C-TEC XFP Installation Instructions

Page 1
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL
1 or 2 Loop 32 Zone Version
engineering manual
Approved Document No. DFU2200510 Rev 2
Page 2
FP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
X
CONTENTS
Important Notes ..................................................................................................................................3
Key features..........................................................................................................................................4
nstallation and wiring ........................................................................................................................5
I
The fire panel enclosure ..................................................................................................................................5
Removing the lid and base PCBs......................................................................................................................5
Mounting the base to the wall ........................................................................................................................6
Planning the cable layout in the panel ..........................................................................................................6
Mains wiring......................................................................................................................................................6
Connecting Mains to the Power Supply PCB ..................................................................................................7
Analogue addressable loop wiring..................................................................................................................8
Connecting the analogue loop to the Main Control PCB..............................................................................9
Conventional sounder circuit wiring ..............................................................................................................9
Auxiliary input wiring ....................................................................................................................................10
Relay output wiring ........................................................................................................................................10
Remote PC connection....................................................................................................................................11
Printer connection ..........................................................................................................................................11
Aux. 24V output ..............................................................................................................................................11
Installing the standby battery supply ............................................................................................................11
Network/repeater wiring (optional) ..............................................................................................................12
Controls and indicators ......................................................................................................................14
Commissioning and programming ..................................................................................................16
Recommended commissioning procedure ....................................................................................................16
System operation / terms of reference ..........................................................................................................16
Access levels menu tree ..................................................................................................................................17
How to enter access level three ....................................................................................................................18
Fitting the panel’s NVM ‘memory unlock’ link ............................................................................................18
A detailed description of the functions available at access level 3 ......................................................19-33
Maintenance ......................................................................................................................................34
Standby battery calculation guide....................................................................................................35
Technical specification ......................................................................................................................36
Disclaimer
© No responsibility can be accepted by the manufacturer or distributors of this range of fire panels for any misinterpretation of an instruction or guidance note or for the compliance of the system as a whole. The manufacturer’s policy is one of continuous improvement and we reserve the right to make changes to product specifications at our discretion and without prior notice. E&OE.
This product has been manufactured in conformance with the requirements of all applicable EU Council Directives.
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 2 of 36
Page 3
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
IMPORTANT NOTES
This equipment must only be installed and maintained by a suitably skilled and technically competent person.
This equipment is a piece of Class 1 equipment and MUST BE EARTHED.
ALWAYS isolate the panel’s Mains and battery backup supplies before making connections to its PCBs.
Items supplied with this panel
• Engineering manual (this manual)
• User Manual / Log Book
• Hex key, for unfastening / securing the panel lid
• Electrical accessory pack, containing: 2 x 6K8 0.25W conventional sounder circuit resistors 1 x 20mm 1ATH 250V HRC ceramic fuse (spare primary fuse) 1 x set of battery connection leads (red wire, black wire, jumper link and 2 x nylon cable ties)
System design
Fire alarm system design is beyond the scope of this document. A basic understanding of general fire alarm system components and their use is assumed.
Contact the Fire Officer concerned with the property at an early stage in case he has any special requirements. We strongly recommend that a suitably qualified and competent person is consult­ed in connection with the design of the fire alarm system and that the system is commissioned and serviced in accordance with the laid down specification and national standards. If in doubt please consult your supplier.
We recommend you read BS 5839 Part 1 "Fire Detection and Alarm Systems for Buildings (Code of Practice for System Design, Installation, Commissioning and Maintenance)" available at your local reference library or from the BSI. Other national standards of installation should be refer­enced where applicable.
Cable types and limitations
All system wiring should be installed to meet current national standards - in the United Kingdom these are BS 5839 Part 1 and BS7671 (Wiring Regulations).
Fire resistant screened cable should be used throughout the installation. This not only shields the data moving up and down the cables from outside interference but is essential to ensure compliance with EMC regulations. Cables such as FP 200, Firetuff™, Firecel™ and MICC may be acceptable provided they are properly terminated at the fire panel and meet national standards / the system specification as applicable. Consult Clause 26 of BS 5839 Part 1 for more detailed information on cables, wiring and other interconnections.
Equipment guarantee
This equipment is not guaranteed unless the complete installation is installed and commissioned in accordance with the laid down national standards (in the UK BS 5839 Part 1) by an approved and competent person or organisation.
Anti-static handling guidelines
Always observe appropriate electro-static handling precautions prior to handling the panel’s PCBs or any other static-sensitive components.
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 3 of 36
Page 4
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
KEY FEATURES
This 1 or 2 loop (dependent on the model purchased) 32 zone analogue addressable fire alarm panel offers the following features:
Full compliance with EN54 parts 2 and 4, including EN54-2 Clauses 7.8 - Output to fire alarm
devices, 8.3 - Fault Signals from points and 9.5 - Disablement of addressable points.
Full compatibility with Hochiki’s ESP and Apollo’s XP95, Discovery and Xplorer protocols
(dependent on the model purchased)
Two independently programmable conventional sounder circuits
Two programmable inputs
A fault output relay and three programmable relay outputs with volt free changeover contacts
A selection of zone dependency functions (EN54-2 Clause 7.12, type A, B or C) as detailed below:
Type A - If there is an alarm from a detector, the panel will look for a confirmatory alarm from the same or another detector in the same zone confirmatory alarm, the first alarm will automatically reset.
Type B - As type A except the confirmatory signal must be from another
Type C - As type A except the confirmatory signal may also be from another zone alarm will not automatically reset.
before a full alarm is established. If there is no
detector in the same zone.
, and the first
A day/night (building occupied/unoccupied) function (engineer programmable day/night
changes include detector sensitivity (high/low) and zone dependency settings
An investigation delay period function (programmable for length of time, which zone(s) it
applies to and whether or not it operates in day/night mode) which works as follows: When there is an alarm in a zone programmed to operate in ‘investigate’ mode, the full alarm condition will occur after a delay. It is possible to manually impose a further delay, to allow the source of the alarm to be investigated. If the second delay expires, or there is another alarm in the same zone, then a full alarm condition is established. During either delay period, the panel may be reset in the case of a false alarm
Individual sensitivity settings for each device
EN54-2 Clause 7.11 Delays to outputs, and a phased evacuation facility
An EN54-2 Clause 7.13 alarm counter to record the number of times the panel has been in an
alarm state
Powerful short circuit protected loop drivers, each capable of supporting a total of 126
addressable devices, giving a total of 252 devices for a 2 loop panel
An integral 3A EN54-4 switch mode PSU rated @ 185-260V a.c. 50/60Hz
Earth fault monitoring
Keypad access code to access levels 2 & 3. Keyswitch entry to access level 2.
40 characters of custom text per device
500 event monitoring
Comprehensive EN54-2 Clause 10 test, with maintenance and commissioning functions
An intuitive Windows based upload-download PC program (Part No. XFP507) that MUST be used
to configure the system.
Networking
If required, the panel can be configured to sit on network of up to eight interconnected XFP master panels or it can have up to eight XFP repeaters connected to it. If you wish to utilise either of these options, the panel will require a separately available Network Communication Card (Part No. AFP711).
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 4 of 36
Page 5
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
INSTALLATION AND WIRING
The fire panel enclosure
The panel is supplied with a hinged metal lid, metal back box and four separate PCBs (a Main Control PCB, a Power Supply PCB, a Switch & Indicator PCB and an LCD PCB. Space is available inside the panel for the rated capacity of VRLA backup batteries and an optional Network Communication Card.
The panel must be sited internally in an area that is not subject to conditions that are likely to affect its performance, e.g. damp, salt-air, water ingress, extremes of temperature, physical abuse, near sources of electromagnetic interference, such as high current machines, welding equipment, radio transmitters, etc. See Page 36 for more details.
It should be sited at a height where it is easily accessible and in a prominent position within the building. Ideally, its front panel indicators should be at eye level. Typical locations for the panel are in the entrance foyer/hallway at ground floor level (the first and most obvious point of contact for emergency services) or a permanently manned security office.
It is recommended that you remove the panel’s lid and base PCBs prior to first fix installation to protect the electronics from damage.
Removing the lid and base PCBs
Fig. 1 : Location of the panel’s base PCBs and removal details
LCD PCB
WITCH & INDICATOR PCB
S
TELECOMS-STYLE LID/BASE
CONNECTOR CABLE
LID EARTH STRAP
TWO-WAY LID/BASE
CONNECTOR CABLE
PL4
PL5
PCB RETAINING
SCREW
EN-WAY PSU
T
ONNECTOR CABLE
C
MAIN
CONTROL
PCB
POWER SUPPLY PCB
EARTH STRAP
PL1
PCB RETAINING
S
P SUPPLY
CREW
OWER
PCB
To remove the lid:
• Take the panel out of its box and undo the two lid screws using the hex key provided.
• Hinge the lid 180° to the left (do not overbend the hinges) and remove the lid earth strap’s spade connector.
• Disconnect the telecoms-style lid/base connecting cable from PL5 on the Main Control PCB. Care should be taken when detaching the connector to depress the locking tab to prevent damage.
• Disconnect the two-way lid/base connecting cable from PL4 on the Main Control PCB.
• Carefully remove the four M4 retaining nuts that secure the hinges and lift off the lid.
To remove the base PCBs:
• Ensure power has been removed from the panel and that the power supply PCB is safe to handle.
• Disconnect the Power Supply PCB connecting cable from PL1 on the Main Control PCB.
• Pull the Power Supply PCB’s earth strap off the spade connector at the main base earth point.
• Carefully undo the PCB retaining screw located at the bottom left hand side of the relevant PCB using a crosshead screwdriver.
• Slide the PCBs up and over the mounting pillars taking care not to damage any of the components.
• Store the PCBs in a clean, dry place which is free from vibration, dust and excessive heat. Retaining the PCBs in a suitable cardboard box will also guard them against mechanical damage.
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 5 of 36
Page 6
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
1.0mm < 2.5mm
PSU
PANEL
MAIN
DISTRIBUTION
BOARD
3A
22
Mounting the base to the wall
The panel can be surface or semi-flush mounted using the five mounting holes provided (note that an optional bezel, Part No. AFP735, is available for semi-flush mounting).
To expose the mounting holes you must first remove the panel’s lid and base PCBs, as described on page 5. The mounting holes are suitable for use with No.8 roundhead or countersunk screws.
Always assess the condition and construction of the wall and use a suitable screw fixing. Any dust or swarf created during the fixing process must be kept out of base.
Fig. 2 : Location of mounting holes and knockouts / side view of panel for flush mounting
60mm ncludes
These two knockouts are reserved for incoming Mains cable only
i dimples
WALL
Planning the cable layout in the panel
All cables should be brought into the panel via the knockouts provided.
