area. Length and shape of the air outlet duct should offer minimum restriction to airflow.
Attach a canvas or sheet metal duct to the flange and the air outlet opening using screws and nuts so duct can be removed for maintenance purposes. The duct prevents circulation of heated air. Before installing the duct, remove the radiator core guard.
Standard Radiator Cooling uses a set mounted radiator and engine pusher fan to cool engine water jacket. Air travels from the generator end of the set, across the engine and out through the radiator. An integral discharge duct adapter flange surrounds the radiator grille.]
INLET AIR
DAMPER
COOL AIR
* Louvers should close when room ambient is above 60
° F (16° C)
FIGURE 4-5. TYPICAL RADIATOR SET INSTALLATION
THERMOSTATIC AIR RE-
CIRCULATING DAMPER
*
RADIATOR FLEXIBLE DUCT
CONNECTOR
WIND/NOISE
BARRIER
HOT AIR
D
DISTANCE SHOULD NOT BE LESS THAN HEIGHT
OF RADIATOR
4-7
Page 26
Remote Radiator Cooling (Optional) substitutes
Redistribution or publication of this document,
by any means, is strictly prohibited.
a remote mounted radiator and an electrically driv­en fan in place of mounted components. Removal of the radiator and the fan from the set reduces noise levels without forcing dependence on a con­tinuous cooling water supply (necessary with heat exchanger cooling). The remote radiator installa­tion must be completely protected against freezing.
Remote radiator plumbing will vary with installation. Follow recommendations given in Application Manual T-030. See product
Data Sheet
for friction
head and static head limits.
Before filling cooling system, check all hardware for security. This includes hose clamps, capscrews, fit­tings and connections. Use flexible coolant lines with heat exchanger or remote mounted radiator.
Engine Coolant Heater (Optional)
An optional coolant heater is available to keep the
engine warm for improved starting and code com­pliance. Connect the heater to a power source that will be energized when the engine is NOT running.
Heat Exchanger (Optional)
The optional heat exchanger (Figure 4-6) uses a shell and tube type heat exchanger instead of the standard radiator and fan. Engine jacket coolant cir­culates through the shell side of the heat exchanger while the cooling water is pumped through the tubes. Engine coolant and raw water do not mix.
This system may reduce set enclosure airflow re­quirements and noise levels. Proper operation de­pends on a constant supply of raw water for heat re­moval. Adjust the flow to maintain engine coolant temperature between165
° C) while viewing the water temperature gauge.
91 The engine coolant side of the system can be pro­tected from freezing; the raw water side cannot be protected.
° F and 195° F (74° C and
COOL AIR
WATER
SOLENOID
VALVE
VENTILATING
FAN
WARM
AIR
FLEXIBLE WA-
TER
CONNECTIONS
MOUNTED HEAT
EXCHANGER
RAW WATER
SUPPLY
RAW WATER DISCHARGE
FIGURE 4-6. TYPICAL HEAT EXCHANGER INSTALLATION
4-8
Page 27

5. DC Control Wiring

Redistribution or publication of this document,
by any means, is strictly prohibited.
CONTROL WIRING
The generator set control panel box contains con­nection points for remote control and monitor op­tions.
CAUTION
for all customer connections to the control pan­el. Solid copper wire may break due to genset vibration.
Use flexible conduit for all wiring connections to the generator set. All conduit used for control wiring is attached to the control housing.
Stranded copper wire must be used
NETWORK COMMUNICATION
MODULE
Route the control wiring through the control housing and into the access holes on the bottom of the con­trol panel box. Figure 5-1 also shows the access holes that should be used according to where the wires are terminated inside the control box.
A compression type strain-relief connector should be used to prevent dust, insects, etc. from entering control box.
Use cable ties to keep control wiring away from sharp edg e s a n d A C power cables within the control housing.
CONTROL RELAYS
(K10, K1 1, K12) &
CONTROL BOX
HEATER
FIGURE 5-1. SUGGESTED CUSTOMER WIRE ROUTING
TB2
5-1
TB1
STRAIN-RELIEF
CONNECTOR
Page 28
TB1 REMOTE MONITOR/CONTROL
Redistribution or publication of this document,
by any means, is strictly prohibited.
CONNECTIONS
Customer monitor/control connections are at­tached to terminal block TB1 (Figure 5-2). Optional equipment such as a remote annunciator panel, sensing devices used to monitor genset operation, remote start/stop switches, battery charger, etc. ar e attached to TB1. Refer to Customer Connections diagram in Section 9.
TB1 Wiring
CAUTION
a separate metal conduit from AC power cables to avoid inducing currents that could cause problems within the control.
Always run control circuit wiring in
Relay Connections: Due to the wide variety of de-
vices that can be attached to the relay outputs of TB1, the electrical contractor must determine the gauge of the stranded copper wire that is used at this installation site. Refer to PCC Customer Con­nections diagram in Section 9 for the relay specifi­cations.
Network Connections: Refer to 900-0366
Power-
Command Network Installation and Operation
manual for the type/gauge wire to use for these con­nections.
Switched B+: (Fused at 5 amps.) Same as Relay Connection description.
B+: (Fused at 10 amps.) Same as Relay Connec­tion description.
Digital Connections: Connection points, other than relayed outputs, network, switched B+ and B+ are considered digital connections to terminal strip TB1. The type/gauge wire to use for these connec­tions are:
Less than 1000 feet (305m), use 20 gauge
stranded copper wire.
