Crydom Series HA60, Series HD60 Data Sheet

MODEL NUMBERS
AC CONTROL HA6025 HA6050 HA6090 HA60125 DC CONTROL HD6025 HD6050 HD6090 HD60125
OUTPUT SPECIFICATIONS
Nominal Line Voltage (±10%) [Vrms] 600 600 600 600 Operating Voltage Range (47-63 Hz) [Vrms] 48-660 48-660 48-660 48-660
Max. Load Current ➂[Arms] 25 50 90 125 Min. Load Current, [mArms] 40 40 40 150 Transient Overvoltage [Vpk] 1200 1200 1200 1200 Max. Surge Current, (16.6ms) [Apk] 250 625 1,200 1,750 Max. On-State Voltage Drop @ Rated Current [Vpk] 1.7 1.7 1.7 1.7
Thermal Resistance Junction to Case (R
θJC
) [° C/W] 1.02 0.63 0.28 0.22
Maximum I2 t for Fusing, (8.3 msec.) [A2sec] 260 1,620 6,000 12,700
Max. Off-State Leakage Current @ Rated Voltage [mArms]
5555
Min. Off-State dv/dt @ Max. Rated Voltage [V/µsec] 500 500 500 500 Max. Turn-On Time 1/2 Cycle (DC Input), 10.0 msec (AC Input) Max. Turn-Off Time 1/2 Cycle (DC Input), 40.0 msec (AC Input) Power Factor (Min.) with Max. Load 0.5 0.5 0.5 0.5
INPUT SPECIFICATIONS DC CONTROL AC CONTROL AC CONTROL
(D PREFIX) (A PREFIX) (E SUFFIX)
Control Voltage Range 3-32 Vdc 90-280 Vrms (60Hz) 18-36 Vrms Max. Reverse Voltage -32 Vdc --- --- Max. Turn-On Voltage 3.0 Vdc 90 Vrms 18 Vrms Min. Turn-Off Voltage 1.0 Vdc 10 Vrms 4.0 Vrms Nominal Input Impedance See Note 60K Ohms 9.0K Ohms Typical Input Current 2.0 mA 2mA @ 120 Vrms, 4mA @ 240 Vrms 3mA @ 24 Vrms
GENERAL NOTES
All parameters at 25°C unless otherwise specified.Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1Heat sinking required, for derating curves see page 2.24 Vac Input option, E suffix.Turn-on time for random turn-on versions is 0.02 msec (DC Control Models).Input circuitry incorporates active current limiter.No internal snubber.
Zero Voltage and Random Turn-On Switching
Panel Mount
1200V Blocking Capability
600Vac - the preferred
choice in Canada
FastFax Document No.159 SERIES HA/HD60. 041900 PAGE 1 OF 3
Featuring state-of-the-art Surface Mount Technology, these SPST-NO relays deliver proven reliability in the most demanding applications. Output consists of an SCR AC switch and is available in zero-cross, random turn-on (phase controllable) and ver- sions with either AC or DC input (coil) control. Manufactured in Crydom’s ISO 9001 Certified facility for optimum product performance and reliability.
Series HA60/HD60
25-125Amp • 600 Vac • AC Output
©2000 CRYDOM CORP, Specifications subject to change without notice.
• Integrated Overvoltage Protection by Automatic Self Turn-On (Suffix P)
For recommended applications and more information contact:  USA: (800) 8 CRYDOM • (800) 827-9366 •(619) 715-7200 • fax (619) 715-7280 Crydom Corp, 9525 Chesapeake Drive, San Diego, CA 92123 • Email: sales@crydom.com WEB SITE: http://www.crydom.com FASTFAX Product Information: (888) 267-9191 UK: (44)1202 857300 • fax (44)1202 857340 Crydom International Ltd., Riverside HouseBrook Road, Wimborne, Dorset, England BH21 2BH, Email: intsales@crydom.com. GERMANY: 0180 3000 506 • fax (49)(0)6874 182585 Crydom GmbH, Gewerbegebiet Im Schachen, D-66687 Nunkirchen, Germany • Email: vertrieb@crydom.com
GENERAL SPECIFICATIONS
Dielectric Strength 50/60Hz Input/Output/Base 4000 Vrms Insulation Resistance (Min.) @ 500 Vdc 109Ohm Max. Capacitance Input/Output 8 pF Ambient Operating Temperature Range -40 to 80°C Ambient Storage Temperature Range -40 to 125°C
MECHANICAL SPECIFICATIONS
Weight: (typical) 3.0 oz. (86.5g) Encapsulation: Thermally Conductive Epoxy Terminals: Screws and Saddle Clamps Furnished, Unmounted
APPROVALS
UL E116950 CSA LR81689 VDE 10143 UG
Crydom Heat Sinks offer excellent thermal management and are per­fectly matched to the load current ratings of Crydom panel mount relays. Request Crydom’s Heat Sink specification sheet for all the details.
