Crown Boiler ODV-100, ODV-125, ODV-75 User Manual

Freeport ODV Series
D ESIGNED TO L EAD
Manufacturer of Hydronic Heating Products
P.O. Box 14818 3633 I. Street
Philadelphia, PA 19134
Tel: (215) 535-8900 • Fax: (215) 535-9736 • www.crownboiler.com
Oil-Fired Direct Vent Hot Water Boilers
Models
ODV-75 ODV-100 ODV-125
WARNING: Improper installation, adjustment, alteration,
service or maintenance can cause property damage, injury, or loss of life. For assistance or additional information
consult a qualied installer or service agency. This boiler requires a special venting system. Read these instructions carefully before installing.
TABLE OF CONTENTS
Product Description 1
Specications 2
BeforeInstalling  3
LocatingTheBoiler 3
VentSystemInstallation 4
SystemPiping 13
FuelPiping 17
Wiring 18
Start-UpAndCheckout 19
ServiceNotes 20
Maintenance 22
Parts 24
WARNING
FAILURE TO VENT THIS BOILER IN ACCORDANCE WITH THESE INSTRUCTIONS COULD CAUSE FLUE GAS TO ENTER THE BUILDING RESULTING IN SEVERE PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH:
Do not attempt to vent this boiler with galvanized, PVC, or any other vent components • not described in this manual Do not obtain combustion air from within the building. • Do not install a barometric damper or vacuum relief valve in the vent system of this
boiler.
CAUTION
Moisture and ice may form on the surfaces around the vent termination. To prevent deterioration, surfaces should be in good repair (sealed, painted, etc.).
DANGER
THE VENT SYSTEM SUPPLIED WITH THE ODV IS NOT DESIGNED FOR VENTING OF FLUE PRODUCTS FROM NATURAL GAS OR PROPANE. DO NOT ATTEMPT TO CONVERT THE ODV TO EITHER GAS.
I Product Description
The ODV series boiler is a cast iron oil red boiler designed for use in forced hot water heating systems. The ODV boiler must be vented using the factory supplied venting system with combus­tion air taken from outdoors. The ODV uses the same three pass “scotch marine” heat exchanger as the CT series boiler. The ODV series boiler is ideal for use in installations where a chimney is not available.
The ODV boiler is not designed for use in gravity or “open” heating systems.
CAUTION
As with any oil appliance, certain adverse conditions can cause this boiler to operate at high smoke levels. Since the ODV is vented through a wall, this can result in severe soot damage to the side of the structure around the terminal. To minimize the risk of this:
Follow these installation instructions exactly
Oil burner must be set up by a qualied serviceman using combustion test instruments
Use only the vent components supplied in the ODV vent kit
Combustion air must be supplied from outdoors
Follow the maintenance procedure in this manual
Use only #2 fuel oil meeting ASTM D-396
1
IISpecications
D.O.E.
HEATING IBR NET FIG. 1
NO. INPUT CAPY. RATING DIMENSION MODEL SECTIONS Gal/hr) (BTU/hr) (BTU/hr) AFUE (%) "A" (IN.) ODV-75 3 0.75 91,000 79,000 85.0 32-1/4 24 14
ODV-100 3 1.00 119,000 103,000 83.1 32-1/4 24 14 ODV-125 4 1.25 150,000 130,000 83.5 37-1/4 24 14
FIG. 1 DIMENSION "B" (IN.)
STANDARD
CONNECTION
USING
OPTIONAL
TEE
TABLE 1: SPECIFICATIONS
Ratings based on #2 fuel oil having a higher heating value of 140,000 BTU/Gal Net ratings based on a piping and pickup loss allowance of 1.15
Exhaust pipe: 4” I.D. insulated exible vent pipe. Maximum exhaust pipe length – 15 ft. Inlet pipe: 4” I.D. Corrugated Aluminum Maximum Inlet pipe length – 20 ft Maximum Wall Thickness in which Terminal is Installed – 12”
2
IIIBeforeInstalling
1) Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict accordance with this manual and the authority having jurisdiction.
In the absence of an authority having jurisdiction, installation must be in accordance with this manual and Installation of Oil-Burning Equipment (ANSI/NFPA 31).
Where required by the authority having jurisdiction, this installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers (ANSI/ASME CSD-1)
2) Read Section VI to verify that the maximum combustion air and exhaust pipe lengths will not be exceeded in the planned installation. Also verify that the vent terminal can be located in accordance with Section VI. Note: The maximum wall thickness through which the terminal can be installed is 12”.
3) Make sure that the boiler is correctly sized:
For heating systems employing convection radiation (baseboard or radiators) use an industry accepted sizing method such as the I=B=R Heat Loss Calculation Guide (Pub. #H21 or #H22) published by the Hydronics Institute in Berkely Heights NJ.
For new radiant heating systems refer to the radiant tubing manufacturer’s boiler sizing guidelines.
For systems including a Crown Mega-Stor indirect water heater, size the boiler to have either the DOE Heating Capacity required for the Mega-Stor or the net rating required for the heating system, whichever results in the larger boiler.
For systems that incorporate other indirect water heaters, refer to the indirect water heater manufac- turer’s instructions for boiler output requirements.
4) Do not install this boiler at altitudes above 2000ft.
