Cruisair Zephyr, Cuddy dc Installation And Operation Manual

Zephyr (ZF) & Cuddy dc
INSTALLATION • OPERATION
Zephyr & Cuddy dc Self-Contained Cooling Only A/C Kits Revised: 5-11-07 L-2028
Table of Contents
Zephyr and Cuddy dc Units • Installation
Warning .............................................................................. 4
Notice ................................................................................. 4
Introduction ......................................................................... 4
Cuddy dc ............................................................................ 4
Unpacking and Inspection .................................................. 4
Safety Considerations ........................................................ 4
Placement Of System ......................................................... 5
Spacing Allowances & Unit Dimensions ............................. 5
How It Works ...................................................................... 6
Mounting Brackets .............................................................. 6
Condensate Drains ............................................................. 6
Blower Assembly ................................................................ 6
Supply & Return Air Grills
and Transition Boxes ........................................................ 6
Ducting ............................................................................... 7
Manual Control Panel Installation ....................................... 7
Electrical Connections, Grounding & Bonding for AC
Powered Zephyr ............................................................... 7
Electrical Connections, Grounding & Bonding for DC
Powered Cuddy dc .......................................................... 7
Electrical System and Wiring for DC Powered Cuddy dc .... 8
Notice and ABYC Standards: ............................................. 8
Seawater Pump and Plumbing ........................................... 8
Installation Checklist
(review prior to and after installation) ............................... 9
Zephyr and Cuddy dc Units • Operation
Operation .......................................................................... 10
Troubleshooting Guidelines .............................................. 10
Zephyr and Cuddy dc Units • Maintenance
Seawater Strainer ............................................................. 12
Condenser Coil Cleaning ................................................. 12
Return Air Filters............................................................... 12
Winterization ..................................................................... 12
Zephyr and Cuddy dc Kits • Parts List 12
Owner’s Limited Warranty 15
Limited Warranty Periods 17
Descriptions of Figures 18
Cruisair Worldwide Service Dealer Locator 27
L-2028
English
Zephyr and Cuddy dc Units • Installation
Warning
This manual contains essential safety information concerning the safe and proper installation and operation of Zephyr and Cuddy dc self-contained direct expansion air conditioners. It is very important that you read and understand the contents of this manual thoroughly before attempting to install any Cruisair equipment. If there are any statements in this manual that you do not understand, contact the Dometic Environmen­tal Applications Department (Dometic) for assistance. Phone (804) 746-1313, Fax (804) 746-7248 (8:00am - 5:00pm United States Eastern Time).
Notice
As of July 1, 1992, United States federal law prohibits the intentional release of refrigerant gases into the environment, including the R-22 refrigerant mostly used in Cruisair air conditioning systems. Special care must be taken when installing, charging and servicing Cruisair equipment to prevent any loss of refrigerant.
Cruisair does to purge air and moisture from the system at installation. This formerly used practice of purging is in violation of United States federal law.
not recommend the practice of using refrigerant
Introduction
You have just purchased the first complete built-in marine air conditioning system designed for self installation. We are confident you will find the added comforts experienced in your boat to be well worth the money spent. If, upon opening your new system, you discover any parts are missing, contact your dealer immediately.
Before attempting to install your new Zephyr (AC powered) or Cuddy dc (DC powered) air conditioning system, you must read this installation manual completely. Failure to perform certain tasks in the proper sequence could result in an inoperative system as well as a voided warranty.
Cuddy dc
The new Cuddy dc marine air conditioner is very similar to the standard Zephyr but is unique in one way–it is designed to be run on 12VDC battery power. Most of the installation, operation and maintenance information in this manual applies to both types of air conditioners, the AC voltage Zephyr and the DC voltage Cuddy dc. Installation of either unit is nearly identical with the exception of the power supply and how that power is connected to the unit, control and pump. With that in mind while reading this manual, please read the Installation, Operation, and Maintenance sections titled “Zephyr and Cuddy dc Units”, and especially the sections subtitled “for DC
Powered Cuddy dc”. Cuddy dc owners may skip the sections that are subtitled “for AC Powered Zephyr.”