Note that the analogue loop and conventional sounder circuit cabling is classed as low voltage and must be segregated away from Mains voltages. Careful planning is needed to ensure this (see Fig. 2, above, for guidance).
Leave sufficient tails inside the panel to ensure straightforward connection of the field wiring to the panel’s terminals. Knockouts should be removed with a sharp, light tap using a flat 6mm broad-bladed screwdriver as shown in the diagram (right).
Always ensure if a knockout is removed, the hole is filled with a good quality 20mm cable gland. Any unused knockouts must be securely blanked off.
Mains wiring
The requirement for the Mains supply to the fire panel is fixed wiring, using three core cable (no less than 1mm switched fused spur, fused at 3A. This should be secure from unauthorised operation and be marked ‘FIRE ALARM: DO NOT SWITCH OFF’. The Mains supply must be exclusive to the fire panel.
(As an alternative to a switched fused spur, a double pole isolating device may be used (see diagram below) providing it meets the appropriate national wiring regulations.)
2
and no more than 2.5mm2) or a suitable three conductor system, fed from an isolating
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 6 of 36
Page 7
BATTERY FUSE
3.15AF
PRIMARY FUSE
+
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Connecting Mains to the Power Supply PCB
The panel’s PSU is a 185-265Va.c. 50-60Hz off line switched mode power supply that combines the functions of a power supply unit, battery charging unit, battery monitoring unit and earth fault monitoring unit. It should be positioned in the panel’s enclosure as shown in Fig. 3 below. DO NOT operate the panel without the Power Supply PCB correctly mounted in the enclosure with its three PCB retaining screws securely tightened.
DO NOT connect Mains to the Power Supply PCB until the installation is complete and ALL relevant PCBs are correctly attached within the panel.
Fig. 3 : Power Supply PCB layout and Mains connection details
Incoming Mains cable must be segregated from other cables
he PSU earth strap MUST
T be connected to the spade
on the main base earth post before operation. The spade is compressed against a shoulder on the post via the lowest nut. The earth post may appear loose, this is intended by design.
and should only enter the panel through either of these knockouts. Good quality cable glands must always be fitted.
Ten-way connection loom
(connects to PL1 on the Main Control PCB).
DO NOT REMOVE WHEN PANEL IS POWERED
Battery fuse (F3) 20mm x 3.15AF glass fuse to IEC 127 (EN60127-2).
Battery leads (note that a battery jumper lead is supplied in the panel’s accessory pack). See page 11 for further details.
Primary fuse (F2) 20mm 1ATH 250V HRC ceramic fuse to IEC 127 (EN60127-2).
The incoming Mains earth wire MUST be connected to the terminal marked and NOT to the main base earth post.
(The PSU earth strap connects the PCB to the base earth post).
WHEN CONNECTED, THE PCB STORES VOLTAGES AT UP TO 400Vd.c. AND
MAY BE LETHAL IF TOUCHED. DO NOT TOUCH THE PCB WHILST THE RED ‘HAZARDOUS VOLTAGES PRESENT’ LED IS LIT.
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 7 of 36
Page 8
FP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
X
Analogue addressable loop wiring
Fig. 4 below shows a typical analogue addressable loop complete with loop isolators, detectors, loop-powered sounders, modules and monitors. The descriptions and availability of the devices shown may not be applicable to all manufacturers’ protocols – check with your supplier for further details. Also this example arrangement of devices may not be permitted by design and installation regulations in certain countries. The loop should be connected to the relevant 5mm connector block on the panel’s Main Control PCB and its screens terminated at the panel’s base earth post as shown on page 9.
Fig. 4 : A typical analogue addressable loop
XFP
panel
Design issues - reducing faults and their consequences
To ensure a reliable system, it should be designed and maintained to local design and installation regu­lations. The XFP has loop isolators included in the panel, and loop isolators should be included in the loop wiring. A single short circuit fault will now only disable devices in the section of wiring between isolators. Local design and installation regulations will dictate how many devices or zones may be lost in the case of this type of fault. In the case of a single open circuit no devices will lost, since communi­cation is from both ends of the loop, but a loop integrity fault will be shown.
Note that a critical design issue with any analogue fire system is the combined effect of loop resistance, loop capacitance and the current demand of items connected to the loop.
Factors that influence this include loop length, cable diameter, cable type, the number of isolators used and the number and type of devices between isolators. There are no hard and fast rules regarding these factors as every situation is unique. However, if the following conservative advice is followed, the loop WILL almost certainly work.
• Absolute maximum loop length = 1km, with either 1mm2or 1.5mm2cables.
• No more than 20 addressable devices between loop isolators of which no more than 6 are loop sounders.
• If loop sounders are used, use 1.5mm
• If more than 10 loop sounders are used per loop then the maximum loop length per loop should be no greater than 750m.
2
cable and do not fit more that 32 loop sounders per loop in total.
The above SHOULD NOT be considered the maximum operating conditions for the panel as many other permutations are possible. Any limitations are a consequence of device manufacturers’ protocol, coupled with the cable’s characteristics. The panel’s loop driver is easily capable of driving lightly loaded loops up to 4 km long without a problem. However, devices connected at the end of 4 km may not be able to read the data once corrupted by the cable.
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 8 of 36
Page 9
A+ A- B+ B-
A+ A- B+ B-
Fault
NC C NO
Relay 3
NC C NO
Relay 2
NC C NO
R
elay 1
NC C NO
Sndr 1
+ -
S
ndr 2
+
-
+24v 1/P1 1/P2 0v
BATTERY FUSE
3.15AF
PRIMARY FUSE
+
L N
P
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
nut
plain washers
c
rimped
c
onnections
Do not untighten lower nut
spring washer
screens
Connecting the analogue loop to the Main Control PCB
The analogue loop(s) should be connected to the Main Control PCB as shown in Fig. 5 below. Remember to isolate the panel’s Mains and battery backup supplies prior to installation.
The loop’s earth screens should be adequately insulated and connected between the nut and washers on the main base earth post using eyed crimp connectors. The lower nut must be secure to ensure earth continuity.
The base earth post is provided for terminating earth screens or drains and is NOT the main earthing point. The installer must review the external earth bonding (if required) with respect to the national wiring rules. If the installation requires protective earth bonding, then this must be applied externally and in conjunction with the type of earthing system
mployed on site.
e
Ensure the PCB retaining screw is properly tightened before operation as it plays an important part in the electrical safety and EMC immunity of the panel.
Fig. 5 : Typical analogue addressable loop connection
Analogue loop
Additional loop
connector
(if applicable).
This LED will be lit amber
if there is a
short circuit
on loop 1’s
A+ A- leg
Conventional sounder circuit wiring
Two conventional sounder circuits are provided. These can accommodate up to 40 conventional polarised sounders (at 20mA) or 32 bells (at 25mA) per system. If a full complement of sounders or bells are to be used, split them equally across both circuits. A 6k8 end of line resistor (provided) must be connected at the end of each sounder circuit to allow the wiring to be monitored. If the sounder circuit is unused, you must still connect the 6k8 resistor at the panel.
Each sounder circuit should be connected to the terminal marked CONN7 on the Main Control PCB as shown in Fig. 6 (page 10) and its earth screens terminated at the panel’s base earth post. Remember to isolate the panel’s Mains and battery backup supplies prior to installation.
This LED will be lit amber
if there is a
short circuit
on loop 1’s
B+ B- leg
CONN8
This LED will be lit amber
if there is a
short circuit
on loop 2’s
A+ A- leg
CONN9
This LED will be lit amber
if there is a
short circuit
on loop 2’s
B+ B- leg
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 9 of 36
Page 10
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
A- B+ B-
A A- B+ B-
F
CTS 0v RX TX
+24v 1/P1 1/P2 0v
A- B+ B-
A A- B+ B-
Fault
NC C NO
Relay 3
NC C NO
Relay 2
NC C NO
Relay 1
NC C NO
E
ND OF LINE RESISTOR (6k8 Ohm)
POLARISED
SOUNDER
POLARISED
SOUNDER
+ + +
+
POLARISED
SOUNDER
+
DO NOT SPUR
(wiring not m
onitored)
A+ A- B+ B-
Sndr 1
+ -
Sndr 2 + -
A+ A- B+ B-
Fault
N
C C NO
R
elay 3
NC C NO
R
elay 2
NC C NO
lay 1
Fig. 6 : Typical conventional sounder circuit connection and detail
Conventional
sounder circuit
Conventional sounder
ircuit detail
c
For more precise
arth screen
e termination details refer to the typical analogue loop wiring diagram on page 9.
Additional conventional
CONN7
sounder circuit
Auxiliary input wiring
Two programmable auxiliary input connections are provided. These can be programmed using the panel’s PC programming software tools to operate as required. The wiring for each input should be connected to the terminal block marked CONN2 on the Main Control PCB as shown in Fig. 7 below. Remember to isolate the panel’s Mains and battery backup supplies prior to installation.
Fig. 7 : Typical auxiliary input wiring / connection
Input 1
Input 2
If applicable (i.e. in electrically noisy environments), input wiring screens should be terminated at the panel’s base earth post in the same way as the analogue loop earth screens, as detailed on page 9.
CONN2
Relay output wiring
Four volt-free relay output connections are provided - a failsafe fault output, which switches for any fault condition, and three programmable auxiliary relay outputs. All four relays are capable of switching 1A @ 30Vdc. They should NOT be used for switching Mains voltages.
The three auxiliary outputs (Relays 1, 2 and 3) can be programmed using the panel’s PC program­ming software tools to operate as required but their default operations are: Relay 1 : Switches when any zone goes into fire, switches back when the panel is silenced; Relay 2 : Switches when any zone goes into fire, switches back when the panel is reset; Relay 3 : Has no default operation
The wiring for each output should be connected to the relevant connector block on the Main Control PCB. Fig. 8 below explains how the outputs work. Remember to isolate the panel’s Mains and battery backup supplies prior to installation.
Fig. 8 : Relay output detail
CONN3
4
CONN5
4
3
4
3
4
3
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 10 of 36
3
CONN6
Page 11
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Space for
batteries
Red wire from panel
Shorting link (supplied in panel accessory pack)
Black wire from panel
12V battery
12V battery
Remote PC connection
A four-way RS232 molex connector (PL2) is provided on the Main Control PCB for the connection of a Windows based PC for pro­gramming purposes. The ONLY way to program this fire panel is using a PC loaded with the panel’s sophisticated programming tools (Part No. XFP507). The lead supplied with the software tools should be connected to the panel and the PC as shown in Fig. 9 (right).
