CUMMINS C13N6H (Spec A), C17N6H (Spec A), C20N6HC (Spec A), C20N6H (Spec A) Installation Manual

Page 1
InstallationInstallation ManualManual
Home Standby Generator Set
C13N6H (Spec A) C17N6H (Spec A) C20N6H (Spec A) C20N6HC (Spec A)
English Original Instructions
12-2016 A053X172 (Issue 6)
Page 2
Page 3
1. IMPORTANT SAFETY INSTRUCTIONS....................................................................................... 1
1.1 Save These Instructions ........................................................................................................ 1
1.2 General Information ................................................................................................................ 1
1.3 General Precautions .............................................................................................................. 1
1.4 Generator Set Voltage Is Deadly ........................................................................................... 5
1.5 Engine Exhaust Is Deadly ...................................................................................................... 5
1.6 Fuel and Fumes Are Flammable ............................................................................................ 6
1.7 Batteries Can Explode............................................................................................................ 6
1.8 Starting Batteries .................................................................................................................... 7
1.9 Moving Parts Can Cause Severe Personal Injury or Death .................................................. 7
1.10 The Hazards of Carbon Monoxide........................................................................................ 8
2. INTRODUCTION............................................................................................................................ 9
2.1 About This Manual.................................................................................................................. 9
2.2 Schedule of Abbreviations...................................................................................................... 9
2.3 Related Literature ................................................................................................................. 11
2.4 Before Installation ................................................................................................................. 12
2.5 Model Specifications............................................................................................................. 13
3. PRE-INSTALLATION CONSIDERATIONS.................................................................................. 17
3.1 Pre-Installation Considerations Introduction......................................................................... 17
3.2 Installation Codes and Standards for Safety ........................................................................ 18
3.3 Required Items for Installation.............................................................................................. 20
4. INSTALLATION............................................................................................................................ 27
4.1 Site Assessment and Preparation ........................................................................................ 27
4.2 Fuel Selection and Fuel System Connection........................................................................ 31
4.3 Engine Exhaust..................................................................................................................... 43
4.4 Electrical Connections .......................................................................................................... 44
5. STARTUP AND CONFIGURATION............................................................................................. 55
5.1 "Establishing Communications" Message ............................................................................ 55
5.2 "Clock Setup" Screen............................................................................................................ 55
5.3 "Exercise" Screen ................................................................................................................ 61
5.4 "Brightness and Contrast" Screen ........................................................................................ 64
5.5 "About" Screen...................................................................................................................... 66
5.6 "Event Log" Screen............................................................................................................... 68
5.7 "Fault Log" Screen................................................................................................................ 69
5.8 "System Status" Screen........................................................................................................ 70
5.9 "Mode" Screen...................................................................................................................... 71
5.10 Automatic Load Management............................................................................................. 74
5.11 Manual Start Sequence (Local).......................................................................................... 75
5.12 Checklist ............................................................................................................................. 75
iA053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 4
Table of Contents 12-2016
5.13 Startup ............................................................................................................................... 78
6. OPTIONAL REMOTE MONITORING SYSTEM (RMS) DESCRIPTION ..................................... 79
6.1 Introduction .......................................................................................................................... 79
6.2 Optional Remote Monitoring System (RMS) Account Setup and Generator Set Control
Connection ............................................................................................................................ 80
APPENDIX A. FUEL LINE SELECTION........................................................................................... 81
A.0 Fuel System Pipe Sizing Introduction................................................................................... 82
A.1 Gas Pipe Sizing.................................................................................................................... 83
APPENDIX B. OUTLINE AND SYSTEM DRAWINGS...................................................................... 95
APPENDIX C. WIRING DIAGRAMS............................................................................................... 101
C.0 Wiring Diagrams................................................................................................................. 102
ii A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 5

1 Important Safety Instructions

1.1 Save These Instructions

This manual contains important instructions for the generator set that should be followed during installation, operation and maintenance of the generator set and batteries.
Thoroughly read the operator manual before operating the generator set. Safe operation and top performance can only be obtained when equipment is properly operated and maintained.
The following symbols in this manual alert you to potential hazards to the operator, service person and equipment.
DANGER
Alerts you to an immediate hazard that will result in severe personal injury or death.
WARNING
Alerts you to a hazard or unsafe practice that can result in severe personal injury or death.
Alerts you to a hazard or unsafe practice that can result in personal injury or equipment damage.

1.2 General Information

This manual should form part of the documentation package supplied by Cummins Power Generation with specific generator sets. In the event that this manual has been supplied in isolation please contact your authorized dealer.
It is in the operator's interest to read and understand all warnings and cautions contained in the documentation relevant to the generator set operation and daily maintenance.

1.3 General Precautions

• Keep ABC fire extinguishers accessible.
CAUTION
NOTICE
• Make sure that all fasteners are secure and torqued properly.
1A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 6
1. Important Safety Instructions 12-2016
• Keep the generator set and its compartment clean. Do not store any items in the generator set compartment.
• Before working on the generator set, make sure the generator set is shut down and disabled.
1. Press the generator set's "O" (Off) button or the red STOP button on the local display (whichever is applicable) to stop the generator set. Allow the generator set to thoroughly cool to the touch.
2. If applicable, turn off and disconnect the battery charger from the AC source before disconnecting the battery cables.
3. Disconnect the negative (–) cable from the battery and secure it from contacting the battery terminals to prevent accidental starting.
• Use caution when making adjustments when the generator set is running, hot, or when parts are electrically live, as all situations may cause personal injury or death.
• Used engine oil has been identified by some state and federal agencies as causing cancer or reproductive toxicity. Do not ingest, inhale, or come into contact with used oil or its vapors.
• Do not work on the generator set when mentally or physically fatigued or after consuming alcohol or drugs.
NOTICE
Only trained and authorized personnel shall maintain or service the generator set.
NOTICE
The installation of the generator set shall provide enough ventilation to ensure that gases generated by vented batteries during charging, or caused by equipment malfunction, are removed.
General Safety Precautions
WARNING
Hazardous Voltage Contact with high voltages can cause severe electrical shock, burns, or
death. Make sure that only a trained and experienced electrician makes generator
set electrical output connections, in accordance with the installation instructions and all applicable codes.
2 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 7
1. Important Safety Instructions12-2016
WARNING
Electrical Generating Equipment Faulty electrical generating equipment can cause severe personal injury or
death. Generator sets must be installed, certified, and operated by trained and
experienced person in accordance with the installation instructions and all applicable codes.
WARNING
Moving Parts Moving parts can cause severe personal injury. Use extreme caution around moving parts. All guards must be properly
fastened to prevent unintended contact.
WARNING
Toxic Hazard Used engine oils have been identified by some state and federal agencies to
cause cancer or reproductive toxicity. Do not ingest, breathe the fumes, or contact used oil when checking or
changing engine oil. Wear protective gloves and face guard.
WARNING
Electrical Generating Equipment Incorrect operation and maintenance can result in severe personal injury or
death. Do not operate equipment when fatigued, or after consuming any alcohol or
drug. Make sure that only suitably trained and experienced service personnel
perform electrical and/or mechanical service.
WARNING
Toxic Gases Substances in exhaust gases have been identified by some state and federal
agencies to cause cancer or reproductive toxicity. Do not breathe in or come into contact with exhaust gases.
WARNING
High Noise Level Generator sets in operation emit noise, which can cause hearing damage. Wear appropriate ear protection at all times.
3A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 8
1. Important Safety Instructions 12-2016
WARNING
Hot Surfaces Contact with hot surfaces can cause severe burns. Wear appropriate PPE when working on hot equipment and avoid contact
with hot surfaces.
WARNING
Combustible Liquid Ignition of combustible liquids is a fire or explosion hazard which can cause
severe burns or death. Do not store fuel, cleaners, oil, etc., near the generator set. Do not use
combustible liquids like ether.
WARNING
Combustible Gases Generator sets in operation have combustible gases under pressure, which
if ignited can cause eye and ear damage.
• Wear appropriate eye and ear protection at all times.
• Do not operate the generator set with any doors open.
WARNING
Fire Hazard Materials drawn into the generator set, as well as accumulated grease and
oil, are a fire hazard. Fire can cause severe burns or death. Keep the generator set and the surrounding area clean and free from
obstructions. Make sure the generator set is mounted in a manner to prevent combustible materials from accumulating under the unit.
WARNING
Automated Machinery Accidental or remote starting of the generator set can cause severe personal
injury or death. The generator set must be off and locked out of service whenever the air
inlet, air outlet, or any interior panels are removed.
WARNING
Automated Machinery Accidental or remote starting of the generator set can cause severe personal
injury or death. Isolate all auxiliary supplies and use an insulated wrench to disconnect the
starting battery cables (negative [–] first).
4 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 9
1. Important Safety Instructions12-2016
NOTICE
Keep multi-class ABC fire extinguishers handy. Class A fires involve ordinary combustible materials such as wood and cloth. Class B fires involve combustible and flammable liquid fuels and gaseous fuels. Class C fires involve live electrical equipment. (Refer to NFPA No. 10 in applicable region.)
NOTICE
Before performing maintenance and service procedures on enclosed generator sets, make sure the service access doors are secured open.
NOTICE
Stepping on the generator set can cause parts to bend or break, leading to electrical shorts, or to fuel, coolant, or exhaust leaks. Do not step on the generator set.

1.4 Generator Set Voltage Is Deadly

• Generator set output connections must be made by a trained and experienced electrician in accordance with all applicable codes.
• This generator set and the public utility may only be connected to house circuits by means of the automatic transfer switch.
CAUTION
Improper connections can lead to electrocution of utility workers and damage to equipment. Make sure that the connections are installed properly by a trained technician.
• Use caution when working on live electrical equipment. Remove jewelry, and make sure clothing and shoes are dry. Stand on a dry wooden platform.

1.5 Engine Exhaust Is Deadly

• See The Hazards of Carbon Monoxide to learn the symptoms of Carbon Monoxide poisoning.
• Locate the generator set away from doors, windows, other openings into the house, and where exhaust gases will disperse away from the house.
5A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 10
1. Important Safety Instructions 12-2016

1.6 Fuel and Fumes Are Flammable

Fire, explosion, and personal injury or death can result from improper practices.
• DO NOT permit any flame, cigarette, pilot light, spark, arcing equipment, or other ignition source near the generator set or fuel system.
• Fuel lines must be adequately secured and free of leaks. Fuel connection at the engine should be made with an approved flexible line. Do not use copper piping on flexible lines because copper will become brittle if continuously vibrated or repeatedly bent.
• Be sure all fuel supplies have a positive shutoff valve.
• Be sure the battery area has been well-ventilated prior to servicing near it. Lead-acid batteries emit a highly explosive hydrogen gas that can be ignited by arcing, sparking, smoking, etc.

1.7 Batteries Can Explode

Batteries can explode, causing severe skin and eye burns and can release toxic electrolytes.
WARNING
Combustible Gases Batteries can explode, causing severe skin and eye burns, and can release
toxic electrolytes. Do not dispose of the battery in a fire, because it is capable of exploding. Do
not open or mutilate the battery.
WARNING
Electric Shock Hazard Batteries present the risk of high short circuit current. Remove watches, rings, or other metal objects. Use tools with insulated
handles.
NOTICE
Servicing of batteries must be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
• Wear safety glasses.
• Do not smoke.
• To prevent arcing when disconnecting the battery:
1. Press the Off switch from the display and then press the E-Stop button.
2. Disconnect AC power from any battery chargers.
6 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 11
3. Remove the negative (-) battery cable to prevent starting.
• To prevent arcing when reconnecting the battery:
1. Reconnect the positive (+) cable.
2. Reconnect the negative (-) cable.
3. Reconnect the battery charger to AC power supply.
• When replacing the generator set battery, always replace it with a battery as specified in this manual.