Cuddy dc kits contain the air conditioning unit and these three components: a Dedicated Power Module (DPM), a 2­knob mechanical control, and the water pump. Each of these components is connected to the a/c unit with a polarized plug. These plugs are configured unique to each component. The DPM is sized to run the Cuddy dc system only and should not be used for any other appliance(s). See Figure 14 in the back of this manual for DPM specifications
! WARNING The DPM is not ignition protected and must not be installed in the engine compartment or in any area with flammable or compressed gasses or liquids (see the Safety Considerations section of this manual for more information).
Dometic recommends using a separate battery bank dedi­cated to run the Cuddy dc. For specific instructions, please see the two sections in this manual titled “Electrical System and Wiring for DC Powered Cuddy dc” and “Electrical Con­nections, Grounding & Bonding for DC Powered Cuddy dc.”
! WARNING The compressor and fan on the Cuddy dc air conditioning unit are AC voltage components, running on 115VAC supplied by the DPM. The pump and 2-knob mechanical control also run on 115VAC supplied by the DPM. Once the DPM is connected to the dedicated 12VDC battery bank, then all necessary power distribution to each of the components is handled through the polarized plugs—truly a “plug & play” system.
Unpacking and Inspection
When the equipment is received, all items should be carefully checked against the packing list to ensure all cartons have been received. Move units in the normal “up” orientation as indicated by the arrows on each carton. Examine cartons for shipping damage, removing the units from the cartons if necessary. If the unit is damaged, the carrier should make the proper notation on the delivery receipt acknowledging the damage.
CAUTION: When unpacking and installing the control, care must be taken not to kink or break the copper cap tube when uncoiling the sensing bulb. The cap tube is hollow and kinking or sharp bends will inhibit system operation.
Safety Considerations
Never install your air conditioner in the bilge or engine room areas. Insure that the selected location is sealed from direct access to bilge and/or engine room vapors. Do not terminate condensate drain line within three (3) feet of any outlet of engine or generator exhaust systems, nor in a compartment
L-2028 Installation
English
housing an engine or generator, nor in a bilge, unless the drain is connected properly to a sealed condensate or shower sump pump. Failure to comply may allow bilge or engine room vapors to mix with the air conditioners return air and contami­nate living areas which may result in injury or death.
Consideration should be given to installing a trap in the condensate drain line(s) so that normal discharge of conden­sate can fill the trap and prevent the ingress of carbon monoxide (CO) or other potentially harmful vapors.
Installation and servicing of this system can be hazardous due to system pressure and electrical components. When working on this equipment, always observe precautions described in the literature, tags and labels attached to the unit. Follow all safety codes. Wear safety glasses and work gloves and place a fire extinguisher close to the work area. The following is a summary of the labels on the unit:
! DANGER Electrical shock hazard. Disconnect voltage at main panel or power source before opening any cover. Failure to comply may result in injury or death.
! WARNING This component does not meet Federal require­ments for ignition protection. Do not install in spaces contain­ing gasoline engines, tanks, LPG/CPG cylinders, regulators, valves or fuel line fittings. Failure to comply may result in injury or death.
NOTICE This component is charged with hydrochlorofluoro­carbon (HCFC) refrigerant R22. Effective July 1, 1992 it shall be unlawful for any person to knowingly vent or otherwise knowingly release any class 1 (CFC) or class 2 (HCFC) substance as a refrigerant in a manner which permits such substance to enter the atmosphere per the clean air act of
1990. Public law 101-549 Title IV Section 608-c. Failure to comply may result in severe penalties, including fines and imprisonment. Note: The Cuddy dc unit is charged with R417A.
! WARNING To minimize the hazard of electrical shock and personal injury, this component must be effectively grounded. Refer to the installation guidelines for further information.
! WARNING The compressor and fan on the Cuddy dc air conditioning unit are AC voltage components, running on 115VAC supplied by the DPM. The pump and 2-knob mechanical control also run on 115VAC supplied by the DPM. Disconnect voltage at main panel or power source before opening any cover. Failure to comply may result in injury or death.
