Crydom CTR User Manual

Installation Sheet
DIN Rail Mount
CTR Series
DIN Rail Mountable SSRs Three-Phase
Crydom CTR Series Solid State Relays were developed to offer the advantages of semiconductor switching technology in a compact, self contained package. Quick and easy installation is coupled with low drive power requirements and efficient, reliable power SCR output.
FEATURES
DIN rail or panel mount 90 mm (width) package Box Clamp terminals Bracket fits all standard 35 mm DIN rail profiles LED input status indicator
PART NUMBER NOMENCLATURE
Control Voltage B: 90-140 VAC
Series
C: 180-280 VAC D: 4-32 VDC
CTR 25 -1060D
Operational Voltage
Required for valid part number For options only and not required for valid part number
(A)
The air gap is the clearance distance adjacent to either side of the relay or assembly measured to the next closer relay or assembly.
(B)
CTRCxxxx is rated at 60ºC max. ambient.
(C)
100% Duty Cycle.
60: 48-600 VAC
Operational Current 25: 25 Amps / Phase
Switching Mode Blank: Zero Voltage Turn-On
-10: Random Turn-On
(DC Control only)
MOUNTING INSTRUCTIONS
Please read all installation instructions before using CTR Series SSRs.
Choose one of the two mounting options and follow the instructions below.
Mounting on DIN Rail
Locate rail and align with non moveable end of CTR DIN clip.
Using reasonable force, push CTR in the direction of the arrow shown in fig.1.
For removal pull release tag in direction of arrow using blade of screwdriver and pull it away from DIN rail.
Mounting on Panel
Locate the panel section on which the CTR SSR will be mounted on.
DIN clip includes tabs for this type of mounting. Tab holes have a diameter of 4.5 mm. You will need two screws (not included) no larger than that to mount the SSR onto panel.
Align SSR tabs with panel surface and screw both top and bottom sides. Recommended torque is 12 in-lbs (1.36 Nm).
To install
on DIN rail
To remove from DIN rail
fig.1 Mounting on DIN Rail
Mounting air gap
To achieve maximum ratings if multiple units are installed, there must be a minimum air gap of 0.8 in (20 mm) between the devices (horizontally) and of 3.15 in (80 mm) measured between DIN clip tabs (vertically).
Earth Bonding (Grounding)
The CTR heat sink is equiped with an earth bonding screw as is required for Class 1 Protection, in accordance with EN 60950 (VDE 0804). Recommended torque is 20 in-lbs (2.2 Nm).
(A)
Rev: 062411
Do not forget to visit us at: www.crydom.com
Copyright © 2015 Custom Sensors & Technologies. Specifications subject to change without notice.
DIN Rail Mount
Installation Sheet
DERATING CURVES
The following deating curves must be observed before installation.
30
25
20
15
10
Load Current (Amps)
5
0
(B, C)
CTRx60xx
20 40 60
Ambient Temperature (ºC)
80
WIRING DIAGRAM
Wire Size
Maximum wire size of AWG #16 (1.3 mm2) on input and AWG #8 (8.4 mm
Connections
Ensure that wires ends are stripped to a minimum length of 0.4 in (10 mm).
Recommended Screw Torque Range
4.4 in-lbs (0.5 Nm) on input and 12 in-lbs (1.3 Nm) on output.
2
) output terminals.
Rev: 062411