1.8 Starting Batteries

Toxic Hazard The electrolyte in starting batteries is a dilute sulfuric acid that is harmful to
the skin and eyes. It is also electrically conductive and corrosive. Always:
1. Wear full eye protection and protective clothing;
2. If the electrolyte contacts the skin, wash it off immediately with water;
3. If the electrolyte contacts the eyes, flush them thoroughly and
immediately with water and seek medical attention; and
4. Wash spilled electrolyte down with an acid neutralizing agent. A
common practice is to use a solution of one pound (500 grams) bicarbonate of soda (also known as baking soda or sodium bicarbonate) to one gallon (4 liters) of water.
5. Continue to add the bicarbonate of soda solution until the evidence of
reaction (that is, foaming) has stopped.
6. Flush the resulting liquid with water and dry the area.
1. Important Safety Instructions12-2016
WARNING

1.9 Moving Parts Can Cause Severe Personal Injury or Death

• Do not wear loose clothing or jewelry near moving parts, such as fans.
• Keep hands away from moving parts.
• Keep guards in place over fans.
7A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 12
1. Important Safety Instructions 12-2016

1.10 The Hazards of Carbon Monoxide

Carbon monoxide (CO) is an odorless, colorless, tasteless and non-irritating gas. You cannot see it or smell it. Red blood cells, however, have a greater affinity for CO than for oxygen. Therefore, exposure even to low levels of CO for a prolonged period can lead to asphyxiation (lack of oxygen) resulting in death. Mild effects of CO poisoning include eye irritation, dizziness, headaches, fatigue and the inability to think clearly. More extreme symptoms include vomiting, seizures and collapse.
Engine-driven generator sets produce harmful levels of carbon monoxide that can injure or kill you.
Special Risks of CO near the Home
WARNING
Toxic Gases Carbon monoxide (CO) gas can cause nausea, fainting, or death. Residents
can be exposed to lethal levels of CO when the generator set is running. Depending on air temperature and wind, CO can accumulate in or near the home.
To protect yourself and others from the dangers of CO poisoning, it is recommended that reliable, approved, and operable CO detector alarms are installed in proper locations in the home as specified by their manufacturer.
Protecting Yourself from CO Poisoning
• Locate the generator set in an area where there are no windows, doors, or other access points into the home.
• Make sure all CO detectors are installed and working properly.
• Pay attention for signs of CO poisoning.
• Check the exhaust system for corrosion, obstruction, and leaks every time you start the generator set and every eight hours when you run it continuously.
8 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 13

2 Introduction

2.1 About This Manual

Improper installation can result in severe personal injury, death and damage to equipment. The installation must comply with all applicable building codes (including project permits and inspections). The installer should be properly trained and licensed to perform electrical and mechanical equipment installations (including gaseous fuel installation).
Manuals are updated from time to time to reflect changes in the equipment and its specifications. The most up-to-date version of this manual is found on the QuickServe website (https://quickserve.cummins.com/info/index.html).
This manual is a guide for the installation of the generator set models listed on the front cover. Proper installation is essential for top performance, reliable operation, and safety. Read through this manual before starting the installation. This manual covers outdoor applications only; this product must never be installed indoors.
WARNING
NOTICE
NOTICE
The installation must comply with all applicable building codes.
See the generator set's specific Operator Manual for operation and maintenance and specific Service Manual for service.
Refer to the Model Specifications section for specific information about the system and its components.
Refer to the Outline and System Drawings appendix and the Wiring Diagrams appendix for specific information about installation and wiring connections.

2.2 Schedule of Abbreviations

This list is not exhaustive. For example, it does not identify units of measure or acronyms that appear only in parameters, event/fault names, or part/accessory names.
Abbr. Description Abbr. Description
AC Alternating Current LED Light-Emitting Diode AMP AMP, Inc. (part of Tyco
Electronics)
MFM Multifunction Monitor
9A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 14
2. Introduction 12-2016
Abbr. Description Abbr. Description
ANSI American National
Mil Std Military Standard
Standards Institute ASOV Automatic Shut Off Valve MPU Magnetic Pickup ASTM American Society for
NC Normally Closed Testing and Materials (ASTM International)
ATS Automatic Transfer
NC Not Connected Switch
AVR Automatic Voltage
Regulator
NFPA National Fire Protection
Agency AWG American Wire Gauge NO Normally Open CAN Controlled Area Network NWF Network Failure CB Circuit Breaker OEM Original Equipment
Manufacturer CE Conformité Européenne OOR Out Of Range CCA Cold Cranking Ampere OORH/
Out Of Range High
ORH CFM Cubic Feet per Minute OORL/ORL Out Of Range Low CGT Cummins Generator
PB Push Button
Technologies CMM Cubic Meters per Minute PCC PowerCommand®Control CT Current Transformer PGI Power Generation
Interface
DC Direct Current PGN Parameter Group
Number DEF Diesel Exhaust Fluid PI Proportional/Integral DPF Diesel Particulate Filter PID Proportional/Integral/
Derivative EBS Excitation Boost System PLC Programmable Logic
Controller ECM Engine Control Module PMG Permanent Magnet
Generator ECS Engine Control System PPE Personal Protective
Equipment EMI Electromagnetic
Interference
PT Potential Transformer
10 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 15
2. Introduction12-2016
Abbr. Description Abbr. Description
EN European Standard PTC Power Transfer Control EPS Engine Protection
System
E-Stop Emergency Stop RFI Radio Frequency
FAE Full Authority Electronic RH Relative Humidity FMI Failure Mode Identifier RMS Remote Monitoring
FSO Fuel Shutoff RMS Root Mean Square Genset Generator Set RTU Remote Terminal Unit GCP Generator Control Panel SAE Society of Automotive
GND Ground scfh Standard Cubic Feet of
HMI Human-Machine
Interface
IC Integrated Circuit SPN Suspect Parameter
PWM Pulse-Width Modulation
Interference
System
Engineers
gas per Hour
SCR Selective Catalytic
Reduction
Number ISO International Organization
for Standardization
LBNG Lean-Burn Natural Gas UL Underwriters
LCD Liquid Crystal Display UPS Uninterruptible Power
LCT Low Coolant
Temperature

2.3 Related Literature

Before any attempt is made to operate the generator set, the operator should take time to read all of the manuals supplied with the generator set and familiarize themselves with the warnings and operating procedures.
SW_B+ Switched B+
Laboratories
Supply
11A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 16
2. Introduction 12-2016
NOTICE
A generator set must be operated and maintained properly if you are to expect safe and reliable operation. The Operator manual includes a maintenance schedule and a troubleshooting guide.
The Health and Safety manual must be read in conjunction with this manual for the safe operation of the generator set, as well as the Warranty Statements.
The literature provided with the generator set is as follows:
• Installation Manual (A053X172)
• Operator Manual (A053X174)
• Quick Start Installation Guide (A053X181)
• Quick Start Operator Guide (A053X183)
• Health and Safety Manual (0908-0110-00)
• Global Warranty Statement (A056F206)
• Emission Warranty Statement (Federal Emissions EPA Title 40 CFR Part 90 Component Warranty) (A028X278)
The relevant manuals appropriate to your generator set are also available. The documents below are in English:
• Generator Set Service Manual (A053X177)
• RA Series RA112L1 Automatic Transfer Switch Owner Manual (A052S254) - if applicable
• RA Series 100A/200A/400A Automatic Transfer Switch Owner Manual (A046S594) - if applicable
• Parts Manual (A053X179)
• Standard Repair Times - HO Family (A053X186)
• Service Tool Manual (A043D529)
• Warranty Failure Code Manual (F1115C)
• Engineering Application Manual T-030: Liquid Cooled Generator Sets (A040S369)

2.4 Before Installation

Before beginning the installation of the generator set, verify that the unit was correctly selected. Check the following features:
• Model
• Specifications
• Options
12 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 17
• Fuel Supply
The gas supplied to the generator set must be of acceptable quality.The gas supply must have sufficient pressure. Care must be taken to be
sure that the gas supply at the generator set, not just at the source, is of proper pressure for operation. The specified pressure must be available while the generator set is starting and running at full load.
The gas must be supplied to the generator set in sufficient volume to
support operation of the generator set. This is normally a matter of selecting fuel line size to be large enough to transport the volume of fuel needed. For liquid propane vapor-withdrawal fuel systems the size and temperature of the fuel tank also affects this requirement.

2.5 Model Specifications

TABLE 1. MODEL VARIATIONS
2. Introduction12-2016
Model
C13N6H Both 13 54.2 C17N6H Both 17 70.8
C20N6H,
C20N6HC
Maximum load imbalance allowed is 50% of generator set rating.
TABLE 2. COLD WEATHER SPECIFICATIONS (ALL MODELS)
Temperature Description
Above 40 °F (4 °C) No starting aids required 0 to 40 °F (-17 to 4 °C) Alternator heater (supplied with the generator set)
Natural Gas or
Propane Vapor
Natural Gas Only 18 75
Propane Vapor
Only
kW Amps Frequency Voltage
20 83.3
NOTICE
60 Hz
120/240 VAC Single Phase
Below 0 °F (-17 °C)
• Alternator, battery, oil and regulator heaters
• 0W30 oil (see Lubricating Oil System Specifications)
• Accessory kit available
13A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 18
2. Introduction 12-2016
TABLE 3. FUEL SPECIFICATIONS (AT FULL LOAD) (ALL MODELS)
C13N6H C17N6H C20N6H, C20N6HC
Type
scfh BTU/hr scfh BTU/hr scfh BTU/hr
Natural Gas 253 260,000 289 297,000 300 309,000 Propane 85 212,000 101 252,000 116 290,000
Natural Gas: 3.5 - 12 inch water column (0.9 - 3.0 kPa)
Fuel Pressure
Propane Vapor: 6 - 12 inch water column (1.5 - 3.0 kPa) Maximum pressure for either fuel under any condition: 13 inch water
column (3.2 kPa)
TABLE 4. ENGINE SPECIFICATIONS (ALL MODELS)
Type Value
Engine
2 cylinder v-twin, OHV, air-cooled, 4-stroke, spark
ignited Displacement 999 cc (60.9 in3) Spark Plug Gap 0.7 - 0.8 mm (0.027 - 0.031 in) Spark Plug Torque (Cold Engine) 25 - 30 Nm (18 - 22 ft-lb) RPM 3600 Lubricating Oil Pressure at Rated
Speed (Minimum)
45 psi (310 kPa)
Full synthetic gasoline engine oil which meets or
exceeds API service SN/SN-RC and ILSAC GF-5: Oil Recommendation
• 5W30: Temperatures above 0 °F (-18 °C)
• 0W30: All temperatures, required below 0 °F (-18 °C)
Lubricating Oil Capacity:
Lubricating Oil Pressure at Rated Speed (Minimum)
310 kPa (45 psi)
--Full at High Mark on Dipstick 2.3 L (2.4 qt)
--Low Mark on Dipstick 1.3 L (1.4 qt)
14 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 19
Model
2. Introduction12-2016
TABLE 5. GENERATOR SET SIZE (ALL MODELS)
Dimension Value
Length 877 mm (34.5 in) Width 915 mm (36 in) Height 694 mm (27.3 in)
TABLE 6. GENERATOR SET WET WEIGHT (INCLUDING BATTERY)
Model Value
C13N6H 218 kg (479 lb) C17N6H, C20N6H, C20N6HC 241 kg (531 lb)
TABLE 7. GENERATOR SET DERATING GUIDELINES
Engine Power Available Up To... Derate At…
Elevation Ambient Temperature Elevation Temperature
C13N6H 2100 m (6900 ft) 25 °C (77 °F) C17N6H 300 m (1000 ft) 25 °C (77 °F)
C20N6H,
C20N6HC
0 m (0 ft) 15 °C (60 °F)
NOTICE
Derating guidelines: This product's output power is limited by factors such
as BTU content of fuel, ambient temperature, altitude, humidity, engine condition, etc. The derating guidelines are based on properly maintained product, using the appropriate fuel. Derate values are based on expected engine power changes from elevation and temperatures listed.
TABLE 8. ALTERNATOR SPECIFICATIONS (ALL MODELS)
Type Specification
Design Rotating field
Poles 2
3.5% per 300 m
(1000 ft)
1% per
5.5 °C (10 °F)
RPM 3600
Voltage 240
Hz 60
15A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 20
2. Introduction 12-2016
TABLE 9. CONTROL SPECIFICATIONS (ALL MODELS)
Control
Integrated Microprocessor-Based Engine, Alternator, Transfer Switch Controller
TABLE 10. DC SYSTEM SPECIFICATIONS (ALL MODELS)
Type Value
Nominal Battery Voltage 12 VDC Battery Group 51 R Battery Type Lead Acid Minimum Cold Crank Amps (CCA) 450
16 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 21

3 Pre-Installation Considerations

3.1 Pre-Installation Considerations Introduction

WARNING
The installer is responsible for complying with all applicable installation codes and safety requirements. See the Installation Codes and Standards for Safety section of this manual for more information.
The following sections create a step-by-step overview of a typical generator set installation. Review these sections to become familiar with specific procedures and important safety before beginning the installation.
NOTICE
For information on tools and materials, see the Required Items for Installation section. For information on locating the generator set, see the Installation section. For codes and standards, see the Installation Codes and Standards for Safety section. For specifications, see the Model Specification section.
Areas of consideration:
• Location of the generator set: this is one of the first decisions to be made, as it affects all other aspects of the installation, such as:
Length of electric wiringLength of gas lines (natural gas or propane - must be inspected by the gas
utility inspectors and building inspectors)
Site preparation:
Access to the siteTrenchesSite preparation materials needed
• Fuel supply pressure
• Automatic transfer switch location and connections
• Tools and materials required
• Minimum distance from the propane tank fill:
Verify the legal minimum distance with local code officials.Verify the minimum distance from the service pressure regulator to the
generator set.
17A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 22
3. Pre-Installation Considerations 12-2016
Verify any minimum clearance requirements to the generator set that the
gas supplier or equipment supplier may have.
• Accessories required (if any) for the customer's application (utility power is required at the generator set for the battery charger and may be required for the heaters; make plans accordingly)
NOTICE
Depending on the locality and use of the generator set, it may be necessary to obtain an air quality emissions permit before installation begins. Check with local pollution control or air quality authority to determine permit requirements.

