DIESEL GENERATING SETS
INSTALLATION RECOMMENDATIONS
AND OPERATIONS MANUAL
HEAD OFFICE
AKSA JENERATÖR SAN.A.Ş.
Rüzgarlıbahçe Mah. Selvi Çıkmazı No:10
34805, Kavacık - Beykoz / İSTANBUL
T : +90 216 444 4 630 F : +90 216 681 57 81
aksa@aksa.com.tr
AUTHORIZED SERVICE
AKSA SERVICE & SPARE PARTS
Muratbey Beldesi, Güney Girisi Caddesi
No: 8 34540 Çatalca/ISTANBUL
T: +90 212 887 11 11
F: +90 2I2 887 10 20
info@aksaservis.com.tr
Page 2
1. INTRODUCTION .................................................................................................................. 1
1.1. Receipt Of The Genset .................................................................................................................................... 1
1.2. Diesel Genset And Its Equipments ............................................................................................................ 2
1.3. Installation That Should Be Done By Customer ................................................................................ 2
1.4. Personnel Classification, Who Will Do Maintenance, Adjustments and Repair .............. 2
1.5. Environmental Protection ................................................................................................................................ 3
1.6. Using Gensets Efficiently ................................................................................................................................... 3
2. GENERAL SAFETY PRECAUTIONS .................................................................................. 3
2.1. General ....................................................................................................................................................................... 3
2.2. Installation Handling And Towing ............................................................................................................... 4
2.3. Fire And Explosion .............................................................................................................................................. 4
2.4. Mechanical ................................................................................................................................................................ 4
2.5. Chemical .................................................................................................................................................................... 5
2.6. Noise ........................................................................................................................................................................... 5
2.7. Electrical ..................................................................................................................................................................... 5
2.8. First Aid For Electric Shock ............................................................................................................................. 6
3. GENERAL DESCRIPTION .................................................................................................... 6
3.1. Generator Set Description And Identification ..................................................................................... 6
3.2. Generator Set Main Parts ................................................................................................................................ 7
3.3. Diesel Engine ........................................................................................................................................................... 7
3.4. Engine Electrical System .................................................................................................................................... 8
3.5. Cooling System ...................................................................................................................................................... 8
3.6. Synchronous Alternator.................................................................................................................................... 8
3.7. Coupling ..................................................................................................................................................................... 8
3.8. Fuel Tank And Base Frame ............................................................................................................................. 8
3.9. Vibration Isolation ................................................................................................................................................ 8
3.10. Silencer And Exhaust System ........................................................................................................................ 8
3.11. Control System ...................................................................................................................................................... 8
4. ELECTRIC STARTING SYSTEM .......................................................................................... 8
4.1. Battery Systems ..................................................................................................................................................... 8
4.2. Maintenance Batteries ........................................................................................................................................ 9
4.3. Maintenance Free Batteries ............................................................................................................................ 10
4.4. Starting Aids ............................................................................................................................................................. 10
5. HEALTHY AND SAFETY ...................................................................................................... 10
5.1. Fire Protection ........................................................................................................................................................ 10
5.2. Exhaust Gases ......................................................................................................................................................... 11
5.3. Moving Parts ............................................................................................................................................................ 11
5.4. Hazardous Voltages ............................................................................................................................................ 11
5.5. Water .......................................................................................................................................................................... 11
5.6. Coolant And Fuel ................................................................................................................................................. 12
Page 3
6. GENERATING SET CONTROL SYSTEM ......................................................................... 12
6.1. Control System P732 ......................................................................................................................................... 12
6.2. Control System P602 ......................................................................................................................................... 13
6.3. Icons And LCD Identification ........................................................................................................................ 15
6.4. Battery Charger ..................................................................................................................................................... 16
6.5. Control System Options .................................................................................................................................. 16
6.6. Heaters ....................................................................................................................................................................... 16
6.7. Electric Fuel Transfer Pump ............................................................................................................................ 16
6.8. Voltage / Frequency Adjustment ................................................................................................................. 16
7. USE REQUIREMENTS ............................................................................................................ 16
7.1. General Precautions And Controls Which Must Be Done Before Starting
Up The Generating Set ..................................................................................................................................... 16
7.2. General Precautions And Controls Which Must Be Done After Starting
Up The Generating Set ..................................................................................................................................... 17
8. LUBRICATING OIL ................................................................................................................ 17
8.1. Oil Performance Properties ........................................................................................................................... 17
8.2. Lubrication Oil Recommendation For Doosan .................................................................................. 17
9. GENERATOR SET MAINTENANCE ................................................................................. 20
9.1. Maintenance Schedule For Gensets .......................................................................................................... 20
9.2. Maintenance Interval Chart............................................................................................................................. 20
10. ENGINE TROUBLESHOOTING.........................................................................................21
11. ALTERNATOR DESCRIPTION ........................................................................................... 23
11.1. General ....................................................................................................................................................................... 23
11.2. Construction And Components .................................................................................................................. 23
11.3. Operation ................................................................................................................................................................. 23
11.4. Automatic Voltage Regulator ........................................................................................................................ 23
11.5. Alternator Insulation Test ................................................................................................................................ 23
11.6. Meccalte Alternator Troubleshooting ...................................................................................................... 24
12. STORAGE .................................................................................................................................24
12.1. Engine Storage ........................................................................................................................................................ 24
12.2. Alternator Storage ............................................................................................................................................... 26
12.3. Battery Storage ...................................................................................................................................................... 26
13. WARRANTY ............................................................................................................................ 26
14. GENERAL PRECAUTIONS ..................................................................................................27
15. CUSTOMER RESPONSIBILITY ............................................................................................ 28
ATTACHMENTS
- CONTROL PANEL WIRING DIAGRAM
- AKSA JENERATÖR AUTHORIZED SERVICE POINTS
- AKSA JENERATÖR WHERE TO BUY ABROAD
- CERTIFICATIONS
- WARRANTY CERTIFICATE
Page 4
1. INTRODUCTION
Aksa Generator set is designed to be commissioned, when delivered, as soon as the necessary cooling wa­ter, antifreeze, fuel, lubrication oil and fully charged battery are provided.
With its long years of experience, Aksa manufactures
efficient, reliable and quality generator set. This operating and maintenance manual is prepared to assist the operator in operation and maintenance of the generator set. Observing the advices and ru­les in this manual will ensure that the generator set
operates in maximum performance and efficiency for
a long time.
Figure 1. Aksa Generator Set Dataplate
If any help is needed, Please consult AKSA Service &
Spare Parts or Authorized AKSA Service department.
1) Care should be taken to perform more frequent maintenance in dirty and dusty environments in order to keep the generator set in good working condition.
2) Necessary adjustment and repairs should be made only by authorized and qualified persons.
3) Each generator set has a model and a serial num­ber indicated on a label on the base frame. This plate also indicates the manufacturing date, voltage, current,
power in kVA and kW, frequency, power factor and
weight of the generator set. These data are necessary in spare part orders, for warranty validity and for ser­vice calls.
4) Make sure that recommended oil, fuel and coolant are used.
5) Use original spare parts for engine and generator.
6) Contact AKSA authorized service in any case.
7) Take necessary precautions for safety during instal­lation.
8) Diesel Generating sets are produced according to ISO 8528.
9) Open Sets are not designed for outdoor use. Open Genset should be used under the carcass buildings or shelters that protects from rain etc. because of inade­quate noise level attenuation of this structures.
1.1. Diesel Gensets and its Equipments
Diesel Gensets and their standard equipments are sent from the factory on trucks. Open type and canopy type Gensets equipments are mentioned below.
Open sets
• Diesel engine and alternator are mounted on the
base frame via anti vibration mounting (AVM).
• Engine mounted radiator and fan
• Base frame includes a fuel tank
• External fuel tanks for the Genset above 825 kVA
• Fuel pipes
• Batteries, battery stand and connection cables
• Industrial type exhaust silencer is sent by the Genset
Canopy sets
• Diesel engine and alternator are mounted on the
base frame via anti vibration mounting (AVM).
• Sound insulation canopy
• Engine mounted radiator and fan
• Base frame includes a fuel tank
• External fuel tanks for the Genset above 825 kVA
• Fuel pipes
• Batteries, battery stand and connection cables
• Exhaust silencers are residential type and inside the
canopy until the 1000 kVA .Silencers are loose supply by Gensets with all mounting parts above 1000 kVA.
According to customer requirements, noise level atte­nuators, ventilation ducks louvers, special silencers are offered.
1
Page 5
Gensets are ready to use. Genset will be ready to run after its oil, coolant and fuel are filled and power cables are provided and then connected. First start has to be done by authorized person from Aksa service; other­wise the warranty will be invalid. After all connection and checks are done by authorized Aksa service, Gen­set will be run and given in to the customer.
1.2. Receipt of the Gensets
When you have received the Genset check the Gen­set to see whether it’s in good condition or not and all equipments are given or mounted. If the Genset won’t be used for a while, it has to be stored in a good storage.
Warning; if you see any missing or broken parts during
the delivery ,note all this into transportation receipt and make it signed by carrier ,if missing or broken parts are found after receipt ,spare them and contact the transportation company for complaint procedure. Mis­sing and damaged parts are not in warranty.
1.3. Installation that should be done by customer
Transportation and installation of the Gensets and its equipments are customer responsibility. Aksa or Aksa authorised service offer turnkey project according to customer requirement after doing neces-
sary exploration.
The person who will transport and install the Gensets,
should be qualified, experienced and authorised to do
this mission. AKSA also gives supervisor support to the customer for proper installation. Below requirements have to be done by customer or a qualified person before first start of the Gensets,
• Gensets room and floor have to be prepared as
mentioned in this manual.
• Necessary equipments for exhaust system have to be prepared. Exhaust system has to be done by an experienced and authorised person.