Fig. 9 : Connecting a PC to the panel’s RS232 connector
RS232
NVM ‘memory unlock’ link, must be fitted when uploading or downloading information from/to the PC
Plug the lead’s ‘D’-type connector into the appro-
riate serial socket (com1, com2, etc) on the PC
p
Printer connection
A second RS232 socket (CONN1) is provided on the Main Control PCB for the optional connection of a serial printer to allow optional printing of the panel’s 500 event log. We recommend the use of the AFP709 off-board printer kit which includes a printer, a 3m long connection lead and an isolation mod­ule/socket. The purpose of the isolation module/socket is to interface the panel to the printer and to prevent earth faults caused by the printers internal 0V to earth connection being generated at the panel. For further information, please refer to the information supplied with the printer kit.
Aux. 24V output
One fused 24V d.c. output, rated at 100mA, is provided and can be used for supplying power to ancil­lary fire alarm equipment. This input should not be used to power electromagnetic door retainers.
Installing the standby battery supply
Two new, good quality and fully charged 12V valve regulated lead acid batteries are required as the emergency stand-by power supply for the panel. The batteries should be connected in series and located in the panel’s enclosure as shown in Fig. 10 below. The battery leads, link wire and nylon cable ties are provided in the panel’s accessory pack. Run the battery leads through the slits in the panel’s lower plastic ribs and secure the batteries into position using the nylon cable ties as shown.
The panel’s sophisticated battery monitoring unit protects the batteries against deep discharge by activating a cut off circuit when the stand-by supply voltage reaches 21V approx. If batteries are not fitted, are discharged or in poor condition, a PSU fault will show at the panel.
The capacity of the batteries used will depend upon the required stand-by time. To calculate the bat­teries required for any given stand-by period, refer to the battery calculation guide on page 35.
Always dispose of used batteries according to the battery manufacturer’s instructions.
Fig. 10 : Battery location and connection details
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 11 of 36
Page 12
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Network/repeater wiring (optional)
The XFP’s network protocol allows the interconnection of up to eight XFP main panels (any mix of single loop 16 zone XFPs and/or 1 to 2 loop 32 zone XFPs) over a two-wire RS485 network. Alternatively, the network can be used to connect up to eight XFP repeaters to one XFP main panel. It is not possible to mix XFP main panels and repeaters on the same network.
Key features of the XFP’s network protocol when used for interconnecting XFP main panels:
Allows the interconnection of up to eight XFP main panels (any mix of single loop 16 zone XFPs and
• 1 and 2 loop 32 zone XFPs)
• Up to 1 km of cable may be fitted to an XFP main panel network.
• Each networked XFP main panel can be programmed to: Accept Fires from other main panels. Accept Faults from other main panels. Accept Control actions such as Silence Alarm Sounders and Control Panel Reset from other main panels. Accept Disablement commands for zones, sounders and output sets from other main panels. (Each of these four functions may be individually selected via the panel’s PC Programming Software Tools.)
• All panels monitor all other panels for network wiring faults.
• Fires on remote panels are displayed on local panels including the point description of the alarm’s origin.
• Faults on remote panels are displayed on local panels.
• Cause and effect can be programmed into local panels dependent on which remote panel is in alarm.
• The network supports the programming of site information into remote panels from a PC connected at a local panel.
• Time and date is common to all panels throughout the network.
Key features of the XFP’s network protocol when used for connecting XFP repeaters
• Allows the connection of up to eight XFP repeaters (any mix of single loop 16 zone repeaters and 1 and 2 loop 32 zone repeaters)
• Up to 500m of cable may be fitted to an XFP repeater network.
• Each XFP repeater offers all the functions and controls of an XFP main panel
Any XFP main panel connected to the RS485 network requires the installation of a Network Communication Card (Part No. AFP711), as shown in Fig. 11 below (Repeaters come with a Network Communication Card already fitted). Typical network wiring details are shown in Fig. 12.
Fig. 11: Installing the Network Communication Card
Important: Before installing the Network Communication Card, isolate the Mains supply and disconnect the panel’s battery back-up supply. With reference to the diagram below:
• Disconnect the 10-way loom from PL1, the lid/base connecting cable from PL5 and all remaining connections from the top of the Main Control PCB as necessary.
• Unfasten the retaining screw at the bottom left of the Main Control PCB using a crosshead screwdriver and push the PCB up and over the panel’s mounting pillars.
• Insert the two hexagon spacers (supplied with the network
See Fig. 12
for typical
network
wiring details
communication card) through the holes on the Main Control PCB and secure them using the nuts and washers provided, see right.
• Take the network communication card and carefully line its holes up with the two hexagon spacers, ensuring that it’s 6 way pin connectors are correctly inserted into PL3 on the Main Control PCB.
• Secure the card onto the hexagon spacers using the two 6mm slotted screws (supplied).
• Refit the Main Control PCB and all relevant connection cables previously removed. Ensure that the PCB retaining screw is firmly fastened down.
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 12 of 36
Page 13
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
REPEATER 1
MASTER REPEATER 2
REPEATER 5
REPEATER 8
SPUR WIRING
NOT ALLOWED
SPUR WIRING
NOT ALLOWED
REPEATER 1
MASTER REPEATER 2
REPEATER 5
REPEATER 8
SPUR WIRING
NOT ALLOWED
SPUR WIRING
NOT ALLOWED
Note the DIP switch (SW1) on the network communication card has no function when used with the XFP. However, all networked XFP main panels require a unique ID number (1-8) so they can be recognised by other panels on the network and this is assigned using the network functions menu options at access level 3 (see page 20 for details). XFP repeaters do not require an ID number.
Fig. 12: Typical network wiring
The network wiring should be installed to meet BS 5839 Part 1 and BS7671 (Wiring Regulations) and/or other national standards of installation where pertinent - see cable types & limitations, page 3.
At ONE networked panel only, connect A to A, B to B and terminate incoming and outgoing earth screens to the panel’s side earth post. This earth post must also be connected to terminal C on the network communication card’s connector block as shown.
IMPORTANT: At all other networked panels, con­nect A to A, B to B and terminate earth screens to terminal C only.
O NEXT NETWORKED
T
PANEL IF REQUIRED
NETWORK COMMUNICATION CARD
A typical XFP main panel network
PANEL 2
A typical XFP repeater network
XFP
MAIN
PANEL 1 PANEL 5
XFP
REPEATER
XFP
REPEATER
TO NEXT NETWORKED
PANEL IF REQUIRED
PANEL 3
XFP
REPEATER
NETWORK COMMUNICATION CARD
PANEL 4
XFP
REPEATER
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 13 of 36
Page 14
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
F
ire Zones
1
7181920 212223242526272829303132
1
2345678910111213141516
Fire
general
fault
p
ower supply
fault
system
fault
sounder
status
delays
running
t
est
a
ccessed
general
disablement
phased
evacuation
more informa tionmenu
s
ilence
i
nternal
s
ounder
s
ilence/res ound
sounders
control panel
reset
i
nvestigate
escape
accept
s
upply
present
General fault
F
ire Alar m Contr ol Panel Instr uct ions
f
lashing light -callengineer
O
I
To view more events use the scroll buttons
To silence the internal sounder:press
To silence/resound the alarm sounders:
Turn key to an d pr essl
press and . Enter code and pressOR
T
oresetthepanel:
Ensure all alarm conditions are silenc ed and
investigations are comple te and press
To exit access mode: ORRemove key press and hold
10:59:03 24 Jun : Normal FREDCO WAREHOUSING
CONTROLS AND INDICATORS
Front panel layout
LED Indicators
Liquid Crystal Display Provides detailed information on the status of the system (the type of messages
displayed and what they mean is covered in greater detail in the panel’s separate user manual)
(General) Fire Flashes red when there is a fire condition on any zone and goes steady red
Fire Zones One or more of these indicators will flash red in an alarm condition and will go (1-16 or 1-32) steady when silenced
Supply Present Normally lit green to show that all of the panel’s power supplies are
Test Lit yellow when the panel is in walk test mode. This LED does NOT illuminate
Accessed Lit yellow when the panel is in Access Level 2 or 3.
General Disablement Lit yellow when one or more zone, sounder, output or relay is disabled.
Phased Evacuation Flashes yellow when there is a phased evacuation in process.
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 14 of 36
when the alarm is silenced. Subsequent fire conditions will restart the (General) Fire indicator flashing until it is silenced again
functioning correctly
for any other test condition
Page 15
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
OO
II
LED Indicators (continued)
General Fault Flashes yellow when there is an fault condition on the panel. Will always
e lit in conjunction with at least one other fault LED.
b
Power Supply Fault Lit yellow when the panel’s power supply or Mains has failed or the panel’s
standby battery is in poor condition.
System Fault Lit amber when a system error, such as a microprocessor fault, occurs. Remains
lit even if the panel automatically clears the fault.
Sounder Status Flashes yellow when a fault is detected on either of the panel’s two
conventional sounder circuits or if there is a sounder disablement anywhere on the system.
elays Running Lit yellow when one or more output delays have been programmed into the
D
panel. Flashes yellow when one or more output delay is running.
Button controls
More Information Displays additional information on any fire, pre-alarm or fault conditions
that appear on the panel’s display. Will also display additional context dependant information where appropriate.
(Scroll Up) (Scroll Down)
Accept Escape
Menu Provides access to the panel’s menus
Silence Internal Sounder Silences the panel’s internal sounder
Control Panel Reset Resets the panel when the sounders are silenced (access levels 2 & 3 only)
Silence / Resound Sounders Silences or resounds the system’s sounders (access levels 2 & 3 only)
Investigate Starts the panel’s investigate timer function (access levels 2 & 3 only)
51 Dependent on the status of the panel, these two buttons:
63 • scroll vertically through any fire, pre-alarm or fault conditions that appear
on the panel’s display
• scroll vertically through the panel’s user menus
• manipulate date, time and disablement settings, etc
• serve as code input buttons to access levels 2 or 3.
42 Dependent on the status of the panel, these two buttons: 34 • scroll horizontally through the panel’s user menus
• escape or accept options available in the panel’s user menus
• serve as code input buttons to access levels 2 or 3.
Keyswitch control
Turning the keyswitch to the armed position (I) gives the user instant access to access level 2 (authorised user level).
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 15 of 36
Page 16
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
COMMISSIONING AND PROGRAMMING
Overview
Commissioning is the setting to work of the equipment. The efficiency with which this is done
epends upon:
d
• The accuracy of information received regarding the wiring and devices fitted.
• The freedom of the installation from faults and errors.
• The completeness of the information received from the client/specifier as regards the zoning, naming and functioning of the system.
The final quality of the installation ALWAYS depends upon the quality of these three factors.
Recommended commissioning procedure
Re-fit the panel’s PCBs and all connection leads by reversing the removal procedure detailed on page 5. Ensure all PCB retaining screws are firmly fastened down and that the PSU earth strap is connected to the base earth post. If a network communication card is required, this should be fit­ted as shown on page 12.