Placement Of System
Selecting a good location for your air conditioner is the most important part of your preparations. Be sure to consider the size of the area you are cooling, the air distribution needs, and the size of the unit you have chosen. Keeping in mind that cool air has a tendency to fall, it is highly recommended that
L-2028 Installation
you locate the supply air grill as high as possible in the cabin. Figure 1a at the back of this manual shows the single duct application and Figure 1b shows a dual duct application.
The air conditioning unit should be installed as low as possible, but never in the bilge or engine room areas.
Insure that the selected location is sealed from direct access to bilge and/or engine room vapors. Installing the
unit as low as possible (such as under a V-berth, dinette seat or bottom of a locker) and ducting the supply air as high as possible, creates an ideal air flow condition. This type of installation will prevent short or premature cycling.
The unit should be positioned on a firm, level, horizontal surface and the condensate drain line should run downward from the unit to a suitable drain location. Plan all connections which must be made including ducting, condensate drain, seawater in and out, electrical power connections, location of control, and seawater pump placement, to assure easy access for routing and servicing.
Tools Required for Installation
• Screw drivers
• Pliers
• Pipe wrench
• Wire cutters/crimpers
• Drill & 7/8" bit
• Jig saw
• Duct tape
• Electrical tape
• Teflon tape
• Bedding compound to seal thru hull fittings
• Hardware to secure unit, pump, strainer, grills & control panel
Spacing Allowances & Unit Dimensions
The following space allowances should be considered when mounting the unit:
1. Allow a minimum of 6" (152mm) around the perimeter of
the unit in the area of the seawater and condensate drain piping.
2. Allow a minimum of 3" (76mm) of air space in front of the
evaporator coil for the return air intake if it is adjacent to a bulkhead.
3. Allow a minimum of 3" (76mm) of air space for the electric
blower motor ventilation. For Cuddy dc systems, allow at least 1" (25mm) above DPM for adequate ventilation.
4. For flexible ducting connection, allow 2" (51mm) for the
duct ring, 1" (25mm) for the duct bend radius and add diameter of the ducting to get the total clearance distance (2" [51mm] + 1" [25mm] + duct diameter) as measured from the blower outlet (this also applies to clearance needed behind the supply air grill). Note that the blower and duct ring can be positioned either vertically or horizontally. See Figure 2 at the back of this manual.
English
These space allowances are suggested minimums. Enough space should be allocated for installation and serviceability. See Figure 2 at the back of this manual for space allowances and unit dimensions.
How It Works
The air conditioning unit consists of four main components and a refrigerant gas circulating through the system. The BLOWER draws warm cabin air across the fins on the EVAPORATOR where the heat from the air is transferred to the refrigerant in the evaporator coil. As the refrigerant evaporates from a liquid into a gas it absorbs the heat from the cabin air. The COMPRESSOR then compresses the refrigerant gas and pumps it through the outer tube in the CONDENSER COIL. The seawater pump circulates cool seawater through the inner tube in the condenser coil, this cools the refrigerant in the outer tube and condenses it from a gas into a liquid. The heat from the refrigerant is exchanged to the seawater and discharged overboard. The liquid refrigerant is then passed through the EVAPORATOR COIL and the cycle repeats. Removing heat from the cabin air lowers its temperature. The cooled air is blown through the ducting and out the supply air grill(s). See Figure 3 at the back of this manual for component identification.
Mounting Brackets
The air conditioning unit is supplied with a base pan that also serves as a condensate pan. Mounting clip brackets and screws (4) are provided to secure the base pan onto a flat, horizontal surface. See Figure 4 at the back of this manual.
6. Install the condensate drain hose downhill from the unit
and aft to a sump - hose should have a trap.
7. Two drain fittings may be used and the hoses teed
together provided there is a minimum 2" (51mm) drop from the bottom of the base pan to the tee connection.
Note:
Do not terminate condensate drain line within 3 feet (91cm) of any outlet of engine or generator exhaust systems, nor in a compartment housing an engine or generator, nor in a bilge, unless the drain is connected properly to a sealed conden­sate or shower sump pump.
Blower Assembly
Horizontal or vertical supply air discharge may be acheived by rotating the blower. Its design allows the blower to be rotated by removing the screws holding the blower plate to the evaporator coil shroud. Rotate the blower to allow the most direct flow of air to the supply air grill. To rotate the 10-16K
blowers, remove the two plastic plugs for access to the mounting screws.
