DIGITAL THERMOSTAT
Owners Manual Model 43054
Congratulations!
Your new Climate Technology thermostat will provide years of reliable service. Using this digital thermostat will provide more uniform com­fort in your home through the seasons. Thank you for buying a Cli­mate Technology product!
Please read this manual for complete instructions on installing and operating your thermostat. If you require further assistance, call Cli­mate Technology Technical Support at 1-800-676-7861 from 8am to 5pm Central Time.
IMPORTANT INFORMATION
1. This thermostat is designed to work on the following sys­tems:
• Gas - Standing Pilot
• Gas - Electronic Ignition
• Gas - Fired Boilers
• Gas - Milivolt Systems
• Oil - Fired Boilers This thermostat will NOT control multistage heat pumps or 110/220 V
baseboard electric heating systems.
2. Temperature Range
This thermostat can be set between 45°F and 95°F (7°C and 35°C). However, it will display room temperatures from 30°F to 99°F (0°C and 37°C). “HI” will be displayed if the temperature is higher than 99°F (37°C), and “LO” will be displayed if the temperature is lower than 30°F (0°C).
This thermostat will automatically cutoff in Heat mode if the tempera­ture rises above 95°F (35°C), and automatically cutoff in Cool mode if the temperature drops below 45°F (7°C).
3. Compressor Protection
This thermostat provides a 3.5 minute delay after shutting off the com­pressor before it can be restarted. This feature will prevent damage to your compressor caused by rapid cycling. It does not prevent a rapid compressor restart due to short power outages.
4. Battery Warning
Two fresh AA alkaline batteries should provide well over one year of service. However, when the batteries become drained, the Low Bat­tery Indicator will flash on the display. When this message occurs, install new alkaline batteries. You have approximately 1 minute to change the batteries and keep the thermostat’s settings. Once the batteries have become too low to ensure proper operation, your sys­tem will be turned Off, and the display will be cleared except for flash­ing Low Battery Indicator on the LCD display.
CAUTION: When only the battery icon flashes on the display, the thermostat is shut down, and your system will no longer operate. In this condition, there is no temperature control of your dwelling.
NOTE: The INDIGLO® night-light will not function when the thermo­stat is in low battery condition.
NOTE: If you plan to be away from the premises over 30 days, we recommend that you replace the old batteries with new alkaline bat­teries prior to leaving.
FEATURES
Filter Change Indicator: Flashes when filter needs to be checked.
Reset: Press with a paper clip to reset the thermostat and return to power-up settings.
System Switch: Selector switch for Heat, Cool, and Off.
Fan Switch: Fan switch for Automatic or Continuous fan operation.
• Oil - Fired Furnace
• Single Stage Heat Pumps - with no auxiliary heat
• Electric Furnace
• Electric Air Conditioning
INDIGLO® night­light: Backlights display automatically with each key press for easy
LCD Display: Shows Room Temperature, Set Temperature, and other feature information as required.
Filter Key: Resets the filter change counter to zero.
viewing.
Low Battery Indicator: Flashes when batteries need to be replaced.
Up and Down Keys: Keys for changing the Temperature setting. Also used for adjusting the Span.
Battery Compartment: Front access allows easy insertion of two AA 1.5V batteries.
Front Doors: Covers keys and batteries when not used for neat appearance. Open with one finger from top or bottom.
INSTALLATION
What You Need
This thermostat includes two #8 slotted screws and two wall anchors for mounting. To install your thermostat, you should have the follow­ing tools and materials.
• Slotted Screwdriver(s)
• Small Philips screwdriver
• Hammer
• Electric drill and 3/16” bit
• Two 1.5 V (AA) size alkaline batteries (included)
Remove Old Thermostat
CAUTION: Do not remove any wiring from existing thermostat before reading the instructions carefully. Wires must be labeled prior to removal.
IMPORTANT! Turn off the power to the furnace at the main power panel or at the furnace.
Remove existing thermostat cover and thermostat. See Figure 1. Some thermostats will have screws or other locking devices that must first be removed. Once the wall mounting plate is exposed, look for wires.
If wires are not visible, they may be connected to the back of the wallplate. Again, look for screws, tabs, etc. Some models have doors that open to expose wires and mounting screws. See Figure 1.
Typical Home Thermostats
Wall Mounting Plate
Wall Mounting Plate
Thermostat
Thermostat
Figure 1
Wire Labeling
• Each wire coming from the wall to the existing thermostat is con­nected to a terminal point on that thermostat. Each of these termi­nal points is usually marked with a code letter as shown in Table A below.