Check the continuity of the loop, the resistance of the conventional sounder circuits (if applicable) and all other field wiring as appropriate to ensure they are free from faults. DO NOT MEGGER! Remove all electronic devices if 500V testing is demanded).
If okay, connect all field wiring to the main control PCB as detailed on pages 8 to 11.
Connect the Mains supply to the L, N and terminals on the power supply PCB and the standby battery supply to its BAT1 terminals.
Upon powering up, the panel’s LCD will display a number of start up messages detailing the proto­col of the panel, etc.
Investigate any faults reported on the panel’s display and take the necessary steps to correct them.
When all faults have been corrected, carry out a loop learn as detailed on page 21. Rectify any problems resulting from loop learn (e.g. double addresses, missing devices, incomplete loops etc. Note that a wide range of test and fault-finding functions are available in access level 3.
When all faults have been cleared, proceed to program the panel as appropriate.
When you are satisfied the panel has been programmed and is working correctly, secure the panel lid and instruct the client/customer in the operation of the system.
Complete and handover all necessary manuals and other documentation prior to leaving site.
System operation / terms of reference
Input devices such as detectors, manual call points and the input channels of I/O units are programmed to be members of a Zone.
Output devices such as loop powered sounders, sounder control units and the panel’s conventional sounder circuits are programmed to be members of a Group.
The output channels of I/O units and the panel’s relays are programmed to be members of a Set. Zones are programmed via the panel’s software to activate Groups and/or Sets as appropriate. The method of activation of Groups can be continuous or pulsed, with or without a delay, as
required. Note that the panel’s two auxiliary inputs can be programmed to function in a multitude of ways
using the special cause and effects options available in the XFP programming software.
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 16 of 36
Page 17
FP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
ENTER ACCESS LEVEL 3
DISPLAY FIRE EVENTS
DISPLAY FAULT EVENTS
DISPLAY DISABLEMENTS
D
ISPLAY ZONES IN TEST
LAMPS TEST
DISPLAY ALARM COUNTER
S
ET TIME/DATE
EVENT LOG FUNCTIONS
SET/CLEAR DISABLEMENTS
CHANGE ACCESS LEVEL 2 CODE
DISPLAY ALARM COUNTER
Clear to todays date?
P
RINT EVENT HISTORY?
DISPLAY EVENT HISTORY?
RESET EVENT HISTORY?
ENABLE/DISABLE ZONES ENABLE/DISABLE SOUNDERS ENABLE/DISABLE OUTPUTS ENABLE/DISABLE RELAYS ENABLE/DISABLE DEVICES ENABLE/DISABLE FAULT RELAY ENABLE/DISABLE OUTPUT DELAYS
E
NTER ACCESS LEVEL 2
DISPLAY FIRE EVENTS
D
ISPLAY FAULT EVENTS
DISPLAY DISABLEMENTS
DISPLAY ZONES IN TEST
ENTER ACCESS LEVEL 3
LAMPS TEST
DISPLAY ALARM COUNTER
DISPLAY FIRE EVENTS
DISPLAY FAULT EVENTS
DISPLAY DISABLEMENTS
SETUP PASSWORDS
CONNECT TO PC
NETWORK FUNCTIONS
COMMISSIONING FUNCTIONS
ENGINEER FUNCTIONS
CHANGE ACCESS LEVEL 2 CODE CHANGE ACCESS LEVEL 3 CODE
SET COMMS FUNCTION SET PANEL NUMBER SET PANEL FITTED
LOOP LEARN FIND NEW DEVICES SHOW FITTED DEVICES ASSIGN ZONE/GROUP CALIBRATE DEVICES COMMISSION THE LOOP(S) SHOW CALIBRATION PROBLEMS SHOW DUPLICATE ADDRESSES SET DAY/NIGHT TIMES ENABLE/DISABLE DST ADJUSTMENT CONFIGURE SOUNDER DISABLEMENTS MAKE A CLEAN START
SET/CLEAR DISABLEMENTS MONITOR A POINT TEST DEVICE OUTPUTS TEST OUTPUTS SETS TEST SOUNDER GROUPS TEST PANEL RELAYS WALK TEST BLINK DETECTORS LEDS INTENSIVE DEVICE MONITOR LOOP TEST DISPLAY DATABASE VERSION NUMBERS SHOW PSU STATS ENABLE/DISABLE EARTH FAULT SHOW LOOP CURRENT SHOW DISCOVERY EEPROM SHOW NETWORKED EVENTS
ENABLE/DISABLE ZONES ENABLE/DISABLE SOUNDERS ENABLE/DISABLE OUTPUTS ENABLE/DISABLE RELAYS ENABLE/DISABLE DEVICES ENABLE/DISABLE FAULT RELAY ENABLE/DISABLE OUTPUT DELAYS
AL1
AL2AL3
M
enu button
on front of panel
CODE ENTRY
CODE ENTRY
K/S ENTRY
OO
II
X
ACCESS LEVELS MENU TREE
Three access levels are available at the panel - access level 1 (general user), access level 2 (authorised user) and access level 3 (engineer). The diagram below shows the menu options available at each level, all of which can be navigated using the panel’s scroll (56), Accept (4) and Escape (3) buttons. Note: Menu options shown in bold will only be available if relevant to the panel’s status.
This manual focuses on the functions available at access level 3 only (access levels 1 and 2 are covered in the panel’s separate user manual). Details of how to gain entry to access level 3 and an explanation of the various functions available can be found on the following pages.
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 17 of 36
Page 18
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
A- B+ B-
A B+ B-
F
C NO
R
-
E
nter Access Level 3 code:
ow to enter access level three
H
Access level 3 can be entered in one of two ways:
(1) By pressing the Menu button on the panel’s front, scrolling down to ENTER ACCESS LEVEL 3 and
pressing the Accept4button. When you have done this, the following prompt will appear:
nter the four-digit access level 3 code using the 5(1) 4(2) 6(3)3(4) buttons as appropriate.
E The default code is 4 4 4 4 (four presses of the
3button). If this does not work, the code may
have been changed. As soon as the code has been entered correctly, you will be taken into access level 3 (see pages 19 to 33).
(2) By entering access level 2 as detailed in the panel’s separate user manual, scrolling down to
ENTER ACCESS LEVEL 3 and repeating the process described above.
In access level 3, the panel’s Silence / Resound Sounders, Control Panel Reset and Investigate buttons become active and you can:
• Scroll through any fire, pre-alarm or fault conditions which are displayed on the panel’s LCD
• View any disablements or zones that are in test (if applicable)
• Change the entry codes to access levels 2 and 3 from their factory default settings
• Connect the panel to a compatible PC for system programming
• Set the panel up to belong to a network of up to eight XFP main panels or allow it to have up to eight XFP repeaters connected to it.
• Gain access to a wide range of commissioning functions including auto loop learn, device calibration and group/zone assignment
• Gain access to a wide range of engineering test and fault finding functions
• Ascertain software revision numbers, loop current and PSU statistics
• Enable/disable earth faults
• Set the time the panel enters and exits day (building occupied) and night (building unoccupied) mode
• Access all of the panel’s access level 2 menu options as described in the panel’s separate user manual.
This section of the engineering manual explains in detail the various functions available via the access level 3 menu options. (Note that information on how fire, pre-alarm and fault conditions are reported, and how the panel’s control buttons operate, can be found in the separate user manual/log book).
Fitting the panel’s NVM ‘memory unlock’ link
To allow site-specific changes to be made to the panel’s non-volatile memory, the NVM ‘memory unlock’ link (PLK2)
NVM memory
unlock link
must be fitted to the Main Control PCB, as shown right. It is recommended that you fit this link as a matter of course whenever you are in access level 3.
Remember to re-lock the memory (remove the link) when programming is complete to guard against data corrup­tion.
PLK2 LINK TO UNLOCK NVM
If you do not re-lock the memory, a reminder message will appear when you leave access level 3.
A detailed description of the functions available at access level 3 can be found overleaf.
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 18 of 36
Page 19
FP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Last Zone: 1:North Stairs :Fire!
1
Zone
Zone 1: Ground Floor
There are faults on this zone
1st Zone: 1: Shop floor
On: This Panel: Is Disabled
Zone 1: North Stairs Is On Test
CHANGE ACCESS LEVEL 2 CODE?
Change Access Level 3 code
Enter NEW Access Level 2 code:
X
Display Fire Events
This function is only available if there are active fire conditions on the system. If available, press the Accept
4button and a window similar to the one below will appear:
Pressing the information (if applicable) can be viewed by pressing the panel’s More Information button. To return to the main access level 3 menu press the Escape
Display Fault Events
This function is only available if there are active faults on the system. If available, press the Accept
Pressing the 5and6buttons will scroll the display through all active faults. More detailed informa­tion (if applicable) can be viewed by pressing the panel’s More Information button. To return to the main access level 3 menu press the Escape
Display Disablements
This function is only available when there are active disablements on the system. If available, press the Accept
Pressing the 5and6buttons will scroll the display through all active disablements. More detailed information (if applicable) can be viewed by pressing the panel’s More Information button. To return to the main access level 3 menu press the Escape
5and6buttons will scroll the display through all active fire conditions. More detailed
3button.
4button and a window similar to the one below will appear:
3button.
4button and a window similar to the one overleaf will appear:
3button.
Display Zones In Test
This function is only available if one or more zones are being tested. If available, press the Accept
Pressing the information (if applicable) can be viewed by pressing the panel’s More Information button. To return to the main access level 3 menu press the Escape
Setup Passwords
This function allows you to change the four digit access codes required to activate the panel’s access level 2 or 3 menu options. When selected, press the Accept
Use the option) and press the Accept LEVEL 2 CODE? prompt is accepted.
Using the digit has been entered, the panel will request you confirm the new code by re-entering it:
4button and a window similar to the one below will appear:
5and6buttons will scroll the display through all zones currently in test. More detailed
3button.
4button and the following window will appear:
5and 6buttons to scroll to the desired option (the option in block capitals is the selected
4button. The following message will appear if the CHANGE ACCESS
5(1) 4(2) 6(3)3(4) buttons, enter the new four digit access level 2 code. After the fourth
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 19 of 36
Page 20
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
SET PANEL NUMBER:1
NETWORK PANEL:1
Enter NEW Access Level 2 code:**** C
onfirm New Access Level 2 code:
PC connected...
