SAVE THESE INSTRUCTIONS. This manual contains important instructions that
should be followed during installation and maintenance of the generator set and
batteries.
Safe and efficient operation can be achieved only if the equipment is properly
operated and maintained.Many accidents are caused by failure to follow
fundamental rules and precautions.
1.1Warning, Caution, and Note Styles Used in
This Manual
The following safety styles and symbols found throughout this manual indicate
potentially hazardous conditions to the operator, service personnel, or equipment.
DANGER
Indicates a hazardous situation that, if not avoided, will result in death or
serious injury.
WARNING
Indicates a hazardous situation that, if not avoided, could result in death or
serious injury.
Indicates a hazardous situation that, if not avoided, could result in minor or
moderate injury.
Indicates information considered important, but not hazard-related (e.g.,
messages relating to property damage).
1.2General Information
This manual should form part of the documentation package supplied by Cummins
Inc. with specific generator sets. If this manual has been supplied in isolation,
please contact your authorized dealer.
It is in the operator's interest to read and understand all warnings and
cautions contained in the documentation relevant to the generator set
operation and daily maintenance.
Hot Surfaces
Contact with hot surfaces can cause severe burns.
The unit is to be installed so that the risk of hot surface contact by people is
minimized. Wear appropriate PPE when working on hot equipment and avoid
contact with hot surfaces.
WARNING
Toxic Hazard
Ethylene glycol, used as an engine coolant, is toxic to humans and animals.
Wear appropriate PPE. Clean up coolant spills and dispose of used coolant
in accordance with local environmental regulations.
WARNING
Combustible Liquid
Ignition of combustible liquids is a fire or explosion hazard which can cause
severe burns or death.
Do not store fuel, cleaners, oil, etc., near the generator set. Do not use
combustible liquids like ether.
WARNING
Combustible Gases
Generator sets in operation have combustible gases under pressure, which
if ignited can cause eye and ear damage.
Wear appropriate eye and ear protection at all times.
WARNING
Combustible Gases
Generator sets in operation have combustible gases under pressure, which
if ignited can cause severe injury.
Do not operate the generator set with any doors open.
WARNING
Fire Hazard
Materials drawn into the generator set, as well as accumulated grease and
oil, are a fire hazard. Fire can cause severe burns or death.
Keep the generator set and the surrounding area clean and free from
obstructions. Make sure the generator set is mounted in a manner to prevent
combustible materials from accumulating under the unit.
Automated Machinery
Accidental or remote starting of the generator set can cause severe personal
injury or death.
Isolate all auxiliary supplies and use an insulated wrench to disconnect the
starting battery cables (negative [–] first).
NOTICE
Keep multi-type ABC fire extinguishers close by. Class A fires involve
ordinary combustible materials such as wood and cloth. Class B fires
involve combustible and flammable liquid fuels and gaseous fuels. Class C
fires involve live electrical equipment. (Refer to NFPA No. 10 in the
applicable region.)
NOTICE
Before performing maintenance and service procedures on enclosed
generator sets, make sure the service access doors are secured open.
NOTICE
Stepping on the generator set can cause parts to bend or break, leading to
electrical shorts, or to fuel leaks, coolant leaks, or exhaust leaks. Do not step
on the generator set when entering or leaving the generator set room.
1.3Generator Set Safety Code
Before operating the generator set, read the manuals and become familiar with
them and the equipment. Safe and efficient operation can be achieved only ifthe equipment is properly operated and maintained. Many accidents are caused
by failure to follow fundamental rules and precautions.
WARNING
Electrical Generating Equipment
Incorrect operation and maintenance can result in severe personal injury or
death.
Read and follow all Safety Precautions, Warnings, and Cautions throughout
this manual and the documentation supplied with the generator set.
1.4Moving Parts Can Cause Severe Personal
Injury or Death
• Keep hands, clothing, and jewelry away from moving parts.
• Before starting work on the generator set, disconnect the battery charger from
its AC source, then disconnect the starting batteries using an insulated wrench,
negative (–) cable first. This will prevent accidental starting.
• Make sure that fasteners on the generator set are secure. Tighten supports and
clamps; keep guards in position over fans, drive belts, etc.
• Do not wear loose clothing or jewelry in the vicinity of moving parts or while
working on electrical equipment.Loose clothing and jewelry can become
caught in moving parts.
• If any adjustments must be made while the unit is running, use extreme caution
around hot manifolds, moving parts, etc.
1.5Electrical Shocks and Arc Flashes Can Cause
Severe Personal Injury or Death
• Only qualified service personnel certified and authorized to work on power
circuits should work on exposed energized power circuits.
• All relevant service material must be available for any electrical work performed
by certified service personnel.
• Exposure to energized power circuits with potentials of 50 VAC or 75 VDC or
higher poses a significant risk of electrical shock and electrical arc flash.
• Refer to standard NFPA 70E, or equivalent safety standards in corresponding
regions, for details of the dangers involved and for safety requirements.
1.6Fuel and Fumes Are Flammable
Fire, explosion, and personal injury or death can result from improper practices.
• Do not fill fuel tanks while the engine is running unless the tanks are outside
the engine compartment. Fuel contact with hot engine or exhaust is a potential
fire hazard.
• Do not permit any flame, cigarette, pilot light, spark, arcing equipment, or other
ignition source near the generator set or fuel tank.
• Fuel lines must be adequately secured and free of leaks. Fuel connection at the
engine should be made with an approved flexible line. Do not use copper piping
on flexible lines as copper will become brittle if continuously vibrated or
repeatedly bent.
• Make sure all fuel supplies have a positive shutoff valve.
• Make sure the battery area has been well-ventilated prior to servicing near it.
Lead-acid batteries emit a highly explosive hydrogen gas that can be ignited by
arcing, sparking, smoking, etc.
Do Not Operate in Flammable and Explosive Environments
Flammable vapor can cause an engine to over speed and become difficult to stop,
resulting in possible fire, explosion, severe personal injury, and death. Do not
operate a generator set where a flammable vapor environment can be created,
unless the generator set is equipped with an automatic safety device to block the air
intake and stop the engine. The owners and operators of the generator set are
solely responsible for operating the generator set safely. Contact your authorized
Cummins distributor for more information.
Spillage
Any spillage that occurs during fueling, oil top-off, or oil change must be cleaned up
before starting the generator set.
Fluid Containment
NOTICE
Where spillage containment is not part of a Cummins supply, it is the
responsibility of the installer to provide the necessary containment to
prevent contamination of the environment, especially water courses and
sources.
If fluid containment is incorporated into the bedframe, it must be inspected at
regular intervals. Any liquid present should be drained out and disposed of in line
with local health and safety regulations. Failure to perform this action may result in
spillage of liquids which could contaminate the surrounding area.
Any other fluid containment area must also be checked and emptied, as described
above.
1.7Batteries Can Explode
Batteries can explode, causing severe skin and eye burns and can release toxic
electrolytes.
Combustible Gases
Batteries can explode, causing severe skin and eye burns, and can release
toxic electrolytes.
Do not dispose of the battery in a fire, because it is capable of exploding. Do
not open or mutilate the battery. Do not charge frozen batteries.
Electric Shock Hazard
Batteries present the risk of high short circuit current.
When servicing the generator set:
• Remove watches, rings, or other metal objects.
• Use tools with insulated handles.
NOTICE
Servicing of batteries must be performed or supervised by personnel
knowledgeable of batteries and the required precautions. Keep unauthorized
personnel away from batteries.
• Wear safety glasses.
• Do not smoke.
• Do not charge frozen batteries.