1000 to 2000 feet (305 to 610m), use 18 gauge
stranded copper wire.
TB2 POWER TRANSFER CONTROL (PTC)
CONNECTIONS (OPTIONAL)
TB2 is used to connect the optional PTC module to the control. With this option installed, the control will monitor the utility voltage (mains) and frequency for failure. If power fails, the PTC control will start the generator, open the mains circuit breakers and close the generator circuit breakers. Refer to Cus­tomer Connections diagram in Section 9 and instal­lation instructions sent with the PTC Module Kit.
5-2
Page 29
BASE
Redistribution or publication of this document,
by any means, is strictly prohibited.
BOARD
VOLTAGE
SUPPRESSOR
TB2
TERMINAL
END BRACKET
CONTROL
RELAYS
TB1
MACHINE
FIGURE 5-2. CONTROL PANEL BOX
SCREW
TERMINAL
DIN RAIL
TERMINAL
END BRACKET
5-3
Page 30
CONTROL RELAYS (K11, K12, K13)
Redistribution or publication of this document,
by any means, is strictly prohibited.
4-pole relay with 2 poles normally open and two poles normally closed.
CAUTION
Damage to the Base board can oc­cur if the voltage suppressors (Figures 5-2 and 5-3) are not installed accross relay coils (A1/A2) of control relays K11, K12 and K13 before con­necting genset battery cables.
The three optional control relays are rail mounted inside the control panel housing. Each relay is a
VOLTAGE
SUPPRESSOR
These relays (Figure 5-3) are used to control auxil­iary equipment, such as fans, pumps and motorized air dampers. Energizing of the relays is user defin­able.
The contacts are rated at 10 amps at 600 VAC. Refer to Customer Connections diagram in Sec-
tion 9.
20 AWG Wire, UL Rated for 600 VAC
FIGURE 5-3. OPTIONAL CONTROL RELAYS (K10, K11, K12)
5-4
Page 31

6. AC Electrical Connections

Redistribution or publication of this document,
by any means, is strictly prohibited.
GENERAL
This section provides the procedure that is used to connect the AC electrical system of the genset.
Before making any AC electrical connections, make certain the generator set cannot be accidentally started. Place the control panel run switch in the OFF position. Turn off or remove AC power from the battery charger and then remove the negative (−) battery cable from the set starting battery.
WARNING
can cause severe personal injury or death. Arc­ing at battery terminals, light switch or other equipment, flame, pilot lights and sparks can ig­nite battery gas. Do not smoke, or switch trouble light ON or OFF near battery. Discharge static electricity from body before touching bat­teries by first touching a grounded metal sur­face.
Ventilate battery area before working on or near battery—Wear goggles—Stop genset and dis­connect charger before disconnecting battery cables—Disconnect negative (−) cable first and reconnect last.
CAUTION
source before disconnecting battery cables. Otherwise, disconnecting cables can result in voltage spikes damaging to DC control circuits of the set.
WARNING
set can cause severe personal injury or death. Prevent accidental starting by disconnecting the negative (−) cable from the battery terminal.
Ignition of explosive battery gases
Disconnect battery charger from AC
Accidental starting of the generator
Connecting the genset AC electrical system in­volves:
Generator insulation check
Installation of transfer switch
Generator output voltage selection
Load cable connection
Standard and optional AC equipment connec-
tions (e.g., control box heater, coolant heater, etc.
Optional enclosure electrical connections (re-
fer to
Section 7
Local regulations often require that wiring connec­tions be made by a licensed electrician, and that the installation be inspected and approved before op­eration. All connections, wire sizes, materials used, etc. must conform to the requirements of electrical codes in effect at the installation site.
WARNING
Improper wiring can cause a fire or electrocution, resulting in severe personal inju­ry or death and/or property and equipment dam­age.
Before starting the genset, check to make sure that all electrical connections are secure, and that all wiring is complete. Replace and secure any access panels that have been removed during installation. Check that the load cables from the genset are properly connected.
).
WARNING
Each of the operations described in this section should be done only by persons trained and experienced in electrical mainte­nance. Improper procedures may result in prop­erty damage, bodily injury or death.
WARNING
Backfeed to utility system can cause electrocution or property damage. Do not connect to any building electrical system except through an approved device and after building main switch is opened.
6-1
Page 32
TRANSFER SWITCH
Redistribution or publication of this document,
by any means, is strictly prohibited.
If the installation is for standby service, a transfer switch must be used for switching the load from the normal power source to the genset (see Figure 6-1). Follow the installation instructions provided with the transfer switch when connecting the load and con­trol wiring.
LOAD
NORMAL SOURCE
FIGURE 6-1. TYPICAL LOAD TRANSFER
FUNCTION
GENSET
6-2
Page 33
AC WIRING
Redistribution or publication of this document,
by any means, is strictly prohibited.
Generator Voltage Connections
The available generator output voltages and maxi­mum current ratings are specified on the generator set nameplate. Line-to-neutral voltage is always the lower voltage shown and line-to-line voltage is the higher rating.
All loads are connected to the generator by bolting stranded load wires to the appropriate terminals on the generator reconnection terminal block or circuit breaker lugs. The terminals are stamped U, V, W and N to indicate the line and neutral connections. (Reference: U, V, and W correspond with L1, L2 and L3; and N with L0 respectively).
