C-TEC CFP702-4, CFP704-4, CFP708E-4, CFP708-4 Installation Instructions

Application Note 0007.0
Exit Access Mode
button (2)
Next Option
button (3)
Enable/Disable
button (4)
How to enabl e/disable functions on a CFP Fire Panel
Make reference to Fig. 1 for the following steps.
1. Enter access level 2 by turning the keyswitch to “I” position, or enter code ‘2143’ using the panel buttons.
2. Press and hold the Next Option button (3) until Zone 1 Fault and General Disablement LEDs start flashing. If Zone Fault and General Disablement LEDs flash at different rates, the option is enabled. If Zone Fault and General Disablement LEDs flash at the same rate, the option is disabled.
3. Press the Enable/Disable button (4) to toggle the selected option between enabled and disabled.
4. To confirm your selection, press the Next Option button (3).
5. Continue to press the Next Option button (3) to select the Zone or Output to enable or disable and repeat steps 3 & 4 until the selection process is complete.
6. To exit the selection process, press the Exit Access Mode button (2), or turn the keyswitch to “O” position.
Approved Document No. DFU0000704 Rev 1 Page 1 of 2
Fig. 1
Application Note 0007.0
The example below (Fig. 2), shows Zone 1, Zone 2 and the alarm sounders disabled.
Fig. 2
Page 2 of 2 Approved Document No. DFU0000704 Rev 1
Loading...