Crydom Series CMD24, Series CMA24 Data Sheet

MODEL NUMBERS CMD2425 CMD2450 CMD2475 CMD2490 CMD24110 CMD24125
OUTPUT SPECIFICATIONS
CMA2425 CMA2450 CMA2475 CMA2490 CMA24110 CMA24125
Operating Voltage (47-63 Hz) [Vrms] 24-280 24-280 24-280 24-280 24-280 24-280 Max. Load Current[Arms] 25 50 75 90 110 125 Min. Load Current, [Arms] 0.15 0.15 0.25 0.25 0.25 0.25 Transient Overvoltage [Vpk] 600 600 600 600 600 600 Max. Surge Current, (16.6ms) [Apk] 250 625 1000 1200 1500 1750 Max. On-State Voltage Drop @ Rated Current [Vpk] 1.6 1.6 1.6 1.6 1.6 1.6
Thermal Resistance Junction to Case (R
θJC
) [°C/W] 1.02 0.63 0.31 0.28 0.25 0.22
Maximum I2 t for Fusing, (8.3 msec.) [A2sec] 260 1620 4150 6000 9340 12700 Max. Off-State Leakage Current @ Rated Voltage [mArms] 10 10 10 10 10 10 Min. Off-State dv/dt @ Max. Rated Voltage [V/µsec] 500 500 500 500 500 500 Max. Turn-On Time 1/2 Cycle (DC Control), 10.0 msec (AC Control) Max. Turn-Off Time 1/2 Cycle (DC Control), 40.0 msec(AC Control) Power Factor (Min.) with Max. Load 0.5 0.5 0.5 0.5 0.5 0.5
Zero Voltage and Random
Turn-On Switching
Panel Mount
Status Indicating LED
DC or AC Control
FastFax Document No. 170 SERIES CMD/CMA. Rev. 072600 PAGE 1 OF 6
Featuring state-of-the-art Surface Mount Technology, these SPST-NO relays deliver proven reliability in the most demanding applications. Output consists of an SCR AC switch and is available in zero-cross or random turn-on versions. Manufactured in Crydom’s ISO 9001 Certified facility for optimum product performance and reliability.
Series CMD24/CMA24
25-125Amp • 240 Vac • AC Output
GENERAL SPECIFICATIONS
Dielectric Strength 50/60Hz Input/Output/Base 4000 Vrms Insulation Resistance (Min.) @ 500 Vdc 10
9
Ohm
Max. Capacitance Input/Output 8 pF Ambient Operating Temperature Range -40 to 80°C Ambient Storage Temperature Range -40 to 125°C Status Indicating Display Green LED
MECHANICAL SPECIFICATIONS
Weight: (typical) 3.0 oz. (86.5g) Encapsulation: Thermally Conductive Epoxy Terminals: Cage Type
Maximum Wire Size- Output: AWG 6 (4.1mm) Input: AWG10 (2.6mm)
©2000 CRYDOM CORP, Specifications subject to change without notice.
GENERAL NOTES
All parameters at 25°C unless otherwise specified.Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1HEAT SINKING REQUIRED, for derating curves see page 2.Turn-on time for DC control random turn-on versions is 0.02msec.Input circuitry incorporates active current limiter.
