DIN Rail Mount
Datasheet
GNR 22.5mm Series
• Current ratings of 10, 20 and 30 amps
• Output voltage ratings: 24-280 and 48-600 VAC
• Direct Bond Copper (DBC) Substrate
• LED input status indicator
• UL 508 Endurance Rating for Enhanced Reliability
• UL/CSA/TUV Approved, CE Compliant
• Built-in overvoltage protection
• DIN Rail or Panel Mount
• Zero voltage or Instantaneous turn-on output
PRODUCT SELECTION
Control Voltage 10A 30A
4-32 VDC GNR10DHZ
90-140 VAC GNR10BHZ
180-280 VAC GNR10AHZ
20A
GNR20DHZ
GNR20BHZ
GNR20AHZ
GNR30DHZ
GNR30BHZ
GNR30AHZ
AVAILABLE OPTIONS
Series
GNR A H Z10
Rated Load Current
10: 10 Amps
20: 20 Amps
30: 30 Amps
Required for valid part number
For options only and not required for valid part number
OUTPUT SPECIFICATIONS
Description
Operating Voltage (47-440Hz) [Vrms]
Transient Overvoltage [Vpk, t=1 min.]
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Static Off-State dv/dt ( V/µsec, Ta=25°C)
Maximum Load Current [Arms]
Minimum Load Current [Arms]
Maximum Surge Current (50/60 Hz, 1 cycle) [Apk]
1 Second Surge Current (Apk Ta=25°C) 50/60 Hz
Forward Voltage Drop (Vpk @ max, Ta=25°C)
Maximum I² t for Fusing (50/60Hz, 1/2 cycle ) [A² sec]
HP Ratings at 120V / FLC [Arms]
HP Ratings at 240V / FLC [Arms]
Min/Max stranded wire
Min/Max solid wire
(1)
(2)
Operating Voltage
A: 180-260 VAC
B: 90-140 VAC
D: 4-32 VDC
Terminal Layout
C: Contactor configuration
H: Relay configuration
GNR10
24-280
600
0.1
500
10
100
190/200
65
1.5
182/166
-
-
16/8 AWG
16/10 AWG
Switching Type
R: Instantaneous Turn-on
(for DC control only)
Z: Zero voltage Turn-on
GNR20
48-600
1100
0.1
500
20
100
286/300
85
1.35
410/374
1.2/9.8
1/8
16/8 AWG
16/10 AWG
GNR30
48-600
1100
0.1
500
30
100
716/750
150
1.35
2562/2334
3/4 / 13.8
2/12
16/8 AWG
16/10 AWG
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.

DIN Rail Mount
Datasheet
INPUT SPECIFICATIONS
Description
Control Voltage Range (3)
Minimum Turn-On Voltage
Must Turn-Off Voltage
Minimum Input Current (for on-state)
Maximum Input Current
Input Resistance
Maximum Turn-Off Time [msec]
Maximum Turn-On Time [msec]
Min/Max stranded/solid wire
(4)
GENERAL SPECIFICATIONS
Ambient Operating Temperature Range (3)
Ambient Storage Temperature Range
Dielectric Strength, Input to Output (50/60Hz)
Dielectric Strength, Input/Output to Ground (50/60Hz)
Maximum Capacitance, Input/Output
Housing Material
Input Status Indicator
Weight (typical)
(1)
GNRxxDx
4.0-32 VDC
Current Regulated Current Regulated Current Regulated
1/2 Cycle
1/2 Cycle
24/16 AWG
(1)
GENERAL NOTES
All parameters at 25°C unless otherwise specified.
(1)
(2) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
(3) For 180-280 VAC Control. Maximum Ambient operating temperatures is 60°C.
(4)
Turn-on time for Instantaneous version (R suffix) is 0.1 msec (for DC control only).
(5) TUV Certification according to EN 60950-1/A1:2010
4.0 VDC
1.0 VDC
6 mA
10 mA
GNRxxBx
90-140 Vrms
90 Vrms
10 Vrms
5 mArms
23 mArms
20
30
24/16 AWG
ParametersDescription
-20 to 80°C
-40 to 100 °C
4000 Vrms
2500 Vrms
8 pF
UL 94V0 (self extinguishing)
Green LED
7.94 oz (225g)
GNRxxAx
180-280 Vrms
180 Vrms
10 Vrms
6 mA
2 mA
20
30
24/16 AWG
For additional information or specific questions, contact Crydom Technical Support.
MECHANICAL SPECIFICATIONS
Tolerances: ±0.02 in / 0.5 mm
All dimensions are in: inches [millimeters]
3.47
[88.2]
(1)
4.75
[120.8]
0.18
[4.6]
Contactor Configuration
3.54
[89.8]
3.85
[97.8]
0.18
[4.5] DIA.
0.21
[5.3] DIA.
0.19
[4.8]
0.68
[17.3]
0.87
[22.5]
0.21
[5.3]
3.54
[89.8]
0.70
[17.8]
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.