• To prevent arcing when disconnecting the battery:
1. Press the Off switch from the display and then press the E-Stop button.
2. Disconnect AC power from any battery chargers.
3. Remove the negative (-) battery cables to prevent starting.
• To prevent arcing when reconnecting the battery:
1. Reconnect the positive (+) cables.
2. Reconnect the negative (-) cables.
3. Reconnect the battery charger to AC power supply.
• When replacing the generator set battery, always replace it with a battery as
specified in this manual.
1.8Exhaust Gases Are Deadly
• Provide an adequate exhaust system to properly expel discharged gases away
from enclosed or sheltered areas, and areas where individuals are likely to
congregate. Visually and audibly inspect the exhaust system daily for leaks per
the maintenance schedule. Make sure that exhaust manifolds are secured and
not warped. Do not use exhaust gases to heat a compartment.
Hot Exhaust Gases
Contact with hot exhaust gases can cause severe burns.
Wear personal protective equipment when working on equipment.
WARNING
Hot Surfaces
Contact with hot surfaces can cause severe burns.
The unit is to be installed so that the risk of hot surface contact by people is
minimized. Wear appropriate PPE when working on hot equipment and avoid
contact with hot surfaces.
WARNING
Toxic Gases
Inhalation of exhaust gases can cause asphyxiation and death.
Pipe exhaust gas outside and away from windows, doors, or other inlets to
buildings. Do not allow exhaust gas to accumulate in habitable areas.
WARNING
Fire Hazard
Contaminated insulation is a fire hazard. Fire can cause severe burns or
death.
Remove any contaminated insulation and dispose of it in accordance with
local regulations.
The exhaust outlet may be sited at the top or bottom of the generator set. Make
sure that the exhaust outlet is not obstructed. Personnel using this equipment must
be made aware of the exhaust position. Position the exhaust away from flammable
materials - in the case of exhaust outlets at the bottom, make sure that vegetation is
removed from the vicinity of the exhaust.
The exhaust pipes may have some insulating covers fitted. If these covers become
contaminated they must be replaced before the generator set is run.
To minimize the risk of fire, make sure the following steps are observed:
• Make sure that the engine is allowed to cool thoroughly before performing
maintenance or operation tasks.
Carbon monoxide (CO) is an odorless, colorless, tasteless and non-irritating gas.
You cannot see it or smell it. Red blood cells, however, have a greater affinity for
CO than for oxygen. Therefore, exposure even to low levels of CO for a prolonged
period can lead to asphyxiation (lack of oxygen) resulting in death. Mild effects of
CO poisoning include eye irritation, dizziness, headaches, fatigue and the inability to
think clearly. More extreme symptoms include vomiting, seizures and collapse.
Engine-driven generator sets produce harmful levels of carbon monoxide that can
injure or kill you.
Special Risks of CO near the Home
WARNING
Toxic Gases
Carbon monoxide (CO) gas can cause nausea, fainting, or death. Residents
can be exposed to lethal levels of CO when the generator set is running.
Depending on air temperature and wind, CO can accumulate in or near the
home.
To protect yourself and others from the dangers of CO poisoning, it is
recommended that reliable, approved, and operable CO detector alarms are
installed in proper locations in the home as specified by their manufacturer.
Protecting Yourself from CO Poisoning
• Locate the generator set in an area where there are no windows, doors, or
other access points into the home.
• Make sure all CO detectors are installed and working properly.
• Pay attention for signs of CO poisoning.
• Check the exhaust system for corrosion, obstruction, and leaks every time you
start the generator set and every eight hours when you run it continuously.
1.10Earth Ground Connection
The neutral of the generator set may be required to be bonded to earth ground at
the generator set location, or at a remote location, depending on system design
requirements. Consult the engineering drawings for the facility or a qualified
electrical design engineer for proper installation.
NOTICE
The end user is responsible to make sure that the ground connection point
surface area is clean and free of rust before making a connection.
The end user is responsible for making sure that an earthing arrangement
that is compliant with local conditions is established and tested before the
equipment is used.
Hazardous Voltage
Contact with high voltages can cause severe electrical shock, burns, or
death.
Make sure that only a trained and experienced electrician makes generator
set electrical output connections, in accordance with the installation
instructions and all applicable codes.
Electrical Generating Equipment
Faulty electrical generating equipment can cause severe personal injury or
death.
Generator sets must be installed, certified, and operated by trained and
experienced person in accordance with the installation instructions and all
applicable codes.
WARNING
WARNING
2.2About This Manual
The purpose of this manual is to provide the users with sound, general information.
It is for guidance and assistance with recommendations for correct and safe
procedures. Cummins Inc. cannot accept any liability whatsoever for problems
arising as a result of following recommendations in this manual.
The information contained within the manual is based on information available at the
time of going to print. In line with Cummins Inc. policy of continuous development
and improvement, information may change at any time without notice. The users
should therefore make sure that they have the latest information available before
starting any work. The latest version of this manual is available on QuickServe
Online (https://quickserve.cummins.com).
Users are respectfully advised that, in the interests of good practice and safety, it is
their responsibility to employ competent people to carry out any installation work.
Consult your authorized dealer for further installation information. It is essential that
the utmost care is taken with the application, installation, and operation of any
generator set due to their potentially hazardous nature. Careful reference should
also be made to other Cummins Inc. literature. You must operate and maintain your
generator set properly if you are to expect safe and reliable operation.
For further assistance, contact your authorized Cummins Inc. dealer.
This device complies with part 15 of the FCC rules. Operation is subject to
the following two conditions:
• This device may not cause harmful interferences.
• This device must accept any interference received, including
interference that may cause undesired operation.
2.3Schedule of Abbreviations
This list is not exhaustive. For example, it does not identify units of measure or
acronyms that appear only in parameters, event/fault names, or part/accessory
names.
The literature provided with the generator set is as follows:
• Installation Manual (A045R241)
• Operator Manual (A045R242)
CAUTION
A generator set must be operated and maintained properly if you are to
expect safe and reliable operation. The Operator Manual includes a
maintenance schedule and a troubleshooting guide.
The Health and Safety Manual must be read in conjunction with this manual
for the safe operation of the generator set:
26 standard, 34 high capacity (a high capacity battery requires an
accessory battery tray)
545 standard, 850 high capacity (a high capacity battery requires
an accessory battery tray)
2.6After Sales Services
Cummins offers a full range of maintenance and warranty services.
Maintenance
Electrical Generating Equipment
Incorrect service or parts replacement can result in severe personal injury,
death, and/or equipment damage.
Make sure service personnel are qualified to perform electrical and
mechanical service.
WARNING
For expert generator set service at regular intervals, contact your Cummins Inc.
serviceprovider.Seepower.cummins.com/sales-service-locatorforservice
locations that service this application. Maintenance tasks should only be undertaken
by trained and experienced technicians provided by your Cummins Inc. service
provider.
Warranty
For details of the warranty coverage for your generator set, refer to the Warranty
Statement listed in the Related Literature section.
Extended warranty coverage is also available. In the event of a breakdown, prompt
assistance can normally be given by factory trained service technicians with
facilities to undertake all minor and many major repairs to equipment on site.
For further warranty details, contact your authorized dealer.
NOTICE
Damage caused by failure to follow the manufacturer's recommendations
will not be covered by the warranty. Please contact your authorized dealer.
For details of the warranty limitations for your generator set, refer to the
warranty statement applicable to the generator set.
How to Obtain Service
For parts, service, and product information, contact the nearest authorized Cummins
Inc. dealer. To easily locate the nearest certified distributor/dealer for Cummins
generator sets in your area, or for more information, contact us at 1-800CUMMINSTM(1-800-286-6467) or visit www.cummins.com/support.
