Crown Steam ETP-10G Installation Manual

ECO-TECH® PLUS
GAS CONVECTION STEAMER
INSTALLATION - OPERATION - MAINTENANCE
 ETP-10G
Telephone: (802) 658-6600 Fax: (802)864-0183
www.marketforge.com PN 14-0270 Rev C (1/17)
© 2017 - Market Forge
Your Service Agency’s Address:
Model
Serial number
Steamer installed by
Installation checked by
IMPORTANT
TABLE OF CONTENTS
WARNING: Improper installation, ad­justment, alternation, service or main­tenance can cause property damage, injury or death. Read the installation, operation and maintenance instruc­tions thoroughly before installing or servicing this equipment.
INSTRUCTIONS TO BE FOLLOWED IN THE EVENT THE USER SMELLS GAS MUST BE POSTED IN A PROMINENT LOCATION. This information may be ob­tained by contacting your local gas sup­plier.
FOR YOUR SAFETY
Do not store or use gasoline or other ammable vapors or liquids in the vicin­ity of this or any other appliance.
Do not attempt to operate this unit in the event of power failure.
Adequate clearances must be maintained
for safe and proper operation.
INSTALLATION
Service Connections ............................................. 2
Introduction ...................................................... 3
Installation....................................................... 4
Water Conditioning ............................................... 7
Filter Change Procedure .......................................... 8
Performance Check .............................................. 9
OPERATION
Operating Instructions ...........................................10
Lighting ....................................................10
Cooking ....................................................10
Cleaning ................................................... 11
Drainage ................................................... 11
Control Panel ................................................... 12
Test Kitchen Bulletin ............................................. 13
Cooking Guide .................................................. 15
MAINTENANCE
Cleaning & Preventative Maintenance.............................18
Cleaning ...................................................18
Deliming .................................................... 19
The appliance area must be kept free and clear of combustibles.
Do not obstruct the ow of combustion
and ventilation air.
The information contained in this manual is important for the proper installation, use, and maintenance of this steamer. Adherence to these procedures and in­structions will result in years of trouble­free service. Please read this manual carefully and retain it for future reference.
ERRORS: Descriptive, typographic or pictorial errors are subject to correction.
Specications are subject to change
without notice.
Service Connections
10 [254]
SERVICE CONNECTIONS
G Gas Connection - 3/4” (19mm) Male NPT. 84,000
BTU’s.
CW Cold Water - 3/8” (10mm) NPT, Maximum 50 PSI,
Minimum 25 PSI.
D Drain - 1-1/2” NPT male from the drain adapter (see
illustration)
EC Electrical Connection - 120 Volts AC, 60 Hz, single
phase, comes with 6 foot cord. NEMA 5-15. Total Amps: 2
INSTALLATION CLEARANCE
Left Side Right Side Rear
3 6 6
GAS CONNECTION
 3/4” NPT male  3 1/2” W.C. natural  10” W.C. propane
NOTES: If the equipment is to be installed where the elevation exceeds 2,000 ft. (609.6 meters) above sea level, specify instal­lation altitudes so that the proper gas orifices can be provided. Rated Input: 42,000 BTU per compartment.
All service connections are made at the rear of the unit.
NOTES: PVC and CPVC pipe are not acceptable materials for drains.
The drain piping must consist of temperature resistant material, greater than 160°F, and be of adequate diameter not to cause flow restriction. Improper materials may deform and cause restric­tions, thus affecting performance.
DIMENSIONS ARE IN INCHES [MM]
24 [610]
2.75 [70]
4 [102]
6.25 [159]
4 [102]
16.75 [425]
cw
76.25 [1937] EC
9.75
[248]
G
CW
EC
D
21.13 [537]
1 [25]
33 [838]
REAR FLANGED FOOT DETAIL
2 EQUALLY SPACED Ø7/16” [11] HOLES ON 2.5 [63] B.C.
12 [305]
WATER SUPPLY
Good quality water feed is the responsibility of the owner. Water quality must be within the following general guidelines.
