Cruisair TWLC User Manual

TWLC - Tempered Water Logic Controller
The Intelligent Control
Chiller Controls
TWLC
Tempered Water
Logic Control
Features:
Menu driven access and programming.
Fault history.
Up to 14 inputs.
Connect to on-board computer.
Fully automatic temperature staging
and chiller rotation.
New for 2009!
Latest firmware revision V40 has new features and improved chiller
protection.
Microprocessor controlled
Same reliability as the SMX logic boards
Chiller boards can be networked together
Only one keypad needed to control up to six chiller units.
Additional keypads can be added up to the number of units in
the system.
Up to six heat and cool temperature set point stages
Easy to use display keypad with menu-driven screens
Features
Capable of operating immersion heaters with high limit protection
Automatic compressor stage rotation to achieve even run-time
Automatic start up time delay on compressors
Ability to monitor the control system locally or remotely via a
computer, a modem, and a dedicated phone line
Complete system fault logs with run time reference
If network is lost, each chiller operates independently
When replacing a board, an initializing routine automatically
integrates the new board into the system
Features (cont’d.)
Removable terminal strips - ease of board replacement
Removable EPROM – software upgrade
Two LED’s - indicate network cable integrity
One display keypad hook up
One serial port connection for computer or modem hook up for
local or remote monitoring
Six outputs:
Compressor
Reversing Valve
Circulating pump
Seawater pump
Immersion Heat
Fault warning (for external alarm, i.e. light or buzzer)
The Board (features and outputs)
TWLC Power Logic Board
Removable Terminal Strip
Removable E-Prom
Display cable
Jack
Computer or Modem Jack
Network cable
Jacks
CNP Cable
CXP Cable
Cables Used To Connect TWLC Control And
Circuit Boards
Use to connect keypad in same enclosure and network connections between boards
Use to connect remote mounted keypad to circuit board
The Board (inputs)
The board contains 16 inputs
Common loop water return temperature sensor
Loop water out temperature sensor
Sea water out temperature sensor
Flow switch
Discharge pressure switch/transducer -Automatically recognizable
Suction pressure switch/transducer - Automatically recognizable
Compressor current transducer
Common loop water supply temperature sensor
Inputs (Cont’d.)
Immersion heater loop water temperature sensor
Common sea water in temperature sensor
Sea water pump current transducer
Loop water pump current transducer
Loop water pressure transducer
Sea water pressure transducer
Two additional auxiliary inputs – future enhancements
The Board (inputs) cont’d.