Overvoltage Protection
Blank: Not Included
P: Included
(1)
• DC control
• Direct Bond Copper substrate
• EMC Compliant to Level 3
• Direct Power Lead Frame
• Epoxy Free Design
Thermal Pad
Blank: Not Included
H: Included
2D
Required for valid part number
For options only and not required for valid part number
Not all part number combinations are available.
*
Contact Crydom Technical Support for information on
the availability of a specific part number.
OUTPUT SPECIFICATIONS
48H125KPGH-10
(2)
(3)
Input Status LED
Blank: Not Included
G: Included
(5)
Operating Voltage
48: 48-530 VAC
Termination
Blank: Screw
F: Quick Connect
(Up to 50 Amps models)
K: Hex standoffs
Switching Type
Blank: Zero Voltage Turn-On
-10: Instantaneous Turn-On
(4)
Description125A90A75A50A25A
Operating Voltage (47-63Hz) [Vrms]48-53048-53048-53048-53048-530
Transient Overvoltage [Vpk]12001200120012001200
Maximum Off-State Leakage Current @ Rated Voltage [mArms]1010101010
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/µsec] 500500500500500
Maximum Load Current [Arms]
Minimum Load Current [mArms]150150150150150
Maximum 1 Cycle Surge Current (50/60Hz) [Apk]239/250597/625954/10001145/12001670/1750
Maximum On-State Voltage Drop @ Rated Current [Vrms]1.151.151.151.151.15
Thermal Resistance Junction to Case (Rjc) [°C/W]0.80.450.30.270.22
Maximum 1/2 Cycle I² t for Fusing (50/60Hz) [A² sec]285/2591770/16294555/41506560/597613950/12709
Minimum Power Factor (at Maximum Load)
INPUT SPECIFICATIONS
(6)(3)25507590125
(1)0.50.50.50.50.5
(5)
DescriptionDC Control
Control Voltage Range4-32 VDC
Minimum Turn-On Voltage (7)4.0 VDC
Must Turn-Off Voltage1 .0 VDC
Maximum Reverse Voltage-32 VDC
Minimum Input Current
Maximum Input Current 12 mADC
Nominal Input Impedance Current Regulated
Maximum Turn-On Time [msec] (8)1/2 Cycle
Maximum Turn-Off Time [msec] 1/2 Cycle
Tolerances: ±0.02 in / 0.5 mm
All dimensions are in: inches [millimeters]
(5)
Screw Termination
1.1
1.88
[47.6]
[27.9]
0.49
[12.4]
OUTPUT
1
S OLID S T A T E R ELA Y
4
INPUT
1.0
[25.4]
1.75
[44.5]
Mounting
Hole/Slot
0.19 [4.9]
DIA.
2
1.7
[43.2]
3
Quick Connect Termination (“F” Option) - Up to 25 Amp (2)
Mounting
Hole/Slot
0.19 [4.9]
DIA.
1.58
[40.2]
0.49
[12.4]
Faston Terminal(13)
0.25 x 0.032
(2 places)
1.31
[33.4]
0.89
[22.6]
2.25
[57.3]
Hex Standoff Termination (“K” Option)
1.88
[47.6]
1.1
[27.9]
0.49
[12.4]
OUTPUT
1
S OLID S T A T E R ELA Y
4
INPUT
1.0
[25.4]
1.75
[44.5]
Mounting
Hole/Slot
0.19 [4.9]
DIA.
2
1.70
[43.2]
3
(4 places)
(2 places)
Quick Connect Termination (“F” Option) - Up to 50 Amp (2)
Faston Terminal(13)
0.25 x 0.032
(4 places)
0.45
[11.4]
(2 places)
Mounting
Hole/Slot
0.19 [4.9]
DIA.
1.58
[40.2]
0.63
[16.0]
(3)
1.04
[26.4]
2.25
[57.3]
0.93
[23.6]
1.0
[25.4]
1.31
[33.4]
2
3
1.7
[43.2]
Faston Terminal(13)
0.187 x 0.020
(2 places)
1.25
[31.8]
2.25
[57.3]
1.88
[47.6]
OUTPUT
1
S OLID S T A T E R ELA Y
4
INPUT
0.49
[12.4]
1.40
[35.6]
1.75
[44.5]
2
3
Faston Terminal(13)
1.7
[43.2]
0.187 x 0.020
(2 places)
2.25
[57.3]
1.25
[31.8]
1.88
[47.6]
OUTPUT
1
S OLID S T A T E R ELA Y
4
INPUT
1.40
[35.6]
1.75
[44.5]
GENERAL NOTES
(1)
O
utput will self trigger between 900-1200Vpk, Min. power factor 0.7 or higher, not suitable for capacitive loads.
(2) Single pair (up to 25A) Double pair* (50A model only). *Caution: User must connect to both pairs
(3) Option “K” is designed and tested for use with printed circuit boards or ring/fork terminals having a thickness between 0.031 and 0.093 inches (0.79 to 2.36 mm), and loads rated up to 50 Amps.
For higher load currents, the “K” standoff temperature must not exceed 105°C. For additional application assistance please contact Crydom Technical Support.
(4)
Instantaneous turn-on version is not recomended for capacitive loads. Use zero turn-on only.
(5)
All parameters at 25°C unless otherwise specified.
(6) Heat sinking required, see derating curves.
(7) Increase minimum voltage by 1V for operations from -20 to -40°C.
(8) Turn-on time for Instantaneous turn-on versions is 0.02 msec.
(9)
All parameters at 50% power rating and 100% duty cycle (contact Crydom tech support for detailed report).
(10)
Load can be wired to either SSR output terminal 1 or 2.
EN60950 : Meets the requirements of sections1.5: 1,7: 2.9: 2.10.5.3: 4.2: 4.5: 4.7:
Designed in accordance with the requirements of IEC 62314
IEC61000-4-2 : Electrostatic Discharge – Level 3
IEC61000-4-4 : Electrically Fast Transients – Level 3
IEC61000-4-5 : Electrical Surges – Level 3
IEC 60068-2-6 : Vibration 0.35mm and 0.75mm Amplitude over 10-55 Hz
IEC 60068-2-27 : Shock Resistance 15g/11ms
Panel Mount
Datasheet
E116949 (25, 50, 75 and 90A)
E116950 (125A)
ACCESORIES
New Accessories!
Protective Cover & Hardware Kits
Protective Cover
Part number: KS101
Clear plastic cover compatible with all new
S1 designs. Safety covers provide added
protection from electric shock when
installing or checking equipment.
Hardware Kit
Part number: HK4
Bag with 2 square brass accessories and 2
screw 8-32 x 5/8 for output. Used to mount
TMR1 lug terminals.
The environmental information disclosed in this annex including the EIP Pollution logo are in compliance with People’s Republic of China
Electronic Industry Standard SJ/T11364 – 2006, Marking for Control of Pollution Caused by Electronic Information Products.