Press ESC to disconnect from PC
COMMS IS SET FOR: REPEATER
Enter the code again by pressing the 5(1) 4(2) 6(3)3(4) buttons in same sequence. If the codes match,
he new code will be accepted and you will be taken back into Access Level 3. If you type an incorrect con-
t firmation code you will be prompted to start the code entry sequence again. The same process can be used to change the access level 3 code. BE SURE TO KEEP A RECORD OF ANY CHANGED CODES FOR FUTURE USE.
onnect to PC
C
This function allows you to activate the panel’s PC connection for system programming purposes. ALL of the panel’s cause and effect programming, device and zone naming, zone dependency functions, etc., must be carried out using our separate PC programming tools (Part No. XFP507). When the CONNECT TO PC? prompt appears, press the Accept
If there is a problem with the panel to PC connection, this will be flagged at the PC when you try to upload or download any site specific data.
4button. If all connections are correct, the following message will appear:
Network functions
Selecting this menu option takes you to the network functions submenu where you can configure the panel to be part of a network of up to eight XFP master panels or allow it to have up to eight XFP repeaters connected to it. This option is only available if you have a network communication card fitted at the panel (see pages 12 & 13 for a detailed overview of master panel networking and repeater panel connection). The network functions submenu has three options - SET COMMS FUNCTION, SET PANEL NUMBER and SET PANEL FITTED. Other options, such as what events and what level of control is allowed between networked panels is implemented using the panel’s PC programming software tools.
SET COMMS FUNCTION
This function allows you to set the panel’s RS485 comms to operate in Network or Repeater mode. When selected, press the Accept
Use the priate. The panel’s flash database will update and you will be returned to the Network Functions submenu.
SET PANEL NUMBER
If networking XFP main panels, this function allows you to give the panel a unique ID number (1-8) so it can be recognised by other panels on the network. Note that Repeaters do not need to be assigned an ID num ber. When selected, press the Accept4button and a message similar to the one below will appear:
Use the The panel’s flash database will update and you will be returned to the Network Functions submenu.
SET PANEL FITTED
This function allows you to turn off the fault monitoring of other networked XFP main panels. It is typically used if maintenance work is to be carried out at a networked panel to temporarily prevent integrity faults being flagged. When selected, press the Accept
5and 6buttons to scroll between Repeater and Network and press the Accept4button as appro-
5and 6buttons to scroll to the desired number and press the Accept4button to select it.
4button and a message similar to the one below will appear:
4button and a message similar to the one below will appear:
-
Use the accept it. The panel’s flash database will update and you will be returned to the Network Functions sub­menu. Remember to reverse the function when maintenance work is complete.
5and 6 buttons to scroll to the desired networked panel and press the Accept4button to
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 20 of 36
Page 21
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Continue with Loop Learn?
Learn Loop:All
Erase ALL loop device data first?
Are you sure you want to erase the Database?
0 changed; 0 removed; 112 total devices Auto learn completed
Commissioning functions
Selecting this menu option takes you to the commissioning functions submenu where you can carry out a loop learn; find new devices; view fitted devices; assign detectors/call points to zones and sounders/beacons to groups; manually calibrate devices; and/or return the panel to its default factory settings. All of these functions are described in detail below. Note that the vast majority of system
ommissioning - cause and effect programming, device and zone naming, etc. - must be carried out
c using our separately available PC programming software tools (Part No. XFP507).
LOOP LEARN
This function activates the panel’s automatic loop learn facility. During a loop learn, the panel inter­rogates every address location on the loop to see if an addressable unit is present and, if so, finds out what type of device it is. When the LOOP LEARN? prompt appears, press the Accept and you will be asked to confirm that you wish to continue:
4button
Press the Accept the panel to learn (1, 2 or ALL, as applicable).
Use the may already have loop device data stored in its memory from a previous loop learn or PC upload, you will be asked if you want to erase this information before the loop learn begins.
You now have two options, as detailed below:
Option 1
If the panel has not previously been programmed or if you want to program an existing system as if it were a new system, press the Accept
Press the Accept start to learn the loop(s) as appropriate.
Option 2
If you DO NOT wish to erase the loop device data, press the Escape3button and the panel will immediately start to learn the loop without overwriting data such as zone and group allocation, detector sensitivities, device names, etc., which will remain as it was before the Loop Learn. The only data that will be overwritten is device type and whether or not it is fitted. See note above about default loop learn settings.
5and 6buttons to scroll to the desired loop(s) and press the Accept4button. As the panel
Note that by default the loop learn will assign all detectors/manual call points to zone 1 and all sounders/ bea­cons to group 1. This is to ensure that all of the system’s sounders will activate in the event of a fire condition anywhere in the building, i.e. one out, all out. These default settings can be modified as appropriate using the panel’s PC programming software tools at a later date. Note that no default sets are assigned to the outputs of I/O units - these must be assigned using the panel’s PC programming software tools.
4button again to continue and you will be asked to select which loop(s) you want
4button. The following message will appear:
4button again and the panel will erase its database, update its flash memory and
Depending on the size of the installation, the loop learn process can take several minutes. When the auto-learn process is complete, a brief summary window will appear, similar to the one below:
Press the Escape
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 21 of 36
3button to return to the Commissioning Functions submenu.
Page 22
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
On loop: 1
Loop:2 Dev :48 :Optical det 0x88 Accept device?
Shop floor: No name allocated Belongs to Zone:- 1
0 changed; 0 removed; 112 total devices Auto learn completed
On loop: 1
L:1D: 1 SMCCOOIC-I 10 L:1D: 11 -C-TT--MMC 20
Continue to find new devices?
IND NEW DEVICES
F
This function allows you to check if any new devices have been connected to the panel since the last loop learn. It works in a similar way to the loop learn function except whilst learning the loop, the panel asks if you want to accept any of the new devices it has found and allows you to assign them to a detector zone or sounder group as appropriate. To start the search process, when the FIND NEW DEVICES? prompt appears press the Accept
4button. The following window will appear:
Press the Accept which loop(s) you want the panel to search for new devices on (1, 2 or ALL, as applicable).
Use the 5and 6buttons to scroll to the desired loop(s) and press the Accept4button. The search will now begin. When a new device is found, the panel will tell you its type, its address (Dev) and the loop it is fitted on, for example:
To accept the new device press the Accept reject it. If the Escape device is found. If the Accept device to a detector zone or a sounder group as appropriate. For example:
Use the 5and 6buttons to scroll to the desired zone or group and press the Accept4button. The device search will now continue until the next new device is found. (Note that I/O units, etc. can only be assigned to output sets via the panel’s programming tools. Therefore, when accepted, the panel will continue its search for new devices straightaway. When the new device search is complete, a brief summary window will appear, similar to the one below:
4button again to confirm you wish to continue and you will be asked to select
4button. Alternatively, press the Escape3button to
3button is pressed, the panel will continue searching until the next new
4button is pressed, you will be given the opportunity to assign the
Press the Escape
SHOW FITTED DEVICES
This function will list all of the addressable devices stored in the panel’s memory. It DOES NOT give a list of what is on the loop at the exact time the function is selected, i.e unlearnt devices will not show but faulty / missing devices will. When the SHOW FITTED DEVICES prompt appears, press the Accept
Use the similar to the one below will appear.
Devices are displayed in groups of 10. In the example above, the top line shows the type of devices fitted at addresses 1 to 10 on loop 1 and the second line shows the type of devices fitted at addresses 11 to 20. The letters displayed will be dependent on the type of device at that address location.
4button and you will be asked to select which loop’s devices you want to view:
5and 6buttons to scroll to the desired loop(s) and press the Accept4button. A window
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 22 of 36
3button to return to the Commissioning Functions submenu.
Page 23
FP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Loop:1 Device:-1
Shop floor: No name allocated Belongs to Zone:- 1
Continue to Calibrate Devices?
This may take several minutes OK to proceed?
X
C = call point I = ionisation detector M = module O = optical detector S = sounder Z = zone monitor H = heat detector D = multisensor ? = unknown
To view the remaining devices on the loop, use the Escape
3button to return to the Commissioning Functions submenu.
ASSIGN ZONE/GROUP
This function allows you to assign devices to be members of detector zones or sounder groups as appropriate. This would normally be done using the panel’s PC programming software tools but is
rovided at the panel in case you need to add a device at short notice, typically when a PC is not avail-
p able. It therefore allows you to get a new device working in a basic manner whilst it is waiting to be properly configured at a later date. When selected, you will be prompted to enter the loop on which the device you want to assign is located followed by the device’s address (device) number:
5and 6buttons as appropriate. Press the
Use the be presented with the zone/group assignment window, for example:
Use the assignment will be made and you will be prompted to select another loop/device to assign using the same procedure. Alternatively, to return to the Commissioning Functions submenu press the Escape Important, although I/O units, etc., can be assigned to be members of zones using this menu, this will only apply to their input functions. The panel’s PC programming software tools must be used to assign them to output sets.
CALIBRATE DEVICES
Daily calibration of the system’s smoke and heat detectors (to take into account environmental changes, drift compensation factors, etc.) takes place automatically at 0400 hours, or at an alternative time as pro­grammed by the engineer. The CALIBRATE DEVICES function allows you to carry out an additional manual calibration of the system’s devices at any time. When selected, you will be asked if you wish to proceed:
Press the Accept some time. When calibration is complete, the system will return to the Commissioning Functions submenu.
COMMISSION THE LOOP(S)
This function refreshes the characteristics (calibration levels, contamination values, etc) and checks the type codes of all devices connected to the loop(s). When selected, you will be asked if you wish to proceed:
5,6 and Accept4 buttons to select the desired loop and address (device). You will then
5 and 6 buttons to scroll to the desired zone or group and press the Accept4button. The
3button.
4button and calibration will start. Depending on the size of the system, this may take
Press the Accept return to the Commissioning Functions submenu.
SHOW CALIBRATION PROBLEMS
This function allows you to view any detector(s) with calibration issues. In addition to listing detectors that have definitely failed to calibrate correctly and will no longer function reliably, it also lists those that are in the process of being checked and MAY fail to operate correctly.
When the SHOW CALIBRATION PROBLEMS prompt is accepted, details of the first detector with a cal­ibration problem will appear. For example:
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 23 of 36
4button and the commissioning function will start. When completed, the system will
Page 24
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Loop: 1 Device: 23 :Calibration issue Turn ON output channels 1&3
Day (Occupied) mode begins:- 06:00
Day (Occupied) mode begins:- 06:00
Night (Un-Occupied) mode begins:- 18:00
Loop: 1 Device: 23 :Duplicate Address
Loop: 1 Device: 23 :Duplicate Address Turn ON output channels 1&3
If there are multiple addresses with calibration issues, press the affected address.
5 button to scroll to the next
Press the Accept Once activated, you will be given the option to switch off output channels 1 and 3 by pressing the Accept
4button again. Press the Escape3button as appropriate to return to the previous menus or to
select another device with calibration issues.
SHOW DUPLICATE ADDRESSES
his function helps you to locate devices with duplicate addresses by asserting their output channels 1&3.