Supply & Return Air Grills and Transition Boxes
As previously indicated, install the supply air grille(s) as high as possible and the return air grille as low and close to the air conditioning unit as possible to insure direct uninterrupted airflow to the evaporator. In no instance should the supply are grille discharge be directed towards the return air grille, as this will cause the system to short cycle.
Condensate Drains
The condensate drain pan is 1¾" high with two drain loca­tions. During conditions of high humidity, condensate may be produced at a rate of approximately ½ gallon (1.9 liters) per hour. With this in mind, it is important to route condensate drains downward to a sump pump. It is not recommended to route condensate drains to the bilge. After the condensate drain installation is complete, test the installation by pouring a quart of water into the pan and checking for good flow.
For installation of the condensate drain (refer to Figure 5 at the back of this manual):
1. Remove the aft facing watertight plug from the base pan of the air conditioning unit.
2. Slip the solid washer and the liquid-seal washer onto the PVC fitting in that order.
3. Connect the fitting through the exposed hole in the base pan with the locking nut.
4. Securely tighten with two (2) wrenches to provide a proper seal.
5. Attach a 5/8" (16mm) I.D. reinforced hose to the hose barb and secure with stainless steel hose clamps.
The cut out for the 3" (76mm) round supply air grille for the
3.5K unit is 3" (76mm) in diameter and the flange is 3 (99mm) in diameter. The cut out for the 4" (102mm) round supply air grille for the 5K unit is 4" (102mm) in diameter and the flange is 5½" (140mm) in diameter. The cut out for the rectangular supply air transition box used with the 10 & 12K units is 11 it is 13 (152mm) or 7" (178mm) oblong duct ring to the transition box by first placing the ring on the box and tracing the hole. Cut the oblong hole out of the box. Secure the ring to the box with rivets (trim ¼" [6mm] from ring flanges if necessary). Com­pletely seal the joint between ring and box with silicone. A minimum clearance of 3" (76mm) plus the duct diameter size is required behind the grille for attaching the ducting (see earlier section, “
The cut outs for the return air grilles are as follows: 7-5/8" (194mm) square for the 3.5K & 5K units, 11-5/8" (295mm) square for the 10K & 12K units, and 13-5/8" (346mm) x 11-5/ 8" (295mm) (width x height) for the 16K unit. The return air grille should have a minimum of 4" (107mm) of clearance in front of it, free from any furniture or other obstructions. The return air filter, mounted to the front of the evaporator,
5
/8" (295mm) by 55/8" (148 mm) and for the 16K unit
5
/8" (346mm) by 55/8" (148 mm). Connect the 6"
Spacing Allowance and Unit Dimensions
7
/8"
”).
L-2028 Installation
English
removes debris from the air prior to the air being drawn across the evaporator coil and fins. Dust and lint can clog and reduce airflow across the evaporator coil resulting in poor performance. See the “ instructions.
Maintenance
” section for filter cleaning
Ducting
Good airflow is critical for the performance of the entire system. It is highly dependent on the quality of the ducting installation. The ducting should be run as straight, smooth and taut as possible minimizing the number of 90 degree bends (two tight 90 degree bends can reduce airflow by 25 percent). The following is a summary of proper ducting connections:
1. Pull back the fiberglass insulation exposing the inner mylar duct hose.
2. Slide the mylar duct hose around the mount ring until it bottoms out.
3. Screw 3 or 4 stainless steel sheet metal screws through the duct hose into the transition ring. Make sure to catch the wire in the duct hose with the heads of the screws. Do not use band clamps, as the hose will slide off.
