Cumberland Evolution Back-Up Owner's Manual

Page 1
Evolution Back-Up
Cumberland
1004 E. Illinois St.
Assumption, IL 62510
Part No. 4801-5309 Rev 1-15 Owners Manual Evolution Back-Up
CUMBERLAND Assumption, IL 62510 • Phone 217-226-4421 • Fax 217-226-4420
Page 2
Table of Contents
Section Title Page
Ratings and Specifications ............................................................................................................................. 3
1.
2.Warnings ........................................................................................................................................................ 3
3.Introduction to the Evolution Back-Up System ............................................................................................. 4
4.Evolution Back-Up Operating Conditions ..................................................................................................... 4
4.1 Normal Evolution Operation .................................................................................................................. 4
4.2 Emergency Operation ............................................................................................................................. 5
4.3 Override Operation ................................................................................................................................. 5
4.4 Fail-Safe Relay Operation ...................................................................................................................... 5
5.Inlet Operation During Back-up ..................................................................................................................... 5
6.Setting EV-Back-Up Stage Jumpers............................................................................................................... 5
7.Day-to-Day Back-Up Operating Instructions ................................................................................................. 6
7.1 Toggle Sequence of Mode Button .......................................................................................................... 6
7.2 Checking/Adjusting Temperatures, and Settings ................................................................................... 6
8.Set Limits ....................................................................................................................................................... 6
9.Program Mode Parameters ............................................................................................................................. 7
10. Calibrate Sensors ........................................................................................................................................ 7
10.1Installation .............................................................................................................................................. 8
10.2Unpacking Components ......................................................................................................................... 8
10.3Installation Instructions .......................................................................................................................... 8
10.4Checklist For Setting Up Control of House Temperature ...................................................................... 8
11. Wiring Diagrams ........................................................................................................................................ 9
11.1Evolution Back-Up Assembly ................................................................................................................ 9
11.2Wiring the Back-Up Board Sensors and Alarm Connections .............................................................. 10
11.3Evolution Back-Up Power Trak Override Settings and Wiring ........................................................... 11
11.4Power Supply Connection .................................................................................................................... 12
11.5Connecting Local Network & Back-up to the Evolution 3000 ............................................................ 13
12. Temperature vs. Sensor Resistance Table ................................................................................................ 14
13. Error Codes............................................................................................................................................... 15
14. Warranty ................................................................................................................................................... 16
Part No. 4801-5309 rev 1-15 Evolution Back-Up Table of Contents
Page 3
1. Ratings and Specifications
115/230 Volts (Depending on switch position.) 50/60 Hz. Room Temperature must be between 32F/0C and 122F/50C.
2. Warnings
When this controller is used in a life support heating and ventilation system
where failure could result in loss or injury, the user should provide
adequate back-up, or accept the risk of such loss or injury!
Warning!
Part No. 4801-5309 rev 1-15 Evolution Back-Up 3 of 17
Page 4
g
3. Introduction to the Evolution Back-Up System
The Evolution system has the option of containing an integrated Back-Up System. This Back-Up System contains 4 stages: 1 Heat and 3 Cool. This system’s purpose is to back up the master controller in the case of failure. The Back-Up System is a stand­alone control system. It contains its own temperature sensors that react to a High and Low Limit.
This Back-Up System is unlike any emergency control system on the market. This system offers a much higher level of protection. In addition to being able to monitor for high and low temperatures, it also stays in constant communication with the master controller. This communication allows the Back-Up System to run a minimum ventilation timer on Cool 1 or override the Evolution panel if certain conditions warrant. The conditions are explained in Section 4. All Back-Up Systems can protect against a high or low temperature, but only this system can protect against today’s biggest grower concern:
MINIMUM VENTILATION FAILURE!
Back-Up
Indicators
Main Display
e
Sta
®
Display Indicator
Control Buttons
4. Evolution Back-Up Operating Conditions
As explained above, this is more than your customary Back-Up System. This system contains three separate modes of operation that are entered depending on the circumstances. These modes are Normal Operation, Emergency Operation, and Override Operation. These modes will be explained in more detail below. These modes are entered based on information that it has received, or not received, from the master controller. No matter what mode of operation the Back-Up System is in, it will always attempt to maintain the temperature inside the High and Low Limits.