T
n the case of detectors and manual call points, activating these channels will turn their LEDs on.
I
Caution:
guishant system, so this function must be used with care. Activating channels 1 and 3 on a sounder/beacon will have no effect.
When the SHOW DUPLICATE DEVICES prompt is accepted, details of the first double address will appear. For example:
If there are multiple duplicate addresses, press the
Press the Accept4button and output channels 1 and 3 of the duplicate address being viewed will be asserted. Once activated, you will be given the option to switch off output channels 1 and 3 by press­ing the Accept
Press the Escape3button as appropriate to return to the previous menus or to select another dupli­cate address to check.
Note that channels 1 & 3 on an I/O unit may be programmed to trigger say, a water extin-
4button and output channels 1 and 3 of the detector being viewed will be asserted.
5 button to scroll to the next affected address.
4button again.
SET DAY/NIGHT TIMES
This function allows the user to alter the time the panel enters day (building occupied) and night (building unoccupied) mode. WE RECOMMEND YOU DO NOT USE THIS FUNCTION UNLESS YOU ARE INTIMATELY FAMILIAR WITH THE OPERATION OF THE FIRE ALARM SYSTEM.
Changes that may take place when the panel is in day/night mode include detector sensitivities (how quick a detector reacts in the event of a fire), cause and effects (what happens in the event of a fire) and sounder volumes (if available). These changes can only be made by an authorised engineer using the panel’s sophisticated programming tools at access level 3. If in doubt, refer to page 20 where any day/night changes will be recorded, provided it has been completed by the system engineer.
When the SET/DAY NIGHT TIMES prompt appears, press the Accept dow (or similar) will appear:
Use the panel has a 24 hour clock so hours 0 to 23 are available).
When the correct hour is displayed, press the Accept Use the When the desired time is displayed, press the Accept A window similar to the one below will appear:
Use the scroll panel to enter night mode. When the desired time is displayed, press the Accept you will be returned to the commissioning functions submenu.
5and6 buttons to set the time in hours that you want the panel to enter day mode (the
4button to move to the minutes field.
5and6 buttons to set the time in minutes you want the panel to enter day mode.
4button to access the night mode entry field.
56and Accept4buttons to set the time in hours and minutes that you want the
4button and the following win-
4button again and
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 24 of 36
Page 25
FP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Auto DST Time Adjustment is: Enabled
Enter confirmation code:
Zone: 1: Shop Floor
Enabled
Sounder Group: All
Sounder Groups can be Disabled/Enabled ‘Globally’
Sounder Groups can be Disabled/Enabled ‘Individually’
X
ENABLE/DISABLE DST (DAYLIGHT SAVING TIME) ADJUSTMENT
This function (when enabled) allows you to programme the panel’s time so it automatically goes forward one hour on the last Sunday in March and goes back one hour on the first Sunday in October:
Press the
CONFIGURE SOUNDER DISABLEMENTS
This function configures the Sounder Groups (1 to 16) to be ‘Globally’ or ‘Individually’ disabled / enabled. When accepted, two windows are available:
Press the
MAKE A CLEAN START
This function allows you to clear the panel’s memory back to its factory default settings. When selected you will be asked to input the five digit clean start confirmation code:
The button sequence for this is
5and6buttons to scroll between enabled and disabled and Accept4to select the desired option.
5
and6buttons to scroll between Globally’ and ‘Individually’ and Accept4to select the desired option.
5(1), 4(2), 6(3),3(4), Silence Internal Sounder button.
Engineer functions
Selecting this menu option takes you to the engineer functions submenu where you can set or clear disablements, access the panel’s comprehensive test functions and display important system status information. All of the panel’s engineering submenu functions are described in detail below.
SET/CLEAR DISABLEMENTS
Selecting this menu option takes you to the disablements sub-menu which allows you to enable or disable zones, sounders, outputs, relays, individual devices and/or the panel’s fault relay. Any disablement(s) will be indicated at all access levels via the DISPLAY DISABLEMENTS menu and the General Disablement LED on the front of the panel. We strongly recommend all disablements are regularly reviewed and immediately enabled when no longer necessary as they can have a major effect on how the system works. The following options are available:
ENABLE/DISABLE ZONES
This function allows you to disable zones from reporting faults, fires, pre-alarms, etc., and is normally used to tem­porarily disable a zone of detectors/call points in areas such as loading bays that are prone to nuisance triggering from vehicle fumes. When selected, press the Accept
4button and a window similar to below will appear:
Select the zone to be disabled/enabled using the
5and6 buttons. Press the Accept4button and
the zone’s status (Enabled or Disabled) will flash.
Next, use the enabled and disabled and press the Accept now move to the next available zone allowing further enablements or disablements to be made. Alternatively, to return to the previous menu press the Escape
Please note: if all the input devices on a zone have been individually disabled using the ENABLE/DISABLE DEVICES function described on page 26, the zone they belong to will also be disabled. If you try to re-enable a zone which has no enabled devices on it, a prompt appears saying this cannot be done. Instead you must first enable at least one device on the zone using the ENABLE/DISABLE DEVICES function before re-enabling the zone itself.
4button to select the desired option. The window will
5and6 buttons to toggle between
3button.
ENABLE/DISABLE SOUNDERS
This function allows you to disable one or more sounder groups from sounding in a fire condition. When selected, press the Accept
status (Enabled or Disabled) will flash. Next, use the and disabled and press the Accept to the next sounder group allowing further enablements or disablements to be made. Alternatively, to return to the previous menu press the Escape
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 25 of 36
4button and a window similar to the one below will appear:
Select the sounder group (1 to 16 or ALL) to be dis­abled/enabled using the the desired sounder group has been selected, press the Accept
4button once and the sounder group’s
5and6 buttons. When
5and6 buttons to toggle between enabled
4button to select the desired option. The window will now move
3button.
Page 26
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Panel Relay:- 1
Shop Floor:- 1: Gent WC Loop 1, Device 3: Enabled
Select Zones:- 1: Shop Floor
Output Set: All
ENABLE/DISABLE OUTPUTS
This function allows you to disable one or more output sets from sounding in a fire condition. It is typically used to disable, for example, auto-diallers from activating during routine maintenance. When selected, press the Accept
4button and a window similar to the one below will appear:
Select the output set (1 to 16 or ALL) to be disabled/enabled using the
When the desired output set has been selected, press the Accept tus (Enabled or Disabled) will flash. Next, use the disabled and press the Accept the next output set allowing further enablements or disablements to be made. Alternatively, to return to the previous menu press the Escape
ENABLE/DISABLE RELAYS
This function allows the disablement of one or more of the panel’s 3 auxiliary relays from activating as pro­grammed. When selected, press the Accept
Select the relay (1, 2 or 3) to be disabled/enabled using the
When the desired relay has been selected, press the Accept or Disabled) will flash. Next, use the press the Accept allowing further enablements or disablements to be made. Alternatively, to return to the previous menu press the Escape
ENABLE/DISABLE DEVICES
4button to select the desired option. The window will now move to the next relay
3button.
4button to select the desired option. The window will now move to
4button and a window similar to the one below will appear:
5and6 buttons to toggle between enabled and disabled and
5and6 buttons to toggle between enabled and
3button.
5and 6 buttons.
4button and the relay’s status (Enabled
5and6 buttons.
4button and the output set’s sta-
This function allows loop devices to be disabled from reporting faults, fires, pre-alarms, etc., and is normally used to temporarily disable detectors/call points that are nuisance tripping. When selected, press the Accept
Use the When selected, press the Accept that zone will appear, for example:
Use the press the Accept
5and6 buttons to select the zone where the device you wish to disable/enable is located.
5and6 buttons to scroll through the available devices. When the desired device appears,
4button and a window similar to the one below will appear:
4button and a list of all devices that can be disabled or enabled in
4button and the device’s status (Enabled or Disabled) will flash. Next, use the
5and6 buttons to toggle between enabled and disabled and press the Accept4button to select
the desired option. The window will now move to the next device allowing further enablements or disablements to be made. Alternatively, to return to the previous menu press the Escape
Please note: if all the input devices on a zone are individually disabled, the zone they belong to will also be disabled. If you try to re-enable a zone which has no enabled devices on it using the ENABLE/DISABLE ZONES function described on page 25, a prompt appears saying this cannot be done. Instead you must first enable at least one device on the zone before re-enabling the zone itself.
3button.
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 26 of 36
Page 27
FP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
L:-1 D:7 AV:63 ZP:62 FP: 192 ATL: 148 F: 0 C: 0 T: 0x88
The loop the point being
monitored is located on
The point's
address
The point's
current analogue value
The point's normal
analogue value
The maximum value
the point will return when
in a fire condition
The point's alarm
threshold level
(the level at which it will
flag an alarm condition)
The code
for any fault
condition that
point may be in
The points
current stage
of calibration
The
point's type
Loop:1 Device:-1
F
ault relay is:-
E
nabled
Delays to Outputs are:­Enabled
Loop:-1 Device 1 Output bits: 0
X
ENABLE/DISABLE FAULT RELAY
This function can be used to suppress the panel’s fault relay from activating in a fault condition. When selected, press the Accept
4button and the following window will appear:
Use the select the desired option. Alternatively, to return to the previous menu press the Escape
5and6 buttons to toggle between enabled and disabled and press the Accept4button to
3button.
ENABLE/DISABLE OUTPUT DELAYS
This function can be used to globally disable or enable any delays to outputs that have been programmed into the panel. When selected, press the Accept
Use the
5and6 buttons to toggle between enabled and disabled and press the Accept4button to
select the desired option. Alternatively, to return to the previous menu press the Escape
4button and the following window will appear:
3button.
MONITOR A POINT
This function allows you to view the current analogue status of any point (any addressable device on the system). When selected, you will be prompted to enter the loop on which the device you want to monitor is located and the device’s address :
Use the
5,6 and Accept4 buttons to select the desired loop and address. The panel will tem-
porarily disable the point in question and return back its analogue values, for example:
To return to the Engineer Functions submenu press the Escape
TEST DEVICE OUTPUTS
This function allows you to assert the output(s) of any addressable device to check it is working cor­rectly. It can be used, for example, to assert a detector’s internal or remote LED (if connected) or to check that an I/O unit is functioning correctly. Addressable devices typically have three output chan­nels (1, 2 and 3), the functions of which depend upon its type - please refer to the device manufac­turers technical data for further information. When selected, you will be prompted to enter the loop on which the device you want to test is located, the device’s address and the relevant output bit code (0 to 7, as explained on the table overleaf):
Use the with reference to the table below.
3button.
