Crydom DRA-CN-024D-24-R, DRA-CN-048D-24-R, DRA-CN-240A-24-R, DRA-CN-024D-05-R, DRA-CN-048D-05-R User manual

...
DRA-CN Assemblies
DIN Rail mountable assemblies of Solid State Relays and Sockets
The DRA-CN assemblies provide a convenient and easy way to select and use Crydom CN series Solid State Relays on a standard 35mm DIN rail. For additional information visit www.crydom.com.
FEATURES
Factory assembled ready to use assemblies for AC and DC input 24VDC @ 3.5A, 48VDC @ 100mA and 240VAC @ 2A Operating Voltage Rating
6.2mm wide socket LED input status indicator Socket clip fits all standard 35mm DIN rails
INSTALLATION INSTRUCTIONS
Please read all installation instructions before using the assemblies.
Mount the assembly on the DIN rail Wire the socket to the control side. AWG #24-14 Solid, AWG #24-14 Stranded. (0.14-2.5mm2) Wire the socket to the load side. AWG #24-14 Solid, AWG #24-14 Stranded. (0.14-2.5mm2) If multiple units are installed be sure to follow derating curves for assemblies
PART NUMBER NOMENCLATURE
A
Assembly Input Voltage 05: 05 VDC 24: 24 VDC 120: 120 V AC/DC 240: 240 V AC/DC
Series
DRA-CN 024D
Load Voltage 024D: 24 VDC, 3.5 A 048D: 48 VDC, 0.1 A 240A: 240 VAC, 2 A
A
Assembly part number is marked on the opposite side of the socket from the socket's labeling.
24 R
Switching Mode Blank: Zero Cross Turn-On
(AC Output Only)
R: Random Turn-On
WIRING DIAGRAM
For DRA-CN assembly wiring diagram see DRSCN wiring diagram shown in installation sheet (reverse side of this sheet).
DERATING CURVES
4.0
3.5
3.0
2.4
No air gap
Air gap ≥ 6.2 mm
1.8
1.2
Load Current (Amperes)
0.6
0.0 0 102030405060
0.12
0.10
0.08
0.06
0.04
0.02
Load Current (Amperes)
0.00
Load Current (Amperes)
No minimum air gap required
0102030405060
2.3
2.0
1.7
1.3
1.0
0.7
0.3
0.0
No air gap Air gap ≥ 6.2 mm
0102030405060
DRA-CN024Dxx
Ambient Temperature (°C)
DRA-CN048Dxx
B
Ambient Temperature (°C)
DRA-CN240Axx
Ambient Temperature (°C)
RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE
WARNING / AVERTISSEMENT / WARNUNG /ADVERTENCIA / AVVERTENZA / 警告
• The product's side panels may be hot, allow the product to cool before touching.
• Follow proper mounting instructions including torque values.
• Do not allow liquids or foreign objects to enter this product.
Failure to follow these instructions can result in serious injury, or equipment damage.
RIESGO DE DAÑOS MATERIALES Y DE SOBRECALENTAMIENTO DE LA UNIDAD
• Los paneles laterales del producto pueden estar calientes. Esperar que el producto se enfríe antes de tocarlo.
• Respetar las instrucciones de montaje, y en particular los pares de apretado.
• No dejar que penetren líquidos o cuerpos extraños en el producto.
Si no se respetan estas precauciones pueden producirse graves lesiones, daños materiales.
B
For 100 mA output SSRs, no airgap is required for full output current rating.
RISQUE DE DOMMAGE MATERIEL ET DE SURCHAUFFE DU BOITIER
• Les panneaux latéraux du produit peuvent être chauds. Laisser le produit refroidir avant de le toucher.
• Respecter les consignes de montage, et notamment les couples de serrage.
• Ne pas laisser pénétrer de liquide ni de corps étrangers à l'intérieur du produit.
Le non-respect de cette directive peut entraîner, des lésions corporelles graves ou des dommages matériels.
RISCHIO DI DANNI MATERIALI E D'INVOLUCRO CALDO
• I pannelli laterali dell'apparecchio possono scottare; lasciar quindi raffreddare il prodotto prima di toccarlo.
• Seguire le istruzioni di montaggio corrette.
• Non far entrare liquidi o oggetti estranei in questo apparecchio.
La mancata osservanza di questa precauzione può causare gravi rischi per l'incolumità personale o danni alle apparecchiature.
GEFAHR VON MATERIALSCHÄDEN UND GEHÄUSEERHITZUNG
• Die Seitenwände können heiß sein. Lassen Sie das Produkt abkühlen, bevor Sie es berühren.
• Beachten Sie die Montageanweisungen,
• Führen Sie keine Flüssigkeiten oder Fremdkörper in das Produkt ein.
Die Nichtbeachtung dieser Anweisung kann Körperverletzung oder Materialschäden zur Folge haben.