4.1 Normal Evolution Operation
During Normal Operation, the Back-Up System always maintains the temperature between its high and low limits. It accomplishes this by using its temperature sensors and its four stage outputs. If the temperature drops below the Low Limit, the Heat stage will come on. That stage will not turn off until it warms the building at least 2. The same is true if the temperature goes above the High Limit however, there are three levels of cooling stages on the Back-Up System. The following example explains the operation of the stages in relationship to the temperature and the limits. In this example the Low Limit is set as 66º F, and the High Limit is set as 86º F. If the temperature drops to 66º F, then the HEAT stage turns on. The HEAT stage turns off when the temperature rises to 68º F (1º above the Low Limit). If the temperature rises to 86º F, then COOL 1 turns on. If the temperature continues to rise to 87º F (1º above the High Limit), then COOL 2 turns on. If the temperature rises to 89º F, then COOL 3 turns on. Stages turn off at temperatures as indicated by the arrows in Graph 1. It is important to note, if COOL 3 turns ‘ON’, COOL 1 will be disabled to insure that sidewall fans or vent inlets are not operating while the Back-Up system is in ‘Tunnel Vent’ mode.
64 68 72
Graph 1
Cool 1, 2, 3 and Heat
Heat Cool 3 - Tunnel Cool 2 Cool 1- Vents
……….
Temperature (ºF)
83
86
85
84
87
88
89
Part No. 4801-5309 rev 1-15 Evolution Back-Up 4 of 17
Page 5
4.2 Emergency Operation
In this mode of operation, the system still maintains the temperature as it does in Normal Operation. In addition, it will begin running the first cooling stage (Cool 1) on a 5 minute timer. The timer percentage is determined by the setting in P3 (Emergency Timer Percentage). This mode of operation is entered if communication is lost between the master controller and the Back-Up System. In this case, the Back-Up System assumes that the master controller is lost and tries to maintain the minimum ventilation until someone recognizes the problem. Emergency Operation is indicated by a “LnE” flashing in the display of the Back-Up System. The alarm relay on the Back-Up System is also engaged in this mode operation.
4.3 Override Operation
In this mode of operation, the system still maintains the temperature as it does in Normal Operation. In addition, it receives commands from the master controller to turn on certain stages of heating or cooling. There are many different circumstances that could cause this to happen, in this manual, we will list one of the most common. For example, if communication were lost inside the EV-3000, the master controller would be unable to turn the appropriate stages on in the usual way. Therefore, the master controller would communicate to the Back-Up System and indicate which stages that it is trying to turn on. At this point, the Back-Up System would obey the command and turn the appropriate stages on. For this mode of operation to work to its fullest potential, care must be taken to insure that the stage jumpers on the relay strips match the stage setting in the master controller (Refer to Section 12). Override Operation is indicated by a “LnO” flashing in the display of the Back-Up System. The alarm relay is also engaged in this mode of operation.
4.4 Fail-Safe Relay Operation
There are two types of Relay strips used in the Evolution 3000. The Normally Open (NO) strip requires a signal from the controller board in order to energize a stage of ventilation. Should power be removed from the EV-3000 the Normally Open Relay strips would not be able to energize a ventilator. On the other hand the Fail-Safe relay strip would close each of the relays in the strip resulting in energizing the ventilators in case of a controller power failure. Each of the relay strips contains four relays for controlling four stages. In the EV-3000 there are a total of four relay strips, three will be N.O. and one will be a Fail-Safe. The operator must insure that the Fail Safe relay strip is connected only to stages that should be turned on in case of a controller failure. See the EV-3000 Owners manual Part No. 4801-5307 for a physical description of the relay strips. It is not recommended to place heating equipment on Fail-Safe stages.
5. Inlet Operation During Back-up
The EV-Back-Up contains a relay that can operate the Vents and/or Tunnel during Back-up operation of the EV-3000. The Inlets will automatically open during back-up. Cool 1 controls Vents Inlet. Cool 3 controls Tunnel Inlets. When Cool 1 and Cool 3 are not set, Back-up reverts to Normal operation.
