Cruisair DX Installation & Operation Manual

DX Built-In Air Cooled A/C Systems v INSTALLATION • OPERATION 2
Distributed By:
DIRECT EXPANSION SYSTEMS
P.O. Box 430
Phone (804) 633-9454
FAX (804) 633-5499
Dometic Corporation
2000 N. Andrews Ave. Ext. • Pompano Beach, FL 33069-1497 USA Phone: 954-973-2477 • Fax: 954-979-4414 Website: www.dometic.com/marine • Email: sales@dometicusa.com
Revised: 20140404 L-0261
For LP-10A
WARNING
This manual contains essential safety information concerning the safe and proper installation of Cruisair direct expansion air conditioning systems. It is very important that you read and understand the contents of this manual thoroughly before attempting to install any Cruisair equipment. If there are any statements in this manual that you do not understand, contact the Dometic Applications Department for assistance. Phone 954-973-2477, Fax 954­979-4414 (8:00 am - 5:00 pm United States EST).
NOTICE
As of July 1, 1992, United States federal law As of July 1, 1992, United States federal law prohibits the intentional release of refrigerant gases into the environment, including the R-22 refrigerant used in Cruisair air conditioning systems. Special care must be taken when installing, charging and servicing Cruisair equipment to prevent any loss of refrigerant.
Cruisair does not recommend the practice of using refrigerant to purge air and moisture from the system at installation. This formerly used practice of purging is in violation of United States federal law.
INTRODUCTION
This manual covers installation procedures for Cruisair direct-expansion air conditioning systems.
In addition, there are specic installation sheets for some models which may be shipped with Cruisair air conditioning equipment, providing additional details for specic components.
2
Table of Contents
Chapter 1: Description of Basic Components ...........................................................................................4
Basic Principles ..............................................................................................................................4
Cooling Unit ....................................................................................................................................4
Controls/Switches ...........................................................................................................................4
Condensing Unit .............................................................................................................................4
Figure 1. SA 3 Series Control..........................................................................................................4
Figure 2. SMX Series Keypad ........................................................................................................4
Chapter 2: Installation of Basic Components ............................................................................................5
Cooling Unit ....................................................................................................................................6
Control or Switch Assembly ............................................................................................................6
Condensing Unit .............................................................................................................................6
Installation Kit .................................................................................................................................7
Figure 3. Minimum Grill and Free Air ..............................................................................................5
Figure 4. Diagram of Flared Joint ...................................................................................................7
Figure 5. Refrigerant Line Sizes .....................................................................................................8
Chapter 3: Start-Up Procedures - Final Inspection ...................................................................................9
Figure 6. Wire and Breaker Size .....................................................................................................9
Chapter 4: Start-Up Procedures - Initial Charging of A New System ......................................................10
Required Tools ..............................................................................................................................10
Field Charging a System .............................................................................................................. 11
Removing Refrigerant from a System ...........................................................................................11
Figure 7a. Charging Pressure Charts for Equipment Built in 1994 and After ................................12
Figure 7b. Charging Pressure Charts for Equipment Built Prior to 1994 ....................................... 13
Chapter 5: Start-Up Procedures - Final Check-Out and Start-Up ........................................................... 14
Chapter 6: General Operation ................................................................................................................15
Operating Instructions - Rotary Knobs .........................................................................................15
Operating Instructions - SMX Series Controls..............................................................................16
Chapter 7: Maintenance .........................................................................................................................17
Cooling Unit and Switch Assembly ...............................................................................................17
Condensing Unit ...........................................................................................................................17
Chapter 8: System Failure Troubleshooting Guide .................................................................................. 18
Chapter 9: System Charging Troubleshooting Guide ..............................................................................19
Chapter 10: Installation Wiring Diagrams ................................................................................................20
Index of Diagrams ........................................................................................................................20
Warning ..................................................................................................................................................31
3
CHAPTER 1: Description of Basic Components
Cooling
Heating
Down Set Up
Inside Outside
Temp
Cool Off Heat
Manual
Mode
Slow Fan Fast
Basic Principles
The Cruisair air conditioning system consists of three basic components and, in some cases, several accessory parts. They are: (1) cooling unit; (2) control or switch assembly; and (3) condensing unit. This instruction manual will describe and explain the function of the basic parts of a Cruisair system and will outline the installation, interconnection and startup of a complete system. It also includes maintenance and operation of Cruisair equipment in general.
Cooling Unit
The cooling unit is a refrigerant to air heat exchanger coupled to a fan or blower which is located in the space to be cooled. A cooling unit is sometimes referred to as an ‘evaporator’ or a ‘cooling coil’, but in this manual, we will use the term ‘cooling unit’. The cooling unit is constructed of a series of copper tubes held in place by vertical aluminum ns. Inside these tubes, the refrigerant expands to produce a chilling effect by absorbing the heat in the air. This air is forced through the coil by the fan or blower.