Generator Set Nameplate
WARNING
Electrical Generating Equipment
Improper service or replacement of parts can lead to severe personal
injury or death and to damage to equipment and property.
Make sure service personnel are qualified to perform electrical and
mechanical service.
Model
Spec
Serial
Number
NOTICE
Unauthorized modifications or replacement of fuel, exhaust, air intake
or speed control system components that affect engine emissions are
prohibited by law in the State of California.
Model, Spec, and Serial Numbers: Be ready to provide the model, spec, and
serial numbers on the generator set nameplate when contacting Cummins Inc.
for information, parts, and service. The nameplate is located on the inside of
the customer access door on enclosed generator sets.
Record these numbers so that they are easy to find when needed. Each
character in these numbers is significant for obtaining the right parts listed in
thePartsCatalog.GenuineCumminsInc.replacementpartsare
recommended for best results.
The control system is used to start and stop the generator set, and provides full
generator set monitoring capability and protection in a stand-alone situation (nonparalleling) from the display screen. It monitors the engine for temperature, as well
as oil pressure and speed. It also provides voltage and current metering. In the
event of a fault, the unit indicates the fault type and, on critical faults, automatically
shuts down the generator set.
All indicators, control buttons, and the display screen are on the face of the operator
panel, as illustrated in the figure below.
There are three fault level signals generated by the control system:
• Event: Signals that a temporary condition exists.
• Warning: Signals an imminent or non-critical fault for the engine. The control
provides an indication only for this condition.
• Shutdown: Signals a potentially critical fault for the engine. The control
immediately takes the engine off-load and automatically shuts it down.
The standard control system operates on 12 VDC (or 24 VDC if applicable) battery
power. History data is stored in non-volatile memory and is not deleted if battery
power is lost.
Standard Operator Panel
The operator panel includes indicator lights (LEDs), display buttons used to
navigate through the menus, control mode buttons, and an LCD display. The display
enables the operator to check the status, adjust the settings, and start and stop the
generator set. The standard operator panel (show below) is located on every
generator set. An optional remote display operator panel accessory is also
available.
The user interface includes two fixed action buttons and four soft key buttons.
The action of the soft key buttons changes to meet the requirements of each
screen.
TABLE 14.KEY FUNCTIONS
Key/SymbolAction
Switches to Off mode (fixed action button).
Switches to Auto mode.
Switches to Manual Run mode.
Navigates to the previous menu level (fixed action button).
(Up Arrow) Navigates to the previous screen/menu in a list.
(Down Arrow) Navigates to the next screen/menu in a list.
andHold the up and down arrows simultaneously for two seconds from any
Info Menu to navigate to the Menu screen.
SaveSaves changes and navigates to the associated screen.
AdjustNavigates to the Adjust Menu of a specific menu.
(Right Arrow) Advances the highlighted field to the next editable field.
-Decreases value of the highlighted editable field.
+Increases value of highlighted editable field.
Standard LED Indicators (HMI211)
The operator panel has six LED indicators. Colors, flashing frequency, and
conditions to turn them on/off/blink are included in the table below.
TABLE 15.LED INDICATORS
LEDColorAction
Not in AutoRedIndicates the generator set is in Manual or Off Mode.
ShutdownRedIndicates a Shutdown Fault has occurred.
WarningYellowIndicates a Warning Fault has occurred.
3. Control System7-2018
Remote
Start
AutoGreenIndicates that the generator set is in Auto Mode. The generator starts
Manual RunGreenIndicates that the generator set has received a Manual Run
GreenIndicates that the generator set has received a Remote Start
Command.
when it receives a Remote Start Command.
Command.
In-Home Operator Panel (Accessory)
The in-home operator panel is an optional display that may be purchased. This
panel is intended to serve as a convenience option to the standard operator panel
mounted on the generator set.
The user interface includes two fixed action buttons and four soft key buttons.
The action of the soft key buttons changes to meet the requirements of each
screen.
TABLE 16.KEY FUNCTIONS
Key/SymbolAction
StopSwitches to Off mode. This key works from any screen (fixed action
button).
(Up Arrow) Navigates to the previous screen/menu in a list.
(Down Arrow) Navigates to the next screen/menu in a list.
andHold the up and down arrows simultaneously for two seconds from any Info
Menu to navigate to the Service Menu.
BackNavigates to the previous screen/menu in a list (fixed action button). In
Adjust screens, settings are not saved.
SaveSaves changes and navigates to the associated screen.
AdjustNavigates to the Adjust Menu of a specific menu.
(Right Arrow) Advances the highlighted field to the next editable field.
-Decreases value of the highlighted editable field.
The operator panel has five LED indicators. Colors, flashing frequency, and
conditions to turn them on/off/blink are included in the table below.
TABLE 17.LED INDICATORS
LEDColorAction
ShutdownRedIndicates a Shutdown Fault has occurred.
WarningYellowIndicates a Warning Fault has occurred.
Auto StartGreenIndicates that the generator set has received a Remote Start
Command.
AutoGreenIndicates that the generator set is in Auto Mode. The
generator starts when it receives a Remote Start Command.
Manual RunGreenIndicates that the generator set has received a Manual Run
Command.
3.2Display Text or Symbolic Version
The operator panel graphical display can be set to show text (English only) or
symbols for fault messages, operator menus, and the Mode Change Menu.
Descriptions of commonly used symbols are included in the following table.
Combinations of symbols are used to display some fault conditions.
When shipped from the factory, the display is set to display symbols. Qualified
service personnel are required to change the default setting.
When battery power is lost, these settings must be reset.
Not applicable without a single phase RA series transfer switch.
To access the Clock/Exerciser Menu:
1. From any Information Menu, hold down the up and down arrows simultaneously
for two seconds. The Service Menu appears.
2. Navigate through the screens to find and select Clock/Excr in the Service
Menu.
The following screens represent the standard operator panel (that is,
HMI211). If using an in-home operator panel, which may be additionally
purchased as an option, the screens may look slightly different. This
procedure applies to both operator panels.
The following screens represent the standard operator panel (HMI211). If
using an in-home operator panel, which may be additionally purchased as an
option, the screens may look slightly different. This procedure applies to
both operator panels.
FIGURE 10.BRIGHTNESS AND CONTRAST SCREEN NAVIGATION
Adjusting the brightness on the operator panel adjusts the brightness of
both the LCD backlight and the LEDs on the display. The contrast should
never be 0 or 100% on any of the screens. The default value for Brightness is
50%.
3.6History and About Menu
To access the History/About screen:
1. From any Information Menu, hold down the up and down arrows simultaneously
for two seconds. The Service Menu appears.
2. Select History/About.
3. Advance through the screens to view information about the generator set,
control, and display.
NOTICE
The following screens represent the standard operator panel (HMI211). If
using an in-home operator panel, which may be additionally purchased as an
option, the screens may look slightly different. This procedure applies to
both operator panels.
1. From any Information Menu, hold down the up and down arrows simultaneously
for two seconds. The Service Menu appears.
2. Select Fault History.
NOTICE
The active faults are displayed first. If there are no active faults, this screen
is skipped. Following the Active Faults screen are the Fault History screens.
These screens display the faults in chronological order from newest to
oldest.
NOTICE
The following screens represent the standard operator panel (HMI211). If
using an in-home operator panel, which may be additionally purchased as an
option, the screens may look slightly different. This procedure applies to
both operator panels.
The generator set's PowerCommand®control has Manual Run, Off, and Auto
operating modes that are available from the operator panel.
Off Mode
When in the Off mode, the control does not allow the generator set to start.