Stage Relay
Stage Jumpers
COOL 3 COOL 2 COOL 1 HEAT
6. Setting EV-Back-Up Stage Jumpers
Pictured at the right is a Stage Relay Board consisting of four stage relays and the associated stage jumper for each stage relay. The stage jumpers are labeled COOL 1, COOL 2, COOL 3 and HEAT. Location of the jumper places the stage in one of these four modes, or if the jumper is not inserted, the stage is not placed on Back-Up. The jumpers should be placed based on the operation of stage equipment and should be the same as assigned in the EV-3000 Controller. Jumpers are placed according the following table:
Part No. 4801-5309 rev 1-15 Evolution Back-Up 5 of 17
Stage Harness
connector
cables to
Terminal Block
STAGE RELAY BOARD
Page 6
Type of Stage Operation Jumper Assignment
Cool Negative Fan COOL 1
Cool Negative Tunnel Fan COOL 2
Cool Tunnel Fan COOL 3
Heat Stage HEAT
Stage not on Back-Up No Jumper Installed
Additional information can be found in the Evolution 3000 Owners Manual, Part Number 4801-5307.
7. Day-to-Day Back-Up Operating Instructions
7.1 Toggle Sequence of Mode Button
Continuously pressing the Mode button cycles the display through the parameter sequence as illustrated below. The parameter data is shown in the display.
Room Temp
Display LEDs
Main Display
High Limit
Low Limit
7.2 Checking/Adjusting Temperatures, and Settings
When you press the Mode button, watch the green LED’s beside the main display. Whichever LED is lit is the parameter you are viewing: “Room Temp”, “High Limit”, and “Low Limit” values. Note: To adjust these parameters, press the Mode button until you see the parameter you want to adjust, then use the + button to increase the value, and the - button to decrease the value.
Room Temperature - The average of the sensors located inside the house. High Limit - The temperature inside the house at which the controller will turn on the first Evolution
Back-Up cooling stage.
Low Limit - The temperature inside the house at which the controller will turn on the first Evolution
heating stage.
8. Set Limits
The EV-3000 Back-Up System requires setting of a High Limit and a Low Limit at which cool/heat stages will turn on. To determine where to set the High Limit and the Low Limit, first decide on a target temperature of the house. This is usually the target temperature of the primary controller. Then set the High Limit to a temperature several degrees above the desired target temperature. Set the Low Limit to a temperature several degrees below the desired target temperature. Note: It is recommended that the
High Limit be at least 10º above the room’s target temperature and that the Low Limit be 10º below the room’s target temperature.
Part No. 4801-5309 rev 1-15 Evolution Back-Up 6 of 17
Page 7
To Set High Limit:
1. Press the “Mode” button to select the High Limit Indicator.
2. Press the ”+” and ”–“ buttons to enter the value of the High Limit.
3. Setting Complete.
To Set Low Limit:
1. Press the “Mode” button to select the Low Limit Indicator.
2. Press the + and – button to enter the value of the Low Limit.
3. Setting Complete.
9. Program Mode Parameters
Settings that are usually set up once per growout, or maybe even just for summer or winter are referred to as program parameters and are accessed by taking the controller to program mode. To get to program mode, press and hold the “Mode” button for five seconds. When the controller has entered program mode, the main display will flash between “P1” and the value of this parameter.
The “P1” is known as a parameter number. All the program items for the controller have a parameter number assigned to them. The numbers are listed in the table “Program Mode Parameters” below with a short description of each parameter. When in program mode, you change the value of certain parameters by using the + and - buttons as needed. When you have finished with the current setting, press the “Mode” button to move to the next parameter. The program mode parameters for the Evolution Back-Up are shown in Table 1.
Table 1. Program Mode Parameters
Parameter Description
P1 P2
P3
P41 PS1
PS2
This selects either English (OFF = Fahrenheit) or Metric (ON = Celsius) temperature units. Determines if an alarm is sent on a Back-Up condition. (ON = Alarm On, OFF = Alarm OFF) An alarm will be generated on an error condition even if P2 is set to OFF. See Section 13. Emergency Timer Percentage. (0% to 100%). This determines the percentage that COOL 1 will be run in an Emergency condition. This is the software version number. Not Changeable.
This is the calibration temperature for Sensor 1. Instructions: independent temperature measuring device to measure the temperature at Sensor 1 location. With PS1 selected, use the + and – buttons to set the calibration temperature to the thermometer reading.
This is the calibration temperature for Sensor 2. Instructions:
10. Calibrate Sensors
The temperature sensors should be calibrated to ensure accurate temperature detection. To calibrate the sensors an independent temperature measurement is required such as a thermometer or thermocouple.