• Air duct, flexible joint (canvas), and louvers prepara-
tion have to be done by customer and installed by an
experienced person.
• Foundation has to be prepared according to instal-
lation manual.
• Fuel system installation has to be done by an experi­enced person according to local regulations.
• Preparation for protection equipments against fire
have to be done.
• Proper size power and control cables have to be
prepared according to the Manual and make the cab-
ling done by experienced electrician.
• The load that will be powered by Gensets, have to be separated by an experienced electrician in distribu-
tion panel.
• To supply Generator/Mains power transfer panel
supply and ensure the system is installed by an aut­horized person.
• Coolant, oil and fuel have to be supplied as mentio­ned in O&M manuals.
After all above preparations are done, AKSA service is called for the first start. After all checks are done, Gensets will be started and loaded by ASKA service personnel, and given in to the customer with receipt form.
1.4. Personnel classification, who will do maintenan­ce, adjustments and repair
The generator set should only be operated by person­nel who are authorized and trained. Only people that have the right skills should be allo­wed to operate, adjust, perform maintenance or repair on Aksa Jeneratör equipment. It is the responsibility of management to appoint operators with the appropria­te training and skill for each category of job.
Skill level1: Operator An operator is trained in all aspects of operating the unit with the push- buttons, and trained to know the safety aspects.
Skill level 2: Mechanical technician A mechanical technician is trained to operate the unit the same as the operator. In addition, the mechani­cal technician is also trained to perform maintenance and repair, as describe in the instruction manual, and is allowed to change settings of the control and safety system. A mechanical technician does not work on live electrical components.
Skill level 3: Electrical technician An electrical technician and has the same qualifications
2
Page 6
as both the operator and the mechanical technician. In addition, the electrical technician may carry out elect­rical repairs within the various enclosures of the unit. This includes work on live electrical components. Skill level 4: Specialist from the manufacturer This is skilled specialist sent by the manufacturer or its
agent to perform complex repairs or modifications to
the equipment. In general it is recommended that not more than two people operate the unit, more operators could lead to un safe operating conditions. Take necessary steps to keep unauthorized person away from the unit and eliminate all possible source of danger at the unit. The manufacturer does not accept any liability for any da­mage arising from the use of non-original parts and for modifications, additions or conversions made without the manufacturer’s approval in writing.
1.5. Environmental Protection
Chose the Gensets installation location very carefully in order to not disturb the anyone, and not to cause noise pollution. If the location is not appropriate, the Gensets rooms have to be insulated for noise reducti-
on and also critical type exhaust silencer could be used
if necessary. Engine oil should be collected in a tank, not to be drained to drainage or floor. Learn how the oils are collected from oil supplier and deliver it to tho­se companies. Prevent oil and fuel from contaminating environment, If the Gensets will be located in a wood or coppice, necessary precautions have to be taken against fire. Around of the Gensets should be cleaned carefully.
Expired and damaged batteries should be sent back
to the battery supplier. Batteries could be recycled, so that poisonous waste, acid and lead are prevented from polluting the environment.
1.6. Using Gensets efficiently;
To ensure the efficient fuel consumption;
• Ventilation of the Gensets have to be done as desc­ribed in this Manual.
• Maintenance of the Gensets should be done in time.
• Do not over load the Gensets, it will decrease en-
gine life.
• Worn parts (pistons ,piston rings ,bearings ,liners
etc.) should be replaced
• Injectors should be clean and adjusted.
• Air filter should be clean
• Engine valve adjustment should be done in time.
• Do not load the engine less than 30%of prime po-
wer, it will increase the fuel consumption, oil consump­tion and damage the engine. If above instructions are followed, Gensets fuel con­sumption efficiency will be increased.
2. GENERAL SAFETY PRECAUTIONS
2.1. General
The generator set is designed to be safe when used in correct manner. However responsibility for safety rests with the personnel who install, use and maintain the set. If the following safety precautions are followed, the possibility of accidents will be minimized. Before performing any procedure or operating technique, it is up to the user to ensure that it is safe. The generator set should only be operated by personnel who are aut­horized and trained.
WARNING ! Read and understand all safety precautions and war­nings before operating or performing maintenance on the generating set. ! Failure to follow the instructions, procedures, and sa­fety precautions in this manual may increase the possi­bility of accidents and injuries. ! Do not attempt to operate the generating set with a known unsafe condition. ! If the generating set is unsafe, put danger notices and disconnect the battery negative (-) lead so that it can­not be started until the condition is corrected. ! Disconnect the battery negative (-) lead prior to at­tempting any repairs or cleaning inside the enclosure. ! Install and operate this generating set only in full compliance with relevant National, Local or Federal Codes, Standards or other requirements.
3
Page 7
2.2. Handling and Towing
The following safety precautions should be noted:
WARNING
! Make electrical connections in comp­liance with relevant Electrical Codes, Standards or other requirements. This includes requirements for grounding and ground/earth faults. ! For stationary generating sets with remote fuel sto­rage systems, make sure such systems are installed in compliance with relevant Codes, Standards or other requirements.
! Engine exhaust emissions are hazardous to person­nel. The engine exhaust for all indoor generating sets
must be piped outdoors via leak-free piping in compli­ance with relevant Codes, Standards and other requirements. Ensure that hot exhaust silen­cers and piping are clear of combustible material and are guarded for personnel protection per safety requ-
irements. Ensure that fumes from the exhaust outlet
will not be a hazard. ! Never lift the generating set by attaching to the engi­ne or alternator lifting lugs, instead use the lifting points on the base frame or canopy. ! Ensure that the lifting rigging and supporting structure is in good condition and has a capacity suitable for the load. ! Keep all personnel away from the generating set when it is suspended. ! When mobile generating set, observe all Codes, Stan­dards or other regulations and traffic laws. These inc­lude those regulations specifying required equipment
and maximum and minimum speeds.
! Do not permit to ride on the mobile generating set, Do not permit personnel to stand or ride on the draw­bar or to stand or walk between the generating set and towing vehicle, ! Do not install and operate a Genset in an area that is classified as dangerous , if necessary precautions are not taken ! Please follow the instruction written in the ‘Diesel Gen-Set Installation Recommendation Manuel,
2.3. Fire and Explosion
Fuel and fumes associated with genera­ting sets can be flammable and poten-
tially explosive. Proper care in handling
these materials can dramatically limit the
risk of fire or explosion. However, safety dictates that fully charged BC and ABC fire extinguishers are kept
on hand. Personnel must know how to operate them.
WARNING
! Ensure that the generating set room is properly ven­tilated. ! Keep the room, the floor and the generating set clean.
When spills of fuel, oil, battery electrolyte or coolant
occur, they should be cleaned up immediately. ! Never store flammable liquids near the engine. ! Do not smoke or allow sparks, flames or other sour­ces of ignition around fuel or batteries. Fuel vapors are
explosive. Hydrogen gas generated by charging batte­ries is also explosive.
! Turn off or disconnect the power to the battery char­ger before making or breaking connections with the battery. ! To avoiding arcing keep grounded conductive objects
(such as tools) away from exposed live electrical parts
(such as terminals). Sparks and arcing might ignite fuel or vapors. ! Avoid refilling the fuel tank while the engine is running. ! Do not attempt to operate the generator set with any known leaks in the fuel system.
! There has to be an emergency exit for the staff in
the case of fire.
2.4. Mechanical
The generating set is designed with guards for pro­tection from moving parts. Care must still be taken to protect personnel and equipment from other mecha­nical hazards when working around the generating set.
WARNING
! Do not attempt to operate the generating set with the safety gu­ards removed. While the genera­ting set is running do not attempt
4
Page 8
to reach under or around the guards to do maintenan­ce or for any other reason. ! Keep hands, arms, long hair, loose clothing and jewe­lers away from pulleys, belts and other moving parts.
Attention: Some moving parts cannot be seen clearly when the set is running. ! If equipped keep access doors on enclosures closed and locked when not required to be open.
! Avoid contact with hot oil, hot coolant, hot exhaust
gases, hot surfaces and sharp edges and corners.
! Wear protective clothing including gloves and hat
when working around the generating set. ! Do not remove the radiator filler cap until the co­olant has cooled. Then loosen the
cap slowly to relieve any excess
pressure before removing the cap completely.
2.5. Chemical
Fuels, oils, coolants, lubricants and battery electrolyte used in this generating set are typical of the industry. However, they can be hazardous to personnel if not treated properly.
WARNING
! Do not swallow or allow skin con­tact with fuel, oil, coolant, lubricants or battery electrolyte. If swallowed, seek medical treatment immediately. Do not induce vomiting if fuel is swal­lowed. For skin contact, wash with soap and water. ! Do not wear clothing that has been contaminated by fuel or lube oil. ! Wear an acid resistant apron and face shield or gogg­les when servicing the battery. If electrolyte is spilled on skin or clothing, flush immediately with large quan­tities of water.
2.6. Noise
Generating sets that are not equipped with sound attenuating enclosures can
produce noise levels in excess of 105 dB(A). Prolonged exposure to noise
levels above 85 dB(A) is hazardous to
hearing.
WARNING
Ear protection must be worn when operating or wor­king around an operating generating set.
2.7. Electrical
Safe and efficient operation of elect­rical equipment can be achieved only if the equipments is correctly instal­led, operated and maintained.
WARNING
! The generating set must be connected to the load only by trained and qualified electricians who are aut­horized to do so, and in compliance with relevant Electrical Codes, Standards and other regulations. ! Ensure that the generating set, including a mobile set is effectively grounded/ earthed in accordance with all relevant regulations prior to operation. ! The generating set should be shutdown with the battery negative (-) terminal disconnected prior to at­tempting to connect or disconnect load connections. ! Do not attempt to connect or disconnect load con­nections while standing in water or on wet or soggy ground. ! Do not touch electrically energized parts of the gene­rating set and/or interconnecting cables or conductors with any part of the body or with any non insulated conductive object.