If the generator set is running in either Manual Run or Auto mode and the Off button
is pressed, the control immediately stops the generator set, and the control
transitions to the Off mode.
Pressing the Off mode button resets all active faults.
Manual Run Mode
When in Manual Run mode, the generator set starts and continues to run until the
control is put into the Off mode. While in Manual Run mode, the remote start signal
is ignored.
Auto Mode
When in Auto mode, the control allows the generator set to be started at any time
with a remote signal only. When a remote start signal is received, the generator set
starts after a time delay start is completed (default delay is zero seconds).
When all remote start signals are removed, the control performs a normal shutdown
sequence which includes a time delay stop (default delay is five minutes).
If the generator set is running in Auto mode and the Off button is pressed, the
control immediately stops the generator set and the control transitions to the Off
mode.
3.9Selecting Operating Modes
Selecting Manual Run Mode
WARNING
Electrical Generating Equipment
When changing modes, the generator set can start or stop without warning
(for example, Auto Mode may have been selected with no mains (utility)
power available).
Make sure there is no danger to personnel or equipment, if the generator set
starts or stops when changing modes.
1. Before proceeding to change the mode, make sure that it is safe to do so.
2.Press theManual Run button on any of the Operator menus or the
"Establishing/Re-establishing communication with control" menus.
Electrical Generating Equipment
When changing modes, the generator set can start or stop without warning
(for example, Auto Mode may have been selected with no mains (utility)
power available).
Make sure there is no danger to personnel or equipment, if the generator set
starts or stops when changing modes.
To switch to Auto mode (see Figure 14 on page 48),
1. Ensure that it is safe to do so before proceeding to change the mode.
2.PresstheAuto buttonon anyof theOperator menus,or the
‘Establishing/Re-establishing communication with control’ menus.
3. If the mode change access code feature is enabled, the Mode Change Access
Code menu is displayed. Enter the Mode Change Access Code.
4. A menu with alternating arrows will then be displayed above a second
Auto symbol.
5.Press this secondAuto button. The Operator menu that was displayed
before Auto mode was selected is re-displayed, but with theAuto symbols
blacked out andManual Run symbols visible.
To disable Auto mode, press the Off button.
The generator set is now ready to receive a remote start signal that will initiate the
Auto run mode.
WARNING
Should a remote start signal be received, the generator set starts
automatically. Make sure there is no danger to personnel or equipment
should the generator set start without warning.
NOTICE
Manual Run mode can also be selected FROM Auto mode. Switching to
Manual Run mode results in the generator set starting up.
Hazardous Voltage
Contact with high voltages can cause severe electrical shock, burns, or
death.
Make sure that only personnel who are trained and qualified to work on this
equipment are allowed to operate the generator set and perform
maintenance on it.
Automated Machinery
Accidental or remote starting of the generator set can cause severe personal
injury or death.
Make sure that the generator set cannot be started accidentally or remotely
before starting work on the generator.
WARNING
WARNING
WARNING
Combustible Gases
Ignition of battery gases is a fire and explosion hazard which can cause
severe personal injury or death.
Do not smoke, or switch the trouble light ON or OFF near a battery. Touch a
grounded metal surface first before touching batteries to discharge static
electricity. Stop the generator set and disconnect the battery charger before
disconnecting battery cables. Using an insulated wrench, disconnect the
negative (–) cable first and reconnect it last.
CAUTION
Hazardous Voltage
Contact with high voltages can cause severe electrical shock, burns, or
death.
Isolate all external electrical supplies prior to access of the control panel.
Internal components have live exposed terminations even when the
generator set is not running.
NOTICE
Isolator switch only: Do not open the output box while the generator set is
running as the isolator switch will cause the generator set to shut down.
Keep the output box covers in place during troubleshooting.
Always disconnect a battery charger from its AC source before
disconnecting the battery cables. Failure to do so can result in voltage
spikes high enough to damage the DC control circuits of the generator set.
NOTICE
Ventilate the battery area before working on or near the battery. Wear
goggles. Stop the generator set and disconnect the battery charger before
disconnecting the battery cables using an insulated wrench. Disconnect the
negative (–) cable first and reconnect it last.
All maintenance tasks must be assessed for health and safety risks; the preventive
measures identified must be performed. An additional person is required for any
task where doing so significantly adds to the safety of the task.
The installation of a generator set can be designed for remote starting. When
troubleshooting a generator set that is shut down, make sure that the generator set
cannot be accidentally re-started. Refer to the Locking the Generator Set Out of
Service section.
4.2Introduction
This section describes the operation of the generator set. The text should be read in
conjunction with the Control System section of this manual.
All indicators, control switches/buttons, and graphical display are located on the
face of the Operator Panel.
4.3Maintenance
To ensure maximum performance and reliability from your generator set, it is
essential that certain components are inspected periodically and, where necessary,
maintenance procedures are carried out, as detailed in the Maintenance chapter.
4.4Operating Recommendations
Running-In
Refer to the Maintenance section of this manual. Special "running-in" oils are not
recommended for new or rebuilt Cummins engines. Use the same type of oil during
"running-in" as is used in normal operation.
The engine should be run at varying loads during the first few hours of operation to
allow the components to "bed in." Avoid long periods of light load or full load running
particularly during the early life of the engine.
Generator sets on continuous standby must be able to go from a cold start to being
fully operational in a matter of seconds. This can impose a severe burden on engine
parts.
Regular exercising keeps engine parts lubricated, prevents oxidation of electrical
contacts, and in general helps provide reliable engine starting.
Exercise the set for a minimum of ten minutes off-load at least once a week and for
a minimum of 30 minutes with load at least once each month so that the engine
reaches normal operating temperatures.
Low Operating Temperatures
NOTICE
Operating engines at idle (650 to 1000 rpm) in cold ambient temperatures
wastes fuel, accelerates wear, and can result in serious engine damage.
Under low temperature conditions, incomplete combustion will occur,
allowing deposits of unburned tars and carbon to buildup on the valve guide
and valves, and eventually cause valve sticking.
In cold climates it is critical that the following items be appropriately maintained and
selected based on ambient operating temperatures. Check to be sure:
• The battery is properly sized.
• An appropriate mixture of antifreeze is used in the cooling system.
• The proper grade of fuel is being used.
• The correct weight of engine oil is being used.
Use a coolant heater if a separate source of power is available. The optional heater
available from Cummins will help provide reliable starting under adverse weather
conditions. Make sure the voltage of the separate power source is correct for the
heater element rating.
High Operating Temperatures
In high ambient temperatures, when operating at full load, it is normal for the high
temperature warning to be given. This indicates that the engine is operating near to
its maximum capacity and is normal. If operation in high temperature environments
is anticipated, increase the frequency of checks for coolant level, obstructions of
cooling air inlets and outlets, and debris at the radiator.
Refer to the generator set nameplate for the maximum operating temperature, if
applicable.
General Operating Conditions
The area surrounding the generator set is critical for safety and its performance.
Follow the guidelines below.
• Do not stack anything on top of the generator set.
• Do not store anything inside of the generator set.
• Keep areas clear in front of the cool air in and hot air out (free of obstructions,
debris, plants, etc.).
NOTICE
All maintenance procedures must be performed or supervised by authorized
and trained service personnel only.
4.5Generator Set Operation
WARNING
Combustible Vapors
Do not operate an engine where there are or can be combustible vapors.
These vapors can be sucked through the air intake system and cause engine
acceleration and overspeeding, which can result in a fire, an explosion,
personal injury and extensive property damage.
Correct care of your engine will result in longer life, better performance, and more
economical operation.