3.2 Installation Codes and Standards for Safety

NOTICE
The generator set installer bears sole responsibility for following all applicable local codes and regulations.
The following list of codes and standards may apply to the installation and operation of the generator set. This list is for reference only and not intended to be inclusive of all applicable codes and standards. The address of each agency is listed so that copies of the codes may be obtained for reference. Installation codes and recommendations are subject to change, and may vary by location or over time.
TABLE 11. INSTALLATION CODES AND STANDARDS FOR SAFETY
RECOMMENDATIONS
Code or Standard Organization
NFPA 37 - Installation and Use of Stationary Combustion Engines and Gas Turbines
NFPA 54 - National Fuel Gas Code NFPA 58 - Storage and Handling of Liquefied
Petroleum Gases NFPA 70 - National Electrical Code
CSA Electrical Bulletin CSA 22.1 Canadian Electrical Code CSA B149 CSA C22.2 No. 100 CSA C22.2 No. 14
National Fire Protection Association 470 Atlantic Avenue Boston, MA 02210
Canadian Standards Association Housing and Construction Materials
Section 178 Rexdale Blvd. Rexdale, Ontario, Canada M9Q 1R3
18 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 23
3. Pre-Installation Considerations12-2016
Code or Standard Organization
California Administrative Code - Title 25 Chapter 3 State of California
Documents Section P.O. Box 1015 North Highlands, CA 95660
Operating the Generator Set Cover Safely
To configure the local display or access the generator set, you will need to lift the cover (lid). The cover of the generator set is designed to latch securely into the "up" position to prevent accidental closure.
To open: Lift the cover until the hinge pin drops into the hinge pin slot. Test that the cover is secure by gently pressing down on the cover.
To close: Lift up on the cover while pressing upward on the hinge pin and slide the pin upwards out of the hinge pin slot. Carefully push the cover downward and let go of the hinge pin allowing it to ride along the hinge until the cover is closed.
19A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 24
3. Pre-Installation Considerations 12-2016
FIGURE 1. HINGE LOCATION

3.3 Required Items for Installation

Tools and materials are used for the installation of this generator set. These items are identified in the following sections. Please refer to local codes and standards, because they may affect the materials required.
Materials Required
NOTICE
Refer to local codes and standards, which may affect material requirements.
20 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 25
3. Pre-Installation Considerations12-2016
NOTICE
A UL-listed grounding electrode terminal within its ratings and suitable for the application must be installed and labeled “Grounding Electrode Terminal”.
NOTICE
Class 1 wiring methods must be used for connecting the generator set.
TABLE 12. MATERIALS REQUIRED
Requirement Specification
Electrical Materials
Code compliant AC power wires Four (L1, L2, N and Gnd) For accessories (alternator heater, oil heater, battery heater,
and/or regulator heater) (if equipped)
Code compliant 20 A, 120 VAC, GFCI protected circuit, copper wire only
RA switches only: Control wires from the generator set to the
Four DC wires
transfer switch Ethernet cable for Internet installation (as required) Cat 5, Cat 5e or Cat 6 All AC and DC wire and cable ratings Must be 75 °C minimum with
600 V minimum insulation, stranded copper, rated for wet
1
Wire sizes (for all DC customer connections): Under 1000 ft
locations. 18-14 AWG
wire length Conduit Code compliant for all wires
Mounting Materials
Bolts or anchor assemblies Two base tie-down
Fuel System Materials
Fuel line Flexible Pipe thread sealant UL listed Fuel service pressure regulator (as required) -­Manual fuel shut-off at generator set ahead of automatic
--
valves on generator set fuel system
Remote Display Materials (if Applicable)
Remote display --
21A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 26
3. Pre-Installation Considerations 12-2016
Requirement Specification
Hardware, Cummins provided:
Pigtail harnesses Two (one for local display and
one for remote display); 5­wire (RS485-A2, RS485-B2, B+, WAKEUP and B-), 1 ft long each
Hardware, customer provided: Intermediate wires of required
Five wires, 600V insulation length to connect to the pigtail harnesses using splices provided in the remote display kit
Wire sizes (RS485-A2,
Under 1000 ft wire length 20-14 AWG
RS485-B2, B+, WAKEUP): Wire sizes (B+ and B-): Under 100 ft wire length 18 AWG
Under 200 ft wire length 16 AWG Under 300 ft wire length 14 AWG
Hardware, Miscellaneous If wires can be concealed in a
wall cavity: If wires cannot be concealed
in a wall cavity:
3 wall anchors and screws
(number 6 or number 8)
3 wall anchors and screws
(number 6 or number 8),
standoffs, and conduit or wire
raceway
1
300V insulation is acceptable for Ethernet and DC cables if routed in a separate conduit
from AC wiring.
2
Use twisted pair wires for RS485-A and RS485-B wires.
1, 2
Tools Required
Use appropriate lifting techniques to position the generator set in place.
Transfer Switch Requirements
A transfer switch must be a part of every generator set installation. Transfer switches transfer loads to the generator set during power outages.
NOTICE
Cummins offers a variety of transfer switches, including residential and light commercial options.
22 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 27
3. Pre-Installation Considerations12-2016
FIGURE 2. CUMMINS AUTOMATIC TRANSFER SWITCH (ATS)
Before beginning the installation of the transfer switch, verify that the unit was correctly selected. Check the following features:
• Specifications (voltage, amperage, frequency, poles, and phases)
• Enclosure (indoor vs. outdoor)
• Model
Cummins recommends that any RA series transfer switch be used with these generator sets. Refer to the appropriate RA series ATS owner manual for more detailed information.
Choosing a Transfer Switch
This section includes block diagrams showing partial or full load coverage for the following Cummins UL 1008 listed transfer switches:
TABLE 13. CUMMINS TRANSFER SWITCH MODELS
Model Non-Service Entrance Service Entrance
RA 100A RA 200A RA 400A
RA112L1
23A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 28
3. Pre-Installation Considerations 12-2016
NOTICE
These generator sets can be used with either service entrance transfer switches or non-service entrance transfer switches.
NOTICE
If the load exceeds the generator set rating, it may be necessary to use Cummins’ load management kit (A051C329).
FIGURE 3. TRANSFER SWITCH CONNECTIONS FOR PARTIAL COVERAGE LOAD
24 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 29
3. Pre-Installation Considerations12-2016
FIGURE 4. TRANSFER SWITCH CONNECTIONS FOR FULL COVERAGE LOAD
Loose Parts Shipped with the Generator Set
The following loose parts are shipped with the generator set:
• Two enclosure keys
• Generator set mounting spacers
• Circuit breaker cover and screw
• Chassis plugs
• Transfer switch TB4 jumper
NOTICE
This jumper must be installed in the RA series transfer switch according to the interconnect diagram in the RA series transfer switch owner manual.
• Literature (Operator Manual, Quick Start Operator Guide, Installation Manual, Quick Start Installation Guide, Health and Safety Manual, and Warranty Statements)
25A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 30
3. Pre-Installation Considerations 12-2016
This page is intentionally blank.
26 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 31

4 Installation

4.1 Site Assessment and Preparation

Proper component location and site preparation have a very important impact on completing a successful installation. The major components and sources of power needed for installation include the following items:
• Generator set
• Transfer switch
• Electrical utility
• Fuel source
• Accessories (may be required under certain conditions)
Generator Set Installation Suggestions and Guidelines
• Locate the generator set on stable ground, not subject to flooding. Generator set should not be installed where significant water runoff from a roof or downspouts is present. Sump pump discharge should be routed away from the generator set.
• Locate and orient the generator set such that prevailing winds will carry exhaust gases and fuel leaks away from the house or occupied areas.
• This unit is to be installed so that the risk of contact by people is minimized.
Picking a Location
WARNING
Exhaust gas is deadly. Install the generator set outdoors only. Locate the generator set away from doors, windows, and other openings to the house and where exhaust gases will disperse away from the house or occupied areas.
NOTICE
All parts of the generator set enclosure must be at least 60 inches (1524 mm) from any openings in walls of structures that may be occupied.
Generator set location is critical for safety and performance. Follow the guidelines below:
• The installation must comply with all applicable codes and standards (NFPA, NEC, IBC, etc.).
• This manual only covers outdoor installations with Cummins factory installed enclosures. This product must never be installed indoors.
27A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 32
4. Installation 12-2016
• Consider access to utilities (electric meters, transfer switch, fuel supply line and fuel tank, etc.).
• Call the local utilities to mark the locations of buried utility services (gas, electric, telephone, etc.) before digging.
• Verify the locations of any other buried components (gas, electric telephone, etc.) with the homeowner before digging.
• Consideration should be given to the location of sprinkler heads for irrigation systems. The generator set should not be located where it is subjected to substantial wetting (especially on the inlet air side) when the irrigation system is in operation.
• Always install this generator set service regulator above the snow line.
Follow the clearance requirements below (refer to the Outline and System Drawings appendix):
• All parts of the generator set enclosure must be at least 60 inches (1524 mm) from any openings in walls of structures that may be occupied. Examples of wall openings include but are not limited to: operable windows, doors, dryer vents, fresh air intake for heaters, etc.
• The engine side and alternator side of the generator set must be located as follows:
One side (either engine or alternator) must be located not less than 18
inches (458 mm) from any structures having combustible walls. This space must be free of any obstructions for service access.
The opposite side must be located not less than 60 inches (1524 mm) from
any structures having combustible walls. A minimum of 18 inches (458 mm) of unobstructed space is required for service access.
• The intake (cooling air inlet) side of the generator set must be located not less than 30 inches (762 mm) from any structures having combustible walls. This space must be free of obstructions to air flow and service access.
• The generator set must be located such that exhaust gases are not able to accumulate in an occupied area. The air discharge side must always be unobstructed and spaced a minimum of 60 inches (1524 mm) from any structures having combustible walls. A minimum of 36 inches (915 mm) must be free of any combustible items, and unobstructed for service access.
• The generator set must have enough room for installation, service, and maintenance.
• The generator set must be located to ensure ventilation openings are not blocked.
• Position the generator set so that cooling air is free to enter and leave the area.
• Locate and position the generator set so that prevailing winds carry exhaust gases and potential fuel leaks away from the house or occupied area.
28 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 33
4. Installation12-2016
Preparing the Generator Set Mounting Surface
Cummins recommends the generator set be installed on a non-combustible mounting pad (available as an accessory) or a poured concrete slab. The surface beneath the mounting surface must be properly prepared to minimize the risk of the generator set settling and causing undue stress on the fuel system or electrical connections. The surface preparation is the same when preparing the site for installing on the accessory mounting pad or poured slab.
Cummins recommends the generator set be installed above grade for easier maintenance, and lower risk of submersion in water.
1. Clear obstructions and make sure that there is adequate clearance for access to the site.
2. Ensure that the ground is stable and is not subject to flooding.
3. Level the ground, and make sure that the subgrade is compacted and settled. Local soil condition may dictate the need for addition of sub-base and base material layers above the subgrade. Consult with your local building officials for requirements and recommendations for your area.
4. Either pour a concrete slab or set an accessory mounting pad on the prepared surface. The poured concrete slab should be:
• Constructed of concrete with a 28-day compressive strength of at least 2500 psi (17,200 kPa); typical bagged concrete mix meets this requirement
• A minimum of 3 inches (76.2 mm) thick
• At least 2 inches (50.8 mm) larger in length and width than the generator set base
5. Place the generator set on the pad and secure it to the mounting surface using the mounting spacers (provided) and appropriate fasteners. See the Securing the Generator Set to the Mounting Pad section for more information.
Lifting and Moving the Generator Set
WARNING
Heavy Load The generator set is heavy. Handle with care. Dropping the generator set can cause severe personal injury or death. Use
appropriate lifting techniques to move the generator set. Keep feet and hands clear when lifting the generator set.
CAUTION
The generator set is shipped with oil in the engine crankcase. Keep the generator set upright.
29A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 34
4. Installation 12-2016
Securing the Generator Set to the Mounting Pad
The generator set should be securely attached to either a poured concrete slab or prefabricated mounting pad (accessory pad) made of non-combustible material.
NOTICE
An accessory mounting pad is available that includes ½ -13 UNC x 1.25 inch mounting holes located in the proper location for these generator sets. Two hex head cap screws (½-13 x 3 inch long) and flat washers are needed with this accessory pad.
1. Position the two spacers (which were shipped with the generator set) appropriately on the generator set base.
No. Description No. Description
1 Spacer Length (2.18 in [55.4 mm]) 2 Spacer Through-Hole Diameter (0.59
in)
FIGURE 5. MOUNTING SPACER
2. Prefabricated pad only: Install the bolts into the prefabricated pad and tighten. Torque value: 37 ft-lb (50 Nm).
3. Poured slab only:
a. Mark the location for the anchor bolts with the generator set in place. b. Install the anchor bolts per the manufacturer's recommendation for both
embedment and tightening torque.
30 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 35
4. Installation12-2016
NOTICE
There are several styles of anchor bolts available. Follow the anchor bolt manufacturer's requirements for hole size and depth. The length of the anchor bolt must accommodate:
• The embedment length of the bolt into the pad
• The length of the spacer
• The thickness of the washer and
• The thickness of the nut (if used)
4. Install the chassis plugs in the generator set's lifting holes after the unit is in its final position.