• Note that this thermostat has multiple function terminals that allow Single-Stage Heat Pump capability. Standard systems use: Rh, Rc, G, Y, W. [Single-Stage Heat Pumps use: R, Y, G, and O or B.] Table A below shows the multiple functions of the terminals. Use the termi­nals that match your system.
• The number of wires in your system can be as few as two (for heat only systems), as many as eight, or any number in between. If you follow the labeling procedures correctly, you do not have to be con­cerned about how many wires there are.
• There is often no terminal marking on the existing thermostat of two wire, heat only systems. Just connect either of the wires to the RH terminal, then connect the other wire to the W terminal to com­plete the circuit.
• IMPORTANT! BEFORE DISCONNECTING ANY WIRES, APPLY THE SELF­ADHESIVE LABELS PROVIDED TO THE WIRE AS SHOWN IN TABLE A BELOW. (For example, attach the label marked W to the wire that goes to the W or H terminal on your existing thermostat.) IGNORE THE COLOR OF THE WIRES since these do not always comply with the standard.
• After labeling wires, disconnect them from the existing thermostat terminals.
• Remove existing wallplate. To make sure wires do not fall back into wall opening, you may want to tape them to the wall.
• If hole in wall is larger than necessary for wires, seal this hole with insulating material so that no hot or cold air can enter the back of the thermostat from the wall. This air could cause a false thermo­stat reading.
Table A
If the code letter on
your existing thermostat is
RH, R, VR or 4 24 Volt
- or ­B Reversing Valve operating in Heat mode. (Single Stage Heat Pumps ONLY.)
RC, VC 24 Volt Cool
- or ­O Reversing Valve operating in Cool mode. (Single Stage Heat Pumps ONLY.)
G or F Fan
Y, Y1, C or M Air Conditioning Compressor
- or ­Single Stage Heat Pump Compressor
W or H Heating
R 24 Volt (Single Stage Heat Pumps ONLY.)
NOTE: Do not connect a “Common” wire (sometimes labeled “C”) to any terminal on this thermostat. Tape up the wire and do not use. This wire provides electricity to non-battery powered thermostats.
then mark the
wire with
label shown
Cover
Cover
and connect to
thermostat terminal
shown
Mount Wallplate and Thermostat
• Remove the wallplate from your thermostat by pressing the release tab on the bottom of the thermostat. See Figure 2.
Figure 2
• Position wallplate on wall and pull existing wires through large open­ing. Then level for appearance. Mark holes for plastic anchors pro­vided, if your existing holes do not line up with those on the wallplate.
• Drill holes with 3/16” bit and gently tap anchors into the holes until flush with wall.
• Reposition wallplate to wall, pulling wires through large opening. Insert mounting screws provided into wall anchor and tighten. See Figure 3.
Figure 3
NOTE: 5-wire Systems
If your thermostat has one wire marked R or Rh (2, 3, or 4-wire system), then leave the jumper wire between the Rh and Rc terminals on the wallplate. Otherwise, if you have separate Rh and Rc wires (5-wire system), then remove the jumper wire between the Rh and Rc termi­nals.
Connect Wires and Mount Thermostat to Wallplate
• Match and connect the labeled wires to the appropriate coded ter­minal screws on the wallplate. (See Figure 4, 5.) Ignore any wires which may be present, but which were not connected to the old thermostat.
Figure 4 Figure 5
• Refer to the Wiring Diagrams below to be sure your system is wired correctly.
• If your system is a single stage heat pump and uses an O or B wire, you must move the System Selector switch inside the thermostat to the Heat Pump position. If you have a normal furnace or electric system, leave the switch in the Standard position. Refer to the Sys­tem Selector section on the back for more information on this switch.
• Be sure to tighten the terminal screws securely, otherwise a loose wire could cause operational problems with your system or thermo­stat.
• Push excess wire back into the hole to prevent interference when installing the thermostat to the wallplate.
• Make sure the System Switch is set to OFF, and the Fan Switch is set to AUTO.
• Insert the tabs on top of the thermostat body into the slots at the top of the wallplate. Press the bottom of the thermostat body into the snap on the bottom of the wallplate. Refer to Figure 2. (NOTE: Do not force the thermostat onto the wallplate, as the terminal pins may be damaged. If it does not snap properly, the thermostat may not work.)
• Insert the two AA size alkaline batteries, observing the polarity marked inside the battery compartment.
• Switch on the main power at the panel or furnace.