Cummins Inc. does not know how you will use your generator set. The equipment
owner and operator, therefore, is responsible for safe operation in the installation
site environment. Consult your authorized Cummins dealer for further information.
NOTICE
Diesel engines only: Cummins Inc. recommends the installation of an air
intake shutoff device or a similar safety device to minimize the risk of
overspeeding where an engine will be operated in a combustible
environment.
NOTICE
Long periods of idling (more than ten minutes) can damage an engine. Do
not idle the engine for excessively long periods.
Sequence of Operation
NOTICE
The following sequences are based on an approximate time duration. Your
generator set may vary slightly from the timing diagrams in this manual. All
referenced times are based on default control settings. The following
sequences are applicable to generator sets connected to an RA series
transfer switch.
The sequence of operation after a power outage (when the generator set is in
Auto Mode) is as follows:
1. In normal operation, the utility power is running to the transfer switch and
then to the building load, and the generator set is off.
2. The utility power turns off (power outage).
3. One second after the power outage, the transfer switch sends the
command to the generator set to start.
4. The generator set starts and provides voltage to the transfer switch, but
the transfer switch does not switch (allowing the voltage to go to the
building) until after a delay.
FIGURE 16.TIME REMAINING UNTIL TRANSFER SCREEN
5. Five seconds after starting, the generator set provides a signal to the
transfer switch to transfer the building load to the generator set.
FIGURE 17.BUILDING LOAD TRANSFER IN PROCESS
6. The transfer switch switches the generator set power to the building load.
The building is now running on generator power.
FIGURE 18.GENERATOR SET POWERING BUILDING LOAD
7. When the utility power is back and providing voltage to the transfer
switch, the transfer switch waits for utility power stability.
2. The Exerciser Scheduler On screen displays every 3 seconds and toggles
between the existing Information screen that is displayed for 1 second.
FIGURE 23.EXERCISER SCHEDULER SCREEN AND INFORMATION SCREEN
TOGGLE - EXAMPLE
3. The transfer switch is not commanded to switch the building load to the
generator set.
NOTICE
The user may navigate to other screens from the Information
screens during this duration. No functional keys are active on the
Exerciser Scheduler On screen.
4. The generator set stops after programmed exercise run time.
Manually Starting the Generator Set Sequence
If the generator set is manually started with the standard operator panel,
HMI211 (the generator set is in Man Mode), the sequence is as follows:
NOTICE
Open the generator set main line circuit breaker to prevent the transfer
switch from transferring building load to the generator set.
1. In normal operation, the utility power is running to the transfer switch and
then to the building load, and the generator set is off.
2. Manually start the generator set via the standard control (HMI211)
mounted on the generator set.
6. Press the Off button to switch the load back to the utility power.
FIGURE 27.BUILDING LOAD TRANSFER IN PROCESS
4. Operation7-2018
FIGURE 28.UTILITY POWERING BUILDING LOAD
7. Normal operation resumes.
Remote Starting the Generator Set Sequence
If the generator set is remote started with the in-home operator panel
accessory, if equipped (the generator set is in Auto Mode), the sequence is as
follows:
1. In a normal operation, the utility power is running to the transfer switch
and then to the building load, and the generator set is off.
2. The generator set-mounted control (HMI211) is set in Auto Mode.
4. The generator set starts and provides voltage to the transfer switch, but
the transfer switch does not switch (allowing the voltage to go to the
building) until after a delay.
FIGURE 31.TIME REMAINING UNTIL TRANSFER SCREEN
5. Five seconds after starting, the generator set provides a signal to the
transfer switch to transfer the building load to the generator set.
Automated Machinery
Accidental or remote starting of the generator set can cause severe personal
injury or death.
Isolate all auxiliary supplies and use an insulated wrench to disconnect the
starting battery cables (negative [–] first).
Hydrogen Gas
Arcing can ignite explosive hydrogen gas given off by batteries, causing
severe personal injury or death. Arcing can occur when cables are removed
or replaced, or when the negative (–) battery cable is connected and a tool
used to connect or disconnect the positive (+) battery cable touches the
frame or other grounded metal part of the generator set.
Insulated tools must be used when working in the vicinity of the batteries.
Always remove the negative (–) cable first and reconnect last.
WARNING
WARNING
WARNING
Explosive Fumes
Arcing can ignite explosive fumes causing severe personal injury or death.
Make sure hydrogen from the battery, engine fuel and other explosive fumes
are fully dissipated before working on the generator set.
WARNING
Working at Heights
Using the incorrect equipment when working at heights can result in severe
personal injury or death.
Suitable equipment for performing these tasks must be used in accordance
with the local guidelines and legislation. Failure to follow these instructions
can result in severe personal injury or death.
Access
Using the generator set or part of as a means of access when attaching
lifting shackles, chains, or other lifting aids, may damage the generator set,
causing severe personal injury or death.
Do not use the generator set as a means of access. Failure to follow these
instructions can result in severe personal injury or death.
WARNING
Exposed Terminations
Some panel internal components may have live exposed terminations even if
the generator set is not running. Voltages are present which can cause
electrical shock, resulting in personal injury or damage to equipment.
Isolate all external electrical supplies prior to access of the control panel
NOTICE
Only authorized and qualified maintenance technicians who are familiar with
the equipment and its operation should carry out maintenance.
NOTICE
Dependent upon the control system fitted, this unit may operate
automatically and could start without warning.
NOTICE
Always disconnect a battery charger from its AC source before
disconnecting the battery cables. Failure to do so can result in voltage
spikes high enough to damage the DC control circuits of the generator set.
All maintenance tasks must be performed, but be sure to assess them for health
and safety risks before starting. For example, perform a task with someone present
if doing so will add significantly to the safety of the task.
Read, understand, and comply with all Caution, Warning, and Danger notes in this
section, the Important Safety Instructions section, and the documentation supplied
with the generator set.
Before any work is carried out for maintenance, etc., the generator set must be
immobilized. Even if the generator set is put out of service by pressing the Off
switch on the Operator Panel (or the STOP button if applicable), the generator set
cannot be considered safe to work on until the engine is properly immobilized, as
detailed in the following procedure.
NOTICE
Refer also to the engine-specific Operator Manual, if applicable. This manual
contains specific equipment instructions that may differ from the standard
generator set.
To immobilize the generator set:
1. Press the Off switch from the display and then press the E-Stop button to shut
down the engine. This will prevent the starting of the generator set regardless of
the Start signal source and will therefore provide an additional safety step for
immobilizing the generator set. Alternatively, make sure the generator set is in
manual mode (which allows it to be started by manually pushing the buttons).
NOTICE
When the E-Stop button is pressed, the Operator Panel indicates the
Shutdown condition by illuminating the red Shutdown status LED
and displaying a message on the graphical LCD display.
2. Thoroughly ventilate the generator set before disconnecting any leads.
3. Turn off and disconnect the heater (where fitted) from the AC source before
disconnecting the battery cables.
4. Turn off and disconnect the battery charger (where fitted) from the AC source
before disconnecting the battery cables.
5. Turn off the fuel supply to the engine.
6. Disconnect the battery. Disconnect the negative (–) cable first, using an
insulated wrench.
7. Place warning notices at each of the above locations that state, "Maintenance
in Progress – Immobilized for Safe Working."
Electrical Generating Equipment
Accidental or remote starting of the generator set can cause severe personal
injury or death.
Before working on the generator set, make sure that the generator set is in
Off mode, disable the battery charger, and remove the negative (– ) battery
cable from the battery to prevent starting.
The table(s) that follow show the recommended service intervals for a generator set
on standby service. If the generator set will be subjected to extreme operating
conditions, the service intervals should be reduced accordingly.
