Powered by
208 163 133 84.5 51.4 37.9 30.6 21.2 13.7 9.16 7.57 4.00
189 147 123 79.7 49.5 36.4 29.2 20.8 13.4 9.00 7.50 3.93
1677 1424 1165 834 531 391 314 228 149 102 85.3 44.8
Specification
Cells Per Unit
Voltage Per Unit
Capacity
Weight
Maximum Discharge Current
Internal Resistance
Operating Temperature Range
Nominal Operating Temperature Range
Float Charging Voltage
Recommended Maximum Charging
Current Limit
Equalization and Cycle Service
Self Discharge
Terminal
Container Material
XTV12750
XTV 12750 is a general battery up to 12 years expected life in
standby service or more than 260 cycles at 100% discharge in
cycle service . XTV has a wider operating temperature range,
which makes them more suitable for the systems in harsh
conditions.
6
12
75 Ah @ 10hr-rate to 1.80 V per cell
Approx. 29.6 kg(65.26 lbs)
800A(5sec)
Approx. 3.9mΩ
Discharge:
Charge:
Storage:
25°C±3°C (77°F±5°F)
13.5 to 13.8 VDC/unit Average at
22.5A
14.4 to 15.0 VDC/unit Average at
CSB Batteries can be stored for more than 6 months at
25°C(77°F). Please charge batteries before using. For
higher temperatures the time interval will be shorter.
I2-Thread lead alloy recessed terminal to accept M6/M8 bolt
PP (UL 94-HB) & Flammability resistance
of (UL 94-V0) can be available upon request.
-20°C~50°C (-4°F~122°F)
-20°C~50°C (-4°F~122°F)
-15°C~40°C ( 5°F~104°F)
12V 75Ah
@25°C (77°F)
25°C (77°F)
25°C (77°F)
CSB-manufactured
VRLA batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
Dimensions :
Unit: mm (inch)
Overall Height (H) Container height (h) Length (L)
214.3±2.5 (8.44±0.10) 211.3±2.5 (8.32±0.10) 308.7±2.5 (12.15±0.10) 169.0±2.0 (6.66±0.08)
Width (W)
Constant Current Discharge Characteristics Unit:A (25°C,77°F)
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V
1.67V
1.70V
285 197 151 91.6 54.6 40.2 32.4 22.3 14.1 9.39 7.89 4.09
252 184 144 90.0 53.5 39.4 31.7 22.1 14.0 9.35 7.73 4.07
235 176 140 88.4 52.9 39.1 31.5 21.8 13.9 9.32 7.67 4.05
1.75V
1.80V
1.85V
156 131 107 72.9 46.2 34.0 27.4 19.7 12.9 8.68 7.14 3.78
Constant Power Discharge Characteristics Unit:W (25°C,77°F)
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V
1.67V
1.70V
1.75V
1.80V
2671 1993 1604 993 606 448 361 256 165 111 92.4 47.9
2469 1895 1557 982 598 442 356 253 163 110 91.6 47.4
2385 1839 1539 973 596 439 354 251 162 109 90.8 47.1
2237 1726 1444 942 583 429 345 245 161 107 90.0 46.9
1971 1602 1322 898 563 413 331 240 156 106 89.2 46.2
1.85V
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.
RA1403

XTV 12750
2.60
0.20
140
2.40
0.17
120
2.20
0.14
100
2.00
0.11
80
1.80
0.08
60
1.60
0.05
40
1.40
0.02
20
(2.275V/Cell)
12V 75Ah
)Ratio
13.65V
140
120
100
80
60
40
20
Application
Cycle Use
Standby
40 8 12 16 20 24
0.20
2.60
2.40
0.17
2.20
0.14
2.00
0.11
1.80
0.08
1.60
0.05
1.40
0.02
40 8 12 16 20 24
Charge Voltage(V/Cell)
Temperature Set Point Allowable Range
(77 )
25
25
(77 )
2.45 2.40~2.50
2.275 2.25~2.30
)Ratio
Max.Charge Current
0.3C
Final Discharge
Voltage V/Cell
Discharge
Current(A)
68
1.75 1.70 1.60 1.30
0.2C>(A) 0.2C<(A)<0.5C 0.5C<(A)<1.0C (A)>1.0C
GLOBAL HQ
CSB BATTERY CO., LTD. (TAIWAN)
Tel : +886-2-2880-5600
Fax : +886-2-2888-3300
mail : service@csb-battery.com.tw
BEIJING OFFICE. (CHINA)
C
SB BATTERY TECHNOLOGIES (BEIJING) CO., LTD.
Tel : +86-10-5820-5336/5338
Fax : +86-10-58203053
mail : chinasls@csb-battery.com
AMERICA HQ
CSB BATTERY TECHNOLOGIES INC. (U.S.A)
Tel : +1-817-244-7777/1-(800)3-CSB-USA(272872)
Fax : +1-817-244-4445
mail : csb@csb-battery.com
SHANGHAI OFFICE. (CHINA)
CSB BATTERY LOGISTIC (SHANGHAI) CO., LTD.
Tel : +86-21-5046-1622/5046-0833
Fax : +86-21-5064-1046
mail : chinasls@csb-battery.com
EUROPE HQ
CSB Battery Europe BV.
Tel : +31(0)-180-418-140
Fax :+31(0)-180-418-327
mail : eurosales@csb-battery.eu
SHENZHEN OFFICE.( CHINA )
CSB BATTERY LOGISTIC ( SHANGHAI ) CO., LTD.
Tel : +86-755-8831-6488/6396/6356
Fax : +86-755-8831-6548
mail : she@csb-battery.com.cn