1. Place a thermometer inside the house at the location of each sensor. Allow a few minutes for the
temperature to stabilize.
2. Take readings from the thermometers located at Sensor 1 and Sensor 2.
3. Use the Program Mode to set calibrations of Sensor 1 and Sensor 2 (Refer to Table 1).
With the controller operating, use a digital thermometer or similar
Same as Sensor 1 except substitute PS2 for PS1 in the instructions above.
Part No. 4801-5309 rev 1-15 Evolution Back-Up 7 of 17
Page 8
10.1 Installation
10.2 Unpacking Components
Unpack the system, and check that all components are present. Locate the required tools.
1 Evolution 3000 Back-Up 1 Temperature Sensor 1 Manual
10.3 Installation Instructions
1. Hang Evolution Back-Up with four screws and the plastic mounting brackets included.
2. Make sure all power supplies are disconnected before breaking any wires, or reaching into the
enclosure.
3. Locate the sensor connections. Refer to Wiring Diagrams, Schematics, etc.
4. For the Back-Up, run sensors out to locations inside the house. Be sure that the sensors are in a safe
location, free from any extreme temperature influences (direct sunlight, water, etc.) Use care when securing sensor wires so that you do not cut the wire. Any short or break in the wire will cause improper sensor operation.
5. Connect each sensor to its appropriate terminals inside the enclosure. See Section 11.2.
6. Wire the power supply. See Section 11.4.
7. Wire the Back-Up to the EV-3000. See Wiring Diagrams at the back of this manual.
8. Wire the Local Network connection.
9. Connect the PowerTrak to the Overrides. See Diagram in Section 11.3.
10. Close the Back-Up and tighten the two screws in th e lid to secure the unit shut.
Tools Required: Mini Screwdriver Wire Strippers Standard Screwdriver
10.4 Checklist For Setting Up Control of House Temperature
Please read and follow the Installation instructions on the followin g pages. Refer to the following checklist as an aid in setting the Evolution Back-Up controller.
1. Physically install the controller, temperature sensors, and wires leading from the output stages to cooling and/or heat equipment or to a control panel.
2. Verify the Back-Up jumpers on the Stage Block. Set Heat/Cooling Stage options.
3. Install power to controller. Refer to Section 11.4.
4. Set High Limit & Low Limit Refer to Section 8, Set Limits.
5. Calibrate Sensors Refer to Section 10, Calibrate Sensors
Refer to Section 11, Wiring Diagrams
Refer to the Evolution 3000 Owners Manual, Part Number 4801-5307 and to Section 6 of this manual,
Part No. 4801-5309 rev 1-15 Evolution Back-Up 8 of 17
Page 9
11. Wiring Diagrams
11.1 Evolution Back-Up Assembly
Tunnel Override Settings
Vent Override Settings
Backup Connections to Evolution
Local Network Connections
Voltage Selector Switch
Power Supply Connections
Alarm Connections
Sensor Connections
Part No. 4801-5309 rev 1-15 Evolution Back-Up 9 of 17
Page 10
11.2 Wiring the Back-Up Board Sensors and Alarm Connections
Jumper Connection to
Inset A
Enable Sensor 2
Sensor 2 Enabled
Installed – Enabled Vacant – Disabled
Jumper
Back-Up Alarm Connection
Contacts
For a Series
Alarm Connection
Inset B
Sensor 1 & 2 Connections
Inset C
Internal Wiring
Switch
NO COM NC
BACK-UP ALARM
Inset A
Inset B
Inset C
NOTE: Tape Shields to Prevent Damage.
For a Parallel Alarm Connection
Part No. 4801-5309 rev 1-15 Evolution Back-Up 10 of 17
Page 11
V
11.3 Evolution Back-Up Power Trak Override Settings and Wiring
Evolution Back-Up Circuit Board
Tunnel Override
Vents Override
Inset A
Vent Override
Inset B
PowerTrak
Cont
PT
Hot
Open
ent Override
PT
Hot
UPPER
AUX
SWITCH
IN
HO
COM
LOWER
OPEN
CLOSE
CONTROLLER AC IN
To
EV-3000
Com Open
Close
NOTE: If curtain is setup to pull curtain up to open, then reverse wires connected
to 'Open' and 'Close' terminals.