5,6 and Accept4 buttons to select the desired loop, address (device) and output bit code
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 27 of 36
Page 28
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Output set:-1
Output set:-1 is Normal Change the state using the Accept button
Sounder group:-1
Output:-1 is Silenced Change the state using the Accept button
UTPUT BIT CODES AND WHICH OUTPUT CHANNELS THEY ASSERT
O
CODE
0
1 Output channel 1 asserted
2 Output channel 2 asserted
3 Output channels 1 and 2 asserted
4 Output channel 3 asserted
5 Output channels 3 and 1 asserted
6 Output channels 2 and 3 asserted
7 All output channels asserted
When you have accepted the required output bit option, the panel will confirm your selection and the device’s output channels will be asserted as programmed. If desired, you can now select alterna­tive sequences using the press the Accept
4 button to make these changes).
5and 6 buttons (note that as the device is now ‘live’ you will not have to
OUTPUT CHANNELS ASSERTED
No output channel asserted
When testing is complete, press the Escape The device will no longer be ‘live’ and its output bits will return to their normal settings.
TEST OUTPUT SETS
This function allows you to test one or all of the system’s output sets (1 to 16) by altering its/their state from Normal to Triggered. When the TEST OUTPUT SETS? prompt appears, press the Accept
Use the Accept
Press the Accept to normal press the Accept
4button and the output set selection window will appear:
5and6 buttons to select the output set you would like to test (all or 1 to 16). Press the
4button and the following window will appear:
4button and the output set you have selected will activate. To change the state back
4button again. Should you wish to test additional output sets, use the
3button to return to the Engineer Functions submenu.
5and6 buttons to change the output set’s number accordingly. To return to the main Engineer
Functions submenu, press the Escape
TEST SOUNDER GROUPS
This function allows you to test one or all of the system’s sounder groups (1 to 16) by altering its/their state between Silenced, Intermittent and Continuous. When the TEST SOUNDER GROUP? prompt appears, press the Accept4button and the sounder group selection window will appear:
3button.
Use the the Accept
Press the Accept Intermittent and Continuous. Should you wish to test additional sounder groups, use the buttons to change the sounder group’s number accordingly. To return to the main Commissioning Functions submenu, press the Escape
5and6 buttons to select the sounder group you would like to test (all or 1 to 16). Press
4button and the following window will appear:
4button to change the state of the selected sounder group between Silenced,
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 28 of 36
5and6
3button.
Page 29
FP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Zone:-1
Zone:-1 Normal operation
Panel relay:-1
Panel relay:-1 is Normal Change the state using the Accept button
END
A
END
B
7
11
12
10
9
6
4
5
8
3
2
1
I
I
13
14
15
16
17
18
19
20
I
21
22
23
Open OR Short Circuit fault here
I
1
Isolator
Loop Devices23to
I
X
TEST PANEL RELAYS
This function allows you to test the panel’s three volt-free relays. When the TEST PANEL RELAYS prompt appears, press the Accept
4button and the panel relay selection window will appear:
Use the Accept
Press the Accept back again press the Accept
5and6 buttons to select the output set you would like to test (all or 1 to 16). Press the
4button and the following window will appear.
4button and the panel relay you have selected will trigger. To change the state
4button again. Should you wish to test additional panel relays, use the
5and6 buttons to change the panel relay’s number accordingly. To return to the main Engineer
Functions submenu, press the Escape
WALK TEST
This function allows you to put one or more of the system’s detection zones into walk test mode. When a zone is in walk test mode, any detector/manual call point triggered on that zone will turn on all of the sounders that are mapped to that zone for a brief period (note that output sets will not operate). When the WALK TEST prompt appears, press the Accept
Use the 5and6 buttons to select the zone you wish to put into walk test mode. Press the Accept
Use the the Accept
4 button and the following window will appear:
5and6 buttons to change the zone’s state from Normal Operation to Walk Test Mode and press
4button. You will now be returned to the Engineering Functions submenu and you can pro-
ceed to test the zone as appropriate (note that you must be in access level 1 if you wish to view the device(s) being tested). Should you wish to put additional zones into test at the same time, you can do so by repeat­ing the above process. To take zones out of test, reverse the procedure. Any zones in test will be indicated at all access levels via the DISPLAY ZONES IN TEST menu and the ‘test’ LED on the front of the panel.
3button.
4button and the zone selection window will appear:
BLINK DETECTOR LEDS
This function allows you to momentarily assert the LED outputs of loop devices such as detectors and manual call points in one continual sweep. This is a particularly useful function for helping to locate any open or short circuit faults on the loop wiring.
LEDs are asserted on all learnt loop devices on a step-by-step basis (each step takes approximately one second. Therefore, on a system with, say, 80 loop devices, each device will blink once every 80 seconds). You can select the test to be carried out from either end of the loop or from both ends at the same time. An example illustration of how this test may be carried out is shown below:
For a fault between points 17 and 18 on the example loop (left):
OPEN CIRCUIT FAULT: If Direction A (End A) is selected, all devices 1-17 will periodically illuminate with devices 18-23 not illuminated. If Direction B (End B) is selected, all devices 18-23 will periodically illuminate with devices 1-17 not illuminated. This would therefore identify an open circuit fault between devices 17 & 18.
SHORT CIRCUIT FAULT: If Direction A (End A) is selected, then all devices 1-14 will periodically illuminate. The short circuit isolator between devices 14 & 15 will have been activated and
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 29 of 36
all other devices 15-23 will not be lit. If Direction B (End B) is selected, then devices 21-23 will periodically illuminate. The short circuit isolator between devices 20 and 21 will have been activated and all other devices 1-20 will not be lit. This would therefore identify a short circuit fault somewhere between the two isolators containing devices 15-20.
Page 30
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
L:-1 D:7 AV:63 ZP:62 FP: 192 ATL: 148 F: 0 C: 0 T: 0x88
The loop the point being
monitored is located on
The point's
address
The point's
current analogue value
The point's normal
analogue value
The maximum value
the point will return when
in a fire condition
The point's alarm
threshold level
(the level at which it will
flag an alarm condition)
The code
for any fault
condition that
point may be in
The points
current stage
of calibration
The
point's type
Loop:-1 Device 1 Output bits: 0
Which loop:-1
Which loop:-1 End A Only
When the BLINK DETECTOR LEDs? prompt appears, the following window will appear:
Select the loop you wish to carry out the test on using the
5and6 buttons and press the Accept4
button. You will then be prompted to select from which end of the loop you wish to run the test:
Use the
5and6 buttons to select End A, End B or Both Ends as appropriate and press the Accept4button.
The LEDs of all detectors on the loop will now start blinking accordingly. Note that addresses do not have to be in sequential order for this facility to work. To end the test press the Escape
3button at
any time.
INTENSIVE DEVICE MONITOR
This function allows you to monitor a specific addressable point to see how it responds to intensive, repeated polls from the panel. In order to do this, the panel suspends all other system activity when this test is taking place - fires, etc, will not be flagged so please use this function with care. By reporting back how many good and bad polls are made between the panel and the monitored device, this function can help pinpoint loop wiring/communication faults and/or faulty devices. When selected, you will be prompted to enter the loop on which the device you want to monitor is located, the device’s address and its output bit sequence:
Use the
5,6 and Accept4 buttons to select the desired loop, address (device) and output bit sequence.
The output bit option allows you to monitor a device whilst it is in a particular state, for example, if an I/O unit is reporting back faults only when it has triggered, say, a rollershutter door (e.g when its output channel 1 is asserted), you can set the device up so it is in this state whilst being monitored. See the table below for the output bit options available:
OUTPUT BIT CODES AND WHICH OUTPUT CHANNELS THEY ASSERT
CODE OUTPUT CHANNELS ASSERTED
0 No output channel asserted 1
2 Output channel 2 asserted
3 Output channels 1 and 2 asserted
4 Output channel 3 asserted
5 Output channels 3 and 1 asserted
6 Output channels 2 and 3 asserted
7 All output channels asserted
Output channel 1 asserted
Caution: Note that any channel on an I/O unit may be programmed to trigger say, a water extinguis­hant system, so this function must be used with care. When you have accepted the device’s output bits sequence by pressing the Accept
4 button, the test will begin and the panel will display the
device’s current analogue values, for example:
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 30 of 36
Page 31
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Loop:-1
Number of polls for each device:25
Loop:1 Device 1:Results Good Polls:128 Bad Polls:3
Loop:1 Device 1: Results Good polls:25 Bad Polls:0
G
ood polls: 592, Bad polls: 3
Loop:1 Device: 1 Turn ON output channels 1&3
As the device is intensively polled, some of its analogue values may change, helping to assist you in the fault finding process. To view a running total of the number of good and bad polls between the panel and the device at any time, press the More Information button and a window similar to the one below will appear:
To return to the analogue value window press the More Information button again. To exit the INTENSIVE DEVICE MONITOR function press the Escape
LOOP TEST
This function helps pinpoint loop wiring/communication faults by continually polling all loop addresses for a specified number of times and reporting back how many good and bad polls there have been on an address by address basis. In order to do this, the panel suspends all other system activity when this test is taking place - fires, etc, will not be flagged so please use this function with care. When selected, you will be prompted to enter the loop you wish to monitor and how many times you want the panel to poll each device (1 to 255).
3button.
Use the required. The test will begin and a test status window will appear, showing the address currently being polled together with a running total of the number of good and bad polls. Polling takes place on an address by address basis in numerical order and will take several minutes.
When the test is complete, the results will appear in a new window, similar to the one below.
Pressing the Escape
A number of bad polls in a particular section of the system indicates a problem area for investigation, e.g. voltage drop, bad connection, etc.
To assert output channels 1 and 3 of the device being viewed, press the More Information button. You will be presented with a window similar to the one below:
In the case of detectors and manual call points, activating channels 1 and 3 will turn their LEDs on.
Caution:
guishant system, so this function must be used with care.
Activating channels 1 and 3 on a sounder/beacon will have no effect.
If you are happy to proceed, press the Accept device. Once activated, you will be given the option to switch off output channels 1 and 3 by press­ing the Accept
Press the Escape
5,6 and Accept4 keys to select the desired loop followed by the number of polls
3button will abort the test at the address currently being polled.
note that channels 1 and 3 on an I/O unit may be programmed to trigger say, a water extin-
4button to assert the output channels of the selected
4button again.
3button as appropriate to return to the previous menus.
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 31 of 36
Page 32
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Loop:-1 Device:22
Loop:-1 Device:22/0: Optical det 0x88 Shop Floor Gents Toilet
XFP 8A22 28/06/2005 2 loops fitted Hochiki protocol
The version of the
panel's firmware
The number of
loops fitted
The date the panel's
firmware was released
T
The protocol of the
panel's loops
Site data = 49191/49191 11/3/2005 Program checksum = 16886/16886
The number of
loops fitted
The identification number
of the site data
T
Program checksum
code
The date the site was last changed
Loop:-1
ISPLAY DATABASE
D
This function allows you to view the panel’s database of loop devices. Available on a loop by loop basis,
he information displayed includes the device’s type, address and description (zone and device text).
t
When the DISPLAY DATABASE? prompt is accepted, you will be prompted to enter the loop you wish to view the database of:
Use the 5and6 buttons to select the desired loop and press the Accept4 button. You will then be prompted to enter the address of a particular device.