DIN Rail Mount
Datasheet
3.47
[88.2]
4.75
[120.8]
Relay Configuration
3.54
[89.8]
0.18
[4.6]
3.85
[97.8]
0.18
[4.5] DIA.
0.21
[5.3] DIA.
0.19
[4.8]
0.68
[17.3]
0.87
[22.5]
0.21
[5.3]
3.54
[89.8]
0.70
[17.8]
WIRING DIAGRAM
A1
DC +
DC -
A2
AC
A1
+
AC
-
A2
DC Input Equivalent Circuit
AC Input Equivalent Circuit
L1
Load can be wired in Position A or B
T1
L1
Load can be wired in Position A or B
T1
LOAD
A
B
LOAD
LOAD
A
B
LOAD
AC
AC
AC
AC
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.

THERMAL DERATE INFORMATION
DIN Rail Mount
Datasheet
10
7.5
5
2.5
Load Current (Amps)
0
GNR10xxx
403020100 50 60 70 80
*GNR10A Series rated to 60°C max ambient
30
25
20
15
10
Load Current (Amps)
5
Load Current (Amps)
GNR30xxx
GNR20xxx
20
15
10
5
0
*GNR20A Series rated to 60°C max ambient
403020100 50 60 70 80
Ambient Temperature (ºC)Ambient Temperature (ºC)
0
0
Ambient Temperature (ºC)
*GNR30A Series rated to 60°C max ambient
AGENCY APPROVALS
Designed in accordance with the requirements of IEC 62314
E79183
LR 38595
(5)
EMC Compatibility
Designed in accordance with the requirements of IEC 62314
IEC 62314
IEC 60068-2-6 35mm/10-55Hz
IEC 60068-2-27 15G / 11ms
IEC 61000-4-2 Level 3 Electrostatic Discharge
IEC 61000-4-3 Level 3 Radiated Electromagnetic Noise
IEC 61000-4-4 Level 3 Immunity to Electrically Fast Transients
IEC 61000-4-5 Level 3 Immunity to Electrical Surges
IEC 61000-4-6 Level 3 Conducted Electromagnetic Noise
CISPR 11 Class A Conducted and Radiated Noise for Industrial Environments
40302010
50 60 70 80
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
Rev. 082316

