CFP Standard 8 Zone Conventional Fire Alarm Panel
Part No. CFP708-4
Overview
LPCB certified to EN54-2/4, C-TEC's CFP 8zone conventional fire alarm panel offers an array of user and installer-friendly features at a very competitive
price.
Supplied in an attractive flush or surface mountable plastic enclosure, it includes eightdetector zones, four conventional sounder circuits, class change
and alert inputs, on-board fire and fault relays and combined keypad/keyswitch entry.
A wide range of engineering functions are also provided including selectable zone delays, coincidence and non-latching zone facilities. Comprehensive
test and fault finding facilities are also provided.
Optional repeaters, relay expansion boards and EN54-13 system compliance devices are also available.
More Information
Third-party certified to EN54 parts 2 and 4 by the Loss Prevention Certification Board (LPCB) with optional EN54 part 13 compliance from the BSI.
Intuitive user-friendly interface with colour-coded buttons and combined keypad/keyswitch entry.
Manufactured by C-TEC in the UK.
Eightdetector zone circuits.
Four conventional sounder circuits.
Integral 1.5A EN54-4/A2 compliant switch mode PSU.
Wide range of engineering functions including zone test, coincidence, zone delay and non-latching zones.
Two on-board relays (Fire and Fault).
Two open-collector outputs (Remote and Reset).
'Class change' and alert inputs.
Installer-friendly design.
Attractive flush or surface mountable plastic lid and enclosure - no bezel required.
Low 25mA quiescent current.
Multiple indicators.

TF01942 322744
01942 829867EW
sales@c-tec.co.uk
www.c-tec.com
Quality System Certificate No: 176
Assessed to ISO9001 : 2008
MANAGEMENT
SYSTEMS
M
A
N
U
F
A
C
T
U
R
E
R
A PROUD BRITISH
C-TEC, Challenge Way, Martland Park, Wigan, WN5 0LD United Kingdom
System expansion connections provided for up to eight two-wire repeaters (one CFP761 network card required per system), optional CFP relay boards
and optional EN54-13 compliant sounder circuit boards.
Space for two x 12V 3.3Ah VRLA batteries.
Fully compatible with C-TEC's ActiV range of conventional fire detectors.
Technical Specifications
Approvals/certifications
Mains supply
Mains rated current
Internal power supply
Total output current limited to
Quiescent current
Alarm voltage
Max battery size and type
No. of detector zone circuits
Call point resistor value
Max. devices per detector zone
No. of conventional sounder circuits
EOL resistor value
Max. sounder output current
Auxiliary relays
Open collector outputs
Other outputs
Auxiliary inputs
Engineer (AL3) functions
Expansion connections
Product dimensions (mm)
Construction & finish
IP Rating
Weight
Operating conditions/temperature
Certified to EN54-2/4 by the LPCB (176b) / (0832-CPD-1704).
230V 50/60Hz.
350mA maximum.
19V-28.5V (27V nominal). Ripple 7V maximum (battery fault).
1.5A @ 230Vac (ImaxA eq 146mA).
25mA (mains failed, internal sounder active, PSU & gen fault LED lit)
27V max, 20V min (final battery voltage).
2 x 12V 3.2Ah VRLA connected in series. Min. battery size 1.2Ah.
8 (Max. length per circuit is 500m).
470 to 680?.
25 detectors (or 32 detectors/manual call points combined).
4 (Max. length per circuit is 500m).
6800? 5% Tol. 0/25W (blue, grey, red, gold).
4 x 200mA (800mA total).
Two: (1) Aux. Fire; (2) Fault. Volt free single pole changeover. Max. switch current 1A; Max. switch
voltage 30Vdc.
Two: (1) Reset (Active during reset cycle); (2) Remote (Active during any unsilenced fire condition
provided all relevant delays have expired). Max. sink current 30mA, Max. open circuit voltage 27Vdc).
24V Aux. Power (Protected by a resettable fuse. 100mA min. hold current. Resets when fault
removed).
Two: (1) ‘Class Change’ (constant sounders); (2) Alert (pulsed sounders). Connect to 0V to trigger,
Max. input voltage 27V (non-latching).
Program coincidence (double knock); Invoke One Man Walk Test; Program delays; Set up zones
for non-latching operation; Program sounders to resound (or not resound) when a new zone enters
alarm; Enter fault diagnostic facilities.
Yes - for optional network driver cards (one required per repeater system), relay output cards and
EN54-13 sounder circuit interface boards.
380 W x 235 H x D 96mm.
Plastic lid and base; RAL7035 textured.
IP30.
1.75kg (without batteries).
-5°C to +40°C. Max relative humidity: 95%.