INPUT SPECIFICATIONS
DC CONTROL AC CONTROL
Control Voltage Range 3-32 Vdc 90-140 Vrms Max. Reverse Voltage 32 Vdc Max. Turn-On Voltage 3.0 Vdc 90 Vrms Min. Turn-Off Voltage 1.0 Vdc 10 Vrms Max. Input Current 30.0mA Typical Input Current 17mA @ 5 Vdc 15mA @ 120 Vrms
Integrated Overvoltage
Protection by Automatic Self Turn-On (Suffix P)
For recommended applications and more information contact:  USA: (800) 8 CRYDOM • (800) 827-9366 •(619) 715-7200 • fax (619) 715-7280 Crydom Corp, 9525 Chesapeake Drive, San Diego, CA 92123 • Email: sales@crydom.com WEB SITE: http://www.crydom.com FASTFAX Product Information: (888) 267-9191 UK: (44)1202 857300 • fax (44)1202 857340 Crydom International Ltd., Riverside HouseBrook Road, Wimborne, Dorset, England BH21 2BH, Email: intsales@crydom.com. GERMANY: 0180 3000 506 • fax (49)(0)6874 182585 Crydom GmbH
Max. Terminal Screw Torque: Output: 8.9 in lb (1.0 Nm) Input: 5.3 in lb (0.6 Nm)
CURRENT DERATING CURVES
FastFax Document No. 170 SERIES CMD/CMA. Rev. 072600 PAGE 2 OF 6
Series CMD24/CMA24
25-125Amp • 240 Vac • AC Output
AVAILABLE OPTIONS
-10 Random Turn-On, Phase Controllable Example: CMD2450-10
E 24 Vac Input (18-36 Vac)
Example: CMA2450E
APPROVALS
UL E116949 CSA LR81689 VDE 126921 UG
©2000 CRYDOM CORP, Specifications subject to change without notice.
P Internal Overvoltage Protection
Relay Will Self Trigger Between 450-600 Vpk. Not Suitable For Capacitive Loads Example: CMD2450P
0.75
MOUNTING HOLE/SLOT
0.17 (4.3) DIA.
2.4
(63.5)
(19.1)
(11.4)
I
N
S
P
U
U
T
T
A
S
T
INPUT
SOLID STATE RELAY
OUTPUT
1.75
(44.5)
.9
(22.9)
.45
2.5
(63.5)
1.15
(29.2)
3.0
(76.2)
MECHANICAL SPECIFICATIONS
All dimensions are in inches (millimeters)
CMRD24/CMRA24 available with factory mounted heat sink and DIN rail mounting clip. Specifications available via FastFax, request document No. 171.
3.0
(76.2)
25A
30
25
20
15
10
Power Dissipation
5
0
5 10 20 2515 20 40 60 80
Load Current [Arms] Max Ambient Temp. [°C]
90A
120
80
40
Power Dissipation
0
20 40 80 060 20 40 60 80
Load Current [Arms] Max Ambient Temp. [°C]
3°C/W
2°C/W
NO HEATSINK
.5°C/W
1°C/W
1°C/W
.2°C/W
.4°C/W
100
110
120
90
100
110
120
50A
95
Base Plate Temp [°C]
60
40
20
Power Dissipation
0
10 20 40 5030 20 40 60 80
Load Current [Arms] Max Ambient Temp. [°C]
1°C/W
1.5°C/W
2°C/W
NO HEATSINK
.5°C/W
90
100
110
120
Base Plate Temp [°C]
90
60
30
Power Dissipation
0
15 30 60 7545 20 40 60 80
Load Current [Arms] Max Ambient Temp. [°C]
110A
Base Plate Temp [°C]
160
120
80
Power Dissipation
40
0
30 60 120 090 20 40 60 80
Load Current [Arms] Max Ambient Temp. [°C]
For recommended applications and more information contact: USA: (800) 8 CRYDOM • (800) 827-9366 •(619) 715-7200 • fax (619) 715-7280 Crydom Corp, 9525 Chesapeake Drive, San Diego, CA 92123 • Email: sales@crydom.com
WEB SITE: http://www.crydom.com FASTFAX Product Information: (888) 267-9191 UK: (44)1202 857300 • fax (44)1202 857340 Crydom International Ltd., Riverside HouseBrook Road, Wimborne, Dorset, England BH21 2BH, Email: intsales@crydom.com. GERMANY: 0180 3000 506 • fax (49)(0)6874 182585 Crydom GmbH
1°C/W
.4°C/W
.5°C/W
90
.2°C/W
100
110
120
Base Plate Temp [°C]
160
120
80
Power Dissipation
40
0
30 60 120 090 20 40 60 80
Load Current [Arms] Max Ambient Temp. [°C]
75A
125A
1°C/W
.5°C/W
1°C/W
.5°C/W
.4ºC/W
.2°C/W
.3°C/W
95
100
110
Base Plate Temp [°C]
120
90
100
110
Base Plate Temp [°C]
120
Loading...