SA type switch assembly has rotary knobs for controlling the system. Figure 1 shows a typical SA switch assembly.
The SMX series controls are advanced microprocessor based systems, with more than 20 user programmable functions. These functions are described in the SMX series owner’s manuals. Figure 2 shows an SMXII control panel.
77
Controls/Switches
There are two basic types of controls and switches used with Cruisair systems: the SMX series of microprocessor controls and the SA family of rotary knob switch assemblies. The
Figure 1. SA 3 Series Control
Figure 2. SMX Series Keypad
Condensing Unit
The condensing unit consists of the refrigerant compressor, the refrigerant receiver, the refrigerant to air heat exchanger or condenser, condenser fan or blower, the associated electrical components, and the system service valves.
The basic function of the condensing unit is to compress the expanded refrigerant, owing back from the cooling unit to the compressor, to a high pressure state. The compressed refrigerant then passes through the heat exchanger (condenser coil) where it gives up the heat which was absorbed in the cooling coil. It is then condensed to a liquid state as it ows to the liquid receiver and the process of ow back to the cooling unit is repeated.
4
CHAPTER 2: Installation Of Basic Components
The following instructions should be followed, in their proper sequence, when installing Cruisair equipment. Read and understand the instructions in this manual before proceeding.
Cooling Unit
In all installations, the cooling unit must be installed so the air discharge grill is installed as high as possible, (minimum three feet above the oor level). The cooling unit must be installed with the condensate drip pan positioned at the bottom of the unit so the water dripping from the evaporator coil collects in it before discharging to a suitable drain outside. The cooling unit drain must be installed so the drain tube makes an immediate 1” drop after leaving the drain tting.
With discharge air grills located high, return air grills should be located as close to the oor as possible to provide the best pattern of air ow. Avoid locating the return air grill in close proximity to the discharge grill since the resulting short circuiting effect of the air ow will impair the effectiveness of the system.
Cooling units with model number prexes EFB, EBH, or EFL should be mounted as high as possible, directly behind the discharge grills.
Centrifugal or blower type cooling units, model number prexes EBS, EBO, EHBO, EBL or EHBL, should be mounted low, near the return air grill, and the discharge air ducted to the discharge grill mounted at a high level.
The cooling unit must be installed so there is an adequate path for the air to re-circulate freely into the unit from the space being cooled. It is important that the cross sectional area of all discharge grills be at least equal to the coil face area of the discharge of the cooling unit involved. An exception is the centrifugal blower type cooling unit.
The cross sectional area refers to the ‘free air’ area of a discharge air grill rather than the total area as determined by the overall measurement of the grill itself. For instance, if a grill is made of expanded metal, perhaps only 50% of the area is open for the passage of air. The metal web itself will block air from passing through the other 50%. In such cases, the total area of the grill must be doubled to achieve the required open area. Observe this carefully when selecting a grill.
The return air grills used should be the type which have removable lters so they
EVAPORATOR DUCT GRILL AREA FREE AIR AREA
Type BTU’s Size In. Return (Sq. In.) Supply Return (70%) (Sq. In.) Supply (60%)
EBL 16,000 2 @ 5 144 2 @ 49 101 2 @30 EBO 4,000 4 64 32 45 19 7,000 5 72 49 51 30 10,000 6 100 60 70 36 14,000 7 144 80 101 48 16,000 7 144 80 101 48 EBS 14,000 7 144 80 101 48 16,000 7 144 80 101 48 EFB 10,000 NA 100 100 70 60 14,000 NA 144 144 101 87 16,000 NA 144 144 101 87 EBH 14,000 NA 144 144 101 87 16,000 NA 144 144 101 87 EFL 1,000 NA 40 40 28 24 14,000 NA 128 128 90 77 16,000 NA 128 128 90 77
Figure 3. Minimum Grill and Free Air
Minimum Grill And Free Air Area
5
can be removed and cleaned easily. The lter material should be a type which will not cause a signicant inlet air ow pressure drop. For all discharge air applications, wood or plastic frames are recommended. Aluminum frame grills will become cold and may produce secondary condensation that will drip from the grill frame.
See Figure 3 to determine the minimum grill and free air areas for each model cooling unit.
Control or Switch Assembly
The control or switch assembly is supplied as a separate item. The rotary switch assembly has three knobs and the plate is printed either for horizontal or vertical installation. It is designed to be mounted in an opening cut on the job and is fastened from the front with four screws. The wiring from the switch assembly terminates in a color coded terminal strip that should be securely mounted in a suitable place. Electrical connections for all systems are typically the same.