4.2 Fuel Selection and Fuel System Connection

This generator set has a convertible fuel system. The generator may run on natural gas or propane, depending on the preferences of the owner. All generator sets come preconfigured from the factory for natural gas fuel. For more information on converting the fuel system type, see the Service Manual.
NOTICE
Fuel systems must be installed by qualified service technicians. Improper installation presents hazards of fire and improper operation, resulting in severe personal injury or property damage.
NOTICE
In some jurisdictions fuel system installations to the generator set must be performed by licensed or registered personnel. Check with the authority having jurisdiction for requirements.
WARNING
Gaseous fuels are flammable, explosive, and can cause severe personal injury or death. Do not smoke if you smell gas, are near fuel tanks for fuel­burning equipment, or are in an area sharing ventilation with such equipment. Keep flames, sparks, pilot lights, electrical arcs, arc-producing equipment and all other sources of ignition well away. Keep a type ABC fire extinguisher handy.
In all fuel system installations, cleanliness is extremely important.
• Make every effort to prevent fuel contamination from:
MoistureDirt
31A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 36
4. Installation 12-2016
Excess thread sealantContaminants of any kind
• Clean all fuel system components before installing.
Gaseous-fuel supply system design, materials, components, fabrication, assembly, installation, testing, inspection, operation, and maintenance must comply with the applicable codes. See NFPA Standards No. 37, 54, and 58. If this is a seismic installation, refer to IBC codes and standards. Where seismic installation is required, there may be specific anchorage requirements for the generator set and other installed components.
Most codes require a manual shutoff valve ahead of a flexible fuel hose. The generator set includes electric (battery-powered) shutoff valves.
NOTICE
It is recommended that a shutoff valve be located near the generator set for emergency shut off or servicing the generator set. Follow applicable codes.
Until the generator set is connected, cap the fuel line stub-up at the generator set to prevent dirt from entering and gas from discharging if the gas supply shutoff valve is opened accidentally.
To determine the required capacity, refer to the Fuel Line Selection section.
Fuel Line Connections
WARNING
Fuel presents the hazard of fire or explosion that can result in severe personal injury or death. Do not smoke or allow any flame, spark, pilot light or other ignition sources near fuel or in the installation area. Read the important safety precautions in this manual.
1. Refer to the Outline and System Drawings appendix for the location of the fuel supply connection through the side of the generator set.
2. Install a flexible fuel hose, which must be used between the engine's fuel system and fuel supply line to protect the fuel system from damage caused by vibration, expansion and contraction. The fuel hose must be installed according to all applicable codes and standards.
Natural Gas Fuel System
WARNING
Fuel leaks can lead to explosive accumulations of gas. Prevent gas leaks and the accumulation of gaseous fuel in the event of a leak.
Requirements for a natural gas generator set are as follows:
32 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 37
4. Installation12-2016
TABLE 14. NATURAL GAS GENERATOR SET REQUIREMENTS
Component Description
Gas Pipeline quality Fuel Supply Adequate fuel supply to operate correctly and run at full load Shutoff Valve Manual Fuel Pipe Size The length of the fuel supply pipe from the gas service entrance to the
generator set must be known to determine the correct fuel pipe size. Refer to the charts in the Fuel Line Selection appendix.
Iron pipe must be a minimum of schedule 40 subject to the authority having jurisdiction.
Flexible Fuel Line Protects the fuel system from vibration, expansion, and contraction. Must
meet code requirements for application and be installed per manufacturer instructions.
33A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 38
4. Installation 12-2016
No. Description No. Description
1 Distance as Required by Code and/or
Component Suppliers
7 Secondary Service Pressure Regulator
(If Required) 2 Primary Service Pressure Regulator 8 Flexible Fuel Line 3 Natural Gas Supply 9 Sediment Trap 4 Gas Meter 10 Fuel Line Connection at Generator Set 5 Note: A branch in the fuel line to the
11 Generator Set generator set may allow selection of a smaller diameter line size to the generator set and remainder of gas appliances.
6 Full Flow Manual Shutoff Valve
FIGURE 6. TYPICAL NATURAL GAS INSTALLATION
Natural Gas Supply Line Size
See the Model Specifications section for fuel specifications (such as BTU/hr). The natural gas supply meter may need to be exchanged for a higher capacity
meter to supply the additional gas consumed by the generator set.
34 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 39
To correctly size the fuel pipe, you must also take other loads operated from the fuel supply line into consideration, such as space heating and water heating equipment.
Use the total fuel requirement of the generator set and other connected appliances to determine the size of the fuel supply pipe. Use the tables and charts in the Fuel Line Selection appendix to determine the correct pipe size.
The installation site might require upgrading and repair of the gas supply system. Schedule an upgrade or repair to minimize power and gas supply interruptions.
Make sure the full load fuel supply pressure at the inlet to the generator set fuel shutoff valves is set between 3.5 - 12 inch water column (0.9 - 3.0 kPa) for all operating loads (no load to full load). Refer to the Model Specifications section.
See the Natural Gas Fuel System section for an example of a typical natural gas installation.
Propane Fuel System
4. Installation12-2016
WARNING
Fuel leaks can lead to explosive accumulations of gas. Propane sinks in air and can accumulate inside housings, basements, and other below-grade spaces. Prevent gas leaks and the accumulation of gaseous fuel in the event of a leak.
NOTICE
NFPA Standard No. 58 requires all persons handling and operating propane to be trained in proper handling and operating procedures.
TABLE 15. REQUIRED COMPONENTS IN A PROPANE VAPOR FUEL SYSTEM
Component Description
Propane Tank Make sure to identify and use the correct tank size based on fuel flow
requirements and the lowest average temperature for your region. If the tank is sized incorrectly, the generator set could run out of fuel. Refer to the Minimum LPG Tank Size figure in the Fuel Line Selection appendix.
Shutoff Valve Useful during installation or in the event of a leak (may be required to
meet local codes).
Primary Pressure Regulator
Located at the tank outlet, the primary regulator reduces the tank pressure to the working pressure in the fuel supply line. Primary and secondary regulators must be properly matched for a safe and functional system. Consult with your propane supplier to ensure that the regulators are properly sized.
35A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 40
4. Installation 12-2016
Component Description
Secondary Pressure Regulator
Located near the generator set, the secondary regulator reduces the higher line pressure to a working pressure of 6 - 12 inch water column (1.5 - 3.0 kPa). Higher pressure before the secondary regulator is necessary to ensure that there is enough fuel available at the secondary regulator for a fully loaded generator set. Always install this generator set’s service regulator above the expected snow line.
Fuel Line Connects to the fuel supply. It must be sized properly using the propane
fuel line sizing charts (see the Fuel Line Selection appendix). Installation must comply with all national, state, and local codes.
Flexible Fuel Line Protects the fuel system from vibration, expansion, and contraction. Must
meet code requirements for application and be installed per manufacturer instructions.
36 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 41
No. Description No. Description
4. Installation12-2016
1 Distance as Required by Code and/or
6 Full Flow Manual Shutoff Valve
Component Suppliers
2 Secondary Service Pressure Regulator 7 Flexible Fuel Line 3 Primary Service Pressure Regulator 8 Sediment Trap 4 Liquid Propane Fuel Tank 9 Fuel Line Connection at Generator Set 5 Note: A branch in the fuel line to the
10 Generator Set generator set may allow selection of a smaller diameter line size to the generator set and the remainder of gas appliances.
FIGURE 7. TYPICAL PROPANE INSTALLATION
Propane Fuel Requirements
WARNING
Propane presents the hazard of fire or explosion that can cause severe personal injury or death. Do not permit any flame, spark, arc-producing equipment, switch, pilot light, cigarette, or other ignition source near the fuel system. Keep an ABC type fire extinguisher nearby.
WARNING
Fuel leaks can lead to explosive accumulations of gas. Propane sinks in air and can accumulate inside housings, basements and other below-grade spaces. Prevent gas leaks and the accumulation of gaseous fuel in the event of a leak.
37A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 42
4. Installation 12-2016
Use clean, fresh HD-5 grade propane or equivalent product consisting of at least 90% propane.
NOTICE
NFPA Standard No. 58 requires all persons handling and operating propane to be trained in proper handling and operating procedures.
NOTICE
Commercial propane may contain more than 2.5% butane, which can result in poor fuel vaporization and low tank pressure, resulting in poor engine starting and operation in below 32 °F (O °C) temperatures.
Propane Tank Size
When propane is used, size the tank correctly to ensure successful generator set operation.
Considerations when figuring the proper propane tank size:
• Temperature is a critical factor that affects the size of the tank. Ambient temperatures can affect how quickly liquid is converted to
gas.
Generator set fuel consumption is the same regardless of the
surrounding temperatures.
Colder weather climates require larger fuel tanks. Larger tanks have
greater surface area, allowing more liquid propane to vaporize and maintain the required fuel rate.
Propane is stored as liquid. Keep the fuel tank at least 50% full to
operate properly. Fuel tanks that are less than 50% full may not have the capacity to vaporize enough propane to operate the generator set and other LP appliances.
• Propane tanks are sized by their internal volume in gallons, not the
amount of fuel they can hold (which is less).
• Propane tanks are generally filled to only 80% of their capacity.
Therefore, a 500-gallon (1892 L) tank results in 400-gallon (1514 L) tank capacity.
• Low ambient temperatures affect the amount of fuel available from the
propane tank.
• Approximately 60% of the fuel (in gallons) filled in the tank can be
effectively used. Therefore, a 500-gallon (1892 L) tank results in 240­gallon (908 L) usable capacity.
38 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 43
4. Installation12-2016
To assist in the proper installation of the propane tank, follow the guidelines below.
• Consult your tank and propane supplier for assistance in all aspects of
determining tank size, selection of components and installation requirements.
• Fit the propane tanks with a pressure reducing regulator before
connection to the generator set to prevent fuel system damage.
• Locate the propane tanks and all other fuel system components at least
10 feet (3 meters) from any source of combustion (including the generator set). The fuel supplier or local code may require a larger distance between the tank and source of combustion.
• Install the propane tanks according to all national and local codes and
standards, and as required by the fuel tank and fuel supplier.
Refer to the Fuel Line Selection appendix for propane figures and tables.
Propane Vapor Fuel Supply Line Size and Pressure
Fuel line size depends on the amount of fuel needed to run the generator set at full load at the distance the fuel must be moved.
To correctly size the fuel pipe, you must also take other loads operated from the fuel supply line into consideration, such as space heating and water heating equipment.
Use the total fuel requirement of the generator set and other connected appliances to determine the size of the fuel supply pipe. Use the tables and charts in the Fuel Line Selection appendix to determine the correct pipe size.
See the Model Specifications section for fuel system specifications, including fuel consumption and required fuel system pressure at the generator set.
See the Propane Fuel System section for a typical propane vapor installation. See the Fuel Line Selection appendix for fuel capacity at given distances and
pipe size.
NOTICE
Make sure the fuel supply pressure at the inlet of the generator set fuel regulator (at service port) matches the requirements in the Model Specifications section.
39A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 44
4. Installation 12-2016
Converting the Fuel System Type
The generator set leaves the factory set up for natural gas. For operation on liquid propane vapor, the generator set must be converted by configuring the generator set control for propane and manually changing the fuel valve position from natural gas to propane.
1. To change the generator set control's fuel type from natural gas to liquid propane vapor:
a. From the Main screen, select Menu. b. Press and hold the Next key on the Menu screen for at least 5
seconds to view the Config Menu.
c. Use the arrow keys to highlight "Config" and click the Enter key. The
Generator Config screen appears.
d. Use the Next key to navigate to the Fuel Type field. Use the arrow
keys to select the fuel type: NG (natural gas; default) or LP (liquid propane).
NOTICE
Do not change the number in the Config field.
NOTICE
The Rating field is not configurable by the user. Instead, it will be automatically populated based on the Config and Fuel Type field selections.
e. Keep selecting the Back button to save the settings and return to the
Main screen.
40 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 45
4. Installation12-2016
FIGURE 8. GENERATOR CONFIG SCREEN
2. Adjust the manual fuel selector to the LP setting:
a. Use a 6 mm external hex wrench to rotate the center section of the
fuel valve. b. Turn the center section clockwise until the detent is reached. c. When you reach the detent, the required force to turn the valve will
increase significantly - do not rotate center section of valve beyond
this point.
41A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 46
4. Installation 12-2016
FIGURE 9. LOCATION OF FUEL SELECTOR VALVE
No. Description No. Description
1 Natural Gas Fuel Position 2 Liquid Propane Vapor Fuel Position
FIGURE 10. MANUAL FUEL SELECTOR
Testing the Fuel System for Leaks
After assembly and before initial operation, all of the fuel system components must be tested and proven free of any leaks.
42 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 47
4. Installation12-2016
WARNING
Fuel presents the hazard of explosion or fire which can result in severe personal injury or death. Do not use an open flame to check for leaks. Do not smoke or allow any flame, spark, pilot light, arc-producing equipment, switch or other ignition sources around fuel or fuel components. Keep multi-class ABC fire extinguishers handy.
NOTICE
Follow any local codes and standards, as they may require a different method or documentation of a leak test.
Perform the following fuel piping system leak check:
1. After assembly and before initial operation of generator set, test all fuel system components as required per the National Fuel Gas Code (NFPA 54).
2. The National Fuel Gas Code requires that the generator set be isolated from the piping system by disconnecting it and capping the outlet prior to test. The test pressure required is the greater of 1.5 times the supply pressure or 3 psi (20.7 kPa) minimum.
3. After successfully completing the previous step, connect the generator set to the fuel piping system.
4. To verify that all connections from the fuel piping system to the generator set are free of leaks, conduct a bubble test using an approved leak detection solution (or equivalent method) with the system pressure of 0.8 to 1.0 psi (5.5 to
7.0 kPa).
5. Spray the bubble solution on all of the joints.
6. Inspect all of the joints and monitor the line pressure. If bubbles appear, there is a leak.
7. If any leaks are found, repair the joint or replace components as needed.
8. Verify the leak has been fixed.
The leak detection solution (that is, bubble solution) must be non-corrosive and be free of ammonia and chlorine.

