Crydom Series H12D Data Sheet

S
25-90
eries
A
m
p
480 Vac - AC OUTPU
H
12
D
T
• 1200 Volt Blocking
Panel Mount
Up to 530 Vac
Zero Voltage and Random
High voltage relays use IC driven cir­cuits for switching loads up to 660 VAC. All models come with 1200 Volts blocking and are available with either AC or DC input (coil) control.
Turn-On
SCR Output
Integrated Overvoltage
Protection by Automatic
Manufactured in Crydoms ISO 9001 Certified facility for optimum product performance and reliability.
Self Turn-On (Suffix P)
MODEL NUMBERS
OUTPUT SPECIFICATIONS
Operating Voltage (47-63 Hz) [Vrms] 48-530 48-530 48-530 48-530 Max. Load Current [Arms] 25 50 75 90 Min. Load Current, [mArms] 150 150 150 150 Transient Overvoltage [Vpk] 1200 1200 1200 1200 Max. Surge Current, (16.6ms) [Apk] 250 625 1000 1200 Max. On-State Voltage Drop @ Rated Current [Vpk] 1.6 1.6 1.6 1.6 Thermal Resistance Junction to Case (RJC) [˚C/W] 1.02 .63 .31 .28 Maximum I2 t for Fusing, (8.3 msec.) [A2sec] 260 1620 4150 6000
Max. Off-State Leakage Current @ Rated Voltage [mArms] 10 10 10 10 Min. Off-State dv/dt @ Max. Rated Voltage [V/µsec] 500 500 500 500 Max. Turn-On Time 1/2 Cycle Max. Turn-Off Time 1/2 Cycle Power Factor (Min.) with Max. Load 0.5 0.5 0.5 0.5
H12D4825 H12D4850 H12D4875 H12D4890
1/2 Cycle 1/2 Cycle
1/2 Cycle
1/2 Cycle
1/2 Cycle 1/2 Cycle
INPUT SPECIFICATIONS
Control Voltage Range 4-32Vdc Max. Turn-On Voltage 4.0 Vdc Min. Turn-Off Voltage 1.0 Vdc Nominal Input Impedance See Note 5 Typical Input Current
GENERAL NOTES
All parameters at 25˚ C unless otherwise specified.
Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
Heat sinking required, for derating curves see page 2.
Turn-on time for DC control random turn-on versions is 0.02 msec.
Input circuitry incorporates active current limiter.
FastFax Document No.157 SERIES H12D. Rev. 111203 PAGE 1 OF 3
15 mA @ 5 Vdc
© 2003 CRYDOM CORP, Specifications subject to change without notice.
For recommended applications and more information contact: USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540 Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com UK: +44 (0)1202 365070 FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com. GERMANY: +49 (0)180 3000 506
WEB SITE: http://www.crydom.com
S
25-90
eries
A
m
p
H
12
D
480 Vac - AC OUTPU
GENERAL SPECIFICATIONS
Dielectric Strength 50/60Hz Input/Output/Base Insulation Resistance (Min.) @ 500 Vdc 10 Max. Capacitance Input/Output Ambient Operating Temperature Range
4000 Vrms
9
Ohm
8 pF
-40 to 80˚C
Ambient Storage Temperature Range -40 to 125˚C
MECHANICAL SPECIFICATIONS
Weight: (typical)
3.0 oz. (86.5g) Encapsulation: Thermally Conductive Epoxy Terminals: Screws and Saddle Clamps Furnished, Unmounted
T
Available Options
F Faston Terminals.
(Up to 50 Amp Models) Example: H12D4850F
Input Status LED.
G
Agencies Approval Pending Example: H12D4850G Note: Control Voltage Range 5.5-32 Vdc
Internal Overvoltage Protection.
P
Relay Will Self Trigger Between 900-1200Vpk. Not Suitable For Capacitive Loads. Agencies Approval Pending. Example: H12D4850P
H Heat Transfer Pad (Attached)
Example: H12D4850H
Ordering System: Combination of the suffixes should be made in the following order: FPG-10.
Example:
H12D4850FPG-10
MOUNTING HOLE/SLOT
0.17 (4.3) DIA.
1.87
(47.5)
BASE PLATE .125 (3.2)
MOUNTING HOLE/SLOT
0.17 (4.3) DIA.
1.87
(47.5)
1.10
(27.9)
.45
(11.4)
OUTPUT
12
1.70
(43.2)
+--
34
INPUT
1.00
(25.4)
1.80
(45.7)
Screw Torque Requirements:
6-32 Screws - 10 in. lbs., 8-32 and 10-32 Screws - 20in. lbs. (Screws dry without grease.)
Fastons:
Single pair (up to 25A) Double pair* (up to 50A). *Caution: User must connect to both pairs
1.10
(27.9)
.45
(11.4)
OUTPUT
12
--
4
INPUT
(43.2)
+
3
6-32 TERMINAL (2 PLACES)
1.70
8-32 TERMINAL
(2 PLACES )
2.30
(58.4)
FASTON TERMINAL .250 X .032 (2 PLCS.)
2.30
(58.4)
.87 REF.
.78
(19.8)
.90
(22.9)
(22.2)
APPROVALS
UL E116949 CSA LR81689 VDE 10143 UG
FastFax Document No.157
SERIES H12D. Rev. 111203 PAGE 2 OF 3
Crydom Heat Sinks offer excellent ther
mal management and are perfectly matched to the load current ratings of Crydom panel mount relays. Request Crydoms Heat Sink specification sheet for all the details.
For recommended applications and more information contact: USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540 Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com UK: +44 (0)1202 365070 FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com. GERMANY: +49 (0)180 3000 506
BASE PLATE
-
.125 (3.2)
All dimensions are in inches (millimeters)
© 2003 CRYDOM CORP, Specifications subject to change without notice.
WEB SITE: http://www.crydom.com
1.00
(25.4)
1.80
(45.7)
FASTON TERMINAL .187 X .032 (2 PLCS.)
.78
(19.8)
.90
(22.9)
25A
30 25 20 15 10
Power Dissipation
5 0
510 202515 20 40 60 80
Load Current [Arms] Max Ambient Temp. [˚C]
CURRENT DERATING CURVES
3˚C/W
NO HEATSINK
2˚C/W
1˚C/W
95
100
110
120
Base Plate Temp [˚C]
60
40
20
Power Dissipation
0
10 20 40 5030 20 40 60 80
Load Current [Arms] Max Ambient Temp. [˚C]
50A
S
25-90
1˚C/W
1.5˚C/W
2˚C/W
NO HEATSINK
eries
A
m
p
480 Vac - AC OUTPU
.5˚C/W
90
100
110
120
H
Base Plate Temp [˚C]
12
D
T
75A
120
80
40
Power Dissipation
0
15 30 60 7545 20 40 60 80
Load Current [Arms] Max Ambient Temp. [˚C]
1˚C/W
.5˚C/W
.3˚C/W
95
100
110
120
Base Plate Temp [˚C]
90A
120
80
40
Power Dissipation
0
20 40 80 060 20 40 60 80
Load Current [Arms] Max Ambient Temp. [˚C]
© 2003 CRYDOM CORP, Specifications subject to change without notice.
.5˚C/W
1˚C/W
.2˚C/W
.4˚C/W
90
100
110
Base Plate Temp [˚C]
120
FastFax Document No.157 SERIES H12D. Rev. 111203 PAGE 3 OF 3
For recommended applications and more information contact: USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540 Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com UK: +44 (0)1202 365070 FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com. GERMANY: +49 (0)180 3000 506