! Replace the generating set terminal box cover as
soon as connection or disconnection of the load cab­les is complete. Do not operate the generating set without the cover securely in place. ! Connect the generating set only to loads and/ or electrical systems that are compatible with its electrical characteristics and that are within its rated capacity. ! Keep all electrical equipment clean and dry. Replace any wiring where the insulation is cracked, cut, abra­ded or otherwise degraded. Replace terminals that are worn, discolored or corroded. Keep terminals clean and tight. ! Insulate all connections and disconnected wires.
! Use only Class BC or Class ABC extinguishers on
electrical fires.
5
Page 9
2.8. First Aid for Electric Shock WARNING
! Do not touch the victim’s skin with bare hands until the source of electricity has been turned off. ! Switch off power if possible otherwise pull the plug or the cable away from the victim. ! If this is not possible, stand on dry insulating material and pull the victim clear of the conductor, preferably using insulated material such as dry wood. ! If victim is breathing, turn the victim clear of the con­ductor, preferably using insulated material such as dry wood. ! If victim is breathing, turn the victim into the recovery position described below. If victim is unconscious, per­form resuscitation as required;
Open the airway
Tilt the victim’s head back and lift the chin upwards. Remove objects from the mouth or throat (including false teeth, tobacco or chewing gum).
Breathing
Check that the victim is breathing by looking, listening and feeling for the breath.
Circulation
Check for pulse in the victim’s neck.
If no breathing but pulse is present
• Pinch the victim’s nose firmly.
• Take a deep breath and seal your
lips around the victim’s lips.
• Blow slowly into the mouth watching for the chest
to rise. Let the chest fall completely. Give breaths at a rate of 10 per minute.
• If the victim must be left to get help, give 10 breaths
first and then return quickly and continue.
• Check for pulse after every 10 breaths.
• When breathing restarts, place the victim into the
recovery position described later in this section.
If no breathing and no pulse
• Call or telephone for medical help.
• Give two breaths and start chest
compression as follows:
• Place heel of hand 2 fingers breadth
above ribcage/breastbone junction.
• Place other hand on top and inter­lock fingers.
• Keeping arms straight, press down
4-5 cm at a rate of 15 times per minute.
• Repeat cycle (2 breaths and 15 compressions) until
medical helps takes over.
• If condition improves, confirm pulse and continue
with breaths. Check for pulse after every 10 breaths.
• When breathing restarts, place the
victim into the recovery position desc­ribed below.
Recovery position
• Turn the victim onto the side.
• Keep the head tilted with the jaw
forward to maintain the open airway.
• Make sure the victim cannot roll for­wards or backwards.
• Check for breathing and pulse regularly. If either
stops, proceed as above.
WARNING
! Do not give liquids until victim is conscious.
3. GENERAL DECRIPTION
3.1. Generator Set Description and Identification;
Diesel generator sets are independent units for the production of electric power; basically, they comprise a constant voltage synchronous generator driven by an internal –combustion, diesel – four cycle engine. The sets are used for two main purposes:
a- Continuous duty sets
Used to produce electric power for countless requi­rements (motive power, lighting, heating, etc) in areas where other sources or power are unavailable.
b- Emergency duty sets
Used during public network failures, when such failures
6
Page 10
are liable to cause serious trouble to persons or mate­rial or financial damage (i.e. in hospitals, industrial plants with non-stop operating cycles, etc) or to meet peak energy demands.
120V/208, 220/380, 277/480 at 60 Hz. Some diesel engines couldn’t be used as 60 Hz.
Water cooled diesel engines which are produced by
Cummins, are used in AKSA generator Sets
According to their application, the sets are further di­vided into:
- Set for use on land.
- Set for use at sea.
The sets for use on land can be either:
- Stationary sets (fixed installation), or
- Mobile sets (mobile installation) These two types of sets are available in a vast range of versions, for every operating requirement, the main ones being:
01. Hand control generating sets
02. Stand-by generating sets The standard stationary generating set comprises:
• Diesel engine.
• Synchronous generator.
• Coupling.
• Radiator.
• Metal sub-base with vibration isolators.
• Starter batteries.
• Fuel tank within the baseframe.
• External fuel tank (for high power generators).
• Instrument panel.
• Exhaust gas silencer.
Aksa Generator Set has been designed as a complete package to provide superior performance and reliabi­lity. Figure 3.1. Identifies the major components. This figure is of a typical generating set. However, every set will be slightly different due to the size and configuration of the major components. This section briefly describes the parts of the generating set. Further information is provided in later sections of this manual.
Aksa generating sets are an Alternating Current gene­rator, built for continuous running at sites where no
electricity is available (some models are excepted) or
as stand-by in case of interruption of the mains. The generator operates at 230/220 V in line-to-neutral mode and 400/440 V in line-to-line mode. at 50 Hz ,
3.2. Generating Set Main Parts
3 2
4
7
Figure 3.1. Typical generator set configuration
No Description
1. Generator set rating label.
2. Diesel engine.
3. Air filter.
4. Radiator.
5. Alternator.
6. Terminal box.
7. Base frame.
8. Control Panel.
3.3. Diesel Engine
The diesel engine powering the generator set (Item 2) has been chosen for its reliability and the fact that it has been specifically designed for powering generator sets. The engine is of the heavy duty industrial type with 4 stroke compression ignition and is fitted with all accessories to provide a reliable power supply. These accessories include, among others, a cartridge type dry air filter (item 3) and a mechanical or an electronic engine speed governor. The engine cylinder block is cast in one piece cast iron, vertical cylinders inline overhead valves and camshaft in block. The cylinder heat is made of special cast iron. The thermally loaded flame plate is efficiently water cooled. The crankshaft is forged in one piece in high tensile steel. Lubrication: forced lubrication via gear pump, special
Spin-on filters, lubricant cooling via heat exchanger.
7
8
5
6
1
Page 11
3.4. Engine Electrical System
The engine electrical system is 12 volt or 24 volts DC, negative ground/earth. This system includes an electric engine starter, a battery and a battery charging alterna­tor. For 12 volts electrical system one battery is given. For 24 volt system two lead-acid batteries are given. Other types of batteries may be fitted if they were specified. Batteries are detailed in Section 4.
3.5. Cooling System
The engine cooling system is water cooled. The water cooled system is comprised of a radiator (item 4) a pusher fan and thermostat. The alternator has its own internal fan to cool the alternator components.
3.9. Vibration Isolation
The generator set is fitted with vibration isolators which are designed to reduce engine vibration being transmitted to the foundation on which the generator set is mounted. These isolators are fitted between the engine /alternator feet and the base frame.
3.10. Silencer and Exhaust system
An exhaust silencer is provided loose for installation
with the generating set (for open sets). The silencer
and exhaust system reduce the noise emission from the engine and can direct exhaust system reduce the noise emission from engine and can direct exhaust ga-
ses to safe outlets.
3.6. Synchronous Alternator
Horizontal axle alternator (synchronous three phase),
on rolling bearings, self-ventilated within the room with low-loss silicon-sheet stator bundle, electrolytic copper winding with class H insulation. Case –type damper winding for parallel operation (on high-powered alternators). The output electrical power is normally produced by IP23 and a screen protected and drip-proof, self-
exciting, self regulating, brushless alternator. (Item 5)
Fine tuned to the output of this generating set. Moun­ted on top of the alternator is a sheet steel terminal
box (item 6)
3.7. Coupling
If Single bearing alternators are used, a special flexible disk is used in place of a flexible coupling. If two bea-
ring alternator is used, Engine and alternator are firmly joined by a coupling cone that guarantees the proper
assembly coaxiality.
3.8. Fuel tank and Base frame
The engine and alternator are coupled together and mounted on a heavy duty steel base-frame (Item 7). This base frame includes a fuel tank with capacity of
approximately 8 hours operation under variable loads.
The tank is complete with filling cap and fuel level ga-
uge and is connected by flexible joints to the intake
piping and to the overflow piping containing fuel from the injector drain. High power Gensets fuel tank is se­parate from set.
3.11. Control System
One of several types of control systems and panels (item 8) may be fitted to control the operation and output of the set and to protect the set from pos­sible malfunctions. Section 6 of this manual provides detailed information on these systems and will aid in identification of the control system fitted on the ge­nerator set.
4. ELECTRIC STARTING SYSTEMS
Electric starting systems are generally used on all gen­sets. Electrical starting system consists of a starter, mo-
unting flange to the flywheel and bendix gear. There
could be 2 starters on big engines. The power source for electric starting systems is a 12V or 24V DC battery system. The starting voltage is de­termined by engine size, 24 VDC being used for larger engines to reduce starting current and hence cable size. Control of starting is via a start solenoid which is controlled by the gen-set control system.
4.1. Battery Systems
Batteries are of two types– lead acid and NiCad. Lead acid batteries are generally used, being the least ex­pensive. NiCad batteries are used where longer life, etc., is required. Batteries are one of the main parts of the Gensets, and it could be said that 90% of the Gensets fault is caused by battery. So it is important to do regular maintenan­ce and checks on batteries. Batteries are mounted on
8
Page 12
the base frames in most of AKSA Gensets. Battery charging systems;
While the Genset is running, batteries are charged by
charging alternator. If the Genset is not running, batteries are charged by battery chargers that powered by mains.
4.2. Maintenance Batteries Warning
- Do not smoke or allow sparks, flames or other sour­ces of ignition around batteries. Hydrogen gas genera-
ted by charging batteries is explosive.
- Wear an acid resistant apron and face shield or gogg-
les when servicing the battery. If electrolyte is spilled on skin or clothing, flush immediately with large quan­tities of water.
- Take out the metallic things in your wrist and protect your wrist and hand.
