These instructions must be axed on or adjacent to the boiler
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage,
injury, or loss of life. For assistance or additional information, consult a qualied installer, service
agency or the gas supplier. This boiler requires a special venting system. Read these instructions
carefully before installing.
Models:
• FWZ060
• FWZ080
• FWZ081
• FWZ100
• FWZ130
• FWZ160
9802605 Rev A, 06-18
Equipped with Hydrolevel
3250-Plus Control System
Crown Boiler Company
P.O. Box 14818
3633 I Street
Philadelphia, PA 19134
www.crownboiler.com
Page 2
Page 3
IMPORTANT INFORMATION - READ CAREFULLY
All boilers must be installed in accordance with National, State and Local Plumbing, Heating and
Electrical Codes and the regulations of the serving utilities. These Codes and Regulations may dier
from this instruction manual. Authorities having jurisdiction should be consulted before installations
are made.
In all cases, reference should be made to the following Standards:
USA BOILERS
A. Current Edition of American National Standard ANSI/NFPA 31, “Installation of Oil
Burning Equipment”, for recommended installation practices.
B. Current Edition of American National Standard ANSI/NFPA 211, “Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances”, For Venting requirements.
C. Current Edition of American Society of Mechanical Engineers ASME CSD-1, “Controls and Safety Devices for Automatically Fired Boilers”, for assembly and operations of controls and safety devices.
D. All wiring on boilers installed in the USA shall be made in accordance with the National Electrical Code and/or Local Regulations.
CANADIAN BOILERS
A. Current Edition of Canadian Standards Association CSA B139, “Installation Code for Oil Burning Equipment", for recommended Installation Practices.
B. All wiring on boilers installed in Canada shall be made in accordance with the Canadian Electrical Code and/or Local Regulations.
The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels,
or to important information concerning product life.
DANGER
Indicates an imminently hazardous situation
which, if not avoided, will result in death, serious
injury or substantial property damage.
Indicates a potentially hazardous situation which,
if not avoided, may result in moderate or minor
injury or property damage.
CAUTION
NOTICE
WARNING
Indicates a potentially hazardous situation which,
if not avoided, could result in death, serious injury
or substantial property damage.
Indicates special instructions on installation,
operation, or maintenance which are important
but not related to personal injury hazards.
DANGER
This boiler is designed for use with #2 fuel oil meeting the specications of ASTM D-396. Attempts to burn
other liquid fuels, or to convert this boiler for use with gaseous fuels, could result in reliability problems,
extensive property damage, or loss of life.
This boiler has a limited warranty, a copy of which is included with this boiler.
The warranty for this boiler is valid only if the boiler has been installed, maintained and operated in
accordance with these instructions.
Surface rust on cast iron sections may be attributed to the manufacturing process as well as condensation
during storage. Surface rust is normal and does not aect the performance or longevity of a boiler.
NOTICE
1
Page 4
DANGER
DO NOT store or use gasoline or other ammable vapors or liquids in the vicinity of this or any other appliance.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal
injury or loss of life. Failure to follow all instructions in the proper order can cause personal injury or death.
Read and understand all instructions, including all those contained in component manufacturers manuals
which are provided with the boiler before installing, starting-up, operating, maintaining or servicing this
boiler. Keep this manual and literature in legible condition and posted near boiler for reference by owner
and service technician.
This boiler requires regular maintenance and service to operate safely. Follow the instructions contained
in this manual.
Installation, maintenance, and service must be performed only by an experienced, skilled and knowledgeable
installer or service agency.
All heating systems should be designed by competent contractors and only persons knowledgeable in
the layout and installation of hydronic heating systems should attempt installation of any boiler.
Installation is not complete unless a pressure relief valve is installed as shown in Figure 8.1 located in
Section VIII, “System Piping” of this manual.
It is the responsibility of the installing contractor to see that all controls are correctly installed and are
operating properly when the installation is completed.