4. Wrap duct tape around the ducting and ring joint to prevent any air leaks.
5. Pull the insulation back up over the mylar to the ring and tape this joint.
6. Remove excess ducting and use the same connection method at the supply air grill.
Manual Control Panel Installation
The manual control panel should be located within cap tube length of the air conditioning unit. The dimensions for the 2-knob panel is 3¼" (83mm) x 5½" (140mm). The cut out size for the 2-knob panel is 2½" (64mm) wide by 4¾" (121mm) tall. The 3-knob panel is configured either vertically or horizontally. Dimensions for the 3-knob is 2 The cut out size for the 3-knob panel is 2" (51mm) by 6¾"(171mm). (Refer to Figures 6 and 7 at the back of this manual.) Once the cut out is made, carefully uncoil the copper cap tube with return air sensor (copper bulb) and route the control wires and cap tube through the hole and back to the unit
using caution not to kink the cap tube
return air sensor into the clips provided on the evaporator coil. If the return air sensor cannot be mounted on the evaporator coil, mount it behind the return air grill. The sensor must be mounted in the return air stream. Make electrical connections according to the wiring diagrams provided. (See wiring diagrams, Figures 8, 9, 10 and 11 at the back of this manual.)
15
/16" (75mm) x 715/16" (202mm).
. Mount the
circuits. Wiring diagrams are provided in the electrical box and in this manual. The correct size circuit breaker should be used to protect the system as specified on the air conditioning unit’s data plate label. A minimum of 12 AWG boat cable should be used to supply power to the air conditioning unit and to the seawater pump (see next paragraph). All connections to the terminal strip shall be made with ring terminals supplied with the Zephyr kit. Turn off AC (alternating current) power
supply circuit breaker before opening electrical box and accessing the terminal strip.
Each air conditioning unit installed requires its own dedicated circuit breaker. If there is only one air conditioning unit installed, the seawater pump does not require a circuit breaker; the wiring from the seawater pump is connected to the terminal strip on the unit. (See wiring diagrams, Figures 8, 9 and 10 at the back of this manual.) A minimum of 12 AWG boat cable should be used to extend the wires on the pump, if necessary, using the butt slices included with the kit. If two or more air conditioning units use the same seawater pump, the pump wires will be connected to a pump relay panel (PRP) which in turn has its own dedicated circuit breaker (see the wiring diagram furnished with the PRP). Any electrical connections in the bilge below the waterline should use heat shrink type butt splices.
The air conditioning unit must be connected to the boat’s bonding system to prevent corrosion due to stray electrical current. All pumps, metallic valves and fittings in the seawater circuit that are isolated from the air conditioning unit by PVC or rubber hoses must be individually bonded to the boat’s bonding system also. This will help eliminate any possibility of corrosion due to stray current.
Note: Failure to properly ground and bond the system will void the warranty!
Electrical Connections, Grounding & Bonding for DC Powered Cuddy dc
All Cuddy dc units are connected by polarized plugs to the Dedicated Power Module DPM, pump, and control (available separately or in kit). These plugs are configured unique to each component. Wiring diagrams and schematics are provided in this manual (see Figure 11 at the back of this manual). A 60 amp circuit breaker or fuse should be installed at the positive side of the battery to protect the wires. Any electrical connections in the bilge below the waterline should be heat shrink type.
Turn off DC power supply circuit breaker before making connections.
Electrical Connections, Grounding & Bonding for AC Powered Zephyr
All Zephyr units have a five position terminal strip mounted inside the electric box. The terminal strip is labeled for proper connections of the electrical supply, ground wires and pump
L-2028 Installation
The air conditioning unit and its components must be con­nected to the boat’s bonding system to prevent corrosion due to stray electrical current. There is a bonding ground stud on the Dedicated Power Module. This stud must be connected to the vessel’s bonding stud, which is typically on the engine
English
block. This connection must be made per ABYC specifica­tions. All pumps, metallic valves and fittings in the seawater circuit that are isolated from the air conditioning unit by PVC or rubber hoses must be individually bonded to the boat’s bonding system also. This will help eliminate any possibility of corrosion due to stray current.
board, per ABYC E-9. Use a 60 amp breaker for 12 VDC systems. This provides protection from possible short circuits. When dockside, the Cuddy dc unit can operate against the batteries while using the AC battery charger (50 amp min) as a backup (most marine battery chargers will shut off when the battery is fully charged).
Note: Failure to properly ground and bond the system will void the warranty!
