Series CSW
10-90Amp • 120/240 Vac • AC OUTPUT
Low Leakage
•
The Series CS has an SCR AC switch
output featuring low off-state leakage
•
SCR Output
•
Panel Mount
• Zero Voltage Switching
(1mA, snubberless), zero-voltage
switching and a broadened operating
range (24-280Vac). This wide range
permits optimum performance at both
120Vac and 240Vac line voltages.
• Wide Control Range
Manufactured in Crydom’s ISO 9001
Certified facility for optimum product
performance and reliability.
MODEL NUMBERS
OUTPUT SPECIFICATIONS
Operating Voltage (47-63 Hz) [Vrms] 24-280 24-280 24-280 24-280 24-280
Load Current Range 3 [Arms] 0.15-10 0.15-25 0.15-50 0.25-75 0.25-90
Transient Overvoltage [Vpk] 600 600 600 600 600
Max. Surge Current, (16.6ms) [Apk] 120 250 625 1000 1200
Max. On-State Voltage Drop @ Rated Current [Vpk] 1.6 1.6 1.6 1.6 1.6
Thermal Resistance Junction to Case (R ) [°C/W]
Maximum I2 t for Fusing, (8.3 msec.) [A2sec] 60 260 1620 4150 6000
Max. Off-State Leakage Current @ Rated Voltage [mA] 1.0 1.0 1.0 1.0 1.0
Min. Off-State dv/dt @ Max. Rated Voltage [V/µsec]
Max. Turn-On Time 1/2 Cycle 1/2 Cycle 1/2 Cycle 1/2 Cycle 1/2 Cycle
Max. Turn-Off Time 1/2 Cycle 1/2 Cycle 1/2 Cycle 1/2 Cycle 1/2 Cycle
Power Factor (Min.) with Max. Load 0.5 0.5 0.5 0.5 0.5
1
θJC
2
CSW2410 CSW2425 CSW2450 CSW2475 CSW2490
1.48 1.02 0.63 0.31 0.28
500 500 500 500 500
INPUT SPECIFICATIONS DC CONTROL
Control Voltage Range 3-32 Vdc
Max. Turn-On Voltage 3 Vdc
Min. Turn-Off Voltage 1.0 Vdc
Nominal Input Impedence See note 4
Typical Input Current 10mA @ 12 Vdc
GENERAL NOTES
Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
1
All parameters at 25ºC unless otherwise specified.
2
1
© 2006 CRYDOM CORP, Specifications subject to change without notice.
3 Heat sinking required, for derating curves see page 2.
4 Input Circuit Incorporates Active Current Limiter.
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com WEB SITE: http://www.crydom.com
SERIES CSW.
Rev. 012506
PAGE 1 OF 3
UK: +44 (0)1202 365070 • FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506

AVAILABLE OPTIONS
F Faston Terminals (Up to 50A Models)
Example: CSW2425F
Input Status LED.
G
Example: CSW2425G
P Internal Overvoltage Protection.
Relay Will Self Trigger Between
450-600 Vpk. Not Suitable For Capacitive Loads.
Example: CSW2425P
-10 Phase Controllable
Example: CSW2425-10
H Heat Transfer Pad (Attached)
Example: CSW2425H
Series CSW
10-90Amp • 120/240 Vac • AC OUTPUT
GENERAL SPECIFICATIONS
Dielectric Strength 50/60Hz , Input/Output/Base 4000 Vrms
Insulation Resistance (Min.) @ 500 Vdc 109Ohm
Max. Capacitance Input/Output 10 pF
Ambient Operating Temperature Range -40 to 80°C
Ambient Storage Temperature Range -40 to 125°C
MECHANICAL SPECIFICATIONS
Weight: (typical) 3.0 oz. (86.5g)
Encapsulation: Thermally Conductive Epoxy
Terminals: Screws and Saddle Clamps Furnished, Unmounted
1.10
(27.9)
.45
(11.4)
OUTPUT
1
+--
34
IN P U T
1.00
(25.4)
1.80
(45.7)
1.10
(27.9)
.45
(11.4)
2.30
(58.4)
1.70
(43.2)
6-32 TERMINAL
(2 PLACES)
Screw Torque Requirements:
6-32 Screws - 10 in./lbs.,
8-32 and 10-32 Screws - 20in./lbs.
(Screws dry without grease.)
Fastons:
Single pair (up to 25A)
Double pair* (up to 50A).
*Caution: User must connect to both pairs
MOUNTING
HOLE/SLOT
0.17 (4.3) DIA.
1.87
(47.5)
BASE PLATE
.125 (3.2)
MOUNTING
HOLE/SLOT
0.17 (4.3) DIA.
8-32 TERMINAL
(2 PLACES )
.78
(19.8)
.90
(22.9)
FASTON TERMINAL
.250 X .032 (2 PLCS.)
.87 REF.
(22.2)
Crydom Heat Sinks
offer excellent
thermal management and are perfectly matched to the load current
ratings of Crydom panel mount
relays. Request Crydom’s Heat Sink
specification sheet for all the details.
EMC Compatibility
Input: EN61000-4-2, Level 3
EN61000-4-4, Level 3
Output:
APPROVALS
UL E116949
CSA LR 81689-10
VDE
SERIES CSW.
Rev. 012506
PAGE 2 OF 3
EN61000-4-2, Level 3
Level 4
EN61000-4-4, Level 3
Level 4
EN61000-4-5, Level 4
10143 UG
ESD
Burst
ESD
ESD (with P option)
Burst
Burst (with P option)
Surge
For recommended applications and more information contact:
USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540
Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154
Email: sales@crydom.com WEB SITE: http://www.crydom.com
UK: +44 (0)1202 365070 • FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham
Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email: intsales@crydom.com.
GERMANY: +49 (0)180 3000 506
1.87
(47.5)
BASE PLATE
.125 (3.2)
OUTPUT
1
--
4
IN P U T
1.00
(25.4)
1.80
(45.7)
+
3
1.70
(43.2)
2.30
(58.4)
FASTON
TERMINAL
.187 X .032
(2 PLCS.)
(19.8)
.90
(22.9)
.78
All dimensions are in inches (millimeters)
© 2006 CRYDOM CORP, Specifications subject to change without notice.