Operating Voltage Range (47-63Hz) [Vrms]24-28024-28024-28024-28024-28024-28024-280
Transient Overvoltage [Vpk]600600600600600600600
Maximum Off-State Leakage Current @ Rated Voltage [mArms]10101010101010
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec]500500500500500500500
Maximum Load Current [Arms] (2)(6)1025507590110125
Minimum Load Current [mArms]4040404040150150
Maximum 1 Cycle Surge Current (50/60Hz) [Apk]115/120239/250597/625954/10001145/12001432/15001670/1750
Maximum On-State Voltage Drop @ Rated Current [Vrms] (7)1.151.151.151.151.151.151.15
Thermal Resistance Junction to Case (Rjc) [°C/W]1.030.80.450.30.270.250.22
Maximum I²t for Fusing (50/60Hz) [A² sec]66/60285/2591779/16214555/41506560/597610249/933813950/12709
Minimum Power Factor (at Maximum Load)0.50.50.50.50.50.50.5
Overvoltage Protection
Blank: Not Included
P: Included (3)
Input Status LED
Blank: Not Included
G: Included
Thermal Pad
Blank: Not Included
H: Included
H
Required for valid part number
For options only and not required for valid part number
*
Not all part number combinations are available.
Contact Crydom Technical support for information on
the availability of a specific part number.
Switching Type
Blank: Zero Voltage Turn-On
-10: Instantaneous Turn-On (4)
-10T
Trigger Circuit
T: Phototransistor
(Not needed with -B suffix,
included as standard)
-B
Output Type
-B: Normally Closed
(Not available with
-10 option)
INPUT SPECIFICATIONS
(5)
A24xxETA24xxTD24xxTDescription
Control Voltage Range 3-32 VDC90-280 Vrms18-36 Vrms
Minimum Turn-On Voltage (8)3.0 VDC
Must Turn-Off Voltage (10)1 VDC10 Vrms4 Vrms
Minimum Input Current for on-state [mA]3.422
Maximum Input Current for on-state [mA]304.94
Nominal Input Impedance [Ohms]1.5K60K9K
Maximum Turn-on Time [msec]1/2 Cycle
Maximum Turn-off Time [msec]1/2 Cycle4040
Tolerances: ±0.02 in / 0.5 mm
All dimensions are in: inches [millimeters]
(5)
Screw Termination
1.1
1.88
[47.6]
[27.9]
0.49
[12.4]
OUTPUT
1
S OLID S T A T E R ELA Y
4
INPUT
1.0
[25.4]
1.75
[44.5]
Mounting
Hole/Slot
0.19 [4.9]
DIA.
2
1.7
[43.2]
3
Quick Connect Termination (“F” Option) - Up to 25 Amp (1)
Mounting
Hole/Slot
0.19 [4.9]
DIA.
1.58
[40.2]
0.49
[12.4]
Faston Terminal(16)
0.25 x 0.032
(2 places)
1.31
[33.4]
0.89
[22.6]
2.25
[57.3]
Hex Standoff Termination (“K” Option)
1.88
[47.6]
1.1
[27.9]
0.49
[12.4]
OUTPUT
1
S OLID S T A T E R ELA Y
4
INPUT
1.0
[25.4]
1.75
[44.5]
Mounting
Hole/Slot
0.19 [4.9]
DIA.
2
1.70
[43.2]
3
(4 places)
(2 places)
Quick Connect Termination (“F” Option) - Up to 50 Amp (1)
Faston Terminal(16)
0.25 x 0.032
(4 places)
0.45
[11.4]
(2 places)
Mounting
Hole/Slot
0.19 [4.9]
DIA.
1.58
[40.2]
0.63
[16.0]
(2)
1.04
[26.4]
2.25
[57.3]
0.93
[23.6]
1.0
[25.4]
1.31
[33.4]
2
3
1.7
[43.2]
Faston Terminal(16)
0.187 x 0.020
(2 places)
1.25
[31.8]
2.25
[57.3]
1.88
[47.6]
OUTPUT
1
S OLID S T A T E R ELA Y
4
INPUT
0.49
[12.4]
1.40
[35.6]
1.75
[44.5]
2
3
Faston Terminal(16)
1.7
[43.2]
0.187 x 0.020
(2 places)
1.25
[31.8]
1.88
[47.6]
OUTPUT
1
S OLID S T A T E R ELA Y
4
INPUT
1.40
[35.6]
1.75
[44.5]
GENERAL NOTES
(1) Single pair (up to 25A) Double pair* (up to 50A). *Caution: User must connect both pairs.
(2)
Option “K” is designed and tested for use with printed circuit boards or ring/fork terminals having a thickness between 0.031 and 0.093 inches (0.79 to 2.36 mm), and loads rated up to 50
Amps. For higher load currents, the “K” standoff temperature must not exceed 105°C. For additional application assistance please contact Crydom Technical Support.
(3) Output will self trigger between 450-600Vpk, Min., not suitable for capacitive loads.
(4) Instantaneous turn-on version is not recomended for capacitive loads. Use zero turn-on only.
(5) All parameters at 25°C unless otherwise specified.
(6) Heat sinking required, see derating curves.
(7)
For 40mA minimum current, the voltage drop increases over maximum rated.
(8)
Maximum turn-on voltage for -B option is: 1VDC for DC control, 10Vrms for AC control, and 4Vrms for E control range.
(9)
For relays with option “G” minimum control voltage is 4.5VDC.
(10)
Must turn-off voltage for -B option is: 3VDC for DC control, 90Vrms for AC control, and 18Vrms for E control range.
(11) T
urn-on time for Instantaneous turn-on versions is 0.02 msec (DC Control Models).
(12)
All parameters at 50% power rating and 100% duty cycle (contact Crydom tech support for detailed report).
(13) Load can be wired to either SSR output terminal 1 or 2.
(14) Elective Input Status LED, “G” option.
(15) Elective Overvoltage Protection, “P” option.
(16)
Mechanical dimensions vary from G3 models.
2.25
[57.3]
For additional information or specific questions, contact Crydom Technical Support.
EN60950 : Meets the requirements of sections1.5: 1,7: 2.9: 2.10.5.3: 4.2: 4.5: 4.7:
Designed in accordance with the requirements of IEC 62314
IEC 61000-4-2 : Electrostatic Discharge – Level 3
IEC 61000-4-4 : Electrically Fast Transients – Level 3
IEC 61000-4-5 : Electrical Surges – Level 3
IEC 600068-2-6: Vibration 0.33mm and 0.75mm Amplitude over 10-55 Hz
IEC 600068-2-27: Shock Resistance 15g/11ms
E116949 LR81689 10143 UG (Not Applicable: -B and 4D)
ACCESORIES
Panel Mount
Datasheet
New Accessories!
Protective Cover & Hardware Kits
Protective Cover
Part number: KS101
Clear plastic cover compatible with all new
S1 designs. Safety covers provide added
protection from electric shock when
installing or checking equipment.
Hardware Kit
Part number: HK4
Bag with 2 square brass accessories and 2
screw 8-32 x 5/8 for output. Used to mount
TMR1 lug terminals.
The environmental information disclosed in this annex including the EIP Pollution logo are in compliance with People’s Republic of China
Electronic Industry Standard SJ/T11364 – 2006, Marking for Control of Pollution Caused by Electronic Information Products.