- Disconnect the battery negative (earth) lead first and reconnect last.
- Always ensure that battery maintenance is carried out in a well ventilated area.
- The starting batteries should be located as close as possible to the generator set while still being accessible for servicing. This will prevent electrical losses.
Adding the first electrolyte in to battery
1. Take out the protective cover above the battery, and vent caps.
2. Add electrolyte to the Battery up to 15mm above the plates. Electrolyte specific gravity should be 1,28 at 20 °C .Battery and electrolyte temperature should be more than 10°C.
3. Wait 15 minutes .the heat will increase between
the plates and bobble will occur above the electrolyte.
4. Fix the vent caps.
5. Check the battery with hydrometer after 15 minu­tes.
6. Minimum charging time is 6 hours. Check the char­ging amps and electrolyte level every one hour .if there is no changing within one hour, it is charged.
7. When the battery is charged, check the electrolyte
level after 2 hour , if the level is decreased add water up to 10 mm above the plates.
Battery Maintenance
• Keep the top of the battery and its terminals clean.
• Cover the battery terminals and its connections with
Vaseline.
• Tighten the terminals but not tighten it hardly.
• Control the electrolyte level periodically. It must be
10 mm above the plates.
• Control the abrasion in the charge alternator belt
and check periodically the belt tension according to producer’ recommendation.
• Ensure that your battery is not uncharged.(please see
the below table).
State of Charge
100%
75%
50%
25%
Discharged
Table 4. 2.1. Typical generator set configuration
Specific Gravity
1.265
1.225
1.190
1.155
1.120
9
Voltage - 12V
12.7
12.4
12.2
12.0
11.90
Page 13
Testing the battery
• Inspect the battery before the test.
• Battery terminals and connections will be corroded
in time. Corrosion will wear the terminals and prevent charging. Disconnect the battery terminals and clean
the oxidation with hot water and then reconnect the
terminals and coat them with Vaseline.
• Don’t allow loose connection.
Hydrometer test
Battery charge situation and the specific gravity of the sulfuric acid could be measured by hydrometer.
1. Don’t use distilled water only use pure water.
2. Insert the hydrometer into electrolyte, hydrometer should stay vertically, Once the hydrometer comes to a rest, observe the plane of the liquid surface. Your eye must be horizontal to this plane Evaluation is mentioned below;
1,270 .......1,280 fully charged
1,220 .......1.230 50% charged
1,150 .......1,220 discharged
4.3. Maintenance Free Batteries
Ensure that all battery connections are correct and batteries are always charged. After that there is not any procedure for this battery.
Control of the Battery;
Conduct an inspection every time before testing the battery.
1. A white powdered element causes abrasion to the pole-heads, its connections. Remove the connections
and wash them with hot water to purify the oxidation.
Reconnect it and coat with Vaseline.
2. Check if any un-tightened connections exist.
4.4. Starting Aids
It is customary to maintain coolant temperatures abo­ve 40°C min. To promote quick starting on an emer­gency generator set and to take the load. Thermosta-
tically controlled external block heaters, deriving their
supply from the primary source of power are fitted in the engine cooling system to provide this heating. Heater warms up the jacket water of the engine when
the generator set is not working.
5. HEALTY and SAFETY
Safety should be the primary concern of the facility de­sign engineer and all personnel engaged on installation and commissioning. Safety involves two aspects:
1) Safe operation of the generator itself (and its ac­cessories).
2) Reliable operation of the system. Reliable operation of the system is related to safety because equipment affecting life and health, such as life support equipment in hospitals, emergency egress lighting, building ventilators, elevators and fire pumps, may depend on the generator set.
5.1. Fire Protection
Diesel Fuel can be stored on the floor in an appropria­te tank .Although the flammability of the diesel is high
, it can still catch fire , so that fire extinguishers have to
be provided in the storage. Foam or CO2 have to be used for diesel , oil , gas etc. For electrical cables and bas bar contactors use CO2 or CTC. Sand could be used for Isolations and small fires. The design, selection and installation of fire protection systems require the following considerations:
• The fire protection system must comply with the
requirements of National Standards.
• Typically, the generator room will be required to
have one hour fire resistance rating. Generator room construction will have to have two hour fire resistance rating.
• Generator room shall not be used for storage pur­poses.
• The authority may specify the quantity, type and si­zes of approved portable fire extinguishers required
for the generator room.
• A manual emergency stop station outside the gene­rator room or enclosure or remote from the genera­tor set in an outside enclosure would facilitate shutting down the generator set in the event of a fire or anot­her type of emergency.
• Generator sets have to be run at full load at least
once a year to prevent the accumulation of diesel in
exhaust system.
10
Page 14
General
• Do not fill fuel tanks when the engine is running,
unless tanks are located outside the generator room.
• Do not permit any flame, cigarette, pilot light, spark,
arcing equipment, or other ignition source near the ge­nerating set or fuel tank.
• Fuel lines must be adequately secured and free of
leaks. Fuel connection at the engine should be made
with an approved flexible line. Do not use copper pi­ping on flexible lines as copper will become brittle if
continuously vibrated or repeatedly bent.
• Be sure all fuel supplies have a positive shut-off.
5.2. Exhaust Gases
• Be sure the exhaust system will properly dispel disc­harged gases a way from enclosed or sheltered areas and areas where individuals are likely to congregate.
• Never connect the exhaust system of two or more
engines.
• Never discharge engine exhaust into a brick, tile or cement block chimney, or a similar structure. Exhaust
pulsations could cause severe structural damage.
• Do not use exhaust gases to heat a compartment.
• Be sure that the unit is well ventilated.
• Ensure that there is independent support for the ex-
haust system. No strain should be imposed on the en-
gine exhaust manifolds. Which is especially important
on a turbocharged engine.
• Exhaust pipes should be logged or protected to pre­vent touching or causing fire.
5.3. Moving Parts
• Tighten supports and keep guards in position over
fans drive belts etc. Make sure that fasteners on the set are secure.
• Keep hands, clothing and jewellery away from mo­ving parts.
• If adjustment must be made while the unit is running, use extreme caution around hot manifolds, moving
parts, etc.
5.4. Hazardous Voltages
Improper wiring can cause fire or electrocution, resul­ting in severe personal injury or death and property or equipment damage. For personal protection, stand on a dry wooden plat­form or rubber insulating mat, make sure clothing and
shoes are dry, remove jewellery from hands and use tools with insulated handles.
• Do not leave cables trailing on the engine room flo­or.
• Do not use the same trunk line for electric cables
and fuel water lines.
• Do not run AC and DC cables in the same looms
or trunk line.
• Always ensure that bonding and equipment earthing
are correctly done. All metallic parts that could be­come energized under abnormal conditions must be properly earthed.
• Always disconnect the batteries and battery charger
when serving or carrying out maintenance particularly on equipment arranged for automatic mains failure operation. Always disconnect a battery charger from its AC source before disconnecting the battery cable. Accidental starting of the generator set while working on it can cause severe personal injury or death.
• Do not tamper with interlocks.
• Electrical connections and installation should be
done by persons trained and qualified
• Do not connect the generator set directly to any
building electrical system.
• Always follow all applicable state and local electrical
codes.
• High voltage sets work differently to low voltage
ones. Special equipment and training is required to work around high voltage equipment. Operation and maintenance must be done only by persons trained and qualified to work on such devices. Improper use or procedures may well result in personal injury or death.
• Do not work on energised equipment. Unauthori­sed personnel must not be permitted near energised equipment. Due to the nature of high voltage electrical equipment includes voltage remains after the equip­ment is disconnected from the power source. Equip­ment should be de-energised and safety earthed.
5.5. Water
Water or moisture inside a generator increases the
possibility of “ flashing” and electrical shock, which can cause equipment damage and severe personal injury or death. Do not use a generator which is not dry inside and out.
11
Page 15
5.6. Coolant and Fuel
The coolant heater must not be operated while the cooling system is empty or when the engine is running or damage to the heater will occur. Coolant under pressure have a higher boiling point than water.
• Do not open a radiator, heat exchanger or header
tank pressure cap while the engine is running. Allow the generator set to cool and bleed the system pres­sure first.
• Never use galvanised or copper fuel lines, fittings or
fuel tanks. Condensation in the thanks and lines com­bines with the sulphur in the fuel to produce sulphuric acid. The molecular structure of the copper or galva­nised lines or thanks reacts with the acid and contami­nates the fuel.
6. GENERATING SET CONTROL SYSTEMS
To control and monitor the generator set, an electro­nic control system has been used. Control panel pro­vides a means of starting and stopping the generating set, monitoring its operation and output and automati­cally shutting down the set in the event of critical con­dition arising such as low oil pressure or high engine temperature.
6.1. Control System P 732
P732 control system is fitted to 220kVA and above generator sets. It is designed to start and stop for all electronic or non–electronic diesel engines Generator Sets automatically , besides control module monitor the mains voltage , frequency and controls the gene­rator set and transfer system. Control, monitor and protection panels are mounted on the generator base frame. “DSE P732 AMF Control Module Operating Manual” is given along with the Gensets.
Equipments
• Control with DSE, model 7320 module.
• Static battery charger.
• Emergency stop push button.
• Relays, terminals etc.
Control Module DSE 7320 Features
• The module monitors mains supply and controls a
standby generating set with automatic transfer switch
• Module indicates operational status and fault conditi­ons by means of its LCD display.
• Microprocessor controlled.
• Front panel programming and also via PC software.
• 132 x 64 pixel LCD display makes information easy
to read.
• Front panel programming and also via PC software.
• Soft touch membrane keypad and five key menu
navigation.
• Remote communication via RS 232, RS 485 and Et­hernet and SMS messaging.
• Event logging (50) showing date and time.
• Engine block heater control.