4.3 Engine Exhaust

NOTICE
The exhaust system for this generator set is complete and was designed specifically for this generator set. Do not modify or add to the exhaust system of this generator set.
43A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 48
4. Installation 12-2016
WARNING
Exhaust gas is deadly. Make sure that the exhaust system terminates away from building vents, windows, doors, and sheltered spaces that may not have ample fresh air ventilation.
WARNING
Engine discharge air and exhaust carry carbon monoxide gas (odorless and invisible) which can cause asphyxiation and death. Never use engine discharge air or exhaust for heating a room or enclosed space.

4.4 Electrical Connections

WARNING
Improper installation can lead to electrocution and damage to property. Electrical connections must be made by a licensed electrician.
NOTICE
Refer to regional codes and the National Electrical Code (NFPA 70) for all electrical installation requirements.
NOTICE
Class 1 wiring methods must be used for connecting the generator set.
Electrical Preparations
1. Run all wires through a single conduit (unless prohibited by the authority having jurisdiction).
NOTICE
Be sure to account for any needed accessories, such as a remote display, etc.
2. Connect the conduit to the generator set. Refer to the specific outline drawing in the Outline and System Drawings section for the size and location of the hole provided for electrical conduit connection. The existing hole may be increased in size to match conduit used.
3. Route and secure customer wiring along the generator set harness above the engine intake manifold, using wire ties.
44 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 49
4. Installation12-2016
AC Connections
WARNING
Automatic startup of the generator set during installation can cause severe personal injury or death.
Make sure the generator set is shut down and disabled:
1. Press the generator set's red STOP button on the local display to stop the generator set. Allow the generator set to thoroughly cool to the touch.
2. Turn off and disconnect the battery charger from the AC source before disconnecting the battery cables.
3. Disconnect the negative (–) cable from the battery and secure it from contacting the battery terminals to prevent accidental starting.
For grounding and neutral connections, look for the following symbols on the generator set. The neutral connection is at the rear of the breaker box; the ground connection is inside the enclosure on the panel to the left of the breaker box.
Equipment Grounding Conductor Symbol Equipment Neutral Connection Symbol
FIGURE 11. SYMBOLS ON CIRCUIT BREAKER BOX
45A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 50
4. Installation 12-2016
No. Description No. Description
1 L1 2 L2
FIGURE 12. CIRCUIT BREAKER AC LOAD CONNECTIONS LOCATION
Make the AC load connections to the generator set in the circuit breaker box as follows:
1. Open the circuit breaker box door.
2. Place the circuit breaker handle in the OFF position.
3. Lift the top cover. Undo the two screws on top of the intake panel and remove the panel.
4. Route the load conductors through the access holes found at the bottom of the circuit breaker box.
5. Connect the conductors to the circuit breaker load side terminals. Torque the circuit breaker terminals to 45 in-lb (5 Nm).
6. Unless there is no utility source connected to ATS or house loads, remove the bonding jumper from the neutral lug on the back of the circuit breaker box to the equipment grounding lug as shown in Figure 12. Refer to NFPA 70E or CEC.
7. Install the neutral line to the neutral lug found on the back of the circuit breaker box. Torque the neutral lug to 120 in-lb (13.6 Nm).
8. Install the ground line to the equipment grounding lug. Torque the equipment grounding lug to 120 in-lb (13.6 Nm).
46 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 51
4. Installation12-2016
9. Install the circuit breaker cover with the screw provided. Torque the pan-head screw to 12 in-lb (1.36 Nm).
10. Reinstall the intake panel.
11. Reinstall the two screws. Torque to 44 - 58 in-lb (5 - 6.6 Nm).
12. Close the lid and lock it if the installation is complete.
13. Close the circuit breaker box door.
Automatic Transfer Switch AC Connections
WARNING
Failure to use an approved transfer switch can lead to the electrocution of personnel working on the utility lines, damage to equipment, fire, or personal injury. An approved switching device must be used to prevent interconnection to the public utility.
Install the transfer switch in accordance with the appropriate RA series transfer switch owner manual.
Customer AC Connections
The customer supplied AC circuit is used to power the following components:
• Alternator heater (if applicable)
• Battery charger (standard)
• Battery heater (if applicable)
• Engine oil heater (if applicable)
The AC circuit must be 120 VAC, 20 Amp protected. The wires from this customer supplied circuit are terminated within the enclosure at the five place connectors labeled "Ground", "Line" and "Neutral". Follow regional regulations and applicable electrical codes for installation.
47A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 52
4. Installation 12-2016
FIGURE 13. CUSTOMER AC CONNECTIONS
DC Connections
NOTICE
See the Wiring Diagrams appendix for DC customer connections.
Automatic Transfer Switch (ATS) DC Connections
WARNING
Failure to use an approved transfer switch can lead to the electrocution of personnel working on the utility lines, damage to equipment, fire, or personal injury. An approved switching device must be used to prevent interconnection to the public utility.
Install the transfer switch in accordance with the appropriate RA Series Transfer Switch Owner Manual.
The following image shows the location of the connectors in the generator set where the ATS DC control wires terminate. This is also the location of the connectors where load management control wires terminate.
48 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 53
4. Installation12-2016
NOTICE
Class 1 wiring methods should be used for connecting the generator set and transfer switch signal wiring.
FIGURE 14. LOCATION OF CONNECTION POINTS FOR ATS DC CONTROL WIRES
AND LOAD MANAGEMENT CONTROL WIRES
Refer to the Wiring Diagrams appendix for generator set to RA transfer switch DC customer connections.
Grounding
Use the Typical System Grounding One-Line Diagrams in this section to be sure that the generator set, transfer switch, power supply wiring and all connected electrical equipment are bonded to a common grounding point in accordance with the applicable codes and standards. Refer to local codes and standards for grounding procedures.
NOTICE
The generator set grounding terminal must be connected to the grounding terminal in the transfer switch. Do not provide a separate grounding rod for the generator set.
49A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 54
4. Installation 12-2016
NOTICE
Generator set neutral is not typically grounded at the generator set, but at the common system grounding point.
WARNING
Contact with electrical equipment can result in severe personal injury or death. It is extremely important that bonding and equipment grounding be properly done. All metallic parts that could become energized under abnormal conditions must be properly grounded.
No. Description No. Description
1 Service Entrance 4 Loads 2 2-Pole Transfer Switch 5 To Utility Service 3 Generator Set
FIGURE 15. TYPICAL SYSTEM GROUNDING ONE-LINE DIAGRAM (SEPARATE
SERVICE ENTRANCE AND 2-POLE TRANSFER SWITCH)
50 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 55
No. Description No. Description
4. Installation12-2016
1 Combined Service Entrance and 2-
Pole Transfer Switch
2 Generator Set 4 To Utility Service
FIGURE 16. TYPICAL SYSTEM GROUNDING ONE-LINE DIAGRAM (COMBINED
SERVICE ENTRANCE AND 2-POLE TRANSFER SWITCH)
3 Loads
Display Communication Wires
NOTICE
There are two unmarked connectors on the back of the display, either one may be used for connecting the display to the generator set.
Class 1 wiring methods should be used for the remote display and transfer switch communication conductors between the generator set and transfer switch.
See the Operator Manual for information regarding using the display to operate and monitor the generator set.
Load Management Wiring
See the Automatic Transfer Switch (ATS) DC Connections section for the location of the connectors (TB-1, TB-2, TB-3, and TB-4) in the generator set, which are used for load management control wire termination. Class 1 wiring methods should be used for installing load management devices.
Cummins offers a kit for load management wiring (A051C329).
51A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 56
4. Installation 12-2016
Battery
The generator set requires a 12V battery for engine cranking and powering the electronic control system. When the generator set is running, the battery is charged from the engine-driven battery charger. When the generator set is not running, an AC powered battery charger is provided to keep the battery charged.
WARNING
To avoid injury, wear proper safety protection when working around batteries. Keep open flames and sparks away from the equipment.
WARNING
Automatic startup of the generator set during installation can cause severe personal injury or death. Make sure the generator set is shut down and disabled:
1. Press the generator set's red STOP button on the local display to stop the generator set. Allow the generator set to thoroughly cool to the touch.
2. Turn off and disconnect the battery charger from the AC source before disconnecting the battery cables.
3. Disconnect the negative (–) cable from the battery and secure it from contacting the battery terminals to prevent accidental starting.
To connect the battery:
1. Connect the battery cables to the battery with the positive (+) cable first. Immediately cover the battery post and terminal with the red terminal cover provided on the battery cable.
2. Connect the negative (-) cable to the battery's minus terminal.
Refer to the Model Specifications section for battery specifications. An optional thermostatically controlled battery heater is available for more reliable
starting.
52 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 57
4. Installation12-2016
FIGURE 17. BATTERY LOCATION
53A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 58
4. Installation 12-2016
This page is intentionally blank.
54 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 59

5 Startup and Configuration

5.1 "Establishing Communications" Message

NOTICE
Once the battery is connected to the generator set and any display button is pressed, the local display shows an "establishing communications" message for approximately 5 seconds. (This may take longer if the signal integrity is poor between the control and display due to a bad wire or Electro-Magnetic Interference [EMI].) Once communication is established, the display shows the HOME screen.
The “establishing communications” message will also be displayed whenever the control is brought out of “sleep” mode by pressing any button on the display. Sleep mode is entered after 30 minutes without utility or generator set power to preserve battery energy since the battery charger will not have AC power. The 30-minute timer is reset with any button press on the display.

5.2 "Clock Setup" Screen

The Clock needs to be reset whenever the battery power is lost or disconnected, or the control has entered “sleep” mode. Sleep mode is entered after 30 minutes without utility or generator set power to preserve battery energy since the battery charger will not have AC power. The 30­minute timer is reset with any button press on the display.
The optional Remote Monitoring System (RMS) uses the generator set's clock. The clock must be set accurately for the RMS to function properly.
To set up the generator set clock for the current date and time:
1. From the Main screen, select Menu.
2. Use the arrow keys to highlight Clock. Select the Enter key.
3. Use the arrow keys to set the time and date.
NOTICE
NOTICE
55A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 60
5. Startup and Configuration 12-2016
FIGURE 18. CLOCK SETUP SCREEN
4. Select the Next key to go to the Daylight Savings screen.
56 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 61
5. Startup and Configuration12-2016
5. Use the arrow keys to enable/disable Daylight Savings. If enabling, select the
Next key to highlight the Offset field.
FIGURE 19. DAYLIGHT SAVINGS TIME (ENABLED)
6. Use the arrow keys and Next key to set the offset value for Daylight Savings time.
57A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 62
5. Startup and Configuration 12-2016
FIGURE 20. OFFSET VALUE
7. Select the Next key to go the screen that is used to set up when Daylight Savings should start. Use the arrow keys and Next key to set Month (1 – 12), Week (0 – 5), Day (Sun – Sat) and Hour (12AM – 12PM).
58 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 63
5. Startup and Configuration12-2016
FIGURE 21. DAYLIGHT SAVINGS TIME (START TIME SETUP)
8. Select the Next key to go the screen that is used to set up when Daylight Savings should end. Use the arrow keys and Next key to set Month (1 – 12), Week (0 – 5), Day (Sun – Sat) and Hour (12AM – 12PM).
59A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 64
5. Startup and Configuration 12-2016
FIGURE 22. DAYLIGHT SAVINGS TIME (END TIME SETUP)
9. Keep selecting the Back button to save the settings and return to the main screen.
60 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 65

5.3 "Exercise" Screen

When installing an RA series transfer switch, follow these steps to configure the Exercise mode in the generator set's local display or remote display.
Exercise settings need to be reset whenever battery power is lost or disconnected, or the control has entered “sleep” mode.
Sleep mode is entered after 30 minutes without utility or generator set power to preserve battery energy since the battery charger will not have AC power. The 30-minute timer is reset with any button press on the display.
To set up the exercise function:
1. From the Main screen, select Menu.
2. Use the arrow keys to highlight Exercise. Select the Enter key.
5. Startup and Configuration12-2016
NOTICE
NOTICE
NOTICE
If the time and date have not been set, a pop-up will appear that says, "Set Valid Date and Time".
3. Use the arrow keys to enable or disable the Crank Exercise feature. Select the Next key to go to the Exercise Time field. See the Exercise Sequences section in the operator manual for more information.
NOTICE
When the Crank Exercise feature is enabled, an exercise command will cause the engine starter to engage and rotate the engine, but will not allow the engine to start. This feature allows the control system to monitor critical generator set systems without running the engine. When Crank Exercise is enabled, the generator set's exercising will alternate between the Crank Exercise sequence and the normal exercise sequence (that is, engine running) at scheduled times.
4. Use the arrow keys to set how long the generator set will exercise (from 1 to 20 minutes). Select the Next key to go to the Exercise field. The Exercise Sched screen appears.
5. Use the arrow keys to set how often the generator set will exercise. The frequency selections are:
• Weekly
• Bimonthly
• Monthly
61A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 66
5. Startup and Configuration 12-2016
• Never
Select the Next key to go to the date and time fields.
6. Use the arrow keys to set the day and time the generator set will be exercised. Select the Next key to highlight the Exercise Now field.
7. Select either arrow key to start the Exercise Now function.
NOTICE
Initiating the Exercise Now function will cause the generator set to start immediately and run for the amount of time indicated by the Exercise Time field, or run the Crank Exercise sequence. The ATS does not transfer to generator power during exercise mode. Normally scheduled exercise events will occur after the completion of the immediate exercise event.
8. Keep selecting the Back button to save the settings and return to the Main screen.
62 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 67
5. Startup and Configuration12-2016
FIGURE 23. EXERCISE SETUP SCREEN
63A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 68
5. Startup and Configuration 12-2016