This boiler is suitable for installation on combustible ooring. Do not install boiler on carpeting.
Do not tamper with or alter the boiler or controls.
Inspect ueways at least once a year - preferably at the start of the heating season. The inside of the
combustion chamber, the vent system and boiler ueways should be cleaned if soot or scale has accumulated.
When cleaning this boiler, take precaution to avoid damage to burner swing door insulation. If damaged,
or if there is evidence of previous damage, burner swing door insulation must be replaced immediately.
Oil Burner and Controls must be checked at least once a year or as may be necessitated.
Do not operate boiler with jumpered or absent controls or safety devices.
Do not operate boiler if any control, switch, component, or device has been subject to water.
Boiler construction materials, products of combustion and the fuel contain alumina, silica, heavy metals,
carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which can cause
death or serious injury and which are known to the state of California to cause cancer, birth defects and
other reproductive harm. Always use proper safety clothing, respirators and equipment when servicing
or working nearby the appliance.
This boiler contains very hot water under high pressure. Do not unscrew any pipe ttings nor attempt
to disconnect any components of this boiler without positively assuring the water is cool and has no
pressure. Always wear protective clothing and equipment when installing, starting up or servicing this
boiler to prevent scald injuries. Do not rely on the pressure and temperature gauges to determine the
temperature and pressure of the boiler. This boiler contains components which become very hot when
the boiler is operating. Do not touch any components unless they are cool.
2
Page 5
WARNINGS FOR THE HOMEOWNER
FOLLOW ALL INSTRUCTIONS and warnings printed
in this manual and posted on the boiler.
INSPECT THE BOILER, BURNER AND CONTROLS
ANNUALLY. To keep your boiler safe and ecient,
have a service technician follow the Service
checklist near the end of this manual.
IF YOU ARE NOT QUALIFIED to install or service
boilers, do not install or service this one.
THE BOILER MAY LEAK WATER at the end of its
useful life. Be sure to protect walls, carpets, and
valuables from water that could leak from the boiler.
PROTECT YOUR HOME IN FREEZING WEATHER.
A power outage, safety lockout, or component
failure will prevent your boiler from lighting. In
winter, your pipes may freeze and cause extensive
property damage. Do not leave the heating system
unattended during cold weather unless alarms
WARNINGS FOR THE INSTALLER
READ THIS ENTIRE MANUAL before attempting
installation, start-up, or service. Improper
installation, adjustment, alteration, service, or
maintenance may cause serious property damage,
personal injury, or death.
DO NOT DISCONNECT PIPE FITTINGS on the boiler
or in the heating system without rst verifying that
the system is cool and free of pressure and that
your clothing will protect you from a release of hot
water or steam. Do not rely solely on the boiler’s
temperature and pressure gauge when making this
judgment.
USE PROPER PERSONAL PROTECTION
EQUIPMENT when servicing or working near the
boiler. Materials of construction, ue products, and
fuel contain alumina, silica, heavy metals, carbon
monoxide, nitrogen oxides, and/or other toxic or
harmful substances that can are hazardous to
health and life and that are known to the State of
California to cause cancer, birth defects, and other
reproductive harm.
or other safeguards are in place to prevent such
damage
DO NOT BLOCK AIR FLOW into or around the boiler.
Insucient air may cause the boiler to produce
carbon monoxide or start a re.
KEEP FLAMMABLE LIQUIDS AWAY from the boiler,
including paint, solvents, and gasoline. The boiler
may ignite the vapors from the liquids causing
explosion or re.
KEEP CHILDREN AND PETS away from hot surfaces
of the boiler, boiler piping, and vent pipe.
CARBON MONOXIDE (CO) is an odorless, deadly
gas that may be introduced into your home by
any malfunctioning fuel-burning product or vent
system failure. Consider installing CO alarms near
bedrooms in all levels of the building to warn you
and your family of potential CO exposure.