• Multiple date and time engine exercise mode and
maintenance scheduler.
Controls;
Stop – Manual – Auto – Test – Start – Mute/Lamp test – Transfer to generator – Transfer to mains – Menu navigations buttons.
Instruments via LCD display Engine
• Oil pressure (PSI & Bar)
• Temperature (°C & °F)
• Speed RPM
• Run time
• Battery volts
• Maintenance due
Generator
• Volts (L-L / L-N)
• Currents (L1, L2, L3)
• Frequency (Hz)
• kW
• Cos φ
• kVA, kVAr,
• kWh, kVAh, kVArh
• Phase sequence
Mains
• Volts (L-L / L-N)
• Frequency (Hz)
12
Page 16
Protections Warning
• Charge failure
• Battery under voltage
• Fail to stop
• Low fuel level (opt.)
• kW over load
• Negative phase sequence
• Loss of speed signal
Pre-alarms
• Low oil pressure
• High engine temperature
• Low engine temperature
• Over/Under speed
• Under/over generator frequency
• Under/over generator voltage
• ECU warning
Shut Downs
• Fail to start
• Emergency stop
• Low oil pressure
• High engine temperature
• Low coolant level
• Over/Under speed
• Under/over generator frequency
• Under/over generator voltage
• Oil pressure sensor open
• Phase rotation
DEEP SEA ELECTRONICS
DSE
DSE 7320
AUTO
Figure 6.1. DSE, model 7320 control module
6.2. Control System P 602
Control, supervision and protection panel is mounted on the generator set base frame.
Equipments:
• DSE, model 6020 Automatic Mains Failure module
• Static battery charger
• Emergency stop push button
DSE 6020 Module Features
• Automatic controls generating set, start and stop
• 3 phase generator and mains voltage monitoring
• Transfer between mains and generator power
• LCD display shows the status of the generator at
all time
• 4- line, 64 x 132 graphic display with LED backlight
• PC and front panel configurable
• Easy push button control
Electrical trip
• Earth fault (opt.)
• kW over load
• Generator over current
• Negative phase sequence
LED indication
• Mains available
• Mains on load
• Generator available
• Generator on load
STOP/RESET - MANUAL - AUTOMATIC - TEST ­START
Display Scroll button Page button
Metering via LCD display
• Generator Volt (L-L, L-N)
• Generator Ampere (LI, L2, L3)
• Generator Frequency (Hz)
• Mains Volt (L-L /L-N)
• Mains Frequency
• Engine cooling temperature
• Engine oil pressure
• Engine speed
• Engine hours run
• Engine battery volt
• Event Log (5) events
13
Page 17
Protections Warnings
• Generator High/Low Voltage
• Generator Over/ Under Frequency
• Over/Under Speed
• Engine low oil pressure
• High coolant temperature
• Battery High / Low voltage
• Charge alternator failure
• Fail to stop
Shutdowns
• Generator High/ Low Voltage
• Generator Over/ Under Frequency
• Over /Under Speed
• Engine low oil pressure
• High coolant temperature
• Emergency stop
• Over current
• Fail to start
• Oil pressure sensor open circuit
• Temperature sensor open circuit
LED display
• Mains Available
• Mains On Load
• Generator Available
• Generator On Load
DSE
6020
AUTO
Figure 6.2. DSE, model 6020 control module
14
Page 18
6.3. Icons and LCD Identification;
6.3.1. Push Buttons;
6.3.2. Status / Measurement Units;
6.3.3. Alarm Indications
15
Page 19
6.4. Battery charger
When the Gensets are not running for a long time ,
battery charger is used in order to charge the battery ,Battery charger is powered by mains , and mounted in the control panel. A battery charger ampere indicator can be added to control pane in order to see whether battery charger is working or not . Battery charger is manufactured with switching-mode and SMD technology and ıt has high efficiency. Battery charger models’ output V-I characteristic is very close to square and output is 5 amper, 13,8 V for 12 volt and 27,6 V for 24 V . Input 198 - 264 volt AC. Pro­line 2405 has fully output shot circuit protection and ıt can be used as a current source. Proline 1205/2405 charger has high efficiency, long life, low failure rate, light weight and low heat radiated in accordance with linear alternatives. The charger is fitted with a protec­tion diode across the output. Connect charge fail relay coil between positive output and CF output. They are equipped with RFI filter to reduce electrical noise radi­ated from the device. Galvanic ally isolated input and output typically 4kV for high reliability.
6.5. Control System Options
According to customer request, different options co­uld be added to control system.
• Parallel with mains continuously and black start
system with mains.
• Automatic synchronizing and power control system
(Multi Gensets parallel).
• Load sharing system (scada).
• Remote monitoring and control.
• Remote alarm panel.
• Backup generator system.
6.6. Heaters
Alternator heaters could be mounted on the alterna­tor stators to keep it dry and protect it from humidity and a heater could be mounted in the control panel to prevent it against humidity too.
6.7. Electric Fuel Transfer Pump
Electric Fuel Transfer Pump could be necessary to pump the fuel from main tank to daily tank .Pump control circuit is mounted in the control panel.
6.8. Voltage / Frequency Adjustment
A potentiometer could be mounted in the control pa­nel to adjust the frequency or voltage or both of them. Frequency adjustment potentiometer is connected the electronic governor control module.
7. USE REQUIREMENTS
7.1. General Precautions And Controls Which Must Be Done Before Starting Up The Generating Set
• Make a general visual inspection on the engine and
alternator. Check if there is any breakage, crack, inden­tation, leakage or looseness. Never operate the gene­rating set before removing any fault, if any.
• Take out foreign materials such as keys, tools, clea­ning wool, papers etc. on the engine and the alternator.
• Check the fuel level in day tank. Refill with fuel if it
is low.
• Check the oil level on the dipstick. Refill with an
appropriate oil if it is low. Oil level normally must be
close to the maximum level line.
• Look at the water level by opening the radiator tap. If it is inadequate add more water. Water level must be
30 mm lower than the water filling neck.
• Engine cooling water must include antifreeze accor­ding to the coolest weather conditions in the area. A
mixture of 50% antifreeze and 50% water provides a
good protection in all area.
• Inspect the radiator air outlet hood, open if clogged
and clear away all obstructions in front of the air outlet.
• Check the air filter gauge. Clean or replace air filter,
if necessary.
• Keep the inlet opening open.
• Make sure that the generating set can easily take air
from the environment.
• Check the battery connection cables. Take care to
tighten the loosened battery terminals with spanner and, cover with special substance and keep clean in
order to avoid oxidation.
• Open the battery caps and check the liquid level in
the cells for maintenance type battery. Add distilled water, if necessary, so as to be 1 cm higher than the separation. Never fill the cells with tap water, acid wa­ter or acid.
• Check if the circuit breaker outlet switch is in OFF
position. (For manually operated Genset).
16
Page 20
• Make sure that the emergency stop button is not
pressed.
7.2. General Precautions And Controls Which Must Be Done After Starting Up The Generating Set
• Check for any abnormal noise or vibration on the
generating set.
• Check if the exhaust system has any leakage.
• Monitor the generating set operation by means of
the control module LCD display. Check the engine temperature and oil pressure Oil pressure must reach the normal value 10 seconds after the generating set operation.
• Monitor the generating set outlet voltage and fre­quency by means of the control module LCD display. Check the voltage, if the voltage between phases is 400 V. and between phase and neutral is 230 V. Volta­ge is adjusted in the factory , do not try to readjust it.
• Check that the frequency is 51 - 52 Hz on generating
sets with mechanical governors and 50Hz on genera­ting sets with electronic governors.
• If an engine block water heater is not available, run
the generating set at no-load for 3-5 minutes and when the engine warm than apply on load (for manual models)
Apply load to the generating set as follows on manual mode
• Set the alternator outlet circuit breaker on the panel
to ON position.
• Set the load circuit beakers (or fuses) on the distri­bution panel to ON position one by one. This way, the generating set cannot be suddenly put under full load. Otherwise, the engine stalling or alternator winding in­sulation of formation or burning can occur.
• Set the alternator outlet circuit breaker on the circuit
to OFF position before stop the generating set.
• Continue to run the unloaded engine for purpose of
cooling period for 2 minutes and then stop.
• Never operate the generating set before removing
any fault, if any.
• Check the oil / coolant/fuel leakage while engine is
running.
• Never run the engine below 30%of prime power
for a long time.
• Share the load on every phase (U,V,W) equally.
• On automatic controlled gen set load will be on and
off automatically.
8. LUBRICATING OIL
Oil system of diesel engine is one of the most impor­tant elements of the engine. Correctly made engine overhaul (this subject includes oil change periods, filter change periods, paying attention about selecting the true type of oil) prolongs the life cost of the engine.
8.1. Oil Performance Properties
The American Petroleum Institute (API) the American Society for Testing and Materials (ASTM) and Society of Automotive Engineers (SAE) has developed and preserved a system in order to classify the lubrication oils for their performance categories
8.2. Lubrication Oil Recommendations for Cummins Diesel Engines
Cummins recommends that high quality multi grade
SAE 15W/40 high service engine oil in diesel engines
are used. At ambient temperatures above –15 °C is
15W40.
The minimum API oil quality levels recommended for use is CH / CI-4, CH or CI-4 can be used in areas where CF4 oil is not yet available, but the oil interval must be reduced API CA, CB, CC, CD, CE, CG4 categories not recommended, do not use.