5.4 "Brightness and Contrast" Screen

To adjust the brightness and contrast of the display:
1. From the Main screen, select Menu.
2. Use the arrow keys to highlight Display Setup. Select the Enter key.
3. Use the arrow keys to set brightness and contrast for the display.
4. Keep selecting the Back button to save the settings and return to the Main screen.
64 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 69
5. Startup and Configuration12-2016
FIGURE 24. BRIGHTNESS AND CONTRAST SCREEN
65A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 70
5. Startup and Configuration 12-2016

5.5 "About" Screen

To retrieve information about the display:
1. From the Main screen, select Menu.
2. Use the arrow keys to highlight About. Select the Enter key.
66 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 71
5. Startup and Configuration12-2016
FIGURE 25. ABOUT SCREEN
67A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 72
5. Startup and Configuration 12-2016

5.6 "Event Log" Screen

To retrieve information from the Event Log:
1. From the Main screen, select Menu.
2. Use the arrow keys to highlight Event Log. Select the Enter key.
3. Use the arrow keys to navigate through the Event Log.
4. Keep pressing the Back button to return to the Main screen.
FIGURE 26. EVENT LOG SCREEN
68 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 73

5.7 "Fault Log" Screen

To retrieve information from the Fault Log:
1. From the Main screen, select Menu.
2. Use the arrow keys to highlight Fault Log. Select the Enter key.
3. Scroll through the fault log using the up and down double-arrows. Each screen provides a brief description of the fault, the fault code number, the engine hours and the time and date of the fault.
If there are no faults recorded, the “No Stored Faults" screen will appear.
4. Keep pressing the Back button to return to the Main screen.
5. Startup and Configuration12-2016
NOTICE
69A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 74
5. Startup and Configuration 12-2016
FIGURE 27. FAULT LOG SCREEN

5.8 "System Status" Screen

To retrieve system status:
1. From the Main screen, select Menu.
2. Use the arrow keys to highlight System Status. Select the Enter key.
3. Keep pressing the Back button to return to the Main screen.
70 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 75
5. Startup and Configuration12-2016
FIGURE 28. SYSTEM STATUS SCREEN

5.9 "Mode" Screen

To prevent unexpected starts from remote devices, disable Remote mode and disconnect the connector on the back of the local display wired to any remote mounted displays.
When Remote is set to Enabled via the local display, the “Remote On” LED on the front of the display will illuminate indicating that the control will accept start commands from remote displays or remote monitoring systems including a web page or cell phone app.
WARNING
71A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 76
5. Startup and Configuration 12-2016
NOTICE
The Remote function can only be activated (that is, enabled) from the local display.
When Standby is on or set to Enabled, the “Standby On” LED on the front of the display will illuminate indicating the control will start the generator set in response to a utility power outage. Standby can be turned on at the local display. It can also be enabled with a remote display, web page, or a cell phone app if Remote has already been enabled at the local display. The Standby function cannot be enabled remotely unless the Remote function is on. A manual Start or Stop event will disable the Standby function. (If the manual Stop event is performed at the local display, the Remote mode will also be disabled.)
1. To enable or disable the Remote and Standby modes on the LOCAL display:
a. From any screen, select the Mode key to get to the Mode screen. b. Use the arrow keys to enable or disable the Remote mode. Select the Next
key to go to the next screen.
c. Use the arrow keys to enable or disable the Standby mode.
NOTICE
Whenever Standby is enabled, the Remote mode will also automatically be enabled.
d. Keep pressing the Back button to save the settings and return to the Main
screen.
72 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 77
5. Startup and Configuration12-2016
FIGURE 29. MODE SETUP SCREEN (LOCAL DISPLAY)
2. To enable or disable the Standby mode on the REMOTE display:
NOTICE
Remote must be enabled before Standby mode can be changed from the Remote display. If Remote mode is not enabled, Standby will remain disabled and cannot be changed.
a. From any screen, select the Mode key to get to the Mode screen. b. Use the arrow keys to enable or disable the Standby mode. c. Keep pressing the Back button to save the settings and return to the Main
screen.
FIGURE 30. MODE SETUP SCREEN (REMOTE DISPLAY)
73A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 78
5. Startup and Configuration 12-2016

5.10 Automatic Load Management

NOTICE
The capability to automatically add or remove specific electrical loads from the generator set requires that load management devices be wired to the generator set load management outputs.
When the generator set is started automatically in Standby mode due to a loss of utility or manually by the operator, the control will energize all four load management outputs, disconnecting the associated loads from AC power. Once the transfer switch transfers to generator set power, the generator set control will evaluate the total load on the generator set versus a set point programmed into the control (80% of rated).
If the generator set’s total load is below the set point, the generator set control will sequentially add the highest priority managed load every three minutes. Managed loads will continue to be added as long as the size of the next priority load to be added won’t increase total generator set load above the set point. The control measures and stores the size of each managed load in its memory. Load priorities are in the following order:
• Priority #1: load control 1
• Priority #2: load control 2
• Priority #3: load control 3
• Priority #4: load control 4
If the load on the generator set is reduced at any time to below the set point, the control will add the next highest priority managed load in three minutes provided it does not increase the total generator set load above the set point.
If the load on the generator set exceeds 95% of its rating, the generator set control will begin disconnecting the lowest managed priority loads in sequence every second until the load on the generator set is below 95% of its rating.
Priority #1 load is always the first added and the last disconnected; therefore, it should be wired to the managed load deemed most critical to the homeowner. Priority #2 load cannot be added before priority #1 load, nor can it be disconnected before priority #3 or #4, etc.
74 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 79

5.11 Manual Start Sequence (Local)

NOTICE
If the utility power supply to the generator set's utility powered battery charger is interrupted, the battery can become discharged due to parasitic loads and the generator set may not start when needed. Whenever utility power is interrupted and the generator set is not in Standby mode for any reason (fuel preservation, etc.), start and run the generator set for 2 hours every 24 hour period when temperatures are above 50 °F (10 °C), or every 9 hour period when temperatures are below 50 °F (10 °C).
The following steps will be executed when Manual Start is used at the local display:
1. If you do not want the ATS to transfer load to the generator set, open the generator set mounted circuit breaker when doing a manual start.
2. From the Main screen, select the START key.
3. A second screen appears notifying the operator that Standby will be disabled. Select the START key again to start the generator set.
5. Startup and Configuration12-2016
4. After the generator set reaches rated voltage and frequency, the transfer switch transfers the building load to the generator set (unless the circuit breaker on the generator set is "off"). The building's electrical power is now provided by the generator set.
FIGURE 31. GENSET POWER

5.12 Checklist

Tick Area
General
Generator set output is sufficient to handle maximum anticipated load.
75A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 80
5. Startup and Configuration 12-2016
Tick Area
Proper clearance is provided around the entire generator set for service and ventilation:
• All parts of the generator set enclosure must be at least 60 inches (1524 mm) from any openings in walls of structures that may be occupied. Examples of wall openings include but are not limited to: operable windows, doors, dryer vents, fresh air intake for heaters, etc.
• The engine side and alternator side of the generator set must be located as follows:
One side (either engine or alternator) must be located not less than 18
inches (458 mm) from any structures having combustible walls. This space must be free of any obstructions for service access.
The opposite side must be located not less than 60 inches (1524 mm) from
any structures having combustible walls. A minimum of 18 inches (458 mm) of unobstructed space is required for service access.
• The intake (cooling air inlet) side of the generator set must be located not less than 30 inches (762 mm) from any structures having combustible walls. This space must be free of obstructions to air flow and service access.
• The generator set must be located such that exhaust gases are not able to accumulate in an occupied area. The air discharge side must always be unobstructed and spaced a minimum of 60 inches (1524 mm) from any structures having combustible walls. A minimum of 36 inches (915 mm) must be free of any combustible items, and unobstructed for service access.
• The generator set must have enough room for installation, service, and maintenance.
• The generator set must be located to ensure ventilation openings are not blocked.
• Position the generator set so that cooling air is free to enter and leave the area.
• Locate and position the generator set so that prevailing winds carry exhaust gases and potential fuel leaks away from the house or occupied area.
The generator set is located in an area not subject to flooding. The generator set's service regulator is installed above the snow line. All operating personnel have read and are familiar with the generator set operator
manual, all health and safety procedures, and all other documentation supplied with the generator set.
All operators have been thoroughly briefed on preventive maintenance procedures. Proper clearance to openings in nearby structures is provided. Clearance around and
over the generator set is provided for operation, service and maintenance.
Generator Set Mounting Pad
The earth on which the generator set mounting pad rests is strong enough and will not allow shifting or movement. Observe local codes on soil bearing capacity.
76 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 81
Tick Area
The generator set is properly supported and attached to an approved base. The supporting base is of non-combustible material and extends 2 inches (50.8 mm)
all around the generator set. The generator set is located to comply with applicable codes and standards.
Fuel System
Verify that the generator set is configured to the fuel being used. (See the Fuel Selection and Fuel System Connection section.)
Verify that the fuel line has proper volume capability. Verify that fuel pressure is correct:
• Natural gas: 3.5 - 12 inch water column (0.9 - 3.0 kPa)
• Propane: 6 - 12 inch water column (1.5 - 3.0 kPa)
Maximum pressure for either fuel under any condition: 13 inch water column (3.2 kPa) Verify the fuel pressure at the generator set connection does not drop below the range
listed above during startup and full load operation and does not exceed 13 inch water column (3.2 kPa).
5. Startup and Configuration12-2016
Verify that all fuel connections are tight. Verify there are no gas leaks in the fuel system. All electrical and fuel lines are properly separated. An approved flexible fuel line is properly installed between the generator set fuel inlet
connection and the fuel supply line.
Exhaust System
All areas around the generator set are well ventilated, with no possibility of exhaust fumes entering building doors, windows, or intake fans.
AC and DC Wiring
Wire sizes, insulation, conduits and connection methods all meet applicable codes. All load, line and generator set connections are well made and correct. Flexible conduit is used between the generator set and the building or surrounding
structure. A transfer switch has been installed properly to prevent connecting the generator set
to the utility. Verify that 120 VAC power has been provided to the power battery charger and other
AC accessories on the generator set.
Generator Set Pre-Start
The generator set engine is properly serviced with oil. All generator set and ATS covers and safety shields are installed correctly.
77A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 82
5. Startup and Configuration 12-2016
Tick Area
All fuel shutoff valves are operational and in the open position. The installation meets all applicable local, state, and federal codes.
Control
Verify that the clock, exerciser and correct fuel type are set.

5.13 Startup

1. Verify that the installation was completed correctly.
2. Read the operator manual. Perform the pre-start checks as instructed.
3. Connect the battery cables to the battery with the positive (+) cable first. Immediately cover the battery post and terminal with the red cover provided on the battery cable.
4. Although the generator set is shipped from the factory with the proper level of engine oil, check the oil level before it is started.
5. Start and test the system.
6. Operate the generator set following all the instructions and precautions in the operator manual.
NOTICE
Before leaving the site, if the generator set is ready to be placed in service, enable the Remote and Standby modes from the local display.
NOTICE
Contact your local Cummins service provider if you encounter a fault code.
78 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 83
6 Optional Remote Monitoring System
(RMS) Description

6.1 Introduction

The Remote Monitoring System (RMS) feature allows for in-home or remote access to your generator set through a web page or smart phone app. Using the RMS, you can start or stop the generator set, adjust the exerciser date and time, determine if utility power is available, and view the last 20 events and/or faults on the generator set. This feature can also help to reduce troubleshooting time and the number of service calls if a generator service provider has access to the same information.
The internet/email interface can make the same fault, maintenance, and event notifications available to you and to your generator set service provider with an appropriate account setup.
RMS is optional. If you do not wish to use this service or do not have an Ethernet connection available, you are not required to set up an RMS account.
NOTICE
Technical support for setup and troubleshooting of the RMS is available through the selling Cummins Power Generation dealer/distributor.
However, due to variations in network equipment, network configurations, and internet and cellular service providers, the owner may be required to contact their Internet Service Provider, email service provider, or cellular service provider for technical support regarding internet connectivity, email notifications, and smart phone applications support.
Cummins does not provide technical support for the setup and troubleshooting of the owner's network, email, and cellular service.
NOTICE
The following Internet browsers are compatible with this option:
• Microsoft Internet Explorer®(version 9 or greater)
• Apple Safari
• Google Chrome™
• Mozilla Firefox®(version 3.6 or greater)
• Microsoft®Edge
®
79A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 84
6. Optional Remote Monitoring System (RMS) Description 12-2016