INSTALL ALL GUARDS, cover plates, and
enclosures before operating the boiler.
SIZE THE BOILER PROPERLY relative to the design
heat load or, if using domestic hot water priority,
the peak hot water load, whichever is larger. A
grossly oversized boiler will cycle excessively and
this will lead to premature failure of the boiler and
its components. Our warranty does not apply to
damage from excessive cycling.
ADHERE TO ALL LOCAL CODE REQUIREMENTS.
Contact your local code inspector prior to
installation. In the absence of a local code, adhere to
the latest editions of the Installation of Oil Burning
Equipment ANSI/NFPA 31 in the USA or CAN/CSA
B139, Installation Code for Oil Burning Equipment in
Canada.
ALL WIRING must comply with the National
Electrical Code ANSI/NFPA 70 (in the USA) or the
Canadian Electrical Code CSA C22.1 (in Canada)
and any local regulations.
3
Page 6
WARNING
This boiler must be properly vented. The chimney must be inspected for any obstructions and cleaned
prior to each heating season. A clean and unobstructed chimney ue is necessary to produce the minimum
draft required to safely evacuate noxious fumes that could cause personal injury or loss of life. Evidence
of loose debris and or condensate induced stains at the base of the chimney ue, connector or smokepipe
joints may be signs of condensing ue gases. Flue gas condensate is corrosive, which requires special
consideration and must be addressed immediately. Refer to Section VII, "Venting" in this manual for
more details.
This boiler needs fresh air for safe operation and must be installed so there are provisions for adequate
combustion and ventilation air.
This boiler is supplied with controls which may cause the boiler to shut down and not re-start without
service. If damage due to frozen pipes is a possibility, the heating system should not be left unattended in
cold weather; or appropriate safeguards and alarms should be installed on the heating system to prevent
damage if the boiler is inoperative.
This boiler is designed to burn No. 2 fuel oil only. Do not use gasoline, crankcase drainings, or any oil
containing gasoline. Never burn garbage or paper in this boiler. Do not convert to any solid fuel (i.e.
wood, coal). Do not convert to any gaseous fuel (i.e. natural gas, LP). All ammable debris, rags, paper,
wood scraps, etc., should be kept clear of the boiler at all times. Keep the boiler area clean and free of
re hazards.
All boilers equipped with burner swing door have a potential hazard which, if ignored, can cause severe
property damage, personal injury or loss of life. Before opening swing door, unplug burner power cord
from receptacle located in lower right corner of jacket front panel and turn o service switch to boiler
to prevent accidental ring of burner outside the combustion chamber. Be sure to tighten swing door
fasteners completely when service is completed.
Table of Contents
I. Product Description ............................................................................... 5
II. Specications ......................................................................................... 5
III. Before Installing .................................................................................... 7
IV. Field Assembly ...................................................................................... 8
V. Locating the Boiler ................................................................................ 11
VI. Air for Combustion & Ventilation ......................................................... 12
VII. Venting ................................................................................................... 16
VIII. System Piping ........................................................................................ 19
IX. Fuel Line Piping .................................................................................... 24
XI. Start-Up & Checkout ............................................................................. 31
XII. Operation ............................................................................................... 35
XIII. Service & Maintenance .......................................................................... 41
XIV. Troubleshooting ..................................................................................... 44
XV. Parts ....................................................................................................... 49
4
Page 7
I Product Description
The FWZ series boiler is a cast iron oil-red water boiler designed for use in closed forced circulation heating systems. This
boiler must be vented by natural draft into a lined masonry or metal chimney, or Type L vent. An adequate supply of air for
combustion, ventilation and dilution of ue gases must be available in the boiler room.
