Crydom DRA1 CX Series Data Sheet

DRA1 CX Series
• 10mm Single Channel DIN Rail Mount SSR Assembly
• AC Ratings up to 380 VAC and 5 Amps
• 3-15 and 15-32VDC control
• Cage style screw terminals for easy connection
• Fits standard 35mm DIN rail
• Includes LED Status indicator
Description 5 A 5 A 5 A 5 A 5 A
3-15 VDC Control DRA1-CX240D5 DRA1-CX240D5-B (2) DRA1-CX240D5R 4-15 VDC Control DRA1-CX380D5 DRA1-CX380D5R 15-32 VDC Control DRA1-CXE240D5 DRA1-CXE240D5R DRA1-CXE380D5
OUTPUT SPECIFICATIONS (1)
Description CX(E)240x5 CX(E)380x5
Operating Voltage [VAC] 12-280 48-380** Transient Overvoltage [Vpk] 600 1200 Maximum Load Current [Arms] (3) 5 5 Minimum Load Current [Arms] 0.06 0.06 Maximum Off-State Leakage Current @ Rated Voltage [mArms] 0.1 0.1 Minimum off-state dv/dt @ maximum rated voltage [V/µsec] (4) 500 500 Maximum 1 Cycle Surge Current (50/60 Hz) [Apk] 239/250 239/250 Maximum I²t for fusing (50/60 Hz, 1/2 cycle) [A² sec] 285/260 285/260 Maximum On-State Voltage Drop @ Rated Current [Vpk] 1.4 1.4
INPUT SPECIFICATIONS (1)
Description DRA1-CX DRA1-CX240D5-B (2) DRA1-CX380D5 DRA1-CXE
Control Voltage Range 3-15 VDC 4-28 VDC 4-15 VDC 15-32 VDC Must Turn On Voltage 3.0 VDC 1.0 VDC 4.0 VDC 15.0 VDC Must Turn Off Voltage 1 0 VDC 4 .0 VDC 1 .0 VDC 1 .0 VDC Typycal Input Current 15 mAdc 10 mAdc 15 mAdc 15 mAdc Nominal Input Impedance 300 Ohm 1360 Ohm 240 Ohm 1500 Ohm Maximum Turn-On Time [msec] (5) 1/2 Cycle 1/2 Cycle 1/2 Cycle 1/2 Cycle Maximum Turn-Off Time [µsec] 1/2 Cycle 1/2 Cycle 1/2 Cycle 1/2 Cycle
GENERAL SPECIFICATIONS
Description Parameters
Dielectric Strength, Input/Output/Base (50/60Hz) 4000 VRMS Minimum Insulation Resistance (@ 500 VDC) Maximum Capacitance, Input/Output 10 pF Ambient Operating Temperature Range -30 to 80°C Ambient Storage Temperature Range -30 to 125 °C Weight (typical) 0.063 lb (28.6g) Encapsulation Themally Conductive Epoxy
GENERAL NOTES
1) All parameters at 25°C unless otherwise specified.
2) The output is normally closed and does not have a LED status indicator
3) See Derating chart on page 3.
4) Off-State dv/dt test method per EIA/NARM standard RS-443, paragraph 13.11.1
5) Turn-on time for DC control random turn-on versions is 0.1 msec
**
NOTE: Voltages in excess of 380V will damage output terminals.
109 Ohms