Installation Instructions
THIS EQUIPMENT MUST ONLY BE INSTALLED AND MAINTAINED BY A SUITABLY SKILLED AND TECHNICALLY COMPETENT PERSON. THE PSU
BF362-5 is a boxed Mains to regulated DC power supply providing 5 A @ 24 Vdc. Combining the functions of a power
upply unit, battery charging unit and battery monitoring unit, it is fully compliant with the current edition of
s EN 54-4:1997 + A1:2003 + A2:2007.
INSTALLATION
Location
The power supply must be sited indoors on a dry, flat surface in an area that is well ventilated. Ideally the panel
ndicators should be at eye level and the ambient light level should allow the status of the indicators to be clearly seen.
i
Mounting
Using the five mounting holes provided, mount the metal base securely onto a wall. Assess the condition and construction of the wall and use suitable screw fixings. The mounting holes are suitable for use with No.8-10 or 4-5 mm countersunk screws. Any dust or swarf created during the mounting process must be kept out of the enclosure and care must be taken not to damage any wiring or components.
Wiring and Cable Entry
All wiring should be installed in accordance with the current edition of the IEE Wiring Regs (BS 7671), or the relevant national standards. The requirement for the Mains supply to the panel is fixed wiring, using 3-core cable (no less than 1 mm or a suitable three conductor system fed from an isolating switched spur fused at 3 A.
In order to maintain cable segregation the incoming Mains cable should be fed into the panel via the top centre knockouts (provided on the metal base). Knockouts should be removed with a sharp, light tap using a flat 6 mm broadsided screwdriver, as shown in the diagram (see right). Always ensure that if a knockout is removed, the hole is filled with a good quality 20 mm cable gland. Any unused knockouts must be securely blanked off.
WARNING: DO NOT ATTEMPT TO CONNECT THE MAINS SUPPLY TO THE POWER SUPPLY PCB UNLESS ALL COMPONENTS ARE SECURELY INSTALLED IN THE ENCLOSURE.
Terminate the Mains cable at the Power Supply connector block CONN1 (see Figure 1 below).
S ARE CLASS 1 EQUIPMENT AND MUST BE EARTHED.
2
and no greater than 2.5 mm2),
Figure 1 - Power Supply PCB Layout and Connection Details
Incoming Mains Cable
Must be segregated from other cables and only enter the panel through the top central knockouts.
Hazardous Voltages Present LED
When lit red, hazardous voltages are present on the components and copper in the hashed area of the PCB. DO NOT TOUCH!
Battery Monitoring Link (PLK1)
If batteries NOT used, fit PLK1 link.
Battery Charge Current Link (PLK2)
Supply Output (CONN5)
Battery Input (CONN5)
FIRE ALARM
ancillaries
Approved Document No. DFU0003611 Rev 5
See Technical Specification overleaf for further details
Mains Input Terminals (CONN1)
L = Live, N = Neutral, = Earth
CLASS 1 EQUIPMENT MUST BE EARTHED.
Connect incoming Mains earth wire to the earth terminal and NOT to the base earth post.
PSU Earth Strap
DO NOT operate this equipment without connecting this strap to the base earth post.
Display Connector (PL1)
High Temp. Output (PL2)
Fault Relay (CONN3)
Charge Off Input (CONN4)
Batteries
+
12 V BATT ERY
+
12 V BATT ERY
P
O
W
E
R
S
U
P
P
L
Y
P
CB
3
x battery connection
l
eads (supplied with
accessories)
LOCATION OF 2 x 12 V BATTE RIES AND CONNECTION OF BATTERY LEADS TO POWER SUPPLY PCB
Black- Red+
Output
CONN5
0V
+V
Battery
CAUTION: There is a risk of explosion if incorrect batteries are used. Always dispose of used batteries in accordance with the battery manufacturers instructions.
For the emergency standby power supply, only use good quality sealed VRLA batteries. Position and connect 2 x 12 V batteries, as shown in diagram (see right).
Note: On a standard ‘as-supplied’ unit, PLK1 (‘Battery
onitoring’ link) is NOT fitted and a fault will occur on initial
M power-up if fully charged batteries are NOT connected.