Load Balancing
These generators can be configured to the name­plate voltages as shown on the Reconnection Dia­gram located on the side access cover of the control housing. Many of the voltages listed will require re­configuration of the generator output leads on the connection terminal block. This reconfiguration must only be done by service personnel that are trained and experienced to perform electrical instal­lation. The generator set was adjusted to produce a specified voltage during production verification test­ing prior to shipment. The installer must always check the stator lead terminal block connections and perform any necessary reconnect to obtain the voltage required.
Some generator sets are capable of producing a wide range of voltages and connection configura­tions, others have specific limited capabilities. Re­fer to wiring diagram and generator voltages (from the nameplate) when reviewing the voltage connec­tion information and use the wiring diagram sup­plied with your generator set when actually perform­ing load connections.
CAUTION
Reconfiguring generator sets to higher voltages can exceed the voltage capabil­ity of the specific generator windings and dam­age the generator and also decrease line cur­rent, rendering line circuit breakers too large. Consult with your distributor before performing reconnection for a different voltage.
CAUTION
Reconfiguring generator sets to lower voltages can reduce generator set rat­ings, and also increase line current, rendering line circuit breakers too small. Consult with your distributor before performing reconnec­tion for a different voltage.
Load Connections
Flexible conduit and stranded conductors must be used for connections to take up movement of the generator set.
When connecting loads to the generator set, bal­ance the loads so the current flow from each line ter­minal (L1, L2 and L3) is about the same. This is es­pecially important if both single phase and three phase loads are connected. Any combination of single phase and three phase loading can be used as long as each line current is about the same, with­in 10 percent of median value and no line current ex­ceeds the nameplate rating of the generator . Check the current flow from each line after connections by observing the control panel ammeter.
Current Transformers
Current transformers (CT’s) are required on gen­sets that contain AC meters. The CT’s must be installed as noted in the following CT Installation Requirements.
Refer to the Reconnection Diagram to identify the output leads/phase that must be routed through each CT, and also appropriate transformer post selection for meter sensing leads. The transformers are labeled CT1, CT2 and CT3 on the reconnection wiring diagram. (The Reconnection Diagram is lo­cated on the upper side cover of the control hous­ing.)
CT Installation Requirements:
A. The CT has a dot on one side. This dot must be
facing toward the generator (conventional cur­rent flowing into the dot). A dot is also used to indicate pin 1 of the CT.
B. CT1 − U load leads (A phase),
CT2 − V load leads (B phase) CT3 − W load leads (C phase)
C. Route the appropriate load wires through each
CT.
D. The CT’s have dual secondaries (3 pins). The
CT secondary wire marked 1 is connected to pin 1 of the CT. CT secondary wire marked 2/3 is connected to pin 2 for high voltage gensets or to pin 3 for low voltage gensets. (Refer to Re­connection Diagram.)
6-3
Page 34
Grounding
Redistribution or publication of this document,
by any means, is strictly prohibited.
The following is a brief description of system and equipment grounding of permanently installed AC generators within a facility wiring system. It is impor­tant to follow the requirements of the local electrical code.
Figure 6-2 illustrates typical system grounding for a 3-pole and a 4-pole automatic transfer switch (ATS). In the 3-pole ATS, note that the generator neutral is connected to the ATS and is NOT bonded to ground at the generator. In the 4-pole ATS sys­tem, a grounding electrode conductor and a bond­ing jumper are used to connect the generator neu­tral to ground.
Make sure the genset is grounded to earth in one location only. On generators without a circuit break­er, ground to the point indicated on the top of the generator. O n gensets with circuit breakers, use the ground lug provided in the circuit breaker box.
WARNING
Electric current can cause severe personal injury or death. Bonding and ground­ing must be done properly. All metallic parts that could become energized under abnormal conditions must be properly grounded.
Typical requirements for bonding and grounding are given in the National Electrical Code, Article
250. All connections, wire sizes, etc. must conform to the requirements of the electrical codes in effect at the installation site.
SERVICE ENTRANCE
THREE-PHASE, FOUR-WIRE UTILITY, THREE-POLE ATS
SERVICE ENTRANCE
GENERATOR SET
3-POLE ATS
LOAD
GENERATOR SET
4-POLE ATS
FIGURE 6-2. TYPICAL SYSTEM GROUNDING ONE-LINE DIAGRAMS
LOAD
THREE-PHASE, FOUR-WIRE UTILITY, FOUR-POLE ATS
6-4
Page 35
CONTROL HEATER (OPTIONAL)
Redistribution or publication of this document,
by any means, is strictly prohibited.
A control heater (Figure 6-3) provides a means of humidity/temperature control of the control box inte-
rior. I t protects the components when the generator set is subjected to varying ambient air conditions during extended periods of non-use.
THERMOSTAT
HEATER
240V PLUG
FIGURE 6-3. OPTIONAL CONTROL HEATER
120V PLUG
6-5
Page 36
COOLANT HEATER
Redistribution or publication of this document,
by any means, is strictly prohibited.
The coolant heater keeps engine coolant warm when the engine is shut down. It heats and circu­lates the coolant within the engine. This reduces startup time and lessens engine wear caused by cold starts. It is electrically operated and thermo­statically controlled.
CAUTION
erated while the cooling system is empty or damage to the heater will occur.
Figure 6-4 shows a typical coolant heater. Connect the heater to a source of power that will be on during
The coolant heater must not be op-
the time the engine is not running. Be sure the sup­ply voltage and circuit amperage is correct for the heater element rating.