PowerTrak
Inset A
OU
GND
NEUT.
HO
Part No. 4801-5309 rev 1-15 Evolution Back-Up 11 of 17
Page 12
Expansion Module
N
N
N
N
11.4 Power Supply Connection
INSET A
Evolution
Inset A
Evolution 3000 16
NOTE: Controllers shipped from HHI set to 240V. Set slide switch of power selector to voltage of power supply connected!
Cabinet
Back-up
171)
on PCB
(AC input
cabinet to a common AC
NOTE: Run power cables
junction box. Do NOT run
including ground from each
Stage
Cabinet
Evolution 3000
Hot
between cabinets.
eutral
External GND
AC power and ground
eutral
Hot
External GND
Hot
eutral
External GND
AC
Junction
Box
Hot
eutral
External GND
Box
Breaker
IMPORTANT!
Protection
From Main Controller For Added
Back-up Can Be On A Separate Breaker
Part No. 4801-5309 rev 1-15 Evolution Back-Up 12 of 17
Page 13
11.5 Connecting Local Network & Back-up to the Evolution 3000
Evolution 3000
Cabinet
Back-up
Local Network
PCB 168
Local Net
Evolution 3000 16 Stage
Expansion Module
Local Network
Back-up
PCB 168
d
l
e
i
n
h
e
S
e
/
r
e
t
G
i h
W
Local Net
d
n
e
e
r G
l
e
i h S
/
e
t
i
h W
Evolut ion
Backup
Local net work
Back-up
PCB 171
Local Net
NOTE: Harness to connect Local Network and Back-up together are connected &
Tape Shield To Prevent Damage!
Warning!
Harness In Expansion & Backup
included in the Back-up and 16 Stage Expansion units.
Back-up
1
T V
2 1
k
c
a
l B
d
e R
L
A
O
E
O
H
C
e g n
a
r O
e
t
i h
W
k
c
a
l B
3
2
L
L
O
O
O
O
C
C
n
e
e
r G
Back-up
1
T
V 2 1
k
c
a
l B
d
e R
L
A
O
E
O
H
C
e g
n
a
r O
e
t
i h
W
k
c
a
l B
3
2
L
L
O
O
O
O
C
C
n
e
e
r G
Back-up
1
T
V 2
1
L
A
O
E
O
H
C
3
2
L
L
O
O
O
O
C
C
Part No. 4801-5309 rev 1-15 Evolution Back-Up 13 of 17
Page 14
12. Temperature vs. Sensor Resistance Table
The following chart gives the resistance when measured between the white and black sensor wires at a given temperature. To check a sensor, first know the temperature in the area, then, use a multi-meter to check the resistance.
Resistance Temp Temp Resistance Temp Temp Resistance Temp Temp
Kohms (F) (C) Kohms (F) (C) Kohms (F) (C)
32.654 32 0 15.714 59 15 8.59 83.3 28.5
32.158 32.5 0.3 15.568 59.4 15.2 8.517 83.7 28.7
31.671 33.1 0.6 15.353 59.9 15.5 8.408 84 28.9
31.191 33.6 0.9 15.211 60.3 15.7 8.336 84.6 29.2
30.72 34.2 1.2 15.001 60.8 16 8.23 85.1 29.5
30.257 34.7 1.5 14.863 61.2 16.2 8.125 85.6 29.8
29.802 35.2 1.8 14.658 61.7 16.5 8.056 86 30
29.355 35.8 2.1 14.457
28.915 36.3 2.4 14.325 62.6 17 7.853 87.1 30.6
28.482 36.9 2.7 14.128 63.1 17.3 7.787 87.4 30.8
28.057 37.4 3 13.999 63.5 17.5 7.689 88 31.1
27.777 37.8 3.2 13.808 64 17.8 7.592 88.5 31.4
27.363 38.3 3.5 13.682 64.4 18 7.496 89.1 31.7
26.957 38.8 3.8 13.496 64.9 18.3 7.433 89.4 31.9
26.557 39.4 4.1 13.373 65.3 18.5 7.34 90 32.2
26.164 39.9 4.4 13.192 65.8 18.8 7.248 90.5 32.5
25.777 40.5 4.7 13.073 66.2 19 7.157 91 32.8
