Crydom Series IAC, Series (S)MIAC, Series X4IAC Data Sheet

Series IAC,
(S)MIAC, X4IAC
AC Input Modules
• Status Indicating LED on X4 Series
• IAC Module for 24 Vac Input Available (E suffix)
• UL, CSA, and CE
Solid state I/O switching modules deliv­er an electrically clean, photo-isolated, noise-free "output" interface from logic level control systems to external loads such as motors, valves, solenoids, etc. -- or an "input" interface from the load or sensors to microprocessor or computer-based logic level systems. Designed for long, reliable service in demanding industrial environments.
INPUT SPECIFICATIONS IAC5 IAC15 IAC24 IAC5A IAC15A IAC24A
(S)MIAC5 (S)MIAC15 (S)MIAC24 (S)MIAC5A (S)MIAC15A (S)MIAC24A
X4IAC5 X4IAC15 X4IAC24 X4IAC5A X4IAC15A X4IAC24A
Nominal input voltage [Vrms/Vdc] 120 120 120 240 240 240
Minimum Input Voltage [Vrms/Vdc] 90 90 90 180 180 180
Maximum Input Voltage [Vrms/Vdc] 140 140 140 280 280 280
Maximum Input Current [mA rms] 10 10 10 8 8 8
Drop Out Current [mA rms] 2.5 2.5 2.5 1.5 1.5 1.5
Allowable Off-state Voltage [Vrms/Vdc] 50.0 50.0 50.0 120 120 120
OUTPUT SPECIFICATIONS
Nominal Logic Voltage [Vdc] 5 15 24 5 15 24
Minimum Logic Voltage [Vdc] (X4 Series) 1.5 (3) 8.5 (10) 16.5 (18) 1.5 (3) 8.5 (10) 16.5 (18)
Maximum Logic Voltage [Vdc] (X4 Series) 6.0 (7) 18.5 (20) 30.5 (32) 6.0 (7) 18.5 (20) 30.5 (32)
Typical Logic Supply Current [mAdc] 10 10 10 10 10 10
Max. Logic Supply Current [mAdc] 18.5 16 14 18.5 16 14
Max. Logic Sup. Leak. Current [µAdc] 10 10 10 10 10 10
Maximum Output Voltage [Vdc] 30 30 30 30 30 30
Maximum Output Current [mAdc] 50 50 50 50 50 50
Max. Output Leakage Current [µAdc] 10 10 10 10 10 10
Max. Output Voltage Drop [mVdc
Maximum Turn-on Time [msec] 20 20 20 20 20 20
Maximum Turn-off Time [msec] 30 30 30 30 30 30
]
200 200 200 200 200
200
© 2003 CRYDOM CORP Specifications subject to change without notice.
SERIES IAC. Rev. 060305 PAGE 1 OF 2
For recommended applications and more information contact: USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540 Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com WEB SITE: http://www.crydom.com UK: +44 (0)1202 365070 • FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com. GERMANY: +49 (0)180 3000 506
Series IAC,
(S)MIAC, X4IAC
AC Input Modules
GENERAL SPECIFICATIONS
Operating temperatue ranger -30 to +80°C
Storage temperature range -40 to +100°C
Isolation 4,000 V rms
Capacitance input to output 8 pF
Line frequency range 47 to 63 Hz
Package Color Yellow
WIRING & MECHANICAL DIAGRAMS
Standard Series, IAC
BOTTOM VIEW
CAPTIVE
#4-40. PHILLIPS
HEAD HOLD
DOWN SCREW
1.25
(31.7)
.25
(6.3)
.040 (1.0) DIA.
(5 PLACES)
(40.6)
1.00
(25.4)
1.70
(43.1)
12345
.70
(17.8)
1.20
(30.5)
1.40
(35.5)
1.60
APPLICATION NOTES
¥ Do not install or remove modules
in live (electrically hot) circuits.
High voltage may be present.
¥ An externally located
commutating diode must be
installed across inductive loads
¥ I/O module boards also available
All dimensions are in inches (millimeters)
.30
(7.6)
.30
(7.6)
.60
(15.2)
.100 (2.5)
.030 (0.8)
CAPTIVE
#4-40.PHILLIPS
HEAD HOLD
DOWN SCREW
(25.4)
1.00
(6.35)
Standard and Mini Pack
1
Vac/d c
2
+
LOGIC
3
OUT
4
-
GND
5
Schmitt
Trigger
Vac/dc
LOGIC
OUT
GND
1
2
+
3
4
-
5
X4 Series
Schmitt Trigger
X4 Series, X4IAC
MINI-PACK Series, (S)MIAC
SM Prefix
1.70
(43.1)
1.00
(25.4)
.25
4
.30 (7.6)
BOTTOM VIEW
(17.8)
123+5
.200 (5.1)
.700
1.100 (27.9)
1.30
(43.1)
1.70
(43.1)
.040(1.0) DIA
.100 (2.5)
(5 PLACES)
.40
(10.2)
(25.4)
(6.35)
M Prefix
1.70
(43.1)
1.00
.25
4
.30
(7.6)
BOTTOM VIEW
(17.8)
123+5
.200 (5.1)
.700
1.100 (27.9)
1.30
(43.1)
1.70
(43.1)
.100 (2.5)
.040 (1.0) DIA.
(5 PLACES)
.40
(10.2)
(45.2)
1.78
0.81
(20.6)
0.15 (3.8)
0.35 (8.9)
0.55
(13.9)
(33.0)
0.20 (5.1)
1.82
(46.2)
0.20 (5.1)
1.3
1.70
(43.1)
© 2003 CRYDOM CORP Specifications subject to change without notice.
CAPTIVE
#4-40. PHILLIPS
HEAD HOLD
DOWN SCREW
0.48
(12.2)
.040 (1.0) DIA.
(5 PLACES)
SERIES IAC. Rev. 060305 PAGE 2 OF 2
For recommended applications and more information contact: USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540 Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com WEB SITE: http://www.crydom.com UK: +44 (0)1202 365070 • FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506
Loading...