6.2 Optional Remote Monitoring System (RMS) Account Setup and Generator Set Control Connection

1. Prior to setting up the account, ensure that the generator set control is connected to the Internet via an Ethernet cable between the generator set control and the home’s router.
2. Access the Cummins ConnectCloud website by navigating to ConnectCloud.Cummins.com.
3. Click on Register to create your account.
4. Add a generator set to your account, using the Serial Number and Customer Access Code from your generator set. The Serial Number and Customer Access Code can be found on the display in the Menu/About section.
NOTICE
Android and iPhone apps for the Cummins ConnectCloud are also available.
80 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 85

Appendix A. Fuel Line Selection

Table of Contents
Table 17. Required Information for Determining Fuel Line Size ............................................................. 82
Table 19. Equivalent Lengths of Pipe Fittings and Valves in Feet (Meters) ........................................... 83
Table 21. Natural Gas Schedule 40 Metallic Pipe Sizing .......................................................................... 85
Table 23. Natural Gas Semirigid Copper Tubing Sizing ........................................................................... 87
Table 25. Propane Vapor Schedule 40 Metallic Pipe Sizing .................................................................... 89
Table 27. Propane Vapor Semirigid Copper Tubing Sizing ..................................................................... 90
Table 29. Propane Schedule 40 Iron Pipe Sizing, Liquid Withdrawal (Maximum Capacity of Pipe in
Cubic Feet of Gas per Hour)* ...................................................................................................................... 92
Figure 32. Minimum LPG Tank Size (50% Full) Required to Maintain 5 PSIG at Specific Withdrawal
Rate and Minimum Expected Winter Temperature ................................................................................... 94
81A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 86
Appendix A. Fuel Line Selection 12-2016

A.0 Fuel System Pipe Sizing Introduction

Incorrect fuel line size may cause the generator set to not run or provide full power output.
Tables are included in this section to help calculate pipe sizing for natural gas and propane vapor withdrawal under specified conditions. Consult NFPA 54 or other applicable codes for other operating conditions or other fuel system installation requirements.
Refer to the Engineering Application Manual T-030: Liquid Cooled Generator Sets manual (A040S369) for more information.
To determine the optimal fuel line size, the following information is needed:
TABLE 17. REQUIRED INFORMATION FOR DETERMINING FUEL
LINE SIZE
Category Description
Fuel Flow Requirements for the Generator Set
Fuel Source (Natural Gas or Propane Vapor)
Fuel Line Length (Including Fittings)
Fuel Line Type (e.g., Copper Tubing or Iron Pipe)
NFPA 54 has selection tables for other approved fuel lines. Verify with the authorities having jurisdiction the allowed fuel line type for the generator set installation.
Fuel flow requirements have a large impact on fuel line size.
Fuel sources can affect fuel line size. Natural gas installations generally require a higher fuel flow rate compared to propane vapor installations, since propane has a higher energy content.
As fuel line lengths increase, they may require larger diameter fuel lines. Be sure to consider the equivalent length of all of the fittings (elbows, tees, valves) in the installation in addition to the straight pipe length.
Most fuel line types are iron pipe or copper tubing. Be sure to use the sizing chart for the fuel line type when sizing the fuel line.
NOTICE
82 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 87