Wiring Diagrams
4-wire Heat/Cool System
Wallplate Terminals
Fan Relay
Heat Relay or Valve
Cool Contactor
Jumper
Heat/Cool 24V Supply
System Selector
STD
HP
5-wire Heat/Cool System
Wallplate Terminals
Fan Relay
Heat Relay or Valve
Cool contactor
No Jumper
Heat 24V Supply
Cool 24V Supply
System Selector
STD
HP
Single-stage Heat Pump System
Wallplate Terminals
24V Supply
Fan Relay
Jumper
Mode
Compressor Contactor
Connect to Proper Reversing Valve Terminal. See Table A
ORHeat
Reversing Valve
Cool Mode
System Selector
STD
HP
2-wire Heat Only System
Wallplate Terminals
Heat Relay or Valve
Jumper
Heat 24V or Millivolt Supply
System Selector
STD
HP
3-wire Heat Only System
Wallplate Terminals
Fan Relay
Heat Relay or Valve
Heat 24V Supply
Jumper
System Selector
STD
HP
3-wire Cool Only System
Wallplate Terminals
X - No Connection
Fan Relay
Cool contactor
Jumper
Cool 24V Supply
System Selector
STD
HP
Selector Switches
In order for this thermostat to control your system, the system type must be specified by the selector switches on the printed circuit board inside the thermostat. There is also a selector switch for your choice of Fahrenheit or Celsius temperature display.
• Heating System Selector (HG - HE switch) The factory position for this switch is in the “HG” position. Leave it in this position if you have a gas furnace or an oil burner. If you have an electric furnace, test to see whether the Heat and Fan come on as expected after installation. If the Fan operation is normal, leave it in the “HG” position. If the Fan does not come on within a minute of the thermostat calling for heat, change the switch posi­tion to “HE”. The system selector has no effect in the cooling mode. NOTE: “HG” position is for gas and most other systems. “HE” posi­tion is for certain electric systems having a fan relay.
• System Selector (STANDARD - HEAT PUMP switch) The factory position for this switch is in the STD position. Leave it in this position if you have ANY system that uses gas, oil, electric, or hot water heating. If you have a single-stage Heat Pump (no auxil­iary or emergency heat source), then slide the switch to the HP position. Be sure the reversing valve wire is connected to the correct terminal for your heat pump (Rc/O) or (Rh/B).
• F° / C° selector (Fahrenheit / Celsius) Your thermostat is set for F° mode from the factory. In order to change to C° mode, slide the switch to C° and press the reset but­ton on front of the thermostat with a paper clip. NOTE: Unless the reset button is pressed, the thermostat will not change temperature mode.
Temperature Display (SW4)
System Selector (SW6)
Fan Option (SW3)
Figure 6
OPERATION
Start-up
The LCD will show the factory default dis­play of 70°F (21°C) when batteries are first installed, or after the Reset button is pressed. The temperature will update after a few sec­onds.
System Selector Switch
The System Selector switch on the front of the ther­mostat determines
the operating mode of the thermostat. You may select COOL, OFF, HEAT.
NOTE: Anytime you install or remove the thermostat from the wallplate, slide the System Selector to the OFF position to prevent the possibility of a rapid sys­tem On-Off.
Fan Switch
The Fan switch should normally be located in the AUTO position. The Fan will be turned on along with normal operation of your system. In a normal gas or oil fur­nace, the Fan will be turned on by your furnace after its warm-up delay. For electric heat, air conditioning, and heat pump operation, the Fan will turn on with the system.
To run the Fan on continuously, slide the Fan switch to the ON position.
Review Current Set Temperature
• Press either the up or down key for less than 1 second to see the Set Temperature.
The factory default is 68°F (20°C) when started with the System Switch Off or Heat, and 78° (26°C) when started with the System Switch on Cool.
Setting New Temperature
• Press either the up or down key and hold for longer than 1 second.
• The display will flash to show that you are in Set Temperature mode, then you can release the key.
• Press either up or down again to change to your desired Set Temperature. Hold the key down for over 2 seconds to fast-ad­vance the Set Temperature.
The display will return to the normal room tempera­ture after the keys have been released for 3 seconds.
Filter Monitor
The thermostat counts the number of hours your system’s filter has been in use. To maximize your system’s performance and energy effi­ciency, change or clean your filter regularly.
When the total system run time for heat and cool reaches 400 hours, the Filter Change Indicator will flash as a reminder to check your system’s filter.
After changing or cleaning the system filter, press and hold the Filter key for 3 seconds. The display will blink, and the counter will be reset to zero.