II Specications
TABLE 2.0: GENERAL SPECIFICATIONS
DIMENSIONSWATER
MODEL
FWZ06016-1/4”24”5”7.7013.29430
FWZ08016-1/4”24”5”7.7013.29430
FWZ08122-1/4”24”6”11.0820.29545
FWZ10022-1/4”24”6”11.0820.29545
FWZ13028-1/4”30”6”14.4627.29658
FWZ16034-1/4”36”7”17.8434.29771
‘A’‘B’‘C’
CONTENT
(GAL)
HEAT TRANSFER
SURFACE AREA
(SQ FT)
SHIPPING
WEIGHT
(LBS)
Maximum working pressure, Water - 50psi
TABLE 2.1: RATING DATA
FWZ Series
AHRI Ratings
BURNER
INPUT
MODEL*
GPHMBH
FWZ0600.6084736386.068 X 815
FWZ0800.80112978486.368 X 815
FWZ0810.80112998687.068 X 815
FWZ1001.0014012310787.068 X 815
FWZ1301.3018216013987.078 X 815
FWZ1601.6022219717187.078 X 815
Burner Capacity Rating, GPH is based on #2 fuel oil with a Gross Heating Value equal to 140,000 BTU/Gal.
* Net Ratings are based on piping and pick-up allowances of 1.15
HEATING
CAPACITY
(MBH)
NET AHRI
RATING*
(MBH)
AFUE
(%)
Other Specications
MINIMUM CHIMNEY
REQUIREMENTS
ROUND
IN. DIA.
SQUARE.
TILE SIZE
HEIGHT
FT.
5
Page 8
BURNER SWING
DOOR CLEARANCE
(FULLY OPEN)
NOTE: THIS DIMENSION INCREASES AND
OBSERVATION
TEMP/PRESSURE
BURNER
BECKETT AFG
SUPPLY PIPING
CONNECTION
IS CONTROLLED BY SMOKEPIPE
ARRANGEMENT.
*
CIRCULATOR
LINE
"
8
3
21
FLOOR
1-1/2"
RETURN
PIPING
REAR
12" MIN.
SERVICE
*
'A'
COMBINATION
RELIEF
VALVE
COVER
CLEAN OUT
'C' DIA.
COLLAR
CLEARANCE
SMOKEBOX
COLLAR
DRAIN VALVE
SPANNER BAR
RIGHT VIEWFRONT VIEWREAR VIEW
LIMIT/LWCO
'B' MIN.
CLEARANCE
FRONT SERVICE
(FLUEWAY CLEANING)
"
2
1
31
TOP VIEW
1-1/2" FPT
6
GAUGE
BURNER
SWING
DOOR
PORT
FLAME
"
3
4
20
19"
* Circulator Supplied Loose - May Be Installed On Supply Or Return.
FIGURE 2.3: GENERAL CONFIGURATION *
Page 9
III Before Installing
1) Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict accordance with
this manual and the requirements of the authority having jurisdiction.
• In the absence of an authority having jurisdiction, installation must be in accordance with this manual and the latest
edition of Installation of Oil Burning Equipment (ANSI/NFPA31). Installations in Canada comply with the requirements
of CSA B139-04 – Installation Code for Oil-burning Equipment.
• Where required by the authority having jurisdiction, this installation must conform to the latest edition of Standard for
Controls and Safety Devices for Automatically Fired Boilers (ANSI/ASME CSD-1).
2) Make sure that a properly sized chimney is available which is in good condition. Consult the authority having jurisdiction,
Part VI of this manual, and ANSI/NFPA31 for additional information on venting requirements.
3) Make sure that the boiler is correctly sized:
• For heating systems employing convection radiation (baseboard or radiators) use an industry accepted sizing method
such as the I=B=R Guide RHH published by the Air-Conditioning, Heating and Refrigeration Institute (AHRI).
• For new radiant heating systems refer to the radiant tubing manufacturer’s boiler sizing guidelines.
• For systems including a Crown Mega-Stor indirect water heater, size the boiler to have either the Heating Capacity re-
quired for the Mega-Stor or the I=B=R Net Rating required for the heating system, whichever results in the larger boiler.
