315 234 183 116 68.1 49.1 38.9 28.4 18.2 12.0 9.86 5.20
3463 2557 2094 1325 785 569 453 328 213 141 115 60.5
2954 2359 1931 1267 763 553 441 320 208 138 113 59.5
2451 1958 1610 1165 725 528 422 306 198 132 109 56.6
GP 121000
GP 121000 is a general purpose battery up to 5 years in standby
service or more than 260 cycles at 100% discharge in cycle
service. As with all CSB batteries, all are rechargeable, highly
efficient, leak proof and maintenance free.
12V 100Ah
Specification
Cells Per Unit 6
Voltage Per Unit 12
Capacity 100Ah@ 20hr-rate to 1.75V per cell
Weight Approx. 31.2 kg(68.78 lbs)
Maximum Discharge Current 800A(5sec)
Internal Resistance Approx. 4.5 mΩ
Operating Temperature Range
Nominal Operating Temperature Range
Float Charging Voltage
Recommended Maximum Charging 30A
Current Limit
Equalization and Cycle Service
Self Discharge CSB Batteries can be stored for more than 6 months at
Terminal I2-Thread lead alloy recessed terminal to accept M6/M8 bolt
Container Material Polypropylene(UL 94-HB) & Flammability resistance
Discharge:
Charge:
Storage:
25°C±3°C (77°F±5°F)
13.5 to 13.8 VDC/unit Average at
14.4 to 15.0 VDC/unit Average at
25°C (77°F).
higher temperatures the time interval will be shorter.
of (UL 94-V0) can be available upon request.
-15°C~50°C ( 5°F~122°F)
-15°C~40°C ( 5°F~104°F)
-15°C~40°C ( 5°F~104°F)
Please charge batteries before using. For
@25°C (77°F)
25°C (77°F)
25°C (77°F)
CSB-manufactured
VRLA batteries are UL-
recognized components
under UL1989.
CSB is also certified by
ISO 9001 and ISO 14001.
Dimensions :
Unit: mm (inch)
Overall Height (H) Container height (h) Length (L)
217.3±2.5 (8.56±0.10) 213.9±2.5 (8.42±0.10) 343.0 . ±2.5 (13.50±0.10) 170.0±2.0 (6.69±0.08)
Width (W)
Constant Current Discharge Characteristics Unit:A (25°C,77°F)
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V
1.67V
372 257 197 121 70.1 50.4 39.9 29.0 18.6 12.3 10.1 5.26
326 242 187 117 68.8 49.5 39.2 28.6 18.3 12.1 9.94 5.23
1.70V
1.75V
1.80V
1.85V
286 213 175 113 66.8 48.3 38.4 27.9 17.9 11.8 9.72 5.10
241 192 157 105 65.4 47.3 37.6 27.3 17.5 11.5 9.59 5.00
202 165 135 96.8 62.5 46.0 36.6 26.5 17.1 11.2 9.24 4.80
Constant Power Discharge Characteristics Unit:W (25°C,77°F)
F.V/Time 5MIN 10MIN 15MIN 30MIN 60MIN 90MIN 2HR 3HR 5HR 8HR 10HR 20HR
1.60V
3593 2696 2223 1366 802 579 459 335 216 143 117 61.1
1.67V
1.70V
3307 2505 2036 1306 778 564 449 325 211 140 114 60.0
1.75V
1.80V
2675 2222 1815 1218 746 542 432 313 203 135 111 58.9
1.85V
Ratings presented herein are subject to revision without notice. Please refer to www.csb-battery.com to confirm the latest version.
RA1308
GP121000
2.60
0.20
140
2.40
0.17
120
2.20
0.14
100
2.00
0.11
80
1.80
0.08
60
1.60
0.05
40
1.40
0.02
20
(2.275V/Cell)
12V 100Ah
)Ratio
13.65V
140
120
100
80
60
40
20
Application
Cycle Use
Standby
40 8 12 16 20 24
0.20
2.60
2.40
0.17
2.20
0.14
2.00
0.11
1.80
0.08
1.60
0.05
1.40
0.02
40 8 12 16 20 24
Charge Voltage(V/Cell)
Temperature Set Point Allowable Range
(77 )
25
25
(77 )
2.45 2.40~2.50
2.275 2.25~2.30
)Ratio
Max.Charge Current
0.3C
Final Discharge
Voltage V/Cell
Discharge
Current(A)
68
1.75 1.70 1.60 1.30
0.2C>(A) 0.2C<(A)<0.5C 0.5C<(A)<1.0C (A)>1.0C
GLOBAL HQ
CSB BATTERY CO., LTD. (TAIWAN)
Tel : +886-2-2880-5600
Fax : +886-2-2888-3300
mail : service@csb-battery.com.tw
BEIJING OFFICE. (CHINA)
C
SB BATTERY TECHNOLOGIES (BEIJING) CO., LTD.
Tel : +86-10-5820-5336/5338
Fax : +86-10-58203053
mail : chinasls@csb-battery.com
AMERICA HQ
CSB BATTERY TECHNOLOGIES INC. (U.S.A)
Tel : +1-817-244-7777/1-(800)3-CSB-USA(272872)
Fax : +1-817-244-4445
mail : csb@csb-battery.com
SHANGHAI OFFICE. (CHINA)
CSB BATTERY LOGISTIC (SHANGHAI) CO., LTD.
Tel : +86-21-5046-1622/5046-0833
Fax : +86-21-5064-1046
mail : chinasls@csb-battery.com
EUROPE HQ
CSB Battery Europe BV.
Tel : +31(0)-180-418-140
Fax : +31(0)-180-418-327
mail : eurosales@csb-battery.eu
SHENZHEN OFFICE.( CHINA )
CSB BATTERY LOGISTIC ( SHANGHAI ) CO., LTD.
Tel : +86-755-8831-6488/6396/6356
Fax : +86-755-8831-6548
mail : she@csb-battery.com.cn