CTI Products Quad Router Panel User Manual

Routers
for MCNMonitoring and Control Systems
QUAD ROUTER PANEL
AB AB AB B A
LU L
U
C
LISTED17BK
TP/FT-10 TP/XF1250
ENERGYMANAGEMENT
EQ UIPMENTSUBASSEMBLY
B
A
Router #
RTR1.LSC
EASTPOLI CE
B
A B A B A
LU LU
C
LISTED17BK
TP/FT-10 TP/XF1250
ENERGYMANAGEMENT
EQUIPMENTSUBASSEMBLY
Router #
RTR2.LSC
WEST POLICE NORTH POLICE SOUTH POLICE
TP/FT-10 TP/XF1250
Router #
EQUIPMENTSUBASSEMBLY
RTR3.LSC
LU LU
C
LISTED17BK
ENERGYMANAGEMENT
TP/FT-10 TP/XF1250
Router #
9819 LISTED17BK
EQUIPMENTSUBASSEMBLY
RTR4.LSC
LU LU
C
ENERGYMANAGEMENT
ID000203580900
ID000203625900
CTI Products, Inc. 1211 West Sharon Road
Cincinnati, Ohio 45240 USA
phone +1.513.595.5900
fax +1.513.595.5983
e-mail
info@ctiproducts.com
www.ctiproducts.com
ROUTER 1
B
1250 78K
IN
OUT IN OUT
ToR TR
1250
RTR1.LSC
A
Rack 1
Term From RTR To RTR Term From RTR To RTR Term From RTR Term
CIB 10-0#2
ROUTER 2
B
A
1250
IN OUT IN OUT
#1 #3 CIB 20-0Network #2 #4 CIB 30-0 CIB 40-0#3 Term
78K
Rack 2 Rack 3
RTR2.LSC
Quad Router Panel with 4 Routers Installed
Introduction
Routers are used with CTI's MCN Remote Comparator Display system for the following
purposes:
To increase the number of I/O Modules
(CIBs, AIBs, IOBs, etc.) past 16.
backbone network.
To provide access to a high-speed
network from a standard speed (78 Kb) HIB module for dial-up applications.
To connect local I/O modules to a high-
speed backbone.
Mounting
A Quad Router Mount is available for mounting on an EIA 19" rack. It will accept up
to 4 routers. It requires 4 RU of space (7"). An MCN power supply is required for operation.
System Operation
The system diagram on the next page shows how routers are used to extend the number of
I/O modules past 16. There are two standard speed (78 Kb) networks segments shown, each with 16 CIB modules.
Each of these segments is connected to the 78 Kb side of a router module. The high-
speed (1.25 Mb) sides of the routers are connected together to form a high-speed backbone network.
The lower router is a HIB router, which allows a dial-up HIB module to be used.
Although not shown in the system diagram, PCs with high-speed PCLTA interface cards can be connected directly to the 1.25 Mb channel.
ROUTER 3
B
A
1250 78K
IN OUT IN OUT
RTR3.LSC
ROUTER 4
B A
1250 78K
IN OUT IN OUT
Rack 4
To 1250
RTR4.LSC
CA-80465-101
The traffic from the CIB modules is passed through the router modules and onto the high-
speed backbone. The routers filter the network traffic so that the
CIB traffic from one 78 Kb segment is not repeated to the other 78 Kb segment. Traffic
from the User Interface (PCLTA or HIB) is passed to the appropriate 78 Kb segment.
Dial-Up HIB Applications
Speed conversion is required when a HIB module is used in dial-up applications that have a high-speed backbone. For these applications, order one router module for each
dial-up HIB module. The HIB Router will convert from the 1.25 Mb
high-speed network to the standard 78 Kb network for the HIB. It also provides filtering so that the HIB will see only a portion of the
network traffic at any one time.
Custom System Configuration
The configuration for the routers will be different for each customer's system. Parameters such as filtering and addressing must be set for each of these systems.
HIB routers are pre-configured for standard addressing. the MCNRCD Comparator Display software on the PC will automatically set up the filtering on the HIB routers, depending on which screens are loaded.
For all non-HIB routers, the Custom Configuration option must be ordered. CTI Products' engineers will work with the customer to define the network. We will then custom configure the routers before shipment.
We will provide the appropriate files to the customer to allow re-configuration if a router needs to be replaced in the field.
Routers ROUTER 2005-08
COMPARATOR I/O MODULES COMPARATOR I/O MODULES
21
78Kbps CHANNEL
T
16 3217 18
78Kbps
1.25Mbps
ROUTER
1.25Mbps
78Kbps
78Kbps CHANNEL
TT
ROUTER
T
78Kbps
1.25Mbps
T
78Kbps CHANNEL
T
HIB MODULE (DIAL-UP)
MCN Remote Comparator Display System with Routers
ROUTER
1.25Mbps CHANNEL To PCs
CA-80244-105
Part Numbers
90-11401 MCN Router 78K / 1250K 90-11518 MCN Router 1250K / 1250K S1-60819 MCN Quad Router Mount and
Manifold 81-10398 Power Supply MCN 120VAC US/CAN 81-10728 Power Supply MCN 230VAC Europe S2-60825 Custom System Configuration & Test
(Required for each Router Module)
General Specifications
Size 7.0" x 19.0"
Power Requiered per Router 16-30VAC or DC, 2VA Temperature -40 -+85oC Humidity 10- 95% non-condensing MCN Network Data Rates 78Kbps, 1250Kbps Network Connector
(Quad Rack) Max. network segment 4000 ft. without repeaters (78K)
Max.standard 78Kb modulesper segment
Network Cabling CAT5 (4 Pair UTP) Safety Approvals
(Router) Emissions
Compliance (EMI)
Susceptibility Compliance (EMC)
(178 x 483 mm)
RJ-45, Standard MCN type
1500 ft. (1250K) 16 per network segment
(Larger, multi-segment systems can be custom-configured.)
UL 916, cUL c22.2 Number 205,
FCC part 15, Class A IC (DOC), Class A (Canada) EN55022, Class A
IEC 801-2, 3, 4 EN50082-1
Other trademarks referenced are properties of their respective owners. Specifications subject to change or improvement without notice.
MCN,MCNRCD, CIB, AIB, IOB, IIB, HIB, and EXB are trademarks of CTI Products, Inc..