Crydom CKR User Manual

Installation Sheet
CKR Series
High Power Ready-to-Use DIN Rail Mounted SSRs
Crydom CKR Series Solid State Relays were developed to offer the advantages of semiconductor switching technology in a standard 22.5 mm industrial package. Quick and easy installation is coupled with low drive power requirements and efficient, reliable power SCR output. This compact new design offers up to 30 Arms in ambient temperatures of 25ºC.
FEATURES
Mounting clip incorporates tabs for screw mounting to panel Box Clamp terminals Bracket fits all standard 35 mm DIN rail profiles LED input status indicator
PART NUMBER NOMENCLATURE
Control Voltage D: 4-32 VDC B: 90-140 VAC A: 180-280 VAC
Series
AxxxxE: 18-36 VAC
CKR 10 -10E P24D
Operating Voltage 24: 24-280 VAC 48: 48-530 VAC
Required for valid part number
For options only and not required for valid part number
60: 48-660 VAC
Rated Load Current 10: 10 Amps 20: 20 Amps 30: 30 Amps
Overvoltage Protection Blank: Not Included P: Included
Switching Type Blank: Zero Voltage Turn-On
-10: Random Turn-On
DIN Rail Mount
MOUNTING INSTRUCTIONS
Please read all installation instructions before using CKR Series SSRs.
Choose one of the two mounting options and follow the instructions below.
Mounting on DIN Rail
Locate rail and align with non moveable end of CKR DIN clip.
Using reasonable force, push CKR in the direction of the arrow shown in fig.1.
For removal pull release tag in direction of arrow using blade of screwdriver and pull it away from DIN rail.
Mounting on Panel
Locate the panel section on which the CKR SSR will be mounted on.
DIN clip includes tabs for this type of mounting. Tab holes have a diameter of 4.5 mm. You will need two screws (not included) no larger than that to mount the SSR onto panel.
Align SSR tabs with panel surface and screw both top and bottom sides. Recommended torque is 12 in-lbs (1.36 Nm).
IMPORTANT CONSIDERATIONS
Mounting Air Gap
To achieve maximum ratings, there must be a minimum spacing of 0.8 in (20 mm) between the devices (horizontally) and of 3.15 in (80 mm) measured between DIN clip tabs (vertically).
Earth Bonding (Grounding)
The CKR heat sink is equiped with an earth bonding screw as is required for Class 1 Protection, in accordance with EN 60950 (VDE 0804). Recommended torque is 20 in-lbs (2.2 Nm).
(A)
To install
on DIN Rail
!
perature
gh Tem Hi
Caution
80
60
40
20
Current Rating 20A @ 25°C
30
20
10
To remove
from DIN Rail
fig.1 Mounting on DIN Rail
perature
!
gh Tem Hi
Caution
80
60
40
20
Current Rating 20A @ 25°C
30
10
20
Rev: 112613
Do not forget to visit us at: www.crydom.com
Copyright © 2014 Custom Sensors & Technologies. Specifications subject to change without notice.
DIN Rail Mount
Installation Sheet
DERATING CURVES
The following deating curves must be observed before installation.
30
25
20
15
10
5
Output Current (Arms)
0
(B)
20 40 60
Ambient Temperature (ºC)
80
CKRxxx30xxxx CKRxxx20xxxx CKRxxx10xxxx
(+/ ) ( / )
+3/A1 4/A2
SOLID
STATE
CONTACTOR
1/L1 2/T1
Load
WIRING DIAGRAM
Wire Size
Maximum wire size of AWG #10 (5.3 mm
Connections
Ensure that wires ends are stripped to a minimum length of 0.4 in (10 mm).
Recommended Screw Torque Range
5-6 in-lbs (0.6-0.7 Nm) on input and 10-15 in-lbs (1.1-1.7 Nm) on output terminations.
The air gap is the clearance distance adjacent to either side of the relay or assembly measured to
(A)
the next closer relay or assembly. 100% Duty Cycle.
(B)
2
) for input and output terminals.
Rev: 112613