Ambient Temparatures ° F
-40 -20 0 20 40 60 80 100 120 140
All Seasons
All Seasons
Winter Conditions
Winter Conditions
Arclic Conditions
0W30
-40 -30 -20 -10 0 10 20 30 40 50 60
5W40-15W40
CI-4-10W30
10W30
5W30
Ambient Temparatures ° C
Fig.8.1. Recommended SAE Oil Viscosity Grades v.s. Ambient Temperatures
17
Page 21
Generating Set,
50 Hz, 400V
Oil Specifications
Model
AC 55
AC 66
AC 110
AC 150
AC 170
AC 200
AC 250
AC 350
AC 400
AC 500
AC 550
AC 700
AC 825
AC 880
AC 1100
AC1100K
AC 1410
AC 1675
AC 2250
AC2500
AC3000
Standby
Power
kVA
55
66
110
150
170
200
250
350
400
500
550
700
825
880
1100
1100
1410
1675
2250
2500
3000
Cummins
Engine
Model
S3,8-G6
S3,8-G7
6BTA 5.9-G5
6BTAA5,9G6
6BTAA5,9G7
6CTA 8,3-G2
6CTAA 8,3-G2
QSL9-G5
NTA 855-G4
QSX 15-G6
QSX 15-G8
VTA 28-G5
VTA 28-G6
QSK 23-G3
QST 30-G4
KTA38G5
KTA 50-G3
KTA 50-G8
QSK 60-G4
QSK 60-G13
QSK 78-G9
Fuel
at Full Load
Consumption
Capacity
Fuel Tank
Coolant
Capacity
L/h Liter Liter Liter
14,5
100
12,8
16,5
240
14,7
19,8
240
25
21,4
470
35
21,4
470
37
27
380
40
45
470
51,8
28,6
470
63
66
700
76
66
850
95,9
66
850
103
170
1000
140
170
1000
164
120
1500
161
342
1500
202
350
1500
209
415
2000
261
420
2000
289
500
2000
394
399
528
2000
2000
-
-
Not; Lubricating oil viscosity level will be chosen from Figure 7.1 according to the ambient temperature
Oil Capacity
11
11
16,4
16,4
16,4
23,8
23,8
26,5
38,6
91
91
83
83
103
154
135
177
204
280
280
466
API CH API CI-4 API CF4
Table 8.2. Fuel consumption and coolant, fuel and lubricating oil capacities and lubricating oil specifications (50 Hz Open Gen-sets).
18
Page 22
Generating Set,
Model
AC 135-6
AC 182-6
AC 290-6
AC 315-6
AC 355-6
AC 400-6
AC 496-6
AC 500-6
AC 501-6
AC 600-6
AC 810-6
AC 820-6
AC 920-6
AC 921-6
AC 1015-6
AC 1016-6
AC 1275-6
AC 1285-6
AC 1530-6
AC 1540-6
AC 2000-6
Standby
Power
kW
135
182
290
315
355
400
496
500
501
600
810
820
920
921
1015
1016
1275
1285
1530
1540
2000
60 Hz, 480V
Cummins
Engine
Model
6BTAA5,9G6
6CTA 8.3-G2
NT 855-G6
QSL9-G5
NTA 855-G3
QSX15-G6
KTA19-G4
QSX15-G9
QSX15-G9
VTA 28-G5
QSK 23-G3
QSK 23-G3
QST 30-G3
QST 30-G3
QST 30-G4
QST 30-G4
KTA 50-G3
KTA 50-G3
KTA 50-G9
KTA 50-G9
QSK 60-G7
Fuel
at Full Load
Consumption
Capacity
Fuel Tank
Coolant
Capacity
L/h Liter Liter Liter
39
470
21,4
16,4
48
380
27
23,8
74
700
66
38,6
75
470
28,6
26,5
87
700
66
38,6
97,6
850
66
91
122
850
120
50
117,8
117,8
154
189
189
207
207
240
240
291
291
330
330
471
850
850
1000
1500
1500
1500
1500
1500
1500
2000
2000
2000
2000
2000
66
66
170
120
120
224
224
342
342
415
415
643
643
682
91
91
83
103
103
154
154
154
154
177
177
204
204
280
Oil Specifications
Not; Lubricating oil viscosity level will be chosen from Figure 7.1 according to the ambient temperature
Oil Capacity
API CH API CI-4 API CF4
Table 8.3. Fuel consumption and coolant, fuel and lubricating oil capacities and lubricating oil specifications (60 Hz Open Gen-sets).
19
Page 23
9. GENERATOR SET MAINTENANCE
A good maintenance program is the key to long gene­rator set life. Maintenance and service should only be carried out by qualified technicians. The maintenance and service which are done must be recorded to the
Maintenance Record Form. In general, the generator set should be kept clean. Do not permit liquids such
as fuel or oil film to accumulate on any internal or ex­ternal surfaces. Wipe down surfaces using an aqueous
industrial cleaner.
9.1. Maintenance Schedule for Generator Sets;
Using hour meter as a guide, perform all services at the hourly intervals indicated on following. At each ma­intenance interval, perform all previous maintenance operations in addition to the ones specified. Keep a record of hourly intervals and services performed.
Important:
Recommended service intervals are for normal ope­rating conditions. Service MORE OFTEN if engine is operated under adverse conditions. Neglecting main­tenance can result in failures or permanent damage to the engine. Use correct fuels, Lubricants and coolant.
9.2. Maintenance Interval Chart A. Daily or every 20 hours Check
1. Visually inspect engine, generator, transfer switch and control panel.
2. For, Oil, Water and Fuel leaks.
3. For, Coolant level, Oil level, Fuel level.
4. Battery charge level.
5. Operation of coolant heater.
6. Drain Fuel/Water separator.
7. Inspect the engine fan blades.
8. Inspect the drive belt.
Cooling System;
1. Adequate fresh air to engine.
2. Hose and connections.
3. Battery charging alternator belts.
4. Inspect the engine fan blades.
5. Inspect the fan belt.
Exhaust System
1. Exhaust leaks.
2. Tighten connections (if necessary).
Alternator
1. Vent screens.
2. Tighten covers.
3. Output voltage and frequency.
Transfer Switch
1. Operation under load.
2. No unusual sounds.
3. Terminals and connections normal colour.
4. Doors closed securely.
Air System
1. Check leakage
2. Check air filter restriction indicator (if engine has). Run the Genset for 5-10 minutes on load (if it is pos­sible) or no load.
C. 6 Months or 200 Hours Check Repeat Weekly Lubricating System
1. Change, lubricating oil.
2. Change, lubricating oil filters.
3. Clean, crankcase breather.
Fuel System;
1. Change, fuel filters.
2. Drain sediment from main tank.
B. Weekly Check
Repeat Daily or every 20 hours. Fuel System;
1. Fuel level in main tank.
2. Day tank float switch.
3. Fuel transfer pump operation.
4. Fuel lines and connections.
Cooling System
1. Check, antifreeze.
2. Change, water filter.
3. Lubricate with grease, bearing of the fan hub.
4. Check the fan and connection bolts
20
Page 24
Engine safety controls
1. Check operating alarms and safeties.
Other controls
1. Clean the dust and dirt on the Gen. Sets by comp­ressed air.
2. Check the exhaust system’s pipes, supports and fle­xible pipes.
3. Check the mounting bolts of the Genset and AVM’s bolt tightness.
4. Check transfer switch ,bus bars ,and connections.
5. Check control panel cable connections.
D. 12 Months or 800 Hours Check
Repeat Maintenance “C”
Fuel System
1. Analyze/replace diesel fuel
2. Check the valves setting and injectors.
Cooling System
1. Clean, exterior of radiators.
2. Replace, radiator’s fill cap (over 600 kVA).
3. Check, coolant treatment.
4. Check, anti-freeze solution.
5. Check, water pumps and circulating pumps.
6. Examine duck work.
7. Clean/check motor operated louvers.
8. Clean, engine block water heater.
9. Inspect the engine fan blades.
10. Inspect the fan belt.
Intake System
1. Check air cleaner element and change at 635 mm H2O.
Clean
1. The engine.
2. Generator rotor and stator with compressed air.
Inspect
1. Magnetic pick-up and adjust.
2. Circuit breakers and fuse holders.
Additional to all above check;
1. Measure/record generator winding resistance with Megger.
2. Perform full load test at Nameplate kW.
E. 24 Months or 2000 Hours Check
1. Turbocharger bearing clearance.
2. Exhaust restriction.
3. The valves settings.
4. The injectors settings.
5. Vibration damper.
6. Change Coolant and antifreeze and flush system.
7. Clean Turbocharger compressor wheel and diffuser. Additional to all above, do the regular maintenance.
10. ENGINE TROUBLESHOOTING
Possible engine failure and engine failure causes is men­tioned below.
The starter motor turns the engine too slowly
• Battery capacity too low.
• Bad electrical connection.
• Faulty in starter motor.
• Wrong grade of lubricating oil.
The engine does not start or difficult to start
• Starter motor turns engine too slowly.
• Fuel tank empty.
• Faulty in fuel control solenoid.
• Restriction in a fuel pipe.
• Faulty in fuel lift pump.
• Dirty fuel filter element.
• Air in fuel system.
• Faulty in injectors or their adjustments.
• Fault in cold start system.
• Restriction in fuel tank vent.
• Wrong type or grade of fuel used.
• Restriction in exhaust pipe.
• Oil pressure sensor / switch or its connection is
faulty.
• Oil pressure is too high.
• Wrong grade of lubrication.
• Oil pressure indicator is faulty.
Not enough power
• Restriction in a fuel pipe.
• Faulty in fuel lift pump.
• Dirty fuel filter element.
21
Page 25
• Air in fuel system.
• Restriction air filter/cleaner or induction system.
• Restriction in exhaust pipe.
• Fault in injectors or injectors are out of adjustment.
• Restriction in fuel tank vent.
• Wrong type or grade of fuel used.
• Restricted movement of engine speed control.
• Engine temperature is too high or low.
Misfire
• Restriction in a fuel pipe.
• Faulty in fuel lift pump.
• Dirty fuel filter element.
• Air in fuel system.
• Fault in injectors or injectors are out of adjustment.