Electrical System and Wiring for DC Powered Cuddy dc
Dometic recommends a separate set of batteries dedicated for the Cuddy dc air conditioning system. Deep cycle AGM or Gel Cell batteries are the best for this application. If need be, please contact your Dometic dealer for assistance in sizing batteries.
The Cuddy dc kit contains the Dedicated Power Module (DPM). The DPM is meant to be used for the Cuddy dc system only and is sized to do so (see Figure 14 at the back of this manual for DPM specifications).
When connecting the DPM to the batteries, maintain correct wire size as shown in the DC Wire Sizing Table (see Figure 15 at the back of this manual), keep wire runs as short as possible, and with as few intermediate connections as possible, to avoid unnecessary resistance or voltage drop. See wiring diagram Figure 11 for location of customer­installed 60 amp fuse. Use an ignition protected fuse holder if installed in the engine compartment or in any area with flammable or compressed gasses or liquids (see the Safety Considerations section of this manual for more information). A standard ABYC approved battery disconnect switch is also recommended and should be used any time the system needs servicing. Do not forget to maintain proper color coding, (red = positive, black = negative) to aid in future electrical troubleshooting. If the wires are incorrectly con­nected (positive and negative reversed), the air conditioning unit will not start and the DPM will be damaged.
Ensure that all DC electrical connections are made in compliance with American Boat and Yacht Council (ABYC) standards section E-9.
Notice and ABYC Standards:
Field wiring must comply with ABYC electrical standards. Power to the unit must be within the operating voltage range indicated on the data plate. Properly sized fuses and circuit breakers must be installed for branch circuit protection. See equipment rating plate for maximum size. All air conditioning units must be effectively grounded to minimize the hazard of electric shock and personal injury. The following standards apply:
1. AC (alternating current) grounding (green) wire must be provided with the AC power conductors and connected to the ground terminal (marked “GRND”) at the AC power input terminal block of the unit(s), per ABYC standard E-8.
2. Connections between the vessel’s AC system grounding conductor (green wire) and the vessel’s DC (Direct Current) negative or bonding system should be made as part of the vessel’s wiring, per ABYC standard E-9.
3. When servicing or replacing existing equipment contain­ing a chassis-mounted “ground” stud, the service person or installer must check the vessel’s wiring for the exist­ence of the connection required in item 2 above.
ABYC standards are available from:
American Boat and Yacht Council 613 Third Street, Suite 10 Annapolis, MD 21403 Phone: (410) 990-4460, Fax: (410) 990-4466
The DPM is wired to the FAN setting on the two-knob switch assembly and is energized only when the Cuddy dc is running (see the Operation section of this manual). For DC wire sizing, see Figure 15 at the back of this manual.
As batteries age, their peak voltage lowers and they dis­charge quicker. This, of course, can affect the air conditioner performance as well as other DC devices. The battery condition should be maintained and monitored regularly and weak batteries should be replaced. A battery isolator, com­biner or selector switch will allow simultaneous charging while preventing the discharge of a fully charged battery into a depleted one.
Over current protection, in addition to fuse provided, must be supplied for the ungrounded conductor at the main switch-
L-2028 Installation
Seawater Pump and Plumbing
Several guidelines should be followed during the installation of the seawater system. Since the circulation pump is centrifugal and not self-priming, it must be mounted so that it is always at least one foot below the water line regardless of which tack the vessel is on. Pump may be mounted horizon­tally or vertically, however the discharge must always be above the inlet. Pump head should be rotated toward the direction of water flow.
intake as far below the water line and as close to the keel as possible in any application, but especially on a sailboat, to keep the intake in the water when the boat heels over so that air does not get into the system.
speed scoop intake must face forward and not be shared with any other pump. A seawater strainer is mandatory between
Install the seawater speed scoop
The
English
the shut off valve (seacock) and the pump to protect the pump from any foreign matter.
strainer will void the pump warranty
should be installed with an upward incline from the speed scoop & seacock, through the strainer, to the inlet of the pump and then up to the inlet of the air conditioning unit’s condenser coil. The discharge from the air conditioning unit should then run to the seawater outlet thru-hull fitting which should be located where it can be visually checked for water flow and as close as practicable to the waterline to reduce noise. All hose connections shall be secured by means of double/reversed stainless steel hose clamps. Use teflon tape on all threaded connections. The following is a summary of the seawater system installation:
1. Install the speed scoop thru-hull inlet as close to the keel and as far below the water line as possible, facing forward. Bed the scoop with a marine sealant designed for underwater use.