5) Inspect shipment. This boiler is shipped in three pieces:
a) Wire-bound crate with boiler b) Vent terminal carton – Includes terminal, vent adapters, inlet piping and hardware c) Vent pipe carton - Includes exible vent pipe.
IVLocatingtheBoiler
1) Observe the clearances below. Top, side and rear clearances are from jacket. Front clearance is from burner door.
To Combustible Construction To Non-Combustible Construction Front 24 15 Left* 6 2-1/2 Right 6 1 Rear Determined by clearance to Flexible Vent Pipe (below) Top 24 24 Terminal 0 0 Flexible Vent Pipe 3 0 * 14 inch clearance required to open door.
2) Boiler must be installed on a non-combustible surface.
3) Boiler must be located so that the 15-foot vent pipe supplied with the boiler will reach the terminal location. Approximately 1.3 feet of pipe length is used up in making a 90-degree bend (Fig 11). See Section V for more information on venting requirements.
3
planned
VVentSystemInstallation
WARNING
Read the installation instructions carefully and completely before proceeding with the installation of vent system.
For continued safe operation, the appliance vent system must be inspected and maintained annually by a qualied agency. Failure to properly maintain the appliance vent system combination can lead to Death, Personal Injury and or Property Damage.
Plan the vent system layout before installation to avoid the possibility of accidental contact with concealed wiring or plumbing inside walls.
The ODV boiler is shipped with a complete venting system consisting of the following components:
FDVS-4 direct vent terminal
Backing plate
15-ft length of insulated 4” FOVP exible oil vent pipe
4” x 7” appliance adapter
(2) Cover rings
(2) Cover sleeves
Bagged hardware
(4) Inner pipe clamps
20 ft length 4” exible aluminum air intake pipe
(2) Hose clamps
“Red” high temperature RTV silicone sealant
CAUTION
Do not use vent system components other than those supplied with the boiler
Use only the red RTV sealant provided with this boiler anywhere that this manual calls for the use of “sealant”
Combustion air must be brought from outside as shown in this manual
Do not install a “vacuum relief” damper
Do not attempt to splice vent piping
Do not put holes in venting
1) LOCATING THE TERMINAL – Observe the following requirements in locating the terminal:
a) Maximum wall thickness through which terminal can be installed is 12”. b) Wall can be combustible or noncombustible. c) Bottom of terminal must be at least 12 inches above the normal snowline. If normal snowfall is negligible, terminal must be at least 12 inches above grade (Fig 2). d) Bottom of Terminal must be at least 7 feet above a public walkway (Fig 2). e) Locate edge of terminal at least 4 ft horizontally from doors, windows, or gravity air inlets. Do not put terminal under windows which can be opened (Fig 2). f) Terminal must be close enough to boiler to be connected to it using the vent components supplied.
4
5
g) Do not locate terminal under decks. h) It is preferable to install the terminal on the wall that is away from the prevailing wind. i) Do not put terminal under a soft or other overhang deeper than 18 inches. Top edge of terminal must be at least 2 ft below soft or overhang (Fig 3). j) Position terminal to avoid accidental contact with people or pets. k) Over time, the area around the terminal may become stained. Locate the terminal on a wall where this is not objectionable. l) No part of an inside corner should extend into the shaded area shown in Figure 4. m) Terminal must be positioned so that no other buildings are within the shaded area shown in Figure 4. Other permanent objects in this area may become stained or otherwise effected by ue gas. n) The terminal is a potential source of odors. Although the above restrictions will generally prevent inltration of these odors into the building, care should be taken in positioning the terminal near outdoor areas where people congregate, such as patios. This is particularly true when the boiler is used with an indirect water heater that will cause the boiler to run during warm months.
2) INSTALLING THE FDVS-4 VENT TERMINAL
a) Remove vent system components from box and inspect for damage. If the carton has been crushed or mutilated, check components very carefully for damage. DO NOT install if any damage is apparent. b) Remove the combustion air tee assembly from the vent terminal. Set the tee aside for later use. c) After determining the location of the vent terminal (Figures 2,3 & 4), cut a 7-1/4” square hole in the wall. (Figure 5a) Note: Maximum wall thickness: 12” d) Seal the back side of the base plate around the outer pipe of the vent terminal with a bead of standard silicone sealant (not supplied). (Figure 5b) Mount the vent terminal through the wall, keeping the outer pipe centered in the hole. (Figure 5a) Fasten the vent terminal to the outside wall with appropriate fasteners. Seal the edges of the vent terminal base plate to the wall with standard silicone sealant.
CAUTION
Failure to apply this bead of silicone properly can cause ue gas to recirculate into the air inlet resulting in sooting of the boiler, vent system, and side of the strucure.
e) Mount the backing plate over the outer pipe. Fasten the backing plate to the inside wall with appropriate fasteners. (Figure 5b)
DO NOT BLOCK the intake or exhaust openings, or the intake access panel on the vent terminal body. Wood or vinyl siding should be cut so that the unit mounts directly on the wallboard to provide a stable support. If the siding is greater than 1/2” thick use a spacer plate or board behind the vent terminal mounting plate. (Figure 5b)
f) If the inside terminal section is not supported by the wall through which it passes, install additional supports or bracing to rigidize the terminal. Bracing in contact with the co-axial section of the terminal may be combustible.
6
7
Loading...
+ 22 hidden pages