Use the
5and6 buttons to select the desired address number and press the Accept4 button. The
information that is stored on the database that relates to that address will now appear, for example:
You can now use the loop as required. To exit the database, press the Escape
5and6 buttons to scroll through the rest of the database for the selected
3 button at any time.
VERSION NUMBERS
This function allows you to view the current version number of the panel’s firmware and to ascertain when the site’s data was last changed. When accepted, the following two windows (with details specific to the panel) will appear in quick succession.
Matching site data codes, i.e. 49191/49191 and program checksum codes, i.e. 16886/16886, show that the panel is functioning correctly. Mis-matched numbers, i.e. 49191/40286, indicate that the panel’s memory may be corrupt. After five seconds the panel will return to the Engineering Functions submenu.
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 32 of 36
Page 33
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Earth fault monitoring is:­Enabled
Loop 1 current = 3mA Loop 2 current = 7mA
B
a
t
t
=
2
4
6
5
1
m
V
E
a
r
t
h
f
a
u
l
t
=
O
K
Ma
i
n
s
=
O
K
B
a
t
t
=
O
K
C
h
a
r
g
e
=
O
K
B
a
t
t
R
=
O
K
Ma
i
n
s
=
O
K
B
a
t
t
=
O
K
C
h
a
r
g
e
=
O
K
Loop : ‘1’
Loop : 1 Device : ‘nn’
XX XX XX XX XX XX XX XX XX XX XX XX XX XX XX XX
LOCATION NUMBERS
0 1 2 3 4 5 6 7
8 9 10 11 12 13 14 15
F F F F F T F F F F F T T F F F
SHOW PSU STATS
This function allows you to view important information regarding the state of the panel’s PSU and its standby battery supply. When accepted, the following two windows (similar to the following) will appear in quick succession:
To return to the Engineering Functions submenu, press the Escape
ENABLE/DISABLE EARTH FAULT
This function allows the panel’s earth fault monitoring circuitry to be temporarily disabled. When accepted the following window will appear:
Use the select the desired option. The panel’s flash database will update and you will be returned to the Engineering Functions submenu.
SHOW LOOP CURRENT
This function allows you to view the level of current being drawn by the addressable loop(s) at any given time to help verify the design of a system. When accepted, a window similar to the following will appear:
The actual current drawn will depend upon the size of the loop and the number of items connected. Press the Escape
5and6 buttons to toggle between enabled and disabled and press Accept4button to
3 button to return to the Engineering Functions submenu.
3 button.
SHOW DISCOVERY EEPROM
This function allows the panel to interrogate and view information held by Apollo Discovery devices. When accepted, enter the loop and address of the Apollo Discovery device, example shown below:
When accepted, a list of 16 ‘Extended Command Field Data’ is shown on the display:
For an explanation of the numbers displayed, refer to the relevant Apollo device documentation.
SHOW NETWORKED EVENTS
This function allows the status of a network event to be displayed, which is useful for fault diagnosis purposes. When accepted, a window similar to the following will appear:
T = Event True; F = Event False
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 33 of 36
Page 34
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
MAINTENANCE
Periodic system maintenance should be carried out on the system as prescribed in the local design, maintenance and installation regulations.
The Fire Alarm panel’s standby batteries should be checked for integrity of the connections, deposits indicating venting, and a periodic load test with the Mains supply disabled to ensure adequate battery capacity. Both batteries should be renewed if there is any doubt about their integrity.
The memory log should be checked for any faults that have automatically cleared, and these dealt with accordingly.
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 34 of 36
Page 35
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
STANDBY BATTERY CALCULATION GUIDE
The standby time of the fire alarm panel after the Mains has failed depends on the quiescent loading of the panel, the alarm load of the panel, and the capacity of the batteries.
To determine the capacity of batteries required for any given stand-by period, the following formula should be used:
Battery Capacity in Ah = 1.25 x [(T x (A + L x 1.5) + H x (P + Z x 1.5)]
The multiplier 1.25 is present to account for lost capacity over the life of the batteries.
H = Number of hours standby required
P = The quiescent current of the panel = 0.065A
This value is with the Mains failed, beeper silenced and the Supply Present and General Fault indicators lit. If there are other quiescent drains on the panel then these must be added in.
Z = The total quiescent current of all loop devices
As a guideline, the average quiescent current addressable devices is typically 0.0003A (300µA). To obtain accurate values consult the device manufacturers’ own specifications.
A = The total alarm current of panel sounders and activated relays [a panel relay consumes 20mA (0.02A) when activated].
L = The total alarm current of loop devices (sounders, beacons etc.)
T = The amount of time in hours required for the alarm (most commonly being half an hour).
Example:
The panel has 150 loop devices each consuming 300µA (0.0003A) each. In alarm, there will 40 loop powered sounders at 8mA (0.008A) each, and 2 panel relays activated, and a conventional sounder load of 0.25A. The required standby time is 24 hours, and the required alarm time is 0.5 hours.
----------------------------------------------------------------------------------------------------------------------------------------
Calculate the alarm capacity: = T x (A + L x 1.5)
T = 0.5 Hrs; A = 0.25 + 2 x 0.02 = 0.29A; L = 40 x 0.008A
So the alarm capacity is: = 0.5 x (0.29 + 40 x 0.008 x 1.5)
= 0 .385Ah
----------------------------------------------------------------------------------------------------------------------------------------
Calculate the quiescent capacity: = H x (P + Z x 1.5)
H = 24 Hrs; P = 0.065A; Z = 150 x 0.0003A
So the standby capacity is: = 24 x (0.065 + 150 x 0.0003 x 1.5)
= 3.18Ah
---------------------------------------------------------------------------------------------------------------------------------------­Total Capacity: = 1.25 x (0.385 + 3.18)
= 4.46Ah
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 35 of 36
Page 36
XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
TECHNICAL SPECIFICATION
POWER SUPPLY SPECIFICATION
ains supply 230V a.c 50/60Hz. Max. current 680mA
M Internal Power Supply 27 V d.c Nominal (Ripple voltage 250mV)
otal output current limited to 3A @ 230 V a.c.
T Power rating Imax. a = 250mA (1 loop), 270mA (2 loop); Imin = 70 mA
aximum internal battery resistance Ri max. = 1.1
M Supply and battery charger monitored for failure Yes
atteries monitored for disconnection and failure Yes
B Batteries protected against deep discharge Yes
ax. battery size and type 7.0Ah VRLA. Use 2 x YUASA NP7-12 for LPCB approved systems
M Quiescent current drain (1 loop unloaded) < 80mA
uiescent current drain (2 loop unloaded) < 100mA
Q Earth fault monitoring Yes (any conductor)
emperature compensated charging Yes
T
LOOP DRIVER SPECIFICATION
Number of loop drivers 1 or 2 (dependent on model purchased) Line monitored for open and short circuit faults Yes On-board loop isolators with LED indication when active Yes
uto-polling from each loop end Yes
A Max. output current per loop 500mA (Voltage: 25 V minimum; 34 V maximum) Max. number of addressable devices 126 per loop (giving a total of 126 for a 1 loop panel, 252 for a 2 loop panel) Max. number of loop powered sounders per loop @ 10mA 40
umber of programmable sounder groups 16
N Number of programmable output sets 16
CONVENTIONAL SOUNDER CIRCUIT SPECIFICATION
Number of programmable circuits 2
nd of line resistor value 6800 ohm 5% Tol. 0.25 W
E
ine monitored for open and short circuit faults Yes
L
utputs fused at 400mA. Protected by resettable overload circuit
O
utput voltage 19.5 V minimum; 28 V maximum
O
ax. number of sounders @ 20mA 80
M
AUXILIARY OUTPUTS
Type Relay voltage free single pole changeover
ax. switching current 1A
M Max. switching voltage 30 V d.c. Relay 1 / Relay 2 / Relay 3 Programmed from cause and effect Fault Active when no faults are present ‘24V’ Aux. power output 19.5 V minimum, 28 V maximum. Max current 100mA. Protected by resettable overload circuit
AUXILIARY INPUTS
Input 1 Connect to 0V to trigger, Max. input voltage 27V d.c (non-latching). Programmed from cause & effect Input 2 Connect to 0V to trigger, Max. input voltage 27V d.c (non-latching). Programmed from cause & effect
FUSES (to IEC - EN60127 Pt2)
Mains fuse 1A HRC Ceramic 20mm Battery fuse 3.15A F 20mm. This limits the current drawn from the battery
PANEL INDICATORS AND CONTROLS
Control buttons Menu, More Information, Silence Internal Sounder, Control Panel Reset, Investigate, Resound Event scrolling and menu access buttons Up5(1), Down6(3), Accept4(2), Escape3(4) Liquid crystal display Two lines x 40 characters, backlit Number of zonal LED indicators 32 Other LED indicators (General) Fire, Supply Present, Test, Accessed, General Disablement, Phased Evacuation, General
Fault, Power Supply Fault, System Fault, Sounder Status, Delays Running
PHYSICAL DIMENSIONS
Approx. dimensions of back box (W x H x D) 410 x 250 x 80mm (metal) Approx. dimensions of lid (W x H x D) 439 x 274 x 7mm (metal) Approx. weight (without batteries) 4.5kg
CABLING REQUIREMENTS
Type of cable Fire resistant screened cable, minimum size 1mm Max. cable length per loop 1 KM Connector blocks Plug-on type, largest acceptable conductor size, 1.5mm Max. allowable loop impedance (each conductor) 20 Ohm Max. cable capacitance .27µF
NETWORK SPECIFICATION
Connection Via AFP711 network driver fitted at main panel Max. no of main panels per network 8 Max. no of repeaters per non-networked master panel 8 Max. cable length per network 1 KM (main panel network); 500m (repeater network)
PC/PRINTER INTERFACE
PC connection Via main panel RS232 molex connector (lead supplied in XFP507 upload/download software kit) Printer connection Via main panel RS232 connector block
OPERATING CONDITIONS
The components are selected to operate within their specification when the environmental conditions outside the enclosure comply with class 3k5 of IEC 721-3-3 : 1978. Temperature range: -5 to +40
o
C. Maximum relative humidity: 95%.
Ω
2
2
XFP ENGINEERING MANUAL • Approved Document No. DFU2200510 Rev 2 • Page 36 of 36
Loading...