• Fault in cold start system.
• Engine temperature is too high.
• Incorrect valve tip clearances.
• Oil pressure sensor / switch or its connection is
faulty.
The pressure of the lubrication oil is too low
• Wrong grade of lubrication.
• Not enough lubrication oil in sump.
• Defective gauge.
• Dirty lubrication oil filter element.
Blue or white exhaust smoke
• Wrong grade of lubrication.
• Fault in cold start system.
• Engine temperature is too low.
The engine knocks
• Faulty in fuel lift pump.
• Fault in injectors or injectors are out of adjustment.
• Wrong type or grade of fuel used.
• Fault in cold start system.
• Engine temperature is too high.
• In correct valve tip clearances.
The engine runs erratically
• Fault in fuel control.
• Restriction in a fuel system.
• Faulty in fuel lift pump.
• Dirty fuel filter element.
• Restriction air filter/cleaner or induction system.
• Air in fuel system.
• Fault in injectors or injectors are out of adjustment.
• Fault in cold start system.
• Restriction in fuel tank vent.
• Restricted movement of engine speed control.
• Engine temperature is too high.
• In correct valve tip clearances.
High fuel consumption
• Restriction air filter/cleaner or induction system.
• Fault in injectors or injectors are out of adjustment.
• Fault in cold start system.
• Wrong type or grade of fuel used.
• Restricted movement of engine speed control.
• Restriction in exhaust pipe.
• Engine temperature is too low.
• Incorrect valve tip clearances.
Black exhaust smoke
• Restriction air filter/cleaner or induction system.
• Fault in injectors or injectors are out of adjustment.
• Fault in cold start system.
• Wrong type or grade of fuel used.
• Restriction in exhaust pipe.
• Engine temperature is too low.
• In correct valve tip clearances.
• Engine over load.
Vibration
• Fault in injectors or injectors are out of adjustment.
• Restricted movement of engine speed control.
• Engine temperature is too high.
• Fan damaged.
• Faulty in engine mounting or flywheel housing.
The engine temperature is too high
• Restriction air filter/cleaner or induction system.
• Fault in injectors or injectors are out of adjustment.
• Fault in cold start system.
• Restriction in exhaust pipe.
• Fan damaged.
• Too much lubrication oil in sump.
• Restriction in air or water passage of radiator.
• Engine thermostats are faulty.
• Insufficient coolant system.
Crankcase pressure
• Restriction in breather pipe.
22
Page 26
Bad compression
• Restriction air filter/cleaner or induction system.
• Incorrect valve tip clearances.
• Faulty piston rings.
The engine starts and stops
• Dirty fuel filter element.
• Restriction air filter/cleaner or induction system.
• Air in fuel system.
• Bad connection towards oil pressure switch/coolant
temperature switch.
Note: Please, look the engine manual for maintenance.
11. ALTERNATOR DESCRIPTION
11.1. General
The alternator fitted on the generator set is of the brushless self-excitation type which eliminates the ma­intenance associated with slip rings and brushes. The control system, consist of an automatic voltage regula­tor, protective circuits.
11.2. Construction and Components
The stator core is produced from insulated low loss electrical grade sheet steel laminations. These are built and welded under a fixed pressure to give an extre­mely rigid core to withstand vibration and load impul­ses. The complete wound stator is, after impregnation, pressed into the frame and pinned into position. The rotor assembly, which comprises the alternator
rotating field systems, the exciter rotating diode system
and the cooling fan. The complete rotor assembly is dynamically balanced to ensure vibration-free running. At the drive end of the rotor assembly a cast-aluminum centrifugal fan draws cooling air through screened co­vers at the non drive end and discharges it through similar side mounted covers at the drive end.
11.3. Operation
The electrical power produced by the generating set is derived from a closed loop system consisting princi-
pally of the exciter rotor the main revolving field and
the automatic voltage regulator (see Figure 11.1) The process begins when the engine starts to rotate the internal components of the alternator. The residual magnetism in the main rotor produces a small alterna-
ting voltage (AC) in the main stator. The automatic voltage regulator rectifies this voltage (converts it to
DC) and applies it to the exciter stator. This DC current to the exciter stator creates a mag-
netic field which in turn, induces an AC voltage in the
exciter rotor. This AC voltage is converted back to DC
by the rotating diodes.
When this DC voltage appears at the main rotor, a
stronger magnetic field than the original residual field is created which induces a higher voltage in the main sta­tor. This higher voltage circulates through the system inducing an even higher DC voltage back at the main rotor. This cycle continuous to build up the voltage unit it approaches the proper output level of the gene­rating set. At this point the automatic voltage regulator
begins to limit the voltage being passed to the exciter
stator which, in turn, limits the overall power output of the alternator. This build-up process takes place in less than one se­cond.
Figure.11.1. Meccalte alternator, operating principles block schematic diagram
11.4. Automatic Voltage Regulator
The Automatic Voltage Regulator (AVR) maintains a no load to full load steady state voltage to tight tole­rances. The AVR has a volt/hertz characteristic which proportionally reduces the regulated voltage at redu­ced speeds.
11.5. Alternator Insulation Test
Before starting the generating set after installation, test
23
Page 27
the insulation resistance of the windings. The Automa­tic Voltage Regulator (AVR) should be disconnected and the rotating diodes either shorted out with tem­porary links or disconnected. Any control wiring must also be disconnected. A 500 V Megger or similar instrument should be used.
11.6. Meccalte Alternator Troubleshooting
SYMTOM POSSIBLE CAUSE CORRECTIVE ACTION
Blown fuse
Alternator does not excite
Insufficient residual voltage No residual voltage
Connections are interruptedAfter being excited alternator
does no excite
Voltage potentiometer out of
Low voltage at no load
setting Invention of protection. Winding failure
Disconnect any earthing conductor connected betwe­en neutral and earth and megger an output terminal to
earth. The insulation resistance should be in excess of
1 MΩ to earth. Should the insulation resistance be less than 1 MΩ the winding must be dried out.
Replace fuse Increase speed by 15 %. For an instant apply on the (+) and (-) terminals of the electronic regulator a 12V battery with 30Ω resistor in series respecting the polarities.
Check connection cables as per attached drawings.
Reset voltage
Check engine speed Check windings
Voltage potentiometer out of
High voltage at no load
setting Failed regulator
Voltage potentiometer out of
Lower than rated voltage at load
setting Intervention by protection Failed regulator Rotating bridge failure
Higher than rated voltage at load
Voltage potentiometer out of setting Failed regulator
Speed variation in engine
Unstable voltage
Regulator out of setting
12. STORAGE
In case of the engine is not used for long time, preser­ve the engine from corrosion, faulty matters in order to run the engine operation easily and keep it long maintenance.
Reset voltage potentiometer
Substitute regulator
Reset voltage potentiometer Current to high, power factor lower than 0,8; speed lower than 4% of rated speed Substitute regulator Check diodes, disconnect cables.
Reset voltage potentiometer
Substitute regulator
Reset voltage potentiometer
Substitute regulator
12.1. Engine Storage:
The engine should be put through an engine “preserva­tion” procedure that includes cleaning the engine and replacing all the fluids with new or preserving fluids. The rate of corrosion varies with climatic conditions. Variance in climatic conditions makes it impossible to state the length of time an engine can be stored witho-
24
Page 28
ut rust and corrosion damage. Following procedure covers the basic method of pre­paring the engine for Temporary/Long storage.
- Short Term Storage:
Note: This procedure describes the correct method of preparing an engine for short-term (1-6 months) storage.
• Operate the engine until the coolant temperature
reaches 70°C (160°F). Shut off the engine.
• Remove the fuel tube to the engine fuel filter and the
injector return tube. Note: Fuel system preservative oil must meet Federal
Specification VV-L-800C. (Example: Daubert Chemi­cal NoxRust No.518)
Fill two containers, one with diesel fuel and the other with the preservative oil. Put both fuel tubes into the container of diesel fuel.
• Start the engine. When it is operating smoothly, put
the fuel supply tube into the container of preservative oil. Remove the injector return tube from the diesel fuel
container. When preservative oil flows from the tube,
shut off the engine. Install the fuel supply tube to the fuel filter, and put a cap on all other fuel tubes.
• Drain the lubricating oil pan, the oil filters, and the
fuel filter. Install the drain plug into the oil pan, and install the filter cans. Tighten according to specifications.
• Disconnect the electrical wires from the fuel pump
solenoid.
• Drain the coolant passages and jackets.
Note: It is not necessary to drain the coolant if it is a permanent-type antifreeze with a rust inhibitor.
• Look the engine over closely, and cover all openings
with tape to prevent dirt and moisture from entering. Install a warming tag which alerts others of no oil in the engine and that it must not be started.
• Store the engine in a dry area of even temperature.
Rotate the crankshaft two to three revolutions every 3 to 4 weeks using the accessory drive
- Removing the Engine from Short – Term Storage
Remove the tape from all openings, and remove the
warning tag.
Refill the oil filters with clean 15W-40 oil, and prime
the lubrication system. Use clean diesel fuel to flush the preservative oil from the fuel system, and fill the fuel filter again. Adjust belt tension
- Long Term Storage
This procedure describes the correct method of pre­paring an engine for long-term (6 to 24 months) sto­rage. Note: If the engine has been stored for 24 months, the cooling system must be flushed with a solvent. Repeat the flushing procedure a second time.
• Operate the engine until the coolant temperature
reaches 70°C (160°F). Shut off the engine.
• Drain the lubricating oil pan. Install the drain plug, and
fill the oil pan to the high level mark on the dipstick with preservative oil. Note: Lubricating system preservative oil must meet
MIL-L-21260 Type PE30-1, SAE 30. (Example: Shell
66202)
• Disconnect the fuel supply tube at the fuel filter and
the injector return tube at a convenient place. Note: Fuel system preservative oil must meet Federal
Specification VV-L-800C. (Example: Daubert Chemi­cal NoxRust No.518)
Fill two containers, one with diesel fuel and the other with the preservative oil. Put both fuel tubes into the container of diesel fuel.