A battery charger is required to prevent battery dis­charge. The heater control relay draws 83 mA of cur­rent when the heater(s) is off. The heater is off when the engine has reached the proper temperature or the engine is running.
CAUTION
Do not connect AC power to the heater before connecting battery cables. Heater will run continuously without DC power and can overheat and damage heater.
THERMOSTAT
COOLANT
FLOW
AC ELECTRICAL CONNECTION
BOX (ELECTRICAL DIAGRAM
INSIDE COVER)
DC SUPPLY
LINE
COOLANT
FLOW
DC CONTROL
LINE
DRAIN
AC POWER
LINE
FIGURE 6-4. TYPICAL COOLANT HEATER
6-6
Page 37
GENERATOR HEATER
Redistribution or publication of this document,
by any means, is strictly prohibited.
A generator heater(s) is used to help keep the gen­erator free of condensation when the generator set is not running. During cool and humid conditions, condensation can form within a generator, creating flashing and a shock hazard.
WARNING
tor increases the possibility of flashing and electrical shock, which can cause equipment damage and severe personal injury or death. Do not use a generator which is not dry inside and out.
Water or moisture inside a genera-
HEATER LEADS
Figure 6-5 illustrates the installation of two heater elements. Connect the heater(s) terminals to a source of power that will be on during the time the engine is not running. Be sure the supply voltage and circuit amperage is correct for the heater ele­ment rating.
HEATER
HEATER LEADS
HEATERS
TERMINAL BOX
HEATER
VOLT/WATTS
LABEL
TERMINAL
BLOCK
FIGURE 6-5. TYPICAL GENERATOR HEATER INSTALLATION
6-7
Page 38
FUEL TRANSFER PUMP
Redistribution or publication of this document,
by any means, is strictly prohibited.
A fuel transfer pump and control are available when a sub-base or in-skid day tank are provided. The au­tomatic control operates the fuel pump to maintain a reservoir of fuel in the day tank.
WARNING
Diesel fuel is highly combustible. Improper installation of this kit can lead to spill­age of large quantities of fuel and loss of life and property if the fuel is accidentally ignited. Instal­lation and service must be performed by trained and experienced persons in accordance with the applicable codes.
Do not smoke near fuel and keep flames, sparks, pilot lights, arcing switches and equip­ment, and other sources of ignition well away.
CONTROL
FLEXIBLE FUEL
RETURN LINE
FLEXIBLE FUEL
SUPPLY LINE
FUEL PUMP
AND MOTOR
FLOAT SWITCH
ASSEMBLY
DAY
TANK
FUEL
GAUGE
FIGURE 6-6. TYPICAL IN-SKID DAY TANK INSTALLATION
6-8
FUEL FILL
CAP
Page 39
Fuel Pump Control AC Connections
Redistribution or publication of this document,
by any means, is strictly prohibited.
The control can be powered by 120 VAC or 240 VAC. The control is set up at the factory for connec­tion to 240 VAC.
1. To convert the day tank controller from 240 VAC to 120 VAC, perform the following steps.
A. Remove the two jumpers between termi-
nals TB1-6 and TB1-7 in the control box and connect one between terminals TB1-5 and TB1-6 and the other between terminals TB1-7 and TB1-8.
2. To convert the day tank controller from 120 VAC to 240 VAC, perform the following steps.
A. Remove the jumpers between terminals
TB1-5 and TB1-6, and TB1-7 and TB1-8 in the control box and connect the two jumpers between terminals TB1-6 and
TB1-7.
B. Move selector switch S103 on the control
PCB to the down position for 240 VAC.
C. If the control is equipped with a transform-
er, remove the jumpers between terminals H1 and H3, and H2 and H4 and connect the two jumpers between H2 and H3.
B. Move selector switch S103 on the control
PCB to the up position for 120V.
C. If the control is equipped with a transform-
er, remove the two jumpers between ter­minals H2 and H3 and connect one be- tween H1 and H3 and the other between H2 and H4.
3 Attach a tag to the control box indicating the
supply voltage.
4 Terminals TB1-8 and TB1-5 are available for
connection of a 120 or 240 VAC electric fuel shutoff valve rated not more than 0.5 amps. The voltage rating of the valve must corre­spond with the voltage utilized for the pump. See Item 2 above.
FIGURE 6-7. FUEL PUMP CONTROL TERMINAL BOARD
6-9
Page 40
GROUND FAULT ALARM RELAY
Redistribution or publication of this document,
by any means, is strictly prohibited.
(OPTIONAL)
The optional Ground Fault Relay (GFR) (Figure 6-8) is typically located behind the lower control housing grille. The ground fault relay continuously monitors the neutral to ground connection and acti­vates a fault alarm when the connection is broken. During genset operation, the relay continuously monitors the line to neutral and activates a fault alarm when a ground fault is sensed.
After the installation of the genset is complete, per­form the following procedure to test the operation of the ground fault relay.
A. Verify that the N-G Fault Indicator on the
GFR is not lit. If lit, it indicates that the bonding jumper circuit (neutral to ground) is open. If genset does not require bonding jumper, a bonding jumper must be installed at the facility service entrance.
The relay alarm contacts are typically connected to the genset control to provide a “Ground Fault Alarm” indication.
A control reset will clear the fault at the control panel and will also reset the ground fault relay.
The relay has a time delay setting of zero to one second and a current setting of 5 to 1200 amperes.