TDS: 40-125 ppm Chlorides: <25 ppm Silica: <13 ppm pH: 7.0 - 8.5 Chloramine: <0.2 ppm Chlorine: <0.2 ppm Hardness: 35-100 ppm
The best defense against poor water quality is a water treatment system designed to meet your water quality conditions.
Appliance to be installed with backflow protection according to federal, state or local codes.
INSTALLATION
Figure 1
2
64 [1626]
6 [152]
3.75 [95]
G
D
DRAIN ADAPTER
10 [254]
23.75 [603]
Introduction
DESCRIPTION
The ETP-10G is a gas red pressureless steam cooker. The cooking compartments are equipped with a three-
piece door with inner gasket plate isolated from the exte­rior surface. Door latch operates by slam action for posi­tive sealing of the door. Operating controls are displayed on a front-mounted panel and include indicator lights for ignition, ready and cooking modes, a timer to set cook times and a selectable hold cycle to keep food warm once cooked, a temperature display to monitor cavity tempera­ture, and an illuminated ON/OFF/DELIME switch. Each stainless steel steam generator operates “0” PSI (0 kg/ cm2) and is rated at 42,000 BTU.
BASIC FUNCTIONING
The cooker is ready for operation when the READY light comes on.
At the end of the set interval, timer contacts switch to shut off the cooking operation and sound a signal buzzer. The buzzer is silenced by returning the timer dial to the OFF position. In the ‘HOLD’ mode, the cooker will maintain a safe food holding temperature at or above 150°F.
Steam and liquids from each cooking cavity pass through
a removable drain screen in the cavity and into the tem­pering tank. When the appliance is shut off, the steam generators will also drain into the tempering tank. The tempering tank condenses any residual steam and tem­pers the waste water to 140°F or less.
3
INSTALLATION
Installation
SETTING IN PLACE
The location of installation must be under an exhaust hood, which will remove water vapour emitted when the cooker door is opened, and exhaust combustion fumes.
Level the unit in nal location by turning the adjustable
feet. Using the cabinet top as a reference, obtain level adjustment left-to-right and front-to-back.
MECHANICAL CONNECTIONS
All electrical and plumbing connections are located on the rear panel of the unit. See ‘SERVICE CONNECTIONS for location of mechanical connections.
INSTALLATION CODES AND STANDARDS
Installation must conform with local codes, or in absence of local codes, with the National Fuel Gas Code - ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Instal­lation Code, CSA B149.1 as applicable.
1. The appliance and its individual shut off valve must be disconnected from the gas supply piping system during any pressure testing of that system at pres­sures in excess of 1/2 PSI (0.035 kg/cm2).
2. The appliance must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply
piping system at test pressures equal to or greater
than 1/2 PSI (0.035 kg/cm2).
Electrical grounding must be provided in accordance with local codes, or in the absence of local codes, with the National Electrical Code ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.2 as applicable.
Ventilation must be provided in accordance with local codes, or in the absence of local codes, with ANSI/NFPA 96 Standard for Ventilation and Fire Protection of Com­mercial Cooking Operations.
EXHAUST FANS AND CANOPIES
Canopies are set over ranges, ovens, kettles, etc., for ventilation purposes. It is recommended that a canopy extend 6” past the appliance and be located 6’ 6” from the
oor. Filters should be installed at an angle of 45 degrees
or more with the horizontal. This position prevents drip­ping of grease and facilitates collecting the run-off grease
in a drip pan, usually installed with the lter. A strong
exhaust fan tends to create a vacuum in the room and may interfere with burner performance or may extinguish
pilot ames. Makeup air openings approximately equal to
the fan area will relieve such vacuum. In case of unsat­isfactory performance on any appliance, check with the exhaust fan in the “OFF” position.
WALL EXHAUST FAN
Exhaust fans should be installed at least two feet above the vent opening at the top of the unit.