• Start the engine. When it is operating smoothly, put
the fuel supply tube into the container of preservative oil. Remove the injector return tube from the diesel
fuel container. When preservative oil flows from the
tube, shut off the engine. Connect the fuel supply tube to the fuel filter, and put a cap on the ends of all the other fuel tubes.
• Drain the lubricating oil pan, and the oil filters. Install
the drain plug into the oil pan. Drain and flush the coo­ling system, using a water-soluble rust inhibitor.
• Remove the aftercooler assembly and the exhaust manifold. Spray preservative oil into the intake and ex-
haust ports of cylinder heat and into the aftercooler
housing and exhaust manifold. Install the aftercooler
25
Page 29
assembly and the exhaust manifold.
• Remove the rocker housing covers, and spray the
rocker levers, crossheads, valve stems, valve guides, and the push rods with preservative oil. Install the roc­ker housing cover. Note: Use a preservative compound that meets Mi­litary Specification MIL-C-16137C Type P-2 Grade 1 or 2.
• Cover all openings with heavy paper and tape to
prevent entrance of dirt and moisture. Put a warning tag on the engine which contains the following information:
- Date the engine was prepared for storage.
- Crankshaft must not be rotated.
- Coolant has been drained.
- Engine must not be operated. Store the engine in a dry area of even temperature.
Removing the Engine from Long-Term Storage
• Remove the paper and the tape from all openings.
Remove the warning tag
• Flush the fuel system with clean diesel fuel to remove
preservative oil.
• Remove a plug from the main oil rifle drilling. Use a
pump to flush the preservative oil from the engine with light mineral oil Note: Rotate the crankshaft three or four revolutions as the engine is flushed. Drain and flush the cooling system.
• Install new oil, water and fuel filters. Fill the cooling
system with coolant. Prime the lubricating system Adjust the belt tension according to specifications. Ad­just the injector and valve clearances. Tighten all cap screws, plugs, and fittings as necessary.
12.1.1. Start procedures for Engines that not stored according to Manuel
- Check the fan belt tension.
- Check the engine before starting.
- Lubricate the turbocharger before starting.
- Before cranking the engine rotate the crankshaft 3 or 4 times.
- Remove the cylinder head
- To ensure that all main bearings are lubricated suf-
ficiently, crank the engine for 15 second and wait 2 minutes , then crank the engine one more time for 15 seconds.
- Run the engine for a while without load , let the engine heated and check all indicators before loading the engine.
- Check the engine if there is any leakage.
12.2. Alternator Storage:
When an alternator is in storage, moisture tends to
condense in the windings. To minimize condensation, store the generating set in a dry storage area. If possib­le use space heaters to keep the windings dry. After removing the generating set from storage, per­form an insulation check as discussed in Section 12.5.
12.3. Battery Storage:
While the battery is stored, it should receive a ref­reshing charge every 4 weeks up to a fully charged condition.
13. GENERAL PRECAUTIONS ABOUT WAR­RANTY
Authorized Service Dealer may perform warranty re­pairs. Most warranty repairs are handled routinely, but sometimes requests for warranty service may not be
appropriate. For example, warranty service would not
apply if equipment damage occurred because of mi­suse, lack of routine maintenance, shipping, handling, warehousing or improper installation. Similarly, the warranty is void if the manufacturing date or the serial number on the equipment has been removed or the equipment has been altered or modified. During the warranty period, the Authorized Service Dealer, at its option, will repair or replace any part that, upon exa­mination, is found to be defective under normal use and service. This warranty will not cover the following repairs and equipment:
• Normal Wear: Outdoor Power Equipment and en­gines, like all mechanical devices, needs periodic parts and service to perform well. This warranty does not cover repair when normal use
has exhausted the life of a part or the equipment.
• Installation and Maintenance: This warranty does not
apply to equipment or parts that have been subjected
26
Page 30
to improper or unauthorized installation or alteration and modification, misuse, negligence, accident, over­loading, over speeding, improper maintenance, repair or storage so as, in our judgment, to adversely affect its performance and reliability. This warranty also does not cover normal maintenance such as adjustments, fuel system cleaning and obstruction (due to chemical, dirt, carbon, lime, and so forth).
• Other Exclusions: This warranty excludes wear items
such as oil gauges, o-rings, filters, fuses, or injectors etc., or damage or malfunctions resulting from accidents, abuse, modifications, alterations, or improper servicing or freezing or chemical deterioration. Accessory parts
are excluded from the product warranty. This warranty excludes failures due to acts of God and other force
majeure events beyond the manufacturer’s control.
14. GENERAL PRECAUTION
Dear AKSA generator set operator. Please take care to the following order to prevent the generator set warranty to become invalid if the warranty period and to ensure trouble-free operation of the generator set with a long life.
1. Maintenance and repair works will not be covered by the warranty certificate. If the invoice or delivery certificate of the generating set is not submitted.
likely to occur in case that the diesel oil used contains dirt or water.
6. The oil type indicated in the maintenance manual should be used in the engine otherwise, the failures which are likely to occur will not be covered by the warranty.
7. Batteries will not be covered by the warranty if they are subjected to breakage, excessive acid fill or harde­ning by leaving uncharged.
8. Don’t over crank the generator set , if the generator is not started at the first attempt , wait 10 second and then try to start the engine again , the cranking mustn’t be done more than 3 times ,and cranking time have to be less than 10 seconds ,otherwise starter gear could be broken or starter could be burn up. These conditi­ons are not covered warranty.
9. Generator sets, never start or stop the diesel engine when the generating set is under load. Engine should be started and stopped after load is disconnected and the generating set is at idle condition. Otherwise, the valves can be seized, the voltage regulator, transformer and diodes can be broken down. These conditions are not covered warranty.
2. The warranty of the generator set will become inva­lid in case of any intervention of any person other than authorized AKSA services or by prior written approval from AKSA power generation on the generator set for any reason.
3. Control and maintenance works indicated in the periodical maintenance schedule and the operating manual must be carried out completely and timely the failures due to incomplete or untimely maintenance are not covered by the warranty.
4. Generator set should be installed as indicated in the installation manual otherwise, the problems which are likely to occur will not be covered by the warranty.
5. Customer is responsible for the failures which are
10. Our company does not take the responsibility of the damages of the automatic generator sets due to over current, low or high voltage.
11. Never remove the battery terminals while the ge­nerating set is in use. Even a moment of disconnection can cause damage on the electronic closing relay of the charge alternator and on the electronic engine speed control circuit these conditions are not covered by the warranty.
12. Failures due to overload and unbalanced load in
excess of the generating set power (such as alternator
and contactor failures) are not covered by the war­ranty.
13. When the manually operated generating set is star-
27
Page 31
ted up, it should be warmed by operating at idle for 5 minutes. When stopping the diesel engine, it sho­uld be unloaded and then continued to be operated for cooling for 5 minutes before stopping. Otherwise problems which are likely to occur will not be covered by the warranty
14. Never run the Genset for a long time under the 30% of prime power , the problems which are likely to occur will not be covered by the warranty
15. Use only original spare parts. The problems which are likely to occur will not be covered by the warranty
16. The first starts of the Gensets have to be done by AKSA Authorized Services; otherwise Genset war­ranty will be invalid.
17. Any project or additional equipments couldn’t be done or installed to the Genset within the warranty period. If those plans (synchronizations, additional control panel, panel, transfer panel etc,) are done wit­hout notifying the AKSA Authorized services, Genset won’t be covered by warranty.
18. Warranty period of product 12monts or 1000 ho­urs of running time whichever expires first. The war-
ranty period begins with the shipment date of product.
15. CUSTOMER RESPONSIBILITY
1. The First Start is only valid for the location where the Genset is installed ,if the location of the Genset is going to be changed , the Genset has to be controlled and tested by AKSA Authorized services again. War­ranty of the generator set will become invalid if the first start and controls are done by any person other than authorized AKSA services .The customer will bear the cost of Second Start.
2. Control and maintenance works indicated in the periodical maintenance schedule and the operating manual must be carried out completely and timely by AKSA Authorized services for a fee. The maintenance schedule and Manuals are given to the customer with the Genset. if these Manual and schedules are lost, cus­tomer has to have a new one.
3. Other than manufacturing defect , Customer will bear the fee of all maintenance, troubleshooting and problems
4. If the Gensets won’t be started more than 2 Months, These Gensets have to be stored as mentioned in the Manuals .The necessary information and help can be provided from AKSA Authorized services
5. The conservation (storage) of the Genset have to be done by AKSA Authorized services, If the Genset is in warranty.
6. If the customer wants service guy work overtime, customer has to bear the cost of overtime pay.
7. Customer has to bear the cost of operations , ins­tallations and structures such as access doors , barriers ,walls, railings, floors, ceiling, or the likes , rental cranes or the likes of cranes , built ramps or the likes ,trailers or protective structures
8. Customer have the right of asking and investigating the service guy authorization, it is also a customer duty.
9. Customer has to keep the Warranty Certificate and
the First Start documentation to have warranty service, for this reason, this documentation should be kept into Generator Room within easy reach.
10. Genset room dimensions have to be according to
norms, adequate ventilation and exhaust outlet have
to be provided by customer.
11. Mains contactors are chosen according to Gene­rator sets nominal power, ASKA is not responsible for the failures which is caused by over current drawn by mains.
12. Main’s lower and upper limits are determined so as to Gensets and customer’s plant will work properly. Changing the mains voltage limits if requested by the customer, the customer is responsible for all faults re­sulting from this change, this change can be made by writing a report on the customer undertakes.