2. Install a bronze, full flow seacock on the speed scoop thru-hull inlet.
3. Install a seawater strainer below the level of the pump with access to filter.
4. Mount the pump above the strainer and at least one foot below the waterline.
5. Connect the seacock and strainer with an uphill run of 5/8" reinforced marine grade hose.
6. Connect the discharge from the pump uphill to the bottom inlet of the air conditioning unit’s condenser coil with 5/8" reinforced marine grade hose. Connect the discharge from the condenser coil to the overboard discharge thru­hull fitting with 5/8" reinforced marine grade hose.
7. Avoid loops, high spots or the use of 90° elbows with seawater hose (each 90° elbow is equivalent in pressure drop to 2.5' of hose and a 90° elbow on the pump outlet is equivalent to 20' of hose).
8. Double clamp all hose connections with stainless steel clamps, reversing the clamps.
9. Use teflon tape on all threaded connections.
10.
Connect all metallic parts in contact with seawater to
Failure to install a seawater
. The seawater system
the vessel’s bonding system including the speed scoop inlet, strainer, pump and the air conditioner
Refer to Figure 12, 13a , and 13b at the back of this manual for seawater kit installation drawings.
.
Installation Checklist (review prior to and after installation)
Seawater cooling system
• Speed scoop located as far below the water line and as close to the keel as possible
• Shut off valve and speed scoop properly sealed and tight
• Seawater pump at least one foot below water line and securely mounted
• Strainer mounted below pump with access to filter
• Double/reversed stainless steel hose clamps on all hose connections
• Teflon tape on all threaded connections
• Hose runs uphill from speed scoop to strainer, pump and air conditioning unit
• Water flowing freely from overboard discharge while pump is running
Air Conditioner Unit Mounting
• Not in engine room or bilge areas, must be sealed away from exhaust or fumes
• Proper spacing allowed around unit
• Attached to solid level platform with four hold down clips provided
• Condensate drain routed aft and down hill to a sealed sump (not bilge), and should have a trap
Grills and Ducting
• Supply air grill mounted as high as possible
• Return air grill mounted as low and as close to the unit as possible
• Return air grill mounted away from exhaust and bilge vapors
• Ducting is pulled taut, straight and properly connected with no excess
Electrical for AC Powered Zephyr
• All butt connections on pump wire tightly crimped and heat shrunk
• AC power source installed and grounded/bonded in accordance with ABYC standards
• Control wires connected to terminal strip with ring terminals
Electrical for DC Powered Cuddy dc
• All polarized plugs connected securely with an audible “snap”
• DC power source installed and grounded/bonded inaccordance with ABYC standards
• Bonding ground stud on Dedicated Power Module con­nected to vessel’s bonding system per ABYC
L-2028 Installation
English
Zephyr and Cuddy dc Units • Operation
Operation
Manual Control Panel Operation:
2-knob (2KB), 3.5-5K units; 3-knob (3KB), 10, 12, 16K units, see figures 6 & 7.
1. Ensure seawater intake ball valve (seacock) is open.
2. Turn top (MODE) control knob to OFF.
3. Turn on air conditioning unit circuit breaker. If the seawater pump has its own circuit breaker, turn that on too.
4. Turn top (MODE) control knob to FAN, this energizes the fan (and the DPM in Cuddy dc systems).
5. Turn THERMOSTAT control knob to the coolest position by rotating it fully clockwise.
6. Turn middle (FAN) control knob to highest setting (for 3KB switch only).
7. Verify that the fan is running and that there is steady airflow out of the supply air grill.
8. Turn top (MODE) control knob to RUN (for 2KB switch) and ON (for 3KB switch). This will start the compressor and seawater pump.
9. Check for a steady solid stream of seawater from the overboard discharge.
10. To set the THERMOSTAT, allow sufficient time for the unit to cool the area to the desired temperature. When the area is sufficiently cooled, turn the thermostat knob slowly toward the center position until it clicks once. The thermostat is now set to maintain a constant temperature.