Adjust the Current and the Time Delay controls on the ground fault relay to the customers specifica­tions.
B. Move the control switch to the Run posi-
tion.
C. Press the TEST switch on the ground fault
relay.
D. Verify that the control panel warning mes-
sage is displayed and the Fault Indicator (>I) on the GFR is lit.
E. Reset the control panel fault (this will also
reset the ground fault relay).
6-10
Page 41
CONTROL
Redistribution or publication of this document,
by any means, is strictly prohibited.
HOUSING
GROUND FAULT
RELAY
ASSEMBLY
GRILLE
TEST BUTTON
FAULT INDICATORS
> I
(OVER CURRENT)
N−G
(OPEN CIRCUIT)
FIGURE 6-8. GROUND FAULT ALARM RELAY
ON INDICATOR
RESET BUTTON
(N.U., FACTORY SET
TO AUTO RESET)
TIME DELAY CONTROL
CURRENT CONTROL
6-11
Page 42
THIS PAGE LEFT INTENTIONALLY BLANK
Redistribution or publication of this document,
by any means, is strictly prohibited.
6-12
Page 43

7. Enclosure Electrical Connections

Redistribution or publication of this document,
by any means, is strictly prohibited.
GENERAL
Generator sets configured with an enclosure can contain one or more optional features. The optional features that require electrical connections when installing the generator set are described in this section. For wiring diagrams of enclosure options, refer to Section 10,
FUEL ALARM
PANEL
Enclosure/Options Wiring
OVERFILL
ALARM
FUEL
FILL
.
CAUTION
Flexible conduit and stranded con­ductors must be used for connections to take up movement of the genset. Solid copper wire may break due to genset vibration.
Figure 7-1 shows the location of the optional fea­tures within the enclosure.
FUEL SYSTEM
CONTROL
EMERGENCY
STOP SWITCH
EXTERNAL
FUEL FILL BOX
MOTORIZED
INLET LOUVER
FIGURE 7-1. OPTIONAL ENCLOSURE FEATURES (WEATHER ENCLOSURE SHOWN)
120 VAC
EXTERNAL
RECEPTACLE
AC DISTRIBUTION
PANEL
7-1
Page 44
OPTIONAL AC DISTRIBUTION PANEL
Redistribution or publication of this document,
by any means, is strictly prohibited.
The AC distribution panel (Figure 7-2) provides a centralized power source (120/220VAC) for all op­tional enclosure features.
CAUTION
the OFF position before applying power to the AC distribution panel. Other options may re­quire additional installation before connecting to power.
CAUTION
the fuel transfer pump option, power to the AC distribution panel must be fed from a transfer switch and step-down transformer to maintain 120V power to the pump when utility power is in­terrupted. If the transfer pump option is not installed, power to the AC distribution panel can be fed from a non-emergency source. (Other op­tional features connected to the AC distribution
Make sure all circuit breakers are in
When the generator set contains
panel are not needed for generator set opera­tion.)
All connections to the AC distribution panel are to be done in compliance with the National Electric Code and all applicable local codes and standards using 60 or 75 degree conductors.
The AC distribution panel is designed to be fed with a 100AMP, 120/240VAC, single phase feeder. The two line conductors connect into the 100AMP main breaker that is listed for #4 to 2/0 conductors, AL or CU when torqued to 50 in-lbs.
The neutral conductor connects into the neutral bus which is listed for #5 to 300KCMIL conductors, AL or CU when torqued to 21 ft-lbs.
The grounding conductor, if used, connects into the ground bar which is listed for #1 to 2/0 conductors, AL or CU when torqued to 17 ft-lbs.
1/3
5/7
CIRCUIT BREAKERS
1/3: 100A MAIN
2: 20A J1/J2 RECEPTACLES 4: 20A J3/J4 RECEPTACLES
5/7: 40A COOLANT HEATERS
6: 20A INLET/OUTLET LOUVERS 8: 20A INTERNAL/EXTERNAL
SERVICE RECEPTACLES
2 4 6 8
FOR OPTIONAL FEATURES
J1: ENGINE OIL HEATER J2: BATTERY HEATER J3: ALTERNATOR /CONTROL
J4: BA TTERY CHARGER/TRANS-
GFCI SERVICE
RECEPTACLE
COOLANT HEATER
CONTROL AC SUPPLY
J1 J2 J3 J4
120VAC RECEPTACLES
24 V AC
TRANSFORMERS
(LOUVER MOTORS)
CABINET HEATERS
FER PUMP CONTROLLER
FIGURE 7-2. AC DISTRIBUTION PANEL FEATURES
7-2
Page 45
OPTIONAL MOTORIZED INLET/OUTLET
Redistribution or publication of this document,
by any means, is strictly prohibited.
LOUVERS
Louvers (inlet and/or outlet) are powered by either 24VDC supplied by genset control switched B+ or 24VAC transformer connected to shore power.
With switched B+ or gensets having the AC distribu­tion panel, the motorized louvers are prewired and require no further installation (Figure 7-3).
Without the AC distribution panel, the 24VAC lou­vers are not prewired. Louvers operating on 24VAC require 30VAC, 24 volt class 2 transformer(s). (Transformers are not supplied with genset that does not contain an AC distribution panel.) Mount and connect the transformer(s) to the 18 gauge wires terminated at the AC distribution panel loca­tion. Connect the transformer(s) to a source of pow­er that will be on during the time the engine is not running.