At each scheduled maintenance interval, perform all previous maintenance checks
that are due for scheduled maintenance.
Some of the factors that can affect the maintenance schedule are:
• Extremes in ambient temperature
• Exposure to elements
• Exposure to salt water
• Exposure to windblown dust or sand
Consult with your authorized Cummins Inc. service provider if the generator set will
be subjected to any extreme operating conditions, and determine if extra protection
or a reduction in service intervals is needed. Use the engine hours shown on the
system status screen to keep to keep an accurate log of all service performed for
warranty support. Perform all service at the time period indicated, or after the
number of operating hours indicated, whichever comes first.
Repair or replace worn, damaged, or improperly functioning components identified
during periodic maintenance procedures.
Periodic Maintenance Guidelines
Regularly performing the following periodic maintenance tasks greatly reduces the
chances of a generator set shutdown:
Perform maintenance tasks as specified using the period of operation that
occurs first.
TABLE 22.PERIODIC MAINTENANCE SCHEDULE
Maintenance Item
Check air cleaner
restriction indicator
(where fitted): If
the service
indicator shows
red, replace air
cleaner elements
and reset the air
cleaner service
indicator.
Check air intake
system for leaks:
Visually inspect
the air intake
system for signs of
wear or damage.
Check audibly
when the
generator set is
running. Replace
worn or damaged
components.
Daily
or After
24 Hours
■
■
Weekly
or After
50 Hours
100
Hours
1 Year
or After
200 Hours
2
Years
1
1
4000
Hours
Check operation of
operator panel:
Check display (the
system will
perform a control
panel test on initial
activation).
Replace
component if not
functioning
properly.
Verify that the
coolant heater has
power and is
running (where
fitted). Check for
evidence of leaks.
Remove any
corrosion from
fittings.
Check engine oil
level: If low, top up
to engine
specifications
level, with
recommended oil.
Check fuel lines
and hoses:
Visually check for
leaks, worn or
damaged hoses.
Daily
or After
24 Hours
■
■
■
Weekly
or After
50 Hours
100
Hours
1 Year
or After
200 Hours
2
Years
1
1
4000
Hours
Check charge
alternator: Check
visually and
audibly when the
generator set is
running.
Check all exhaust
components, and
hardware (fittings,
clamps, fasteners,
etc.): Visually
inspect the
exhaust system for
signs of wear or
damage. Check
audibly when the
generator set is
running.
Check generator
set enclosure:
Visually check
enclosure, walk
around inspection
of generator set.
Make sure no
inlets/outlets are
covered/restricted,
service access
doors are
operational and
safety systems are
in place and
operational.
Check operation of
Emergency Stop
Button (where
fitted): With the
generator set
running, press the
Emergency Stop
button. Check all
systems, before
resetting the fault.
Replace engine oil
and filters. Refer
to the procedure in
the Engine Oil
section.
Daily
or After
24 Hours
■
Weekly
or After
50 Hours
■
2
■
100
Hours
1 Year
or After
200 Hours
2
■
2
Years
1
1
4000
Hours
Check battery:
Check connections
to verify that they
are secure.
Replace air
cleaner.
Clean radiator
core.
Check charge air
cooler for damage
and debris (where
fitted).
Check electrical
connections
(battery, starter
motor, alternator
connections).
Check for tight
connections,
general condition
and remove any
corrosion.
Check alternator
heater (where
fitted). Check
general condition
and wiring
connections.
Check battery
heater (where
fitted). Check
general condition
and wiring
connections.
Daily
or After
24 Hours
Weekly
or After
50 Hours
100
Hours
1 Year
or After
200 Hours
■
■
■
2
Years
1
1
4000
Hours
Replace cooling
■
system coolant.
Inspect all sealed
bearings every
4000 to 4500
hours
1
To be performed by a qualified Service Technician.
2
After the initial 50 hour interval and every 200 hours thereafter.
3
Cleaning schedule may be reduced depending on operating conditions/environment.
4
Replace all bearings every 30000 hours or 5 years (or if necessary after 10000 hours or 2
years).
Maintenance Record
Record all periodic and unscheduled maintenance and service. See the Periodic
Maintenance Schedule for a list of scheduled maintenance frequency.
Record the name, address, and phone number of your authorized Cummins Inc.
service center:
NameAddressPhone
Exercising the Generator Set
NOTICE
Audible engine RPM variation may be heard when there is no load applied.
This is normal and does not affect the generator set performance.
Exercising the generator set drives off moisture, relubricates the engine, and
removes oxides from electrical contacts. The result is better starting, more reliable
operation and longer engine life.
The generator set exerciser mode defaults are as follows.
• Day: Tuesday
• Time: 2:00 pm
• Period: Monthly
• Run Time: 5 minutes
Refer to the Exercise Settings section of this manual for more information on setting
up the exerciser.
5.3Engine Oil
Recommended Engine Oil
Check the oil level prior to starting the generator set to verify that the oil level is
between the High and Low marks. The generator set is shipped with engine oil
(5W30 API SM or newer engine oil is recommended).
Checking Engine Oil Level
NOTICE
Check the engine oil level when the engine is not running and is out of Auto
mode.
WARNING
Crankcase pressure can blow out hot oil and cause severe burns. Do NOT
check oil while the engine is operating.
CAUTION
Overfilling can cause foaming or aeration of the oil while operation below the
low mark may cause loss of oil pressure. Do not operate the engine with the
oil level below the low mark or above the high mark.
WARNING
State and federal agencies have determined that contact with used engine oil
can cause cancer or reproductive toxicity. Avoid skin contact and breathing
of vapors. Use rubber gloves and wash exposed skin. Accidental or remote
starting of the generator set can cause severe personal injury or death.
Disconnect the negative (-) battery cable and place the control switch in its
OFF position (or press the STOP button if applicable) before starting work.
Too much oil can cause high oil consumption. Too little oil can cause severe
engine damage. Keep the oil level between the High and Low marks on the
dipstick.
Adding Oil
If the oil level is found to be insufficient, oil must be added.
1. Ensure that the oil fill cap area is clean, and prevent debris from entering
the engine.
2. Add the appropriate amount of oil, based on the engine oil level check.
RefertotheCheckingEngineOilLevelsectionandtheModel
Specifications section.
3. Recheck the engine oil level. Based on the results, add or drain oil.
4. Clean up and dispose of any oil in accordance with local/state regulations.
Draining Oil
If the oil level is found to be excessive, oil must be drained from the engine.
1. Detach the oil drain hose from the side of the engine.
2. Place the end of the drain hose into an appropriate container.
Refer to local regulations to determine the appropriate container for used oil.
• Open the oil drain valve to release oil from the engine into the appropriate
container.
• Recheck the engine oil level. Based on the results, add or drain oil.
• When a sufficient amount of oil has been drained from the system:
1. Close the oil drain valve.
2. Wipe the oil drain valve clean.
3. Re-attach the drain hose to the side of the engine.
4. Dispose of the used oil in accordance with local/state regulations.
Changing Engine Oil and Oil Filter
WARNING
Toxic Hazard
State and federal agencies have determined that contact with used engine oil
can cause cancer or reproductive toxicity.
Avoid skin contact and breathing of vapors. Use rubber gloves and wash
exposed skin. Accidental or remote starting of the generator set can cause
severe personal injury or death. Disconnect the negative (-) battery cable
and place the control switch in its OFF position (or press the STOP button if
applicable) before starting work.
If the oil and/or oil filter are not reused, dispose of them in accordance with
local environmental regulations.
NOTICE
Change the engine oil and filter when the engine is not running and is out of
Auto mode.
