AC/DC Output Single Channel &
AC Output Dual Channel
Crydoms SeriesOne DR Solid State Relays were developed to offer the advantages of Crydom's thermal
management technology in a compact 11 & 18 mm wide IP20 housing with unique integrated heat sink.
The SeriesOne DR provides a quick and easy installation onto any standard 35 mm DIN rail profile
paired with high output power ratings.
FEATURES
Single channel 6 & 12 Amps output power rating
Two independent 6 Amp channels in dual channel versions
Single channel 60 & 100 VDC, 24 to 600 VAC operating voltage ratings
Dual channel 24 to 600 VAC operating voltage ratings
4-32 VDC, 24, 120 & 230 VAC control input options available for single channel versions
4-32 VDC control input for dual channel versions
AC Output versions with Zero Voltage Turn-On for resistive loads and Random Turn-On for inductive loads
INSTALLATION INSTRUCTIONS
Please read all installation instructions before using SeriesOne DR SSRs.
Install the relay on the DIN rail (as shown in drawing)
Wire the relay to the input side. 22 AWG minimum,
16 AWG maximum
Wire the relay to the output side. 22 AWG minimum,
14 AWG x 2 or 12 AWG x 1 (standed/solid) maximum
Maximum recommended terminal screw torque
input 4.4 in/lbs (0.5 Nm) & output 7.0 in/lbs (0.8 Nm)
If multiple units are installed be sure to follow
derating curves (reverse side of this sheet)
To remove from
To install on DIN rail
DIN rail
PART NUMBER NOMENCLATURE
Single Channel
Series
(A)
Max Output Voltage
06:
1 to 60 VDC
1 to 100 VDC
10:
48:
48 to 600 VAC
Control Voltage
D:
A:
B:
E:
4 to 32 VDC
208 to 265 VAC
90 to 140 VAC
18 to 36 VAC
Dual Channel
Max Output Voltage
24:
24 to 280 VAC
48:
Series
Required for valid part number
For options only and not required
for valid part number
(A)
Not all combinations of ratings are available.
48 to 600 VAC
Control Voltage
D:
4 to 32 VDC
Output Current
06:24:
12:
1224 DDR
Output Current
06:
0624 DDRD
6 Amps24 to 280 VAC
12 Amps
AC
Output
Only
6 Amps
R
Option
Zero Voltage Turn-On
Blank:
Random Turn-On
R:
(AC Output Only)
R
Option
Blank: Zero Voltage Turn-On
R: Random Turn-On
(AC Output Only)
Rev: 072310
WIRING DIAGRAMS
(B)
For DRxxx06 or DRxxx12 versions
DC/AC CONTROL
VOLTAGE
(D, E)
INPUT
STATUS
+3/A1
+3/A1
4/A2
4/A2
1/L1
2/T1
DC CONTROL
DC/AC SUPPLY
(B)
No grounding wire required. DC inductive loads must be diode suppressed.
(C)
4 Pin connector for dual channel ouput only. Matting connector: MOLEX 050579404 or equivalent.
(D)
4 Terminal screws Pozidriv #1, 3/16 in [4.8 mm].
(E)
Minimum wire strip lenght 0.20 in [5.1 mm], maximum 0.28 in [7.1 mm].
Load
(D, E)
(C)
AC SUPPLY
+A
-A
+B
-B
AC SUPPLY
WARNING
RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE
• The product's side panels may be hot, allow the product to cool before touching.
• Follow proper mounting instructions including torque values.
• Do not allow liquids or foreign objects to enter this product.
Failure to follow these instructions can result in serious injury, or equipment damage.
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
•
Turn off power supply before working on this equipment.
Failure to follow these instructions will result in death or serious injury.
DRDxxD06 versions
For
Load A
2/A2
2/A2
INPUT
STATUS
INPUT
STATUS
4/B2
Load B
DANGER
DERATING CURVES
DRxxx06
6.0
5.0
1/A1
1/A1
3/B1
(Amps )
t
4.0
3.0
2.0
1.0
Load Curren
0.0
0102030405060
70 80
Ambient Temperature (°C)
DRxxx12 & DRDxxD06
12.0
10.0
8.0
rent
r
6.0
Cu
4.0
Load
2.0
0.0
(Combined for Dual) [Amps]
0102030405060
Ambient Temperature [°C]
Installed single unit, distance to adjacent components ≥ 11 mm
for DRxxx06 and ≥ 18 mm for DRxxx12 & DRDxxD06
Multiple units, no minimum spacing between components
70 80
Rev: 072310