Crydom DRACN Series Data Sheet

DRACN Series
• 6.2mm Din-Rail Mount (35 mm) SSR Assembly
• Ratings 24VDC @ 3.5A, 48VDC @ 100mA and 240VAC @ 2A
• UL & cUL recognized @ 40°C, 100K-Cycle Endurance Test (SSR Only)
• AC output SSR is UL rated for Pilot Duty @ 240VAC
• CE & RoHS Compliant
• Yellow LED input status indicator
• 5 & 24 VDC Control
Description 3.5 A 100 mA 2 A
3-12 VDC DRA-CN024D05 DRA-CN048D05 DRA-CN240A05 15-30 VDC DRA-CN024D24 DRA-CN048D24 DRA-CN240A24
AVAILABLE OPTIONS
OUTPUT SPECIFICATIONS (1)
Description DRA-CN024DXX DRA-CN048DXX DRA-CN240AXX
Operating Voltage 0-24 VDC 0-48 VDC 24-250 VAC Maximum Load Current @ 40°C (2) 3.5 A 100 mA 2 A Minimum Load Current [mA] 1 1 70 Maximum Blocking Voltage 30 VDC 60 VDC 600 VAC Maximum Surge Current [Apk] 9 A (10 ms) 300 mA (10 ms) 120/115 A (16.6/20 ms) Maximum I²t for fusing 50/60Hz (1/2 cycle) [A² sec] N.A. N.A. 285/260 Typical On-State Voltage Drop @ Rated Current (V) 0.4 1.0 1.1 Maximum Off-State Leakage Current @ Rated Voltage [mA] 0.001 0.001 4.0 Maximum PWM (Hz) (3) 500 500 N.A. Switch Configuration N.O. N.O. N.O.
INPUT SPECIFICATIONS for CN024 (1)
Description DRA-CN024D05 DRA-CN024D24
Control Voltage Range 3-12 VDC 15-30 VDC Must Turn On Voltage 3.0 VDC 15 VDC Must Turn Off Voltage 1.0 VDC 5 VDC Nominal Input Impedance 500 Ohm 2.67K Ohm Typical Input Current 10 mA @ 5.0 VDC 9 mA @ 24 VDC Typical Turn-On Time 120 µs 350 µs Typical Turn-Off Time 100 µs 80 µs