Operation of the SA type controls is covered in Chapter 6.
Condensing Unit
Cruisair condensing units are designed to be installed in a compartment ventilated to the outside. Air entry and exit openings to the exterior should be protected by rain proof louvers or grills. Space should be provided on all sides of the unit to allow air to enter it for cooling the condenser. All refrigeration components are hermetically sealed and all electrical components are spark proof for maximum safety. Make sure the wood base is positioned at the bottom of the unit in a horizontal plane. Fasten the condensing unit wood base securely and in such a way that the unit can be removed for service if necessary.
ACA Series Condensing Units
Return Air
Minimum Grill Area Free Air (70%) 240 sq. in. 168 sq. in.
The thermostat in the switch assembly has a 10 foot capillary tube leading from it to the temperature sensing bulb. This bulb must be located in the system’s return air stream so that the bulb is exposed only to the air returning from the space being cooled.
The SMX control system uses a Temperature Sensing Element (TSE) to control the operation of the system. Like the thermostat bulb on the SA type control, this TSE must be installed in the return air path of the conditioned air. These sensors are available in various lengths from 10 to 80 feet.
Operation of the SMX type controls is covered in the SMX Series Control Systems User’s Guide, L-634.
6
Installation Kit
1. Copper Tubing
When installing the two connecting copper tubes between the cooling unit and the condensing unit, there are several important factors to consider. First, the tubing can be run in lengths up to 50 feet. It can run uphill, downhill, or sloping, as required and can have as many bends as necessary. (Avoid sharp bends and do not use soldered elbows.) Both the suction and discharge lines should be insulated individually to prevent moisture from forming on the tube and for vibration protection. Also insulate the connecting are nut joints carefully to prevent drip ping of moisture from these joints.
-
Caution • • • • • • • • • • • • • •
Always use refrigeration grade, seamless, soft copper tubing. Never use neoprene, rubber or any other type hose not de signed specically for use with R-22 and approved by Cruisair. The refrigerant used in Cruisair systems is monochlorodiuoro­methane or R-22. This gas is compatible with very few tube compositions with copper being the most frequently used. (Engine driven systems use a different type refrigerant so therefore can use a neoprene refrigerant lines.) The copper tubing is connected to the cooling unit and condensing unit with are joints. Flares of exceptional quality are essential to prevent refrigerant leaks. Flares must be of the 45°, single are type. Do not use a double are. The are should be large enough in diameter to ll the are nut completely. See Figure 4.
-
Figure 4. Diagram of Flared Joint
Only the long stem forged are nuts, such as those that are supplied with Cruisair equipment, are strong enough for mobile duty. Do not use long stem machined are nuts. Flare nuts should be tightened until the nut ceases to offer resistance to tightening. This is the point where the ared portion of the copper tubing is beginning to ow or mash under the force of the nut being tightened. After the tubing is insulated and in place, secure it with clamps. For proper line sizes, see Figure 5.
2. Wire Harness
SA Series Controls
The wire harness connects the condensing unit to the main switch assembly terminal strip. The harness or cable should include six conductors. Normally the wire harness is run along with the connecting copper tubing but this is not necessary.
SMX Series Controls
An interconnect cable (CX) is available in various lengths from 10 to 80 feet. The cable includes a plug on each end for ease of installation. The SMX series also uses an electronic temperature sensor which comes in various lengths and it too plugs in.
7
Air Conditioning System
with (1) Cooling Unit
& (1) Condensing Unit
Air Conditioning System
with (2) Cooling Units
& (1) Condensing Unit
Suction Lines
Unit Cap Line Size
14000 BTU - 1/2”
16000 BTU - 1/2”
Discharge Lines
14000 BTU - 1/4” 16000 BTU - 1/4”
Suction Line
Discharge Line
Cooling Unit Line Sizes
Unit Cap Suction Discharge
4000 BTU - 3/8” 1/4”
7000 BTU - 3/8” 1/4” 10000 BTU - 3/8” 1/4”
Condensing Unit Line Sizes
14000 BTU - 1/2” 1/4”
Discharge Tee
1/4” X 1/4” X 1/4”
Suction Tee
3/8” X 3/8” X 1/2”
Notes:
1) Insulate entire length of both refrigerant lines with closed cell foam or equivalent
2) All tubing should be seamless refrigeration grade copper
3) Tee’s (where applicable) should be within 2-3 ft. of condensing unit
Figure 5. Refrigerant Line Sizes.