Important
Do not turn the unit off and immediately turn it back on. Wait at least 30 seconds (2 minutes for the Cuddy dc) for system refrigerant pressures to balance.
Troubleshooting Guidelines
Before you call for service, review this list. It may save you time and expense. This list contains common occurrences that are not a result of defective workmanship or materials. If you need service after trying these procedures, call your nearest Cruisair dealer.
Problem: System will not start.
Possible Reason/Solution
1. Air conditioner circuit breaker is off. Turn circuit breaker on at ship’s panel.
2. Wiring at terminal strip is miswired (VAC unit only). Check wiring diagram; correct if necessary.
3. Input line voltage is insufficient (VAC unit only). Check power source for proper voltage. Check wiring and terminals for proper sizes and connections.
L-2028 Operation
4. Cuddy dc plugs are not connected tightly (DC unit only). Check polarized plugs from unit to pump, power module, and control. There should be an audible “snap” when plugs go together.
5. Batteries are not fully charged (DC unit only). Turn Cuddy dc unit off and charge battery bank.
6. DC power wires are incorrectly sized (DC unit only). See the “Electrical System and Wiring for DC Powered Cuddy dc” section of this manual. Ensure that DC power wires are sized and connected correctly.
7. Dedicated Power Module (DPM) is in lockout mode
(DC unit only).
The DPM has a protective overload lockout feature that will cause it to shutdown in case of a problem. When this occurs, turn Cuddy dc off and wait 2 minutes before turning back on. If that does not solve the problem, then continue reading:
a) If DPM has overheated (167°F [75°C]) then ensure that it
has at least one inch of air space above unit for, and is in an area that provides, proper ventilation.
b) If compressor has overheated then check water pump,
strainer and hoses. When operating properly, there should be a steady stream of water from the overboard dis­charge. Strainer may need cleaning. Ensure that hoses are not kinked or restricted in some other way. Pump should come on with the compressor when control is set to RUN.
c) If refrigerant pressure is too high, then turning the system
off for 2 minutes should correct that by allowing pressure to equalize. Note: Turning the Cuddy dc on and off too quickly may cause a high-pressure shutdown. During normal operation wait at least 2 minutes from the time control is turned off until it is turned back on.
d) If DC voltage is too high (>16-17VDC) or too low
(<10.5VDC), then check battery bank for correct charge. Charge batteries if need be. Note: Turn Cuddy dc off and charge batteries for 5 minutes. Try turning Cuddy dc on again. If it runs, then that is a good indicator the batteries were low. Fully charge batteries at this time.
e) If there is a dead short in the wiring, then disconnect
power supply and repair wiring.
If, after trying all of the above, the fan runs, but the compress and pump do not, then that is a good indicator there is a problem with the compressor and/or pump. Whereas, if the fan does not come on at this time, then that is a good indicator there is a problem with the fan or the DPM. Either way, call for a service technician – please see listing in back of this manual.
10
English
Problem: No cooling.
Possible Reason/Solution
1. Selector knob may not be in “cool” position. Reset selector knob.
2. Temperature set point is above ambient temperature. Lower temperature setting.
3. Obstructed water flow. Clean seawater strainer. Check for good steady flow from overboard discharge.
4. Pump may be air locked. Remove hose from pump discharge to purge air from line.
5. Coil iced. See below.
Problem: Coil iced.
Possible Reason/Solution
1. Thermostat set point is too low. Check setting on temperature knob. If setting is extreme for conditions, raise set point.
2. Improper air flow. Clean return air filter or remove obstructions from return air stream. Check for crushed or restricted ducting. Ducting run must be as straight as possible; remove any excess ducting.
Problem: Short cycling compressor.
Possible Reason/Solution
1. Cold supply air returning directly to return air grill. Redirect supply air so that it is not directed into the return air stream.
Problem: System runs continuously.
Possible Reason/Solution
1. Port hole or hatch open. Close all port holes and hatches.
2. Thermostat setting is excessive for conditions. Raise thermostat setting to cycle compressor.
L-2028 Operation
11
English
Loading...
+ 25 hidden pages