25.523 40.8 4.9 12.896 66.7 19.3 7.098 91.4 33
25.147 41.4 5.2 12.779 67.1 19.5 7.009 91.9 33.3
24.777 41.9 5.5 12.607 67.6 19.8 6.922 92.5 33.6
24.413 42.4 5.8 12.493 68 20 6.836 93 33.9
24.055 43 6.1 12.325 68.5 20.3 6.779 93.4 34.1
23.82 43.3 6.3 12.215 68.9 20.5 6.695 93.9 34.4
23.472 43.9 6.6 12.051 69.4 20.8 6.612 94.5 34.7
23.13 44.4 6.9 11.943 69.8 21 6.531 95 35
22.793 45 7.2 11.783 70.3 21.3 6.45 95.5 35.3
22.572 45.3 7.4 11.678 70.7 21.5 6.371 96.1 35.6
22.244 45.9 7.7 11.522 71.2 21.8 6.319 96.4 35.8
21.922 46.4 8 11.42 71.6 22 6.241 97 36.1
21.71 46.8 8.2 11.268 72.1 22.3 6.165 97.5 36.4
21.397 47.3 8.5 11.168 72.5 22.5 6.089 98.1 36.7
21.088 47.8 8.8 11.02 73 22.8 6.015 98.6 37
20.886 48.2 9 10.874 73.6 23.1 5.941 99.1 37.3
20.586 48.7 9.3 10.778 73.9 23.3 5.869 99.7 37.6
20.29 49.3 9.6 10.636 74.5 23.6 5.798 100.2 37.9
20.096 49.6 9.8 10.542 74.8 23.8 5.728 100.8 38.2
19.809 50.2 10.1 10.404 75.4 24.1 5.658 101.3 38.5
19.526 50.7 10.4 10.312 75.7 24.3 5.59 101.8 38.8
19.34 51.1 10.6 10.177 76.3 24.6 5.522 102.4 39.1
19.065 51.6 10.9 10.088 76.6 24.8 5.456 102.9 39.4
18.884 52 11.1 9.956 77.2 25.1 5.39 103.4 39.7
18.616 52.5 11.4 9.869 77.5 25.3 5.326 104 40
18.352 53.1 11.7 9.741 78.1 25.6 5.262 104.5 40.3
18.179 53.4 11.9 9.614 78.6 25.9 5.199 105.1 40.6
17.503 54.9 12.7 9.53 79 26.1 5.137 105.6 40.9
17.339 55.2 12.9 9.407 79.5 26.4 5.076 106.2 41.2
17.095 55.8 13.2 9.325 79.9 26.6 4.995 106.9 41.6
16.856 56.3 13.5 9.205 80.4 26.9 4.936 107.4 41.9
16.698 56.7 13.7 9.086 81 27.2 4.877 108 42.2
16.465 57.2 14 9.007 81.3 27.4 4.82 108.5 42.5
16.312 57.6 14.2 8.891 81.9 27.7 4.763 109 42.8
16.085 58.1 14.5 8.815 82.2 27.9 4.688 109.8 43.2
15.935 58.5 14.7 8.702 82.8 28.2
62.2 16.8 7.954 86.5 30.3
Part No. 4801-5309 rev 1-15 Evolution Back-Up 14 of 17
Page 15
13. Error Codes
If your controller is displaying an “E1” or “E2”, etc. the controller has recorded an error. The controller records errors based on sensor reading and the communications links. When any of these errors occur an alarm will be generated.
Error Codes for the Evolution Back-Up System
Error Code Description Explanation
E1
E2
E3
LnE
LnO
Sensor 1 Error Sensor 2 Error Usually indicates a shorted sensor
Sensor 1 and Sensor 2 Sensors 1 and 2 both shorted.
Local Network Error The Back-Up has lost
Local Network Override Error The Master Controller has lost
Usually indicates a shorted sensor wire. Check sensor resistance.
wire. Check sensor resistance.
Note: If Sensor 2 is switched OFF, then this error code is not active.
Communications with the Master Controller. NOTE: During this
condition the Back-Up will run Cool 1 on a 5 minute timer.
communications with one or more of the StageUnits (PCB
168) connected to it. In this condition the Back-Up takes control over the stages.