8
CHAPTER 3: Start Up Procedures - Final Inspection
The following is a list of items to be checked before any Cruisair system is started. Be sure that the:
p Cooling unit is bolted securely in place.
p Cooling unit return air cross sectional
open area is equal to the face area of the unit evaporator coil as a minimum
p Return air to the cooling unit should pass through a lter and should come only from the space being cooled.
p Switch assembly terminal strips are securely mounted in a dry place, safely out of reach, and covered.
p Thermostat temperature sensing bulb or temperature sensing element (TSE) is installed in the cooling unit return air stream. NOTE: These should not be touching metal parts of the cooling unit which may become cold.
14,000 BTU/hr Condensing Unit
Voltage 115 230 Wire size 10 12 Breaker size 30 20
Figure 6. Wire and Breaker Size
p Power line from the vehicle’s panel is connected securely to the condensing unit terminal strip. See wiring diagram. Be sure the proper size circuit breaker of the time delay type is installed. See Figure 6 for proper wire and breaker sizes.
p The refrigerant lines between the cooling unit and condensing unit are insulated completely.
p Copper tubes and wire harness are secured throughout their length.
p Condensing unit is securely mounted.
p Cooling unit condensate drain is in place and
working properly. Test by pouring two quarts of water rapidly into the cooling unit drip pan.
p Cooling unit wires are connected securely to the condensing unit terminal strip.
p Flare nut joints at the cooling unit are tight.
p Flare nut joints at the cooling unit are
insulated to prevent dripping. Insulate after testing for leaks.
p Wire harness to the condensing unit is securely connected to the switch assembly terminal strip.
p Flare joints at the condensing unit are tight and insulated, after testing for leaks.
9
CHAPTER 4: Start Up Procedures - Initial Charging Of A New System
Warning • • • • • • •
Federal law prohibits the intentional release of refrigerant gas into the environment and requires that you use EPA approved refrigerant handling equipment and procedures to prevent any refrigerant gas from escaping into the air.
The following instructions should be followed in evacuating and charging a Cruisair remote con densing unit system with R-22.
There are three refrigerant circuit components in a Cruisair remote condensing unit system: the condensing unit, the cooling/heating unit and the copper refrigerant lines. The condensing unit is shipped from the factory charged with approximately the amount of refrigerant needed for the whole system. The cooling unit is pressurized with dry nitrogen and the copper tubing contains air.
The procedure will be to evacuate the nitrogen and air from the cooling unit and the copper tubing, then release the refrigerant from the condensing into the entire system. To facilitate this procedure, there is a special port with a red cap located on the right hand base valve of the condensing unit.
Required Tools
• Refrigerant 22 container (typically the disposable type container color coded green for R-22)
• Four valve gauge manifold with self closing
ttings on the charging hoses
• Vacuum pump
• Base valve wrench and hand tools
• Accurate thermometer
Proceed as Follows
1. Make sure all are joints are well made and
tight.
2. Do not touch the condensing unit base valve stem covers or service port caps. Remove the red port cap on the right hand base valve.
3. Connect the vacuum pump hose to the vacuum pump. Connect the refrigerant supply line to the refrigerant container (make sure the container valve is OFF). Connect the low
pressure gauge hose, equipped with self closing ttings to the red capped port. At this point do not connect the high pressure charging hose to anything.
4. Close all gauge manifold valves.
5. Energize the vacuum pump and open manifold valves for the vacuum pump, the refrigerant container, and the red capped access port low pressure test gauge).
6. As the pump operates, you will see the low pressure test gauge fall to a vacuum. When he vacuum reaches 28 in. HG, close the vacuum
-
pump valve and turn the vacuum pump off. Leave the system for 15 minutes and then observe the gauge. If any vacuum is lost, a leak is indicated. Find the source of the leak and correct. Return to step #3 above and re-evacuate the system. Continue until the system will hold the vacuum.
7. Open the vacuum pump valve and leave the vacuum pump operating for at least 6 hours or until a vacuum of at least 29 in. HG is achieved. Close the vacuum pump valve and turn the vacuum pump off. Wait one hour. If no vacuum is lost, proceed with charging. If any vacuum is lost, a leak is indicated. Find the source of the leak and correct. Return to step #3 above and re-evacuate the system. Continue until the system will hold the vacuum.
8. Open the refrigerant container valve slowly and allow gas to enter the system until the gauge rises to zero. You have now lled the evacuated lines and cooling/heating unit with refrigerant to a gauge pressure of zero. Close the refrigerant container valve.
9. Remove the low pressure gauge hose from the red capped port. Replace and tighten the red cap.
10. Remove both condensing unit base valve
stem caps. Open both base valves fully by turning the valve seems fully counterclock wise. This will allow the refrigerant in the condensing unit to enter the system. Replace and tighten the valve stem caps.
At this point, the system is basically charged and
ready for nal gas charge adjustment.
10
Loading...
+ 22 hidden pages