A.1 Gas Pipe Sizing

The following tables in this section are reprinted with permission from NFPA 54-2015, National Fuel Gas Code, Copyright © 2014, National Fire Protection Association.
• Natural Gas Schedule 40 Metallic Pipe Sizing
• Natural Gas Semirigid Copper Tubing Sizing
• Propane Vapor Schedule 40 Iron Pipe Sizing
• Propane Vapor Semirigid Copper Tubing Sizing
• Propane Schedule 40 Iron Pipe Sizing, Liquid Withdrawal (Maximum Capacity of Pipe in Cubic Feet of Gas per Hour)
This reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented only by the standard in its entirety.
Appendix A. Fuel Line Selection12-2016
NOTICE
Sizing of gas piping for proper fuel delivery, both flow and pressure, can become quite complex. A simplified method is to convert all fittings, valves, etc. to equivalent lengths of pipe in the diameter(s) being considered. The total equivalent length can then be related to flow capacity. Equivalent lengths of pipe fittings and valves can be found in the table below.
TABLE 19. EQUIVALENT LENGTHS OF PIPE FITTINGS AND VALVES IN FEET
(METERS)
NOMINAL INCH (MILLIMETER) PIPE SIZE
TYPE OF
FITTING
90° Std. Elbow or
Tee Reduced ½. 90° Long Radius
Elbow or Straight
Run Tee
45° Elbow 0.8
1/2
(15)
1.6
(0.5)
1.0
(0.3)
(0.2)
3/4
(20)1(25)
2.0
(0.6)
1.4
(0.4)
0.9
(0.3)
2.6
(0.8)
1.7
(0.5)
1.3
(0.4)
1-1/4
(32)
3.3
(1.0)
2.3
(0.7)
1.7
(0.5)
1-1/2
(40)
4.0
(1.2)
2.6
(0.8)
2.1
(0.6)
2
(50)
5.0
(1.5)
3.3
(1.0)
2.6
(0.8)
2-1/2
(65)
6.0
(1.8)
4.1
(1.3)
3.2
(1.0)
(80)
7.5
(2.3)
5.0
(1.5)
4.0
(1.2)
3
4
(100)
10.0
(3.1)
6.7
(2.0)
5.2
(1.6)
180° Std. Bend 2.5
(0.8)
TEE, Side Inlet or
Outlet
(0.9)
3.0
3.2
(1.0)
4.0
(1.2)
4.1
(1.2)
5.0
(1.5)
5.6
(1.7)
7.0
(2.1)
6.3
(1.9)
8.0
(2.4)
83A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
8.2
(2.5)
10.0
(3.0)
10.0
(3.1)
12.0
(3.7)
12.0
(3.7)
15.0
(4.6)
17.0
(5.2)
21.0
(6.4)
Page 88
Appendix A. Fuel Line Selection 12-2016
Foot Valve and
Strainer
Swing Check
Valve,
Fully Open
Globe Valve,
Fully Open
Angle Valve, Fully
Open
Gate Valve, Fully
Open
3.7
(1.1)
6.0
(1.8)
18.0 (5.5)
7.0
(2.1)
0.7
(0.2)
4.9
(1.5)
8.0
(2.4)
22.0
(6.7)
9.0
(2.7)
0.9
(0.3)
7.5
(2.3)
10.0
(3.0)
29.0
(8.8)
12.0
(3.7)
1.0
(0.3)
8.9
(2.7)
14.0
(4.3)
38.0
(11.6)
15.0
(4.6)
1.5
(0.5)
11.0 (3.4)
16.0 (4.9)
43.0
(13.1)
18.0 (5.5)
1.8
(0.5)
15.0
(4.6)
20.0
(6.1)
55.0
(16.8)
24.0
(7.3)
2.3
(0.7)
18.0
(5.5)
25.0
(7.6)
69.0
(21.0)
29.0
(8.8)
2.8
(0.9)
22.0
(6.7)
30.0
(9.1)
84.0
(25.6)
35.0
(10.7)
3.2
(1.0)
29.0
(8.8)
40.0
(12.2)
120.0 (36.6)
47.0
(14.3)
4.5
(1.4)
The remaining tables in this section show maximum gas capacity for equivalent lengths of various pipe sizes.
Here are some basic but very important steps that all installers must follow to make sure that fuel lines are sized correctly:
1. Verify adequate fuel flow, quality, and pressure available from the natural gas utility connection or the propane system.
2. Obtain the maximum fuel consumption requirements at full load for the specific generator set from the Model Specifications section and for all gas appliances attached to the pipe system.
3. Make a list of all the fittings and valves in the proposed system used in this generator set installation.
4. Determine the equivalent length of all fuel line fittings (elbows, tees, and valves). (See the NFPA Pipe Fittings table in this appendix to determine the equivalent lengths for all fuel line fittings.)
5. Add the equivalent length of the fuel line fittings to the lengths of straight pipe to determine the total equivalent length of the system.
6. Choose the applicable table in this appendix based on the fuel type (natural gas, propane vapor or liquid propane) and fuel line material.
7. Determine the fuel line size at full load:
a. Locate the equivalent length of pipe (or next larger equivalent
length) in the left hand column.
b. Move across the row to where the maximum flow capacity
number is as large or larger than the maximum fuel consumption.
c. Move to the top of that column to where the minimum nominal
pipe size or tubing size required for the system as designed is shown.
84 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 89
Appendix A. Fuel Line Selection12-2016
TABLE 21. NATURAL GAS SCHEDULE 40 METALLIC PIPE SIZING
Gas: Natural Inlet Pressure: Less than 2 psi Pressure Drop: 0.5 in. w.c. Specific Gravity: 0.60
Pipe Size (in.)
Nominal:12 34 1 114 112 2 212 3 4 5 6 8 10 12
Actual
Length
0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938
ID:
Capacity in Cubic Feet of Gas per Hour
(ft)
10 172 360 678 1,3902,0904,0206,40011,30023,10041,80067,600139,
000
252,
000
20 118 247 466 957 1,4302,7604,4007,78015,90028,70046,50095,500173,
000
30 95 199 374 768 1,1502,2203,5306,25012,70023,00037,30076,700139,
000
40 81 170 320 657 985 1,9003,0205,35010,90019,70031,90065,600119,
000
50 72 151 284 583 873 1,6802,6804,7409,66017,50028,30058,200106,
000
399,
000
275,
000
220,
000
189,
000
167,
000
60 65 137 257 528 791 1,5202,4304,2908,76015,80025,60052,70095,700152,
000
70 60 126 237 486 728 1,4002,2303,9508,05014,60023,60048,50088,100139,
000
80 56 117 220 452 677 1,3002,0803,6707,49013,60022,00045,10081,900130,
000
90 52 110 207 424 635 1,2201,9503,4507,03012,70020,60042,30076,900122,
000
100 50 104 195 400 600 1,1601,8403,2606,64012,00019,50040,00072,600115,
000
125 44 92 173 355 532 1,0201,6302,8905,89010,60017,20035,40064,300102,
000
150 40 83 157 322 482 928 1,4802,6105,3309,65015,60032,10058,30092,3
00
175 37 77 144 296 443 854 1,3602,4104,9108,88014,40029,50053,60084,9
00
85A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 90
Appendix A. Fuel Line Selection 12-2016
200 34 71 134 275 412 794 1,2702,2404,5608,26013,40027,50049,90079,0
00
250 30 63 119 244 366 704 1,1201,9804,0507,32011,90024,30044,20070,0
00
300 27 57 108 221 331 638 1,0201,8003,6706,63010,70022,10040,10063,4
00
350 25 53 99 203 305 587 935 1,6503,3706,1009,88020,30036,90058,4
00
400 23 49 92 189 283 546 870 1,5403,1405,6809,19018,90034,30054,3
00
450 22 46 86 177 266 512 816 1,4402,9405,3308,62017,70032,20050,9
00
500 21 43 82 168 251 484 771 1,3602,7805,0308,15016,70030,40048,1
00
550 20 41 78 159 239 459 732 1,2902,6404,7807,74015,90028,90045,7
00
600 19 39 74 152 228 438 699 1,2402,5204,5607,38015,20027,50043,6
00
650 18 38 71 145 218 420 669 1,1802,4104,3607,07014,50026,40041,8
00
700 17 36 68 140 209 403 643 1,1402,3204,1906,79014,00025,30040,1
00
750 17 35 66 135 202 389 619 1,0902,2304,0406,54013,40024,40038,6
00
800 16 34 63 130 195 375 598 1,0602,1603,9006,32013,00023,60037,3
00
850 16 33 61 126 189 363 579 1,0202,0903,7806,11012,60022,80036,1
00
900 15 32 59 122 183 352 561 992 2,0203,6605,93012,20022,10035,0
00
950 15 31 58 118 178 342 545 963 1,9603,5505,76011,80021,50034,0
00
1,00014 30 56 115 173 333 530 937 1,9103,4605,60011,50020,90033,1
00
1,10014 28 53 109 164 316 503 890 1,8103,2805,32010,90019,80031,4
00
1,20013 27 51 104 156 301 480 849 1,7303,1305,07010,40018,90030,0
00
86 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 91
Appendix A. Fuel Line Selection12-2016
1,30012 26 49 100 150 289 460 813 1,6603,0004,8609,98018,10028,7
00
1,40012 25 47 96 144 277 442 781 1,5902,8804,6709,59017,40027,6
00
1,50011 24 45 93 139 267 426 752 1,5302,7804,5009,24016,80026,6
00
1,60011 23 44 89 134 258 411 727 1,4802,6804,3408,92016,20025,6
00
1,70011 22 42 86 130 250 398 703 1,4302,5904,2008,63015,70024,8
00
1,80010 22 41 84 126 242 386 682 1,3902,5204,0708,37015,20024,1
00
1,90010 21 40 81 122 235 375 662 1,3502,4403,9608,13014,80023,4
00
2,000NA 20 39 79 119 229 364 644 1,3102,3803,8507,91014,40022,7
00
NA: Applies to a flow of less than 10 cfh. Note: All table entries are rounded to 3 significant digits.
TABLE 23. NATURAL GAS SEMIRIGID COPPER TUBING SIZING
Gas: Natural Inlet Pressure: Less than 2 psi Pressure Drop: 0.5 in. w.c. Specific Gravity: 0.60
Tube Size (in.)
Nominal
K & L:
Nominal
ACR:
Outside: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125
Inside:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
Length
14 38 12 58 34 1 114 112 2
38 12 58 34 78 118 138
Capacity in Cubic Feet of Gas per Hour
(ft.)
10 27 55 111 195 276 590 1,060 1,680 3,490 20 18 38 77 134 190 406 730 1,150 2,400 30 15 30 61 107 152 326 586 925 1,930
87A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 92
Appendix A. Fuel Line Selection 12-2016
40 13 26 53 92 131 279 502 791 1,650 50 11 23 47 82 116 247 445 701 1,460 60 10 21 42 74 105 224 403 635 1,320 70 NA 19 39 68 96 206 371 585 1,220 80 NA 18 36 63 90 192 345 544 1,130
90 NA 17 34 59 84 180 324 510 1,060 100 NA 16 32 56 79 170 306 482 1,000 125 NA 14 28 50 70 151 271 427 890 150 NA 13 26 45 64 136 245 387 806 175 NA 12 24 41 59 125 226 356 742 200 NA 11 22 39 55 117 210 331 690 250 NA NA 20 34 48 103 186 294 612 300 NA NA 18 31 44 94 169 266 554 350 NA NA 16 28 40 86 155 245 510 400 NA NA 15 26 38 80 144 228 474 450 NA NA 14 25 35 75 135 214 445 500 NA NA 13 23 33 71 128 202 420 550 NA NA 13 22 32 68 122 192 399 600 NA NA 12 21 30 64 116 183 381 650 NA NA 12 20 29 62 111 175 365 700 NA NA 11 20 28 59 107 168 350 750 NA NA 11 19 27 57 103 162 338 800 NA NA 10 18 26 55 99 156 326 850 NA NA 10 18 25 53 96 151 315 900 NA NA NA 17 24 52 93 147 306 950 NA NA NA 17 24 50 90 143 297
1,000 NA NA NA 16 23 49 88 139 289 1,100 NA NA NA 15 22 46 84 132 274 1,200 NA NA NA 15 21 44 80 126 262 1,300 NA NA NA 14 20 42 76 120 251 1,400 NA NA NA 13 19 41 73 116 241 1,500 NA NA NA 13 18 39 71 111 232
88 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 93
Appendix A. Fuel Line Selection12-2016
1,600 NA NA NA 13 18 38 68 108 224 1,700 NA NA NA 12 17 37 66 104 217 1,800 NA NA NA 12 17 36 64 101 210 1,900 NA NA NA 11 16 35 62 98 204 2,000 NA NA NA 11 16 34 60 95 199
NA: A flow of less than 10 cfh. Note: All table entries are rounded to 3 significant digits. *Table capacities are based on Type K copper tubing inside diameter (shown), which has the
smallest inside diameter of the copper tubing products.
TABLE 25. PROPANE VAPOR SCHEDULE 40 METALLIC PIPE SIZING
Gas: Undiluted Propane Inlet Pressure: 11.0 in. w.c. Pressure Drop: 0.5 in. w.c. Specific Gravity: 1.50
INTENDED USE: Pipe Sizing Between Single- or Second-Stage (Low-Pressure)
Regulator and Appliance
Pipe Size (in.)
Nominal
Inside:
Actual: 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026
Length
12 34 1 114 112 2 212 3 4
Capacity in Thousands of BTU per Hour
(ft.)
10 291 608 1,150 2,350 3,520 6,790 10,800 19,100 39,000
20 200 418 787 1,620 2,420 4,660 7,430 13,100 26,800
30 160 336 632 1,300 1,940 3,750 5,970 10,600 21,500
40 137 287 541 1,110 1,660 3,210 5,110 9,030 18,400
50 122 255 480 985 1,480 2,840 4,530 8,000 16,300
60 110 231 434 892 1,340 2,570 4,100 7,250 14,800
80 101 212 400 821 1,230 2,370 3,770 6,670 13,600 100 94 197 372 763 1,140 2,200 3,510 6,210 12,700 125 89 185 349 716 1,070 2,070 3,290 5,820 11,900 150 84 175 330 677 1,010 1,950 3,110 5,500 11,200 175 74 155 292 600 899 1,730 2,760 4,880 9,950
89A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 94
Appendix A. Fuel Line Selection 12-2016
200 67 140 265 543 814 1,570 2,500 4,420 9,010 250 62 129 243 500 749 1,440 2,300 4,060 8,290 300 58 120 227 465 697 1,340 2,140 3,780 7,710 350 51 107 201 412 618 1,190 1,900 3,350 6,840 400 46 97 182 373 560 1,080 1,720 3,040 6,190 450 42 89 167 344 515 991 1,580 2,790 5,700 500 40 83 156 320 479 922 1,470 2,600 5,300 550 37 78 146 300 449 865 1,380 2,440 4,970 600 35 73 138 283 424 817 1,300 2,300 4,700 650 33 70 131 269 403 776 1,240 2,190 4,460 700 32 66 125 257 385 741 1,180 2,090 4,260 750 30 64 120 246 368 709 1,130 2,000 4,080 800 29 61 115 236 354 681 1,090 1,920 3,920 850 28 59 111 227 341 656 1,050 1,850 3,770 900 27 57 107 220 329 634 1,010 1,790 3,640 950 26 55 104 213 319 613 978 1,730 3,530
1,000 25 53 100 206 309 595 948 1,680 3,420 1,100 25 52 97 200 300 578 921 1,630 3,320 1,200 24 50 95 195 292 562 895 1,580 3,230 1,300 23 48 90 185 277 534 850 1,500 3,070 1,400 22 46 86 176 264 509 811 1,430 2,930 1,500 21 44 82 169 253 487 777 1,370 2,800 1,600 20 42 79 162 243 468 746 1,320 2,690 1,700 19 40 76 156 234 451 719 1,270 2,590 1,800 19 39 74 151 226 436 694 1,230 2,500 1,900 18 38 71 146 219 422 672 1,190 2,420 2,000 18 37 69 142 212 409 652 1,150 2,350
Note: All table entries are rounded to 3 significant digits.
TABLE 27. PROPANE VAPOR SEMIRIGID COPPER TUBING SIZING
Gas: Undiluted Propane Inlet Pressure: 11.0 in. w.c.
90 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 95
Appendix A. Fuel Line Selection12-2016
Pressure Drop: 0.5 in. w.c. Specific Gravity: 1.50
INTENDED USE: Tube Sizing Between Single- or Second-Stage (Low-Pressure)
Regulator and Appliance
Tube Size (in.)
Nominal
K & L:
14 38 12 58 34 1 114 112 2
Nominal
ACR:
Outside: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125
Inside:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
Length
38 12 58 34 78 118 138
Capacity in Thousands of BTU per Hour
(ft.)
10 45 93 188 329 467 997 1,800 2,830 5,890
20 31 64 129 226 321 685 1,230 1,950 4,050
30 25 51 104 182 258 550 991 1,560 3,250
40 21 44 89 155 220 471 848 1,340 2,780
50 19 39 79 138 195 417 752 1,180 2,470
60 17 35 71 125 177 378 681 1,070 2,240
70 16 32 66 115 163 348 626 988 2,060
80 15 30 61 107 152 324 583 919 1,910
90 14 28 57 100 142 304 547 862 1,800 100 13 27 54 95 134 287 517 814 1,700 125 11 24 48 84 119 254 458 722 1,500 150 10 21 44 76 108 230 415 654 1,360 175 NA 20 40 70 99 212 382 602 1,250 200 NA 18 37 65 92 197 355 560 1,170 250 NA 16 33 58 82 175 315 496 1,030 300 NA 15 30 52 74 158 285 449 936 350 NA 14 28 48 68 146 262 414 861 400 NA 13 26 45 63 136 244 385 801 450 NA 12 24 42 60 127 229 361 752 500 NA 11 23 40 56 120 216 341 710 550 NA 11 22 38 53 114 205 324 674
91A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 96
Appendix A. Fuel Line Selection 12-2016
600 NA 10 21 36 51 109 196 309 643 650 NA NA 20 34 49 104 188 296 616 700 NA NA 19 33 47 100 180 284 592 750 NA NA 18 32 45 96 174 274 570 800 NA NA 18 31 44 93 168 264 551 850 NA NA 17 30 42 90 162 256 533 900 NA NA 17 29 41 87 157 248 517 950 NA NA 16 28 40 85 153 241 502
1,000 NA NA 16 27 39 83 149 234 488 1,100 NA NA 15 26 37 78 141 223 464 1,200 NA NA 14 25 35 75 135 212 442 1,300 NA NA 14 24 34 72 129 203 423 1,400 NA NA 13 23 32 69 124 195 407 1,500 NA NA 13 22 31 66 119 188 392 1,600 NA NA 12 21 30 64 115 182 378 1,700 NA NA 12 20 29 62 112 176 366 1,800 NA NA 11 20 28 60 108 170 355 1,900 NA NA 11 19 27 58 105 166 345 2,000 NA NA 11 19 27 57 102 161 335
NA: A flow of less than 10,000 BTU/hr. Note: All table entries are rounded to 3 significant digits. *Table capacities are based on Type K copper tubing inside diameter (shown), which has the
smallest inside diameter of the copper tubing products.
TABLE 29. PROPANE SCHEDULE 40 IRON PIPE SIZING, LIQUID WITHDRAWAL
(MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS PER HOUR)*
Schedule 40 Iron Pipe Size (in.): Nominal (Inside Diameter)
Equivalent
Length
of Pipe (ft.)
1/2
(0.622)
3/4
(0.824
)
1
(1.049)
1 1/4
(1.38)
1 1/2
(1.61)2(2.067)3(3.068
)
3 1/2
(3.548)4(4.026
)
30 733 1,532 2,885 5,924 8,876 17,094 48,16470,519 98,23
8
40 627 1,311 2,469 5,070 7,597 14,630 41,22260,355 84,07
9
92 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 97
Appendix A. Fuel Line Selection12-2016
Schedule 40 Iron Pipe Size (in.): Nominal (Inside Diameter)
Equivalent
Length
of Pipe (ft.)
1/2
(0.622)
3/4
(0.824
)
1
(1.049)
1 1/4
(1.38)
1 1/2
(1.61)2(2.067)3(3.068
)
3 1/2
(3.548)4(4.026
50 556 1,162 2,189 4,494 6,733 12,966 36,53453,492 74,51
60 504 1,053 1,983 4,072 6,100 11,748 33,10348,467 67,51
70 463 969 1,824 3,746 5,612 10,808 30,45444,589 62,11
80 431 901 1,697 3,484 5,221 10,055 28,33141,482 57,78
90 404 845 1,593 3,269 4,899 9,434 26,58338,921 54,22
100 382 798 1,504 3,088 4,627 8,912 25,11036,764 51,21
)
8
9
6
7
0
6
150 307 641 1,208 2,480 3,716 7,156 20,16429,523 41,12
8
200 262 549 1,034 2,122 3,180 6,125 17,25825,268 35,20
0
250 233 486 916 1,881 2,819 5,428 15,29522,395 31,19
8
300 211 441 830 1,705 2,554 4,919 13,85920,291 28,26
7
350 194 405 764 1,568 2,349 4,525 12,75018,667 26,00
6
400 180 377 711 1,459 2,186 4,209 11,86117,366 24,19
3
450 169 354 667 1,369 2,051 3,950 11,12916,295 22,70
0
500 160 334 630 1,293 1,937 3,731 10,51215,391 21,44
2
600 145 303 571 1,172 1,755 3,380 9,525 13,946 19,42
8
700 133 279 525 1,078 1,615 3,110 8,763 12,830 17,87
3
800 124 259 488 1,003 1,502 2,893 8,152 11,936 16,62
8
93A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 98
Appendix A. Fuel Line Selection 12-2016
Schedule 40 Iron Pipe Size (in.): Nominal (Inside Diameter)
Equivalent
Length
of Pipe (ft.)
1/2
(0.622)
3/4
(0.824
)
1
(1.049)
1 1/4
(1.38)
1 1/2
(1.61)2(2.067)3(3.068
)
3 1/2
(3.548)4(4.026
)
900 116 243 458 941 1,409 2,715 7,649 11,199 15,60
1
1000 110 230 433 889 1,331 2,564 7,225 10,579 14,73
7
1500 88 184 348 713 1,069 2,059 5,802 8,495 11,83
4
2000 76 158 297 611 915 1,762 4,966 7,271 10,12
8
*Pipe size recommendations are based on schedule 40 black iron pipe.
FIGURE 32. MINIMUM LPG TANK SIZE (50% FULL) REQUIRED TO MAINTAIN 5 PSIG
AT SPECIFIC WITHDRAWAL RATE AND MINIMUM EXPECTED WINTER TEMPERATURE
94 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Page 99

Appendix B. Outline and System Drawings

Table of Contents
Figure 33. Generator Set Outline (Sheet 1 of 4) ........................................................................................ 97
Figure 34. Generator Set Outline (Sheet 2 of 4) ........................................................................................ 98
Figure 35. Generator Set Outline (Sheet 3 of 4) ........................................................................................ 99
Figure 36. Generator Set Outline (Sheet 4 of 4) ...................................................................................... 100
95A053X172 (Issue 6) Copyright © 2016 Cummins Inc.
Page 100
Appendix B. Outline and System Drawings 12-2016
The drawings included in this section are representative. For current complete information, refer to the drawing package that was shipped with the unit.
96 A053X172 (Issue 6)Copyright © 2016 Cummins Inc.
Loading...