NOTICE
Change the oil more often in hot and dusty environments.
NOTICE
Cummins highly recommends that any service or maintenance work be
performed by qualified technicians.
1. Before changing the oil, the generator set should be operated until the water
temperature is approximately 140 °F (60 °C).
2. Turn off the generator set.
3. Drain the oil.
4. Remove the oil filter, and clean the filter mounting surface on the engine block.
Remove the old gasket if it remains.
5. Make sure the gasket is in place on the new filter and apply a thin film of clean
oil to the gasket. Install the new filter until the gasket just touches the block.
Turn it an additional 1/2 to 3/4 turn. Do not over-tighten.
6. Close the oil drain valve.
7. Refill with oil until full.
NOTICE
Too much oil can cause high oil consumption. Too little oil can cause
severe engine damage. Keep the oil level between the High and Low
marks.
8. Operate generator set with no load to inspect for leaks at the lubricating oil filter
and the drain plug.
9. Confirm that the correct oil level is in the pan:
a. Shut the generator set off and wait 5 minutes.
b. Check the engine oil level.
10. Check and repair any leaks identified.
11. Dispose of the used oiland oil filteraccording to local environmental
regulations.
The direct flow air cleaner consists of a primary filter and a secondary filter within
the air cleaner housing. The air cleaner has been designed for a maximum
restriction, at which point the filter elements should be changed. Refer to the Model
Specifications section.
Normal Duty Air Cleaner
Normal Duty Air Cleaner Element Replacement
Holes, loose-end seals, dented sealing surfaces, corrosion of pipes,
and other forms of damage render the air cleaner inoperative and
require immediate element replacement or engine damage can occur.
Cummins Inc. does not recommend cleaning paper-type air cleaner
elements.
5. Maintenance7-2018
NOTICE
NOTICE
1. Remove the existing air cleaner:
a. Loosen the strap clamp (2).
b. Wipeawayanydebrisaccumulatedaroundtheaircleaner
connection to the engine. Ensure that no debris is allowed to enter
the body of the air cleaner or the connection on the engine.
c. Remove the dirty air cleaner (1).
d. Dispose of the dirty element in accordance with local environmental
agency requirements.
2. Install the replacement air cleaner (1) as follows:
a. Install the air cleaner (1).
b. Tighten strap clamp (2). Torque to 2.5 - 3.3 ft-lb (4.3 - 4.65 Nm).
Fall Hazard
Falls can result in severe personal injury or death.
Make sure that suitable equipment for performing tasks at height are
used in accordance with local guidelines and legislation.
There is a dust ejector valve (DEV) on the bottom of each filter pre-cleaner
that should be checked periodically to make sure it is free of dust and dirt.
When there is a filter pre-cleaner, it includes a primary and secondary element
that is checked periodically to make sure they are clean. Refer to the PeriodicMaintenance Schedule table for additional information.
Heavy Duty Air Cleaner Element Replacement
Holes, loose-end seals, dented sealing surfaces, corrosion of pipes,
and other forms of damage render the air cleaner inoperative and
require immediate element replacement or engine damage can occur.
AC AmmeterAt no load, the current readings should be zero. With a load applied,
each line current should be similar.
Panel LampsWhen the operating panel is first connected to the DC supply, the
system runs a check by illuminating each of the indicator lamps in turn.
2. If all of the LEDs do not illuminate, replace the operator panel.
5.6DC Electrical System
WARNING
Combustible Gases
Ignition of battery gases is a fire and explosion hazard which can cause
severe personal injury or death.
Do not smoke, or switch the trouble light ON or OFF near a battery. Touch a
grounded metal surface first before touching batteries to discharge static
electricity. Stop the generator set and disconnect the battery charger before
disconnecting battery cables. Using an insulated wrench, disconnect the
negative (–) cable first and reconnect it last.
5. Maintenance7-2018
1. Check the harness connections. If any harness connections are damaged,
contact your service representative.
FIGURE 41.CHECK HARNESS CONNECTIONS
2. Check the terminals on the batteries for clean and tight connections. Loose or
corroded connections create resistance, which can hinder starting. Clean and
reconnect the battery cables if loose, using an insulated wrench. Always
disconnect both ends of the negative battery cable. Reconnect one end of the
cable to the negative battery terminal and the other end to ground. This will
make sure that any arcing will be away from the battery and least likely to ignite
explosive battery gases.
3. Check connections at the battery charging alternator.
4. Visually inspect the alternator belt to make sure it is not loose or cracked.
Batteries are an essential part of any standby generator set system. A significant
amount of generator set failures are due to battery issues.
It is therefore vital that batteries are stored, commissioned, and maintained as
detailed here. Reference should also be made to the battery manufacturer’s
instructions.
Maintenance free batteries (if supplied with the generator set) need no maintenance
for commissioning.
Storage
Batteries must be stored in a cool, dry, well-ventilated place, in the upright position,
and with the vent caps securely in place.
Batteries must never be stacked on top of each other and must be protected from
the floor by a wooden pallet or suitably thick cardboard sheet.
Safety Precautions
Servicingofbatteriesaretobeperformedorsupervisedbypersonnel
knowledgeable of batteries and the required precautions. Keep unauthorized
personnel away from batteries.
General Precautions for Maintenance-Free Batteries
Handling and proper useof batteries is not hazardousif the correct
precautions are observed and personnel are trained in their use.
WARNING
Arcing Hazard
Laying tools or metal objects across the battery can cause arcing that
may ignite battery gases causing explosions resulting in personal
injury.
Never lay tools or metal objects across the top of the battery.
WARNING
Electric Shock Hazard
Voltages and currents present an electrical shock hazard that can
cause severe burns or death.
Use tools with insulated handles to prevent the risk of electric shock.
Toxic Hazard
Electrolyte is a dilute sulphuric acid that is harmful to the skin and
eyes. It is electrically conductive and corrosive.
Wear full eye protection and protective clothing. If electrolyte contacts
the skins, wash it off immediately with water. If electrolyte contacts the
eyes, flush thoroughly and immediately with water and seek medical
attention. Wash spilled electrolyte with an acid neutralizing agent.
NOTICE
Keep batteries upright to prevent spillage.
Fire Hazard
WARNING
Combustible Gases
Lead acid batteries present a risk of fire because they generate
hydrogen gas.
Do not smoke near the batteries. Do not cause flame or spark in the
battery area. Discharge static electricity from your body before
touching batteries by first touching a grounded metal surface.
WARNING
Before disconnecting a battery, always remove power from the AC
powered battery charger.
WARNING
When putting a battery into service on a generator set, connect the
negative lead LAST; when removing the battery, disconnect the
negative lead FIRST.
Toxic Hazard
The electrolyte in vented batteries is a dilute sulfuric acid that is
harmful to the skin and eyes. It is also electrically conductive and
corrosive.
Always:
1. Wear full eye protection and protective clothing;
2. If the electrolyte contacts the skin, wash it off immediately with
water;
3. If the electrolyte contacts the eyes, flush them thoroughly and
immediately with water and seek medical attention; and
4. Wash spilled electrolyte down with an acid neutralizing agent. A
common practice is to use a solution of one pound (500 grams)
bicarbonate of soda (also known as baking soda or sodium
bicarbonate) to one gallon (4 liters) of water.
5. Continue to add the bicarbonate of soda solution until the evidence
of reaction (that is, foaming) has stopped.
6. Flush the resulting liquid with water and dry the area.
Battery Maintenance
WARNING
Automated Machinery
Accidental or remote starting of the generator set can cause severe personal
injury or death. Arcing at battery terminals or in light switches or other
equipment, and flames or sparks can ignite battery gas causing severe
personal injury.