• For systems that incorporate other indirect water heaters, refer to the indirect water heater manufacturer’s instructions for
boiler output requirements.
4) In some cases, boilers installed at altitudes above 2000ft may require a dierent burner conguration from that at sea level.
Consult the local Crown representative for more information.
CAUTION
As with all oil-fired appliances, “Power Venting” this boiler creates a number of potential
problems, especially when this is done through a side wall. These include, but are not
necessarily limited to:
• Accelerated rate of soot buildup on the oil burner cad-cell, burner head, and/or in the
boiler itself.
• Odor complaints
• Severe damage to the side of the structure in the event that the boiler operates at a high
smoke level.
These problems can occur for many reasons, some of which are out of the control of both the
installer and the appliance manufacturer. The use of a chimney to vent this boiler is therefore
recommended. If a power venter must be used, it is the responsibility of the installer and power
venter manufacturer to “engineer” the power vent system. CROWN BOILER COMPANY WILL
ASSUME NO RESPONSIBILITY FOR DAMAGE TO SIDING, ETC. FROM A POWER VENTED OILFIRED BOILER. THIS APPLIES REGARDLESS OF THE CAUSE OF THE SOOTING.
7
Page 10
CAUTION
Fuel oil used with this boiler must conform to ASTM D396. The ASTM D396 standard sets a
5% limit on biodiesel concentration, requires that the biodiesel feedstock comply with ASTM
D6751, and also specifies the procedure that must be used to blend the biodiesel feedstock
with the #2 fuel oil. Attempts to use biodiesel blends not meeting all ASTM D396 requirements
may result in unreliable operation or severe property damage.
IV Field Assembly
This boiler is shipped in two pieces:
a) The crated boiler itself with the following loose parts either packed in the combustion chamber or glued to the skid:
• Barometric Draft Regulator (if supplied)
• Circulator (if supplied)
• Relief valve
• Pipe Fittings
b) The burner carton consisting of the following items:
• Oil Burner assembly
• Baes in some cases (see Table 4.1)
• Refractory blanket in some cases (see Table 4.1)
It is recommended that the boiler be moved to its nal location before the items in the burner carton are installed. To complete
eld assembly:
WARNING
Installation of burners on the FWZ other than those provided by Crown, and marked for use
with this boiler, may result in unreliable operation, property damage, personal injury, or loss of
life.
1) Make sure that the burner carton supplied is the correct one for the boiler. The crate tag on the boiler lists the Crown part
numbers for the burner cartons that may be used with it.
2) Remove the burner mounting bolts and washers from the front door. Make sure that the burner gasket is in place and undamaged and mount the burner to the door.
3) Plug the burner cord into the receptacle on the lower right front corner of the boiler as shown in Figure 4.0
4) Install the barometric draft regulator, and other piping/trim, as described in the Venting and Piping sections of this manual.
5) Dierent bae arrangements are used based on the boiler size and choice of burner. In some cases these bafes are included in the boiler and in other cases they are provided in the burner carton. In addition, some models use a refractory blanket which is shipped in the burner carton and which must be installed in the combustion
c h a m b e r. F i n a l l y, i n s o m e c a s e s b u r n e r s a r e s u p p l i e d w i t h i n s u l a t i o n w r a p p e d a r o u n d t h e i n s e r t e d b u r n e r t u b e .
Table 4.3 summarizes the use of baes, blankets, and burner tube insulation.
6) Attach the model-specic rating plate for the specic boiler model that is provided in the burner box to the left of the
permanent rating plate already on the boiler (Figure 4.0). Note that some burner boxes may contain rating plates for both
water and steam models; be sure to select the appropriate FWZ series rating plate. Before applying the rating plate clean the
area where it is to be applied with a clean, dry lint free cloth.
8
Page 11
FIGURE 4.0: RATING PLATE LOCATION
TABLE 4.1: BASIC BOILER CONFIGURATIONS
Model
Boiler
Part No.