֌ଙ໦࣋ࢅߛ࿒ྔڦླ၃Ⴀ!
t!ׂ೗ڦᅃ֨௬ӱీ࢔ඤLjሞഄૐඐമ൩փᄲةಸă t!ፏቷኟඓڦҾጎຫ௽LjԈઔ౦ኵă t!൩ကඟᅂ༹ഄ໱ᅴ࿿৊෇Ԩׂ೗ă
සփీኟඓኴႜኄၵ֡ፕຫ௽Lj ᆶీሰׯჹዘට༹ฅ࡞ኁยԢڦ໦࣋ă
Rev: 021910
DRSCN Series
DIN rail mountable sockets
The DRSCN sockets provide a convenient and easy way to install Crydom CN series Solid State Relays on a standard 35mm DIN rail. For additional information visit www.crydom.com.
FEATURES
Sockets are fully compatible with CN series SSRs
6.2mm wide socket LED input status indicator Socket clip fits all standard 35mm DIN rails
RELAY/SOCKET COMPATIBILITY
SSR PN DR Socket PN
CN024D05 CN048D05 CN240A05
CN024D24 CN048D24 CN240A24
CN024D60 CN048D60 CN240A60
DRSCN05
DRSCN24
DRSCN120
A B
INSTALLATION INSTRUCTIONS
Please read all installation instructions before using the sockets and relays.
Match CN series SSR to appropriate DRSCN socket part number to create an Assembly Insert the CN SSR on the socket Mount the socket on the DIN rail Wire the socket to the control side. AWG #24-14 Solid, AWG #24-14 Stranded. (0.14-2.5mm2) Wire the socket to the load side. AWG #24-14 Solid, AWG #24-14 Stranded. (0.14-2.5mm2) If multiple units are installed be sure to follow derating curves for assemblies
PART NUMBER NOMENCLATURE
Series
DRSCN 120
Socket Input Voltage 05: 05 VDC 24: 24 VDC 120: 120 V AC/DC 240: 240 V AC/DC
MECHANICAL DIMENSIONS
3.15 in
[80.0 mm]
R
NC
0.24 in
[6.1 mm]
CN024D60 CN048D60 CN240A60
A
Installing a CN series solid state relay in a socket that does not have matching input/output
DRSCN240
specifications may result in damage to either the relay, socket, or both, and/or in non-operation.
B
Maximum output rating for DRSCN Series sockets is 250V / 6 Amps regardless of chosen SSR.
WIRING DIAGRAM
Control
C, D
R
Socket Part Number
DRSCN24
A2-
Maximum Socket Rating:
N = 24VDC
Input: U
Output: max. 250V/6A
Plug in Relay Options: Solid State Relay: CN024D24
CN048D24 CN240A24
SSR Ratings should not exceed socket rating
1413+A1+A2-
DC Output
1411A1+A2-
AC Output
A2- A1+
A1+
A2-
CN240A24
11
14
24 VDC 2A/240VAC
11 14
R
A1+
NC
14
Load
(13+)11
Socket Part Number
DRSCN24
A2-
Maximum Socket Rating: Input: U
N = 24VDC
Output: max. 250V/6A
Plug in Relay Options: Solid State Relay: CN024D24
CN048D24 CN240A24
SSR Ratings should not exceed socket rating
1413+A1+A2-
DC Output
1411A1+A2-
AC Output
(13+)11
A1+
3.64 in
[92.6 mm]
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Turn off power supply before working on this equipment.
Failure to follow these instructions will result in death or serious injury.
RIESGO DE ELECTROCUCIÓN, EXPLOSIÓN O ARCO ELÉCTRICO
Desconecte toda alimentación antes de realizar el servicio.
Si no se siguen estas instrucciones provocará lesiones graves o incluso la muerte.
C
For sockets intended for AC input control voltage, the AC line can be wired to either DRS socket
14
terminal A1+ or terminal A2-. Proper polarity must be observed for DC input control voltage sockets being terminal A1+ positive with respect to terminal A2-.
D
For AC loads, the AC line can be wired to either DRS socket terminal 11 or terminal 14. The AC load may also be wired on either the line or neutral side of the SSR. For DC loads, the proper polarity must be observed for the power supply, load and DRS socket with terminal 13 being positive with respect to terminal 14.
DANGER / DANGER / GEFARH / PELIGRO / PERICOLO /
RISQUE D'ELECTROCUTION, D'EXPLOSION OU D'ARC ELECTRIQUE
Coupez l'alimentation avant de travailler sur cet appareil.
Le non-respect de ces instructions provoquera la mort ou des blessures graves.
RISCHIO DI SCOSSA ELETTRICA, DI ESPLOSIONE O DI OFTALMIA DA FLASH
Scollegare l'apparecchio dalla presa di corrente prima di qualsiasi intervento.
Il mancato rispetto di queste istruzioni provocherà morte o gravi infortuni.
Rev: 021910
STROMSCHLAG-, EXPLOSIONS- ODER LICHTBOGENGEFAHR
Vor dem Arbeiten an dem Gerät dessen Stromversorgung abschalten
Die Nichtbeachtung dieser Anweisungen führt zu Tod oder schwerer Körperverletzung.
.