Part No. 4801-5309 rev 1-15 Evolution Back-Up 15 of 17
Page 16
Limited Warranty
14. Warranty
The GSI Group, LLC. (“GSI”) warrants products which it manufactures to be free of defects in materials and workmanship under normal usage and conditions for a period of 12 months after sale to the original end-user or if a foreign sale, 14 months from arrival at port of discharge, whichever is earlier. The end-user’s sole remedy (and GSI’s only obligation) is to repair or replace, at GSI’s option and expense, products that in GSI’s judgment, contain a material defect in materials or workmanship. Expenses incurred by or on behalf of the end-user without prior written authorization from the GSI Warranty Group shall be the sole responsibility of the end-user.
Warranty Extensions: The Limited Warranty period is extended for the following products:
Product Warranty Period
Performer Series Direct Drive AP Fans and Flooring
AP/Cumberland Flex-Flo/Pan Feeding Systems 2 Years Cumberland
Feeding/Watering Systems
Grain Systems Grain Bin Structural Design 5 Years Grain Systems Farm Fans Zimmerman
GSI further warrants that the frame, basket and excluding all auger and auger drive components of the portable and tower dyer shall be free from defects in materials for a period of time beginning on the twelth (12 from the date of purchase and continuing until the sixtieth (60 warranty period). During the extended warranty period, GSI will replace the frame or basket components that prove to be defective under normal conditions of use without charge, excluding the labor, transportation, and/or shipping costs incurred in the performance of this extended warranty.
Feeder System Pan Assemblies 5 Years **
Feed Tubes (1.75" & 2.00") 10 Years *
Portable & Tower Dryer Frames
and Internal Infrastructure †
Fan Motor
All Fiberglass Housings Lifetime
All Fiberglass Propellers Lifetime
Centerless Augers 10 Years *
Watering Nipples 10 Years *
Portable & Tower Dryers 2 Years
3 Years
5 Years
th
) month from the date of purchase (extended
* Warranty prorated from list price: 0 to 3 years – no cost to end-user 3 to 5 years – end-user pays 25% 5 to 7 years – end-user pays 50% 7 to 10 years – end user pays 75%
** Warranty prorated from list price: 0 to 3 years – no cost to end-user 3 to 5 years – end-user pays 50%
† Motors, burner components and moving parts not included. Portable Dryer screens included. Tower Dryer screens not included.
th
) month
Conditions and Limitations:
THERE ARE NO WARRANTIES THAT EXTEND BEYOND THE LIMITED WARRANTY DESCRIPT ION SET FORTH ABOVE. SPECIFICALLY, GSI MAKES NO FURTHER WARRANTY OF ANY KIND, EXPRESS OR IMPLIED, INCLUDING, WITHOUT LIMITATION, WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OR USE IN CONNECTION WITH: (i) PRODUCT MANUFACTURED OR SOLD BY GSI OR (ii) ANY ADVICE, INSTRUCTION, RECOMMENDATION OR SUGGESTION PROVIDED BY AN AGENT, REPRESENTATIVE OR EMPLOYEE OF GSI REGARDING OR RELATED TO THE CONFIGURATION, INSTALLATION, LAYOUT, SUITABILITY FOR A PARTICULAR PURPOSE, OR DESIGN OF SUCH PRODUCTS.
GSI shall not be liable for any direct, indirect, incidental or consequential damages, including, without limitation, loss of anticipated profits or benefits. The sole and exclusive remedy is set forth in the Limited Warranty, which shall not exceed the amount paid for the product purchased. This warranty is not transferable and applies only to the original end-user. GSI shall have no obligation or responsibility for any representations or warranties made by or on behalf of any dealer, agent or distributor.
GSI assumes no responsibility for claims resulting from construction defects or unauthorized modifications to products which it manufactured. Modifications to products not specifically delineated in the manual accompanying the equipment at initial sale will void the Limited Warranty.
This Limited Warranty shall not extend to products or parts which have been damaged by negligent use, misuse, alteration, accident or which have been improperly/inadequately maintained. This Limited Warranty extends solely to products manufactured by GSI.
Prior to installation, the end-user has the responsibility to comply with federal, state and local codes which apply to the location and installation of products manufactured or sold by GSI.
Part No. 4801-5309 rev 1-15 Evolution Back-Up 16 of 17
Page 17
Part No. 4801-5309 rev 1-15 Evolution Back-Up 17 of 17
Loading...