DIN Rail Mount
Datasheet
DANGER / PELIGRO / DANGER /GEFAHR / PERICOLO / 危险
HAZARD OF
ELECTRIC
SHOCK,
EXPLOSION,
OR ARC FLASH.
• Disconnect all
power before
installing or
working with
this equipment.
• Verify all
connections
and replace all
covers before
turning on
power.
Failure to follow
these
instructions will
result in death
or serious injury.
RIESGO DE
DESCARGA
ELECTRICA O
EXPLOSION.
• Desconectar
todos los
suministros de
energia a este
equipo antes
de trabajar
con este equipo.
• Verificar todas
las
conexiones
y colocar todas
las
tapas antes
de energizer
el equipo.
El
incumplimiento
de estas
instrucciones
puede provocar
la muerte o
lesiones serias.
RISQUE DE
DESCHARGE
ELECTRIQUE
OU EXPLOSION
• Eteindre
toutes les
sources
d'énergie de
cet appareil
avant de
travailler
dessus de cet
appareil
• Vérifier tous
connections, et
remettre tous
couverts en
olace avant de
mettre sous
De non-suivi de
ces instructions
provoquera la
mort ou des
lésions sérieuses
sérieuses.
GEFAHR EINES
ELEKTRISCHE
N SCHLAGES
ODER EINER
EXPLOSION.
• Stellen Sie
jeglichen
St
rom ab, der
dieses Gerät
versorgt, bevor
Sie an dem
Gerät Arbeiten
durchführen
• Vor dem
Drehen auf
Energie alle
Anschlüsse
überprüfen
und alle
Abdeckungen
ersetzen.
Unterlassung
dieser
Anweisungen
können zum
Tode oder zu
schweren
Verletzungen
führen.
RISCHIO DI
SCOSSA
ELETTRICA O
DELL’ESPLOSIONE.
• Spenga tutta
l'alimentazione
che fornisce
questa
apparecchiatura
prima di lavorare
a questa
apparecchiatura
• Verificare tutti
i collegamenti
e sostituire
utte le coperture
t
prima
dell’accensione
L'omissione di
queste istruzioni
provocherà la
morte o
lesioni serie
存在电击、
爆炸或电弧
闪烁危险
•
在操作此设
备之前请先
关闭电源。
若不遵守这些说明,
可能会导致严重的
人身伤害甚至死亡。
WARNING / AVERTISSEMENT / WARNUNG /ADVERTENCIA / AVVERTENZA / 警告
RISK OF MATERIAL DAMAGE AND HOT
ENCLOSURE
• The product's side panels may be hot, allow
the product to cool before touching.
• Follow proper mounting instructions including
torque values.
• Do not allow liquids or foreign objects to enter
this product.
Failure to follow these instructions can result in
serious injury, or equipment damage.
RIESGO DE DAÑOS MATERIALES Y DE
SOBRECALENTAMIENTO DE LA UNIDAD
• Los paneles laterales del producto pueden
estar calientes. Esperar que el producto se
enfríe antes de tocarlo.
• Respetar las instrucciones de montaje, y en
particular los pares de apretado.
• No dejar que penetren líquidos o cuerpos
extraños en el producto.
Si no se respetan estas precauciones pueden
producirse graves lesiones, daños materiales.
RISQUE DE DOMMAGE MATERIEL ET DE
SURCHAUFFE DU BOITIER
• Les panneaux latéraux du produit peuvent être
chauds. Laisser le produit refroidir avant de le
toucher.
• Respecter les consignes de montage, et
notamment les couples de serrage.
• Ne pas laisser pénétrer de liquide ni de corps
étrangers à l'intérieur du produit.
Le non-respect de cette directive peut entraîner,
des lésions corporelles graves ou des
dommages matériels.
RISCHIO DI DANNI MATERIALI E D'INVOLUCRO
CALDO
• I pannelli laterali dell'apparecchio possono
scottare; lasciar quindi raffreddare il prodotto
prima di toccarlo.
• Seguire le istruzioni di montaggio corrette.
• Non far entrare liquidi o oggetti estranei in questo
apparecchio.
La mancata osservanza di questa precauzione può
causare gravi rischi per l'incolumità personale o
danni alle apparecchiature.
GEFAHR VON MATERIALSCHÄDEN UND
GEHÄUSEERHITZUNG
• Die Seitenwände können heiß sein. Lassen Sie
das Produkt abkühlen, bevor Sie es berühren.
• Beachten Sie die Montageanweisungen,
• Führen Sie keine Flüssigkeiten oder
Fremdkörper in das Produkt ein.
Die Nichtbeachtung dieser Anweisung kann
Körperverletzung oder Materialschäden
zur Folge haben.
材料损坏和高温外壳的危险性
• 产品的一侧面板可能很热,在其冷却前请
不要触碰。
• 遵照正确的安装说明,包括扭矩值。
• 请勿让液体及其他异物进入本产品。
如不能正确执行这些操作说明,
极有可能造成严重人体伤害或者设备的损坏。
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.

DIN Rail Mount
Datasheet
ANNEX - ENVIROMENTAL INFORMATION
The environmental information disclosed in this annex including the EIP Pollution logo are in compliance with People’s Republic of China
Electronic Industry Standard SJ/T11364 – 2006, Marking for Control of Pollution Caused by Electronic Information Products.
Part
Name
Semiconductor die
Solder
Toxic or hazardous Substance and Elements
Lead Mercury Cadmium Hexavalent Polybrominated Polybrominated
(Pb) (Hg) (Cd)
Chromium
(Cr (VI))
biphenyls
(PBB)
diphenyl ethers
(PBDE)