FastFax Document No.159 SERIES HA/HD60. 053000 PAGE 2 OF 3
Series HA60/HD60
25-125Amp • 600 V ac • AC Output
©2000 CRYDOM CORP, Specifications subject to change without notice.
Screw Torque Requirements:
6-32 Screws - 10 in./lbs., 8-32 and 10-32 Screws - 20in./lbs. (Screws dry without grease.)
Fastons:
Single pair (up to 25A) Double pair* (up to 50A).
*
Caution: User must connect to both pairs
.90
(22.9)
FASTON TERMINAL .187 X .032 (2 PLCS.)
BASE PLATE .125 (3.2)
FASTON TERMINAL .250 X .032 (2 PLCS.)
1.87
(47.5)
.78
(19.8)
2.30
(58.4)
1.70
(43.2)
.87 REF.
(22.2)
12
OUTPUT
43
INPUT
1.00
(25.4)
1.80
(45.7)
.45
(11.4)
1.10
(27.9)
MOUNTING HOLE/SLOT
0.17 (4.3) DIA.
.90
(22.9)
FASTON TERMINAL .187 X .032 (2 PLCS.)
BASE PLATE .125 (3.2)
FASTON TERMINAL .250 X .032 (2 PLCS.)
1.87
(47.5)
.78
(19.8)
2.30
(58.4)
1.70
(43.2)
.87 REF.
(22.2)
12
OUTPUT
43
INPUT
1.00
(25.4)
1.80
(45.7)
.45
(11.4)
1.10
(27.9)
MOUNTING HOLE/SLOT
0.17 (4.3) DIA.
All dimensions are in inches (millimeters)
AVAILABLE OPTIONS
E
24 VAC Input (18-36 Vac) Example: HA6025E
F Faston Terminals (Up to 50 Amp Models)
Example: HD6050F
Input Status LED.
G
Agencies Approval Pending Example: HD6050G Note: Control Voltage Range 4.5-32Vdc for DC Control Models.
P Internal Overvoltage Protection.
Relay Will Self Trigger Between 900-1200 Vpk. Not Suitable For Capacitive Loads. Agencies Approval Pending. Example: HD6025P
-10 Random Turn-On (AC & DC Control)
Phase Controllable (DC Control) Example: HD6090-10
Ordering System: Combination of the suffixes should be made in the following order: EFPG-10. Example: HA6050EFPG-10
MOUNTING HOLE/SLOT
0.17 (4.3) DIA.
BASE PLATE .125 (3.2)
1.10
(27.9)
.45
(11.4)
OUTPUT
12
1.87
(47.5)
SOLID-STATE RELAY
INPUT
1.00
(25.4)
1.80
(45.7)
(43.2)
+--
34
2.30
(58.4)
1.70
6-32 TERMINAL (2 PLACES)
8-32 TERMINAL
(2 PLACES )
.78
(19.8)
.90
(22.9)
For recommended applications and more information contact: USA: (800) 8 CRYDOM • (800) 827-9366 •(619) 715-7200 • fax (619) 715-7280 Crydom Corp, 9525 Chesapeake Drive, San Diego, CA 92123 • Email: sales@crydom.com
WEB SITE: http://www.crydom.com FASTFAX Product Information: (888) 267-9191 UK: (44)1202 857300 • fax (44)1202 857340 Crydom International Ltd., Riverside HouseBrook Road, Wimborne, Dorset, England BH21 2BH, Email: intsales@crydom.com. GERMANY: 0180 3000 506 • fax (49)(0)6874 182585 Crydom GmbH, Gewerbegebiet Im Schachen, D-66687 Nunkirchen, Germany • Email: vertrieb@crydom.com