25-90Amp - 120/480 Vac - AC OUTPUT
>
Phase Angle Controller/SSR in One Package
>
Low Voltage, Current or Potentiomer Control
>
Output Status Indicator (Load Open, No Voltage)
>
0-100% Control Range
>
Separate Output Enable/Disable Control
>
SCR Based Output Load Switching
>
Internal Snubber Network
series MCPC
GENERAL SPECIFICATIONS
Dielectric Strength 50/60Hz, Input/Output/Base 4000 Vrms
Insulation Resistance (Min.) @ 500 Vdc 10
Max. Capacitance Input/Output 10 pF
Ambient Operating Temperature Range -20 to 80°C
Ambient Storage Temperature Range -40 to 125°C
MECHANICAL SPECIFICATIONS
Weight: (typical) 3.0 oz. (86.5g)
Encapsulation Thermally Conductive Epoxy
Terminals - Power Screws and Saddle Clamps Furnished, Unmounted
OUTPUT SPECIFICATIONS 12 24 48
Operating Voltage (47-63 Hz) [Vrms] 48-140 180-280 300-530
Transient Overvoltage [Vpk] 400 600 1200
Max. Off-State Leakage Current @ Rated Voltage [mA] 5 7 12
Power Factor (Min.) with Max. Load 0.5 0.5 0.5
Maximum Voltage Drop (100% On) [Vpk] 1.6 1.6 1.6
Minimum Off-State dv/dt [V/µsec] 200 200 200
Max. Load Current [Arms] 25 50 90
Min. Load Current (mArms) 150 150 150
Max. Surge Current (16.6ms) [Apk] 250 625 1200
Thermal Resistance Junction to Case (R
Maximum I
INPUT SPECIFICATIONS* Minimum Typical Maximum
DC Voltage Supply Range [Vdc] [P1] 8 12 or 24 32
Input Current [mA] 28 30
Control Must Operate Voltage "On" [Vdc][P3] 5 32
Control Must Release Voltage "Off" [Vdc][P3] 0 4
Control Input Current [mA] [P3] 0 1.25
Control Nominal Input Impedance 30K
PLVI Range Option A [Vdc][P4]** 0.8 5
PLVI Range Option B [Vdc][P4]** 1 7
PLVI Range Option C [Vdc][P4]** 2 10
PLVI Range Option D [mA][P4] 4 20
Nominal Input Impedance Option A,B,C [Ohms][P4] 20K
Nominal Input Impedance Option D [Ohms][P4] 220
*Voltages are reference to GND (Ground = 0Vdc) P2.
**PLVI voltage can go up to max. supply voltage without damage.
Control Barrier Strip Screw Terminals
25 Amp 50 Amp 90 Amp
) [°C/W] 1.02 0.63 0.28
2
t for Fusing, (8.3 msec.) [A2s] 260 1620 6000
ØJC
9
Ohm
Voltage Suffix
Current Suffix
The Crydom MCPC series of Proportional
Controllers incorporate a complete phase-fired
logic system and Solid State Relay in one small
industry standard package. The MCPC uses
microprocessor controlled logic, accepts a wide
range input logic power supply, provides an
output load status indicator, and five modes of
analog control input along with an Enable/Disable
control.
The MCPC does not require any calibration
adjustment, is optically isolated to 4000Vrms,
includes an internal snubber network, and is
available in load ratings up to 90A and 530Vac.
The Crydom MCPC series is particularly suited to
applications such as tungsten lamp dimming,
vibratory feeders, universal motor control, and
resistive heating element control.
© 2004 Crydom Corp, All Rights Reserved.
CrydomMCPC_E0405.pdf page 1 of 3
Specifications are subject to change without prior notice. Crydom and the Crydom logo are trademarks of Crydom Corp. Crydom
series MCPC
1.87
(47.5)
.78
(19.8)
2.30
(58.4)
.45
(11.4)
1.10
(27.9)
8-32 TERMINAL
(2 PLACES )
1.80
(45.7)
MOUNTING
HOLE/SLOT
0.17 (4.3) DIA.
BASE PLATE
.125 (3.2)
Screw Torque Requirements:
8-32 Screws - 20in. lbs. (Screws dry without grease.)
Input Connections via Screw Type Barrier Strip
P4
P3
P2
P1
1.87
(47.5)
.78
(19.8)
2.30
(58.4)
.45
(11.4)
1.10
(27.9)
8-32 TERMINAL
(2 PLACES )
1.80
(45.7)
OUTPUT
STATUS
MOUNTING
HOLE/SLOT
0.17 (4.3) DIA.
BASE PLATE
.125 (3.2)
P3
P2
P1
Analog Input OPTIONS: A,B,C,D
Analog Input Option: E (Internal Potentiometer)
1/L1
2/T1
OUTPUT
STATUS
1/L1
2/T1
25-90Amp - 120/480 Vac - AC OUTPUT
Part Number Nomenclature
Electrical Connections
LOAD
OUTPUT
1/L1
P4 0-5V, 0-7V, 0-10V, 4-20mA
Wiring Example
(for Options A, B or C using an external potentiometer)
Terminal #4
OUTPUT
STATUS
P1 8-32Vdc (+)
P2 Ground (-)
P3 ON/OFF Control
Terminal #1
AC
2/T1
Setpoint Adjust
Enable
GND
+Vdc
P1
10K - 50K
For A,B or C Option
P4
P2
10k to 50k pot for
Options A, B or C
DC
Supply
Output Status Functions
CONDITIONS LED
Initial Logic Supply On Flash Once
Load Voltage Missing / Load Open (w/control disabled) Flash Once Intermittently
Load Voltage Missing / Load Open (w/control enabled) Flash Twice Intermittently
Analog Input < Threshold Off
Analog Input > Threshold < max Varying Brightness
Analog Input > max On, Bright
Mechanical
Dimensions are in inches (millimeters)
© 2004 Crydom Corp, All Rights Reserved.
CrydomMCPC_E0405.pdf page 2 of 3
Specifications are subject to change without prior notice. Crydom and the Crydom logo are trademarks of Crydom Corp. Crydom