Always follow these procedures to avoid injury and/or damage:
• Ventilate the battery area before working on or near the battery.
• Wear safety glasses.
• Do not smoke.
• Switch a work light on or off away from the battery.
Make sure the generator set is shut down and disabled:
1. Press the generator set's red STOP button on the local display to stop
the generator set. Allow the generator set to thoroughly cool to the
touch.
2. Turn off and disconnect the battery charger from the AC source before
disconnecting the battery cables.
3. Disconnect the negative (–) cable from the battery and secure it from
contacting the battery terminals to prevent accidental starting.
4. Once work is complete, reconnect the negative (-) battery cable last.
See Battery Charger Maintenance for troubleshooting the charger.
Always:
• Keep the battery case and terminals clean and dry and the terminals tight.
• Remove battery cables with an insulated wrench or battery terminal puller.
• Make sure which terminal is positive (+) and which is negative (-) before
making battery connections, always removing the negative (-) cable first and
reconnecting it last to reduce arcing.
NOTICE
If the battery needs to be replaced, make sure that the replacement battery
specifications match those found in the Model Specifications in this manual.
Charging
Where a consistent source of AC power is available, Cummins recommends the use
of a battery charger to maintain battery condition and charge. Cummins offers
several battery chargers.
Where generator sets are used infrequently and a consistent source of AC power is
not available, battery recharging must be put on a recharge schedule to ensure that
a fully charged condition is maintained.
NEVER allow a battery to become completely flat (fully discharged), or to
stand in a discharged condition, or damage will result.
Follow the battery charger operating instructions for proper use.
5.8Spark Plugs
Make sure service personnel are qualified to perform electrical and
mechanical service.
The generator set has four spark plugs, all accessible from the top of the engine.
The spark plugs must be in good condition for proper engine starting and
performance. A spark plug that fouls frequently or has heavy soot deposits indicates
the need for engine service.
NOTICE
NOTICE
1. Set the generator set control to the Off position before checking the spark
plugs.
2. To prevent cross-threading a spark plug, always thread it in by hand until it
seats. Torque the spark plug to 20 Nm (15 lb-ft).
3. Return the generator set control to the desired setting when finished performing
maintenance.
5.9Cleaning the Generator Set Housing
The housing of the generator set housing can be damaged by pressure washing or
solvents and other cleaning agents. Only use soap and water or an “all citrus
degreaser" to clean the housing.
5.10Complete System Test
NOTICE
Only authorized and qualified maintenance technicians who are familiar with
the equipment and its operation should carry out this test.
A complete system test is recommended to verify that the electrical system is
working properly. Testing the system once every 200 hours or every 2 years is
required to make sure the transfer switch will transfer the load to the generator set if
there is a utility power failure. For more information, see the transfer switch owner
manual.
To initiate a complete system test:
1. Before starting:
• Check the oil level.
• Make sure there is enough fuel.
• See the Checklist section in the installation manual.
2. Place the generator set in Standby mode.
3. Switch the main utility disconnect from the ON to the OFF position.
4. Make sure the following occurs:
a. The generator set starts.
b. After the generator set starts and stabilizes, the load is transferred from the
utility to the generator set.
5. Switch the main utility disconnect from the OFF to the ON position.
6. Make sure the following occurs:
a. After approximately 5 minutes, the load is transferred back to the utility.
b. Once the transfer switch is connected to utility power, after approximately 5
minutes, the generator set stops.
NOTICE
If the test fails, call your authorized Cummins service provider to fix the
problem.
By regularly performing the following periodic maintenance and guidelines, you will
greatly reduce the chances of a generator set shutdown:
• Maintain an appropriate oil level.
• Keep battery connections clean and tight.
• Do not overload the generator set.
• Keep the air inlet and outlet openings clear.
Refer to the Maintenance section for more information.
6.2Control System
The generator setcontrol system continuously monitorsengine sensors for
abnormal conditions, such as low oil pressure and high coolant temperature. If any
of these conditions occur, the control will light a yellow Warning lamp or a red
Shutdown lamp and will display a message on the graphical display panel. In the
event of an engine shutdown fault (red Shutdown LED), the control will stop the
engine immediately.
6.3Fault Finding
Troubleshooting procedures.
Troubleshooting procedures present hazards that can result in severe
personal injury or death.
Only qualified service personnel with knowledge of fuels, electricity, and
machinery hazards should perform service procedures.
Review safety precautions listed in this manual together with the
documentation supplied with the generator set.
For any symptom not listed, contact your authorized dealer for assistance.
Before starting any fault finding, ensure that the following basic checks are carried
out:
• All switches and controls are in their correct positions
• Fuel system is connected and fuel is available
• The lubricating oil level is correct
• The coolant level is correct
• The radiator cooling air flow is free from obstruction
• The battery charge condition is satisfactory and the connections are secure
• The generator set electrics and alternator connections are secure
• The panel connections are secure
• The protection circuits have been reset
• Blown fuses have been replaced
• Tripped contactors or circuit breakers have been reset
6.4Fault/Status Codes - PowerCommand 1.1
Fault Code Introduction
Fault code information, together with warning and shutdown information, is provided
in this section to assist in locating and identifying the possible causes of faults in the
generator set system.
Refer also to the engine-specific operator manual, if it exists. The engine operator
manual contains additional information regarding the running and care of the
generator set as well as specific equipment instructions that may differ from the
standard generator set.
For any fault codes that occur but are not listed, contact your Cummins service
representative.
Fault/Status Codes Warnings
WARNING
Electrical Generating Equipment
Incorrect installation or servicing can result in severe personal injury or
death.
Make sure that only suitably trained and experienced service personnel with
knowledge of fuels, electricity, and machinery hazards perform electrical
and/or mechanical service.
WARNING
Automated Machinery
Accidental or remote starting of the generator set can cause severe personal
injury or death.
Prevent accidental starting by disconnecting the starting battery cables,
negative (–) cable first.
Code 143 - Engine Oil Pressure Low (Warning)
Logic: Engine oil pressure is below the low oil pressure shutdown threshold.
d. Inspect the radiator cap and gasket for damage and proper pressure
operation.
i. Contact your local dealer if repair or replacement is required.
e. Inspect upper and lower radiator hoses for collapse, distortion, or fluid
leaks.
i. Contact your local dealer if repair or replacement is required.
f. Inspect cooling system components for external contaminates and clean as
required.
i. Open the radiator cap and inspect for contaminated coolant and scale.
ii. Contact your local dealer if flushing of cooling system is required.
Code 155 - Intake Manifold Temperature High (Shutdown)
Logic: The engine intake manifold temperature has exceeded 95 °C (203 °F) for
greater than 10 seconds.
Diagnosis and Repair:
For the troubleshooting procedure, refer to DTC 127 in the E-Controls Manual,
which applies to several applications. See the drawings provided with the generator
set or the wiring diagrams appendix for the appropriate pin numbers.
Code 197 - Coolant Level Low (Warning)
Logic: Coolant level sensor signal is showing a low coolant level for greater 10
seconds.
Possible Cause:
1. Low coolant
Diagnosis and Repair:
1. Low coolant
a. Remove radiator cap and check that coolant is up to the required level.
Code 415 - Engine Oil Pressure Low (Shutdown)
Logic: Engine oil pressure is below the low oil pressure shutdown threshold.
Possible Causes:
1. Lubricating oil level is low
2. External leak
Diagnosis and Repair:
1. Lubricating oil level is low
a. Check the oil level. Add oil, if necessary.
2. External leak
a. Inspect the engine and surrounding area for external oil leaks.