Note: Pressing the Filter key at any time for less than 3 seconds will cause the Filter Change Indicator to appear on the LCD. This is only to confirm key operation, and the counter is not affected unless the key is held for greater than 3 seconds.
SPAN Setting
Your thermostat is set at the factory to cycle at 1°F (0.5°C) above and below the set temperature. (Span = 2) This setting has been designed to provide a comfortable room temperature under most all conditions. However, if you find your system cycling too fast or too slow, then the Span can be adjusted to modify the cycle time.
• Press and hold BOTH for three seconds. The display will flash, and SPAN will be displayed on the LCD.
• Press to raise the Span to 3. This setting INCREASES the cycle time by allowing your system to run LONGER.
• Press to lower the Span to 1. This setting DECREASES the cycle time by causing your system to run SHORTER.
The Span settings remain the same for both HEAT and COOL, and can be changed in any System Switch position.
When batteries are installed in the thermostat, or the Reset key is pressed, the Span is reset back to setting 2.
Backlighting (INDIGLO® Night-Light)
Your thermostat has an electroluminescent lamp that backlights the display for easy viewing in the dark.
When any key is pressed or the System Switch is changed, the display is illuminated.
The display will remain illuminated for 5 seconds after the last key is pressed. This allows the light to stay on if you need to operate several keys.
Note: If the thermostat is in Low Battery warning condition, the back­light will not operate. Replace with 2 new AA alkaline batteries to restore the Backlight function.
Low Battery Warning
Your thermostat has a two-stage low battery warning system. When the batteries are first detected to be weak, the first stage low bat­tery warning is indicated by battery symbol flashing on the LCD display. At your earliest convenience, you need to replace the batter­ies with 2 new AA alkaline batteries.
When the batteries become too weak for normal operation, the thermostat enters the second stage low battery warning which shuts down the thermostat. In this condition, “BATT” flashes alone on the display, and the thermostat will turn your system Off. Your system will remain shut-off until the batter­ies are replaced.
Note: The thermostat will still keep the current Set Temperature and Filter run time in memory until new batteries are installed. After con­firming that new batteries have been inserted, the thermostat will return to normal operation.
Error Mode
If the thermostat is unable to control your system due to an unexpected battery prob­lem, the thermostat will enter Error Mode. In this condition, the thermostat flashes
“Er” on the LCD display, and shuts off your system.
To correct this problem, replace the batteries with 2 new AA alkaline batteries, even if you have recently replaced them. Next, use a paper clip to press the RESET button next to the keypad. You will need to reprogram your thermostat and confirm normal operation.
If Error Mode returns, please call Technical Support at 1-800-676-7861 for further information.
Auto Cut Off
Your thermostat will automatically cutoff in Heat mode if the room temperature rises above 95°F (35°C). It will cutoff in Cool mode if the room temperature drops below 45°F (7°C).
Note that if your system has malfunctioned and no longer responds to thermostat controls, the Auto Cut-Off will have no effect.
Mechanical Heat Backup
This thermostat includes a bimetal switch that will automatically turn on the Heat when the temperature reaches about 41° F (5° C).
WARNING: This switch only activates the Heating terminal (W). The system itself must be capable of automatically turning the Fan On. Without normal Fan operation, severe damage to the heating system could result.
TROUBLESHOOTING
Problem
No Display.
Entire Display Dims.
Auto Fan Does Not Turn On Properly.
Heating or Cooling Does Not Go On or Off.
Erratic Display.
If unit continues to operate in the Off position.
Thermostat permanently reads “HI”, “LO”, or “Er”.
If you experience any other problems, call 1-800-676-7861 from 8 AM to 5 PM Central Time for technical assistance.
Solution
1. Check battery connections and batteries.
2. Press RESET button with a small pin and hold in for two seconds.
1. Replace Batteries.
1. Move HG/HE selector to correct position.
1. Check that the function switch is in the correct position (“HEAT” or “COOL”).
2. There may be as much as 4-minute delay before the system turns On ­wait and check. (Compressor protection delay.)
3. Check your circuit breakers and switches to ensure there is power to the system.
4. Replace batteries.
5. Make sure your furnace blower door is closed properly.
6. If your non-heat pump system only uses 4-wires, be sure the jumper wire is installed between the Rh/B and Rc/O terminals.
7. Check the position of the Reversing Valve selector switch: Standard or Heat Pump.
8. If you have single-stage heat pump, be sure the jumper wire is installed between the Y and W terminals.
1. Press the reset button once with a small pin and hold for two seconds. Then reprogram.
1. Replace unit.
1. Replace unit.