TECHNICAL SPECIFICATION
OWER SUPPLY SPECIFICATION
P
Mains supply voltage / Rated current / VA: 230 Vac, 50/60 Hz / 1.35 A / 310 VA Max. continuous output current (including charging): 5 A
attery charge capacity: 7 Ah to 18 Ah
B
ax VRLA battery size/type determined by cabinet size: BF360 range = up to 3 Ah (Note: BF360-12 without STU plate = 7 Ah)
M
various models listed) BF361 range = 7 Ah
(
ower rating: I max a = 4.6 A or 4.0 A (if PLK2 link fitted)
P
aximum internal battery resistance: Ri max = 600 mohm
M Maximum output voltage: V max = 30 V Minimum output voltage at battery cut off: V min = 19.2 V
utput ripple voltage (peak-to-peak): 450 mV @ 30 MHz bandwidth, 350 mV with a 100 nF loading.
O Mains supply/battery charger monitored for failure: YES Batteries monitored for disconnection and failure: YES
FUSES
Mains supply fuse (F1): 2 A HRC, 20 mm ceramic Battery fuse (F2): 5 A F, 20 mm glass
POWER SUPPLY PCB CONNECTIONS
Mains Input (CONN1): Three Mains supply input terminals: Live, Neutral & Earth Fault Relay (CONN3): Isolated relay output rated 1 A @ 50 V Charge Off Input (CONN4): Disablement of the battery charge, enabling the charge current to be used at the output during heavy load
Supply Output (CONN5): 24 Vdc output for auxiliary equipment at PSU’s rated output of 5 A Battery Input (CONN5): Connection to the VRLA batteries PL1: 4-way connector for wiring loom from PCB to a display card, or OEM equipment, for transmission of C-TEC data protocol. PL2: High Temperature Output. Operates at approx. 55 PLK1: ‘Battery Monitoring’ link. Fit link if batteries NOT used. PLK2: ‘Battery Charge Current’ link.
INDICATORS
Panel indicators (LEDs): SUPPLY PRESENT (Green) – Indicates the supply is present at the output.
Power Supply PCB (LED): Hazardous Voltages Present (Red)
PHYSICAL ATTRIBUTES
Dimensions: 404 mm (width) x 404 mm (height) x 110 mm (depth) Weight / Construction: 5.25 Kg (without batteries) / Metal lid and base Enclosure finish: RAL7035 textured
ACCESSORY PACK
1 x Instructions – Document No. DFU0003611 (this document); 1 x Allen key (for unfastening/securing the panel’s lid); 1 x 2 A HRC, 20 mm ceramic fuse (spare Mains supply fuse F1); 1 x 5 A F, 20 mm glass fuse (spare battery fuse F2); 1 x set of links for PLK1 & PLK2; 1 x battery connection kit.
OPERATING CONDITIONS
The power supply enclosures have an IP30 rating (to EN60529:1992) and are designed for indoor use only. The components are selected to operate within their specification when the environmental conditions outside the enclosure comply with class 3k5 of the latest edition of IEC 721-3-3:1978. Temperature range: -5
CERTIFICATION
VdS Approval No.: G209197 CE Cert. No.: 0786-CPD-20892
E&OE. No responsibility can be accepted by the manufacturer or distributors of these power supplies for any misinterpretation of this instruction, or for the compliance of the system as a whole. The manufacturers policy is one of continuous improvement and we reserve the right to make changes to product specifications at our discretion and without prior notice.
o
C to +40 oC. Maximum relative humidity: 95%.
FIRE ALARM
ancillaries
Manufacturer: Computionics Limited (C-TEC), Stephens Way, Wigan, Lancashire WN3 6PH, England - C-TEC.co.uk Niederlassung Deutschland: C-TEC Germany Limited, Virchowstr. 32, D-33332 Gϋtersloh -C-TEC-Germany.de
periods, volt-free short to 0 V to disable charger. Maximum cable length = 2.5 m.
Fitted for 7 Ah to 18 Ah (1 A charge). Note: Special requests can be catered for, up to 60% of the total PSU output.
GENERAL FAULT (Amber) – Indicates a fault is present on the PSU. Call the engineer. AUXILIARY FAULT (Amber) – Indicates a fault with an auxiliary unit (user-definable). 19 to 30 V, 3.5 to 6 mA.
Approved Document No. DFU0003611 Rev 5
F362 range = up to 18 Ah
B
I max b = 5 A, charging turned off via CONN4 short
I min = 12 mA approx.
o
C internal box temperature, 30 V, 200 mA max. current sink.