MOTORIZED
INLET LOUVER
30VAC
TRANSFORMER(S)
MOTORIZED
OUTLET LOUVER
AC DISTRIBUTION
PANEL
FIGURE 7-3. MOTORIZED LOUVER
7-3
Page 46
OPTIONAL FUEL TRANSFER PUMP
Redistribution or publication of this document,
by any means, is strictly prohibited.
A fuel transfer pump and control are available when a sub-base fuel tank is provided. The automatic control operates the fuel pump to maintain a reser­voir of fuel in the sub-base tank.
CAUTION
must be fed from a transfer switch and step­down transformer to maintain 120V power to the pump when utility power is interrupted. Power must be supplied to the transfer pump during the time the genset is running or not running.
The fuel transfer pump/controller is prewired and ready to connect to a 120VAC source.
NOTE: When power is applied to the control or is re­stored after a power interruption, the control will au-
Power to the fuel transfer pump
tomatically go to the power on mode (functions the same as pressing the ON switch). The pump will start if the control detects low fuel in sub-base tank.
CAUTION
Do not connect AC power to the fuel transfer pump control without having fuel in the supply tank. Damage to the pump can occur if pump operates with no fuel in supply tank.
Supply Tank
Refer to installation/plumping of the supply tank to the sub­base fuel tank.
The fuel transfer pump has a maximum inlet restric­tion capability of 16 inch Hg (which is approximately equivalent to 20 feet of diesel).
FUEL SYSTEM
CONTROL
Section 4
for information regarding the
FUEL
FILL
OVERFILL
ALARM
TO 120 VAC
EMERGENCY SUPPLY
FIGURE 7-4. FUEL TRANSFER PUMP/CONTROL LOCATION
7-4
Page 47

8. Prestart Preparation

Redistribution or publication of this document,
by any means, is strictly prohibited.
GENERAL
Before attempting the initial start of the generator set, be sure to complete the
Section 9
.
Installation Checklist
in
INPOWER SERVICE TOOL
GENERAL INFORMATION
InPower is a PC based service tool for the Power­Command
Make adjustments to the controls trims and set-
Perform diagnostics and monitoring.
Create a capture file of the controls trims and
Update control calibrations (InPower PRO ver-
Refer to INPOWER User’s Guide for specifics.
tings.
settings.
sion).
2100 Control (PCC). Use InPower to:
InPower Adjust Mode
when troubleshooting the genset (determine if pa­rameters/settings have been modified after installa­tion) and when replacement of the Base board is necessary. The capture file can be used as a tem­plate to write the previous settings to the new Base board software.
ELECTRICAL SYSTEM
Verify all electrical connections are secure and all wiring is complete and inspected. Replace and se­cure any access panels that may have been re­moved during installation.
Battery Connections
WARNING
set can cause severe personal injury or death. Make sure that the Run/Off/Auto switch on the control panel is set to the Off position before connecting the battery cables.
Starting the unit requires a 12 volt battery . Connect positive battery cable before connecting negative battery cable to prevent arcing.
Accidental starting of the generator
The adjustment feature allows you to make adjust­ments to genset parameters, calibrations and set­tings. There are several groups of adjustment pa­rameters; note that not all gensets will have the same adjustments available.
InPower Capture File Description
InPower provides a method of extracting (captur­ing) a device’s parameter values. Capturing saves device information in a file that is identified with a .CAP extension.
Capture files are used to store a copy of the gen­set’s parameter values. During genset installation, it is suggested that a capture file be made before and after changes are made to the genset operating parameters. This information can be a very useful
Service the batteries as necessary. If an automatic transfer switch is installed without a built-in charge circuit, connect a separate battery charger. A bat­tery charger is required when the PowerCommand control is set to the Awake mode.
WARNING
Ignition of explosive battery gases can cause severe personal injury or death. Al­ways connect negative (−) battery cable last to prevent arcing.
WARNING
Ventilate battery area before work­ing on or near battery. Arcing at battery termi­nals, light switch or other equipment, flame, pi­lot lights and sparks can ignite battery gas. Do not smoke, or switch trouble light ON or OFF near battery. Discharge static electricity from body before touching batteries by first touching a grounded metal surface.
8-1
Page 48
PCC OPTIONS PRESTART CHECKS
Redistribution or publication of this document,
by any means, is strictly prohibited.
All generator set configuration options are set at the factory except for site related options, (e.g., Lan­guage, Start/Stop Time Delays, Idle Start, Cycle Crank, Customer Fault 1 and 2, etc..
Adjustment of these options are divided into two categories within the menu driven system. These two categories are
tion/Adjust.
Setup
and
Controller Configura-
Controller Configuration
Figure 8-1 shows a block representation of the Con­troller Configuration menus.
To view the first Controller Configuration menu, make sure Main Menu 1 is displayed and simulta­neously press the Home Menu and Previous Main Menu buttons.
As shown in the diagram, the Controller Configura­tion menu has three submenus.
Press the buttons next to the digital display to navigate between the menus.
and symbols in the
The
Setup
submenus are intended for qualified ser­vice personnel only and require a password to modify these submenus. The
tion
and
Adjust
submenus are intended for service
Controller Configura-
personnel and site personnel.
Controller Configuration,
The
submenus are used to change the default language, temperature units, and pressure units to be displayed in menus.