CLEARANCES
Adequate clearance must be provided in aisle and at the side and back. Adequate clearances for air openings into
the combustion chamber must be provided, as well as for serviceability. Minimum clearance from combustible and noncombustible construction, 3” on left side, 8” on right side and 6” from back.
WARNING
These procedures must be followed by quali-
ed personnel or warranty will be voided. An open gap oor drain is required immediately
below the appliance drain.
WARNING
Electrical grounding instructions - Units come equipped with a three-prong (grounding) plug for your protection against shock hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug. (120 VOLT UNITS ONLY)
WIRING DIAGRAM FOR APPLIANCE IS LOCATED ON RIGHT HAND SIDE PANEL OF THE COOKER CABINET.
INSTALLATION
4
Installation
To Install
1. Uncrate carefully. Report any freight damage to the freight company immediately.
2. Set the unit in place. Be certain to maintain the mini­mum clearances from combustibles and non-com­bustibles.
3. For an appliance supplied with legs, level the ap-
pliance using a spirit level. Four anged adjustable
feet are provided for permanent anchoring to the
oor. With the unit in location, mark hole locations on the oor through the anchoring holes. Remove
the steamer and drill holes at marked locations on the
oor. Insert proper anchoring devices.
4. Set steamer back in proper position.
5. Install bolts through anchoring holes and into anchors
to secure the steamer to the oor. Seal bolts and anged feet with Silastic™ or equivalent silicone seal-
ant.
6. After the drain is connected, check for level by pour-
ing water onto the oor of the compartment. All water
should drain through the opening at the back of the compartment cavity.
WARNING
For an appliance equipped with casters, the installation shall be made with a connector that complies with the Standard for Con­nectors for Moveable Gas Appliances, ANSI Z21.69/CSA 6.16 and a quick-disconnect device that complies with the Standard for Quick-Disconnect Devices for use with Gas Fuel, ANSI Z21.41/CSA 6.9; adequate means must be provided to limit the movement of the appliance without depending on the connector and the quick-disconnect device or its associ­ated piping to limit the appliance movement: the location where restraining means may be attached is directly above the gas supply inlet pipe on the rear of the appliance.
The water inlet connections must also be
installed with a exible water supply line, a
quick disconnect and strain relief.
GAS CONNECTION
1. The Serial and Rating Plate on the unit indicates the
type of gas your unit is equipped to burn. DO NOT
connect to any other gas type.
2. A 3/4” NPT line is provided at rear for the connection. Each compartment is equipped with an internal pres­sure regulator which is set at 3.5” W.C. manifold pres­sure for natural gas and 10” W.C. for propane gas. Use C” pipe tap on the burner manifold for checking pressure.
An adequate gas supply is imperative. Undersized or low pressure lines will restrict the volume of gas required for
satisfactory performance. A steady supply pressure, be­tween 6” W.C. and 14” W.C. for natural gas and 11” W.C. and 14” W.C. for propane gas is recommended. With all units operating simultaneously, the manifold pressure on all units should not show any appreciable drop. Fluctua­tions of more that 25% on natural gas and 10% on pro­pane gas will create problems, affecting burner operation. Contact your gas company for correct supply line sizes.
Purge the supply line to clean out any dust, dirt or other foreign matter before connecting the line to the unit. Use pipe joint compound which is suitable for use with LP on all threaded connections.
Test pipe connections thoroughly for gas leaks.
WARNING
Never use an open ame to check for gas
leaks. Check all connections for leaks using soapy water before use.
NOTICE
If this equipment is being installed at over
2,000 feet altitude and was not so specied on
order, contact service department. Failure to
install with proper orice sizing may void the
warranty.
ELECTRICAL CONNECTION
120 VAC-60 Hz - Single Phase
Units with this electrical rating are factory supplied with a three-wire cord and three-prong plug which ts any stan­dard 120V, three-prong grounded receptacle. A separate 15 amp supply is needed for each unit.
5
INSTALLATION
Loading...
+ 14 hidden pages