FWZ060FWZ002
FWZ080FWZ002
FWZ081FWZ003
FWZ081FWZ003
FWZ081FWZ003
FWZ100FWZ003
FWZ100FWZ003
FWZ100FWZ003
FWZ130FWZ004
FWZ130FWZ004
FWZ130FWZ004
FWZ160FWZ005
FWZ160FWZ005
FWZ160FWZ005
Burner
1
Beckett
1
Beckett
1
1
1
1
1
1
1
1
1
1
1
1
2
2
Beckett41081BYes
Riello41081RYe s
Carlin41081CYes
Beckett41100BNoNoNoYes
Riello41100RNoNoNoYe s
Carlin41100CYes
Beckett41130BNoNoNoYe sNo
Riello41130RNoNoNoYe sNo
Carlin41130CYes
Beckett41160BNoNoNoYe sNo
Riello41160RNoNoNoYe sNo
Carlin41160CYes
Burner
Carton
Blanket
Part #
41060BNoNoNoNoYes
41080BNoNoYes
3
3
3
3
3
3
1 Boiler PN may contain additional characters after those shown to designate other options
2 FWZ060 and FWZ080 not available with Carlin or Riello Burner.
3 Included in burner box.
Burner
Insulation
Tube
2nd Pass
Bae
(410009)
3
2nd Pass
Bae
(410008)
NoYes
3rd Pass
Bae
(410007)
NoNoNoYe s
YesNoNoYes
YesNoNoYes
3
3
YesNoYes
3
YesNoYesYes
YesNoYesYes
No
No
Yes
3
3
3
3
3
3
Figure 4.2 identies the type and location of baes. When used, lay the refractory blanket in the combustion chamber with
the 19-1/2” side oriented as shown in Figure 4.2. Line the front edge of the blanket up with the edge of the combustion chamber.
The blanket should run the entire length of the chamber. No adhesive is required to hold the blanket in place.
When required, burner tube insulation is applied at the factory and secured in place with masking tape. This tape is only needed
to hold the insulation in place while the burner is being installed through the door. After installation, the tape will harmlessly burn
away and the insulation will be secured by the door refractory.
• Do not omit the blanket when called for in the table above.
• Do not add any extra baffles beyond those prescribed for the model/burner combination
shown in Table 4.1.
Doing either of these things could cause accelerated chimney deterioration due to
condensation or inadequate draft resulting in severe property damage, personal injury or
death.
WARNING
9
Page 12
FIGURE 4.2: BAFFLE AND BLANKET INSTALLATION
10
Page 13
V Locating the Boiler
WARNING
Failure to observe the following location requirements could result in property damage, a fire,
explosion or carbon monoxide (CO) hazard.
1) Clearances:
• Observe the minimum clearances shown below. Except as noted, these clearances apply to all combustible construction,
as well as noncombustible walls, ceilings and doors. Also see Figure 5.0.
Front - 24” (from front Jacket surface)
Left Side – 6”
Right Side – 6”
Rear – 12”
Top – 6”
Single Wall Chimney Connector (to combustible construction) - 18”
• A 24” service clearance is recommended above the top of the boiler, as well as on the side to which the burner swing
door opens (the left side as the boiler is shipped). See also dimension ‘B’ in Table 2.0 for recommended service clearances to the front of the boiler. These clearances may be reduced to those shown above; however, servicing the boiler
will become increasingly dicult as these clearances are reduced.
FIGURE 5.0: CLEARANCES
11
Page 14
1) Do not install this boiler directly on a combustible oor. Where it is desired to install an FWZ on a non-carpeted combustible
oor, install the boiler on a base constructed as shown in Figure 5.1
2) If listed Type L vent is used, follow vent pipe manufacturer recommendations for minimum clearances.
3) Do not install this boiler in a location where gasoline or other ammable vapors or liquids will be stored or used. Do not
install this boiler in an area where large amounts