The
Adjust
submenus allow site personnel to cali­brate the generator set voltage/frequency, idle speed and start/stop time delays. For the prestart checks, adjustment of only the start/stop delays is required.
Press the button next to the
symbol in the display
until the + and − symbols are displayed. Press the button next to the + or − symbol to select
the desired option. After selecting option, pressing the
symbol results in the changes being saved. If the Home button or Previous Main Menu button is pressed before pressing the
Language Selected submenu:
symbol, the changes are not saved.
Used to select de-
sired language (default = English).
Temperature Units submenu:
Used to select
Fahrenheit or Centigrade for temperature readings.
Fluid Pressure Units submenu:
Used to select
PSI or kPA for pressure readings.
8-2
Page 49
CONTROLLER CONFIGURATION MENU
Redistribution or publication of this document,
by any means, is strictly prohibited.
Main Menu 1
Engine Alternator
Language Selected
English
Temperature Units
Deg F
Adjust More>>
+Language Selected
− English
Back
+Temperature Units
− Deg C
Back
Fluid Pressure Units
PSI
+Fluid Pressure Units
− kPa
FIGURE 8-1. CONTROLLER CONFIGURATION MENU
8-3
Back
Page 50
Adjust Menu
Redistribution or publication of this document,
by any means, is strictly prohibited.
Figure 8-2 shows a block representation of the Ad­just menu. If you press the button next to the word “Adjust” in the display, the first Adjust submenu is displayed.
As shown in the diagram, the Adjust menu has five submenus. Each submenu includes a parameter or value that can be changed.
Press the buttons next to the digital display to navigate between the menus. Press the Home button or the Previous Main Menu button to return to Main Menu 1.
Adjusting Values/Parameters:
1.. Press the button next to the symbol in the dis­play until the + and − symbols are displayed.
2.. If necessary, press the button next to the or symbols to move to the numeric character you wish to change.
3.. Press the button next to the + symbol to in­crease the value or select parameter; press the button next to the − symbol to decrease the val­ue or select parameter.
4.. After adjusting values/selecting parameters, pressing the
symbol results in the changes being saved. (When adjusting values, make sure the cursor is on the last numeric character before pressing the
If the Home button or Previous Main Menu but­ton is pressed before pressing the
the changes are not saved.
and symbols in the
symbol).
symbol,
Voltage Adjust submenu:
Voltage can be ad­justed to 5 percent of the nominal voltage. For ex- ample, if genset output voltage is 208 volts, the volt­age can be adjusted from 197 to 218 volts.
If the revised value is greater or less than the allowed (5%) range, the control will round off the displayed value (up or down). For example, if changing the val­ue by −5% (maximum) equals 197.6, the display will show 197, but will display and change the output to 198 when saved.
Frequency Adjust submenu:
Frequency can be adjusted to 5 percent of the nominal frequency. For example, if the genset frequency is 60.0 Hz, the frequency can be adjusted from 57.0 to 63.0 Hz.
Start Delay submenu:
Start Delay can be set from 0 to 300 seconds (default = 0). This function is by­passed during a manual start/stop sequence.
Stop Delay submenu:
Stop Delay can be set from 0 to 600 seconds (default = 0). This function is by­passed during a manual start/stop sequence and engine shutdown faults.
Rated To Idle (Beginning Version 2.303):
Rated To Idle delay can be set from 0 to 10 seconds (de­fault = 0). (Enter 1 or more to enable.) Entering a non-zero delay will cause the genset to delay the transition to Cooldown At Idle.
Idle Start submenu (Only available on some models):
Idle Start can be enabled or disabled (de­fault = Disable). This function is only enabled when the genset is started in manual mode. Idle Start can also be enabled while the set is running in manual mode.
Enabling Idle Start will cause the genset to run in idle mode until Idle Start is disabled. A warning is displayed if genset is left in idle more than 10 min­utes. Long periods of engine idling can eventually affect engine performance and may void engine warranty.
8-4
Page 51
ADJUST MENU
Redistribution or publication of this document,
by any means, is strictly prohibited.
Main Menu 1
Voltage Adjust
nnn V
Frequency Adjust
nn.n Hz
Start Delay
nnn Sec
Engine Alternator
Adjust More>>
+Voltage Adjust
− nnn V
Back
+Frequency Adjust
− nn.n Hz
Back
+Start Delay
− nnn Sec
Back
Stop Delay
nnn Sec
Rated To Idle Delay
nn Sec
Idle Start
Disable
+Stop Delay
− nnn Sec
Back
+Rated To Idle Delay
− nn Sec
Back
+Idle Start
− Enable
Back
FIGURE 8-2. ADJUST MENU
8-5
Page 52
STARTING
Redistribution or publication of this document,
by any means, is strictly prohibited.
Refer to the generator set
Operator’s
manual for im­portant safety precautions and recommended pro­cedures for starting the genset and verifying proper operation. Start the generator set and verify all en­gine and generator menus are displaying the cor­rect values.
8-6
Page 53

9. Installation Checklist

Redistribution or publication of this document,
by any means, is strictly prohibited.
GENERAL
Generator set wattage capacity is sufficient to handle maximum anticipated load.
At least 3 feet of clearance (or greater for housing door) is provided around entire generator set for servic-
ing and ventilation.
Generator set is located in an area not subject to flooding.All operating personnel have read and are familiar with Operator’s Manual.All operators have been thoroughly briefed on preventive maintenance procedures.All operators have read and understand all Important Safety Instructions in Operator’s Manual.
GENERATOR SET SUPPORT
Floor, roof or earth on which the generator set rests is strong enough and will not allow shifting or move­ment. Observe local codes on soil bearing capacity due to freezing and thawing.
Generator set is properly supported and retained to approved base.Supporting base is large enough and is of non-combustible material − extends 6-inches all around set.
COOLING AIR FLOW
Generator set air inlet is faced into direction of strongest, prevailing winds.
Air inlet openings are unrestricted and at least 1−1/2 times larger than air outlet area.Cooling air outlet is on downwind side of building (if not, wind barrier is constructed).Proper ducting material (sheet metal, canvas) is used between radiator and air outlet.
DIESEL FUEL SYSTEM
Fuel tanks meet or exceed all Local, State or National codes.
Fuel lines are properly installed, supported and protected against damage.Approved flexible fuel line is installed between main fuel supply line and generator set’s fuel system, near
the generator set, to protect the fuel system from damage caused by vibration, expansion and contrac­tion.
Strainer or fuel screen (100 to 120 mesh) is installed in the fuel supply line to protect the fuel lift pump, day
tank transfer pump or float valve seat from fuel supply tank debris.
Fuel supply line shutoff valves are installed to prevent fuel flow in case of leaks.No shutoff valves are installed on engine fuel return line.External fuel pumps are connected and operational at all times (generator set started or shut down).Fuel system is properly primed.No fuel leaks are found in supply line or engine fuel system.
9-1
Page 54
EXHAUST SYSTEM
Redistribution or publication of this document,
by any means, is strictly prohibited.
Operators are thoroughly briefed on the dangers of carbon monoxide gas.
Areas around set are well ventilated. No possibility of exhaust fumes entering building doors, windows, or
intake fans.
Exhaust gases are piped safely outside and away from building.The correct length of approved rigid pipe is connected to the generator set flexible pipe using approved
securing methods with no weight resting on engine exhaust components. There are no bends in flex sec­tion.
Condensation drain is provided in lowest section of exhaust piping.Exhaust piping is insulated to guard against burns to personnel.Exhaust piping passing through walls or ceilings have approved fire-proof materials and are in com-
pliance with all codes.
Exhaust piping is large enough in diameter to prevent excessive back pressure on engine.
AC AND DC WIRING
Wire sizes, insulation, conduits and connection methods all meet applicable codes.
AC and DC wires are separated in their own conduit to prevent electrical induction.All load, line and generator connections are proper and correct.Flexible conduit between generator set and building or surrounding structure.
GENERATOR SET PRESTART
Generator set engine is properly serviced with oil and coolant.
Batteries are properly installed, serviced and charged.Battery charger and engine coolant heater are connected and operational.All generator set covers and safety shields are installed properly.All fuel and coolant shutoff valves are operational.Created capture file of the genset’s parameter values before and after modifications.
9-2
Page 55

10. Wiring Diagrams

Redistribution or publication of this document,
by any means, is strictly prohibited.
GENERAL
This section consists of the schematic and connec­tion wiring diagrams referenced in the text. The fol­lowing drawings are included.
Page 10-2 − Customer Connections Diagram
Page 10-3 and 4 − Enclosure/Options Wiring
10-1
Page 56
THIS IS A REPRESENTATIVE (GENERIC)
Redistribution or publication of this document,
by any means, is strictly prohibited.
SCHEMATIC/WIRING DIAGRAM. FOR TROUBLESHOOTING, REFER TO THE WIRING DIAGRAM PACKAGE THAT WAS INCLUDED WITH YOUR GENSET.
TB1-CUSTOMER FAULTS:
TB1-CUSTOMER RELAYS:
DEFAULT SETTING
1 CUSTOMER FAULT 1 2 GROUND FAULT 3 LOW FUEL 4 RUPTURE BASIN FAULT
1 COMMON WARNING 2 COMMON SHUTDOWN 3 NOT IN AUTO 4 READY TO LOAD
No. 620-0247 sh 1 of 1 Rev. A Modified 4-18-02
CUSTOMER CONNECTIONS DIAGRAM
10-2
Page 57
THIS IS A REPRESENTATIVE (GENERIC)
Redistribution or publication of this document,
by any means, is strictly prohibited.
SCHEMATIC/WIRING DIAGRAM. FOR TROUBLESHOOTING, REFER TO THE WIRING DIAGRAM PACKAGE THAT WAS INCLUDED WITH YOUR GENSET.
No. 630-2672 sh 2 of 4 Rev. B Modified 10-03
ENCLOSURE/OPTIONS WIRING (SHEET 1 OF 2)
10-3
Page 58
THIS IS A REPRESENTATIVE (GENERIC)
Redistribution or publication of this document,
by any means, is strictly prohibited.
SCHEMATIC/WIRING DIAGRAM. FOR TROUBLESHOOTING, REFER TO THE WIRING DIAGRAM PACKAGE THAT WAS INCLUDED WITH YOUR GENSET.
No. 630-2672 sh 4 of 4 Rev. B Modified 10-03
ENCLOSURE/OPTIONS WIRING (SHEET 2 OF 2)
10-4
Page 59
Cummins Power Generation
Redistribution or publication of this document,
by any means, is strictly prohibited.
1400 73rd Avenue N.E. Minneapolis, MN 55432 1-800-888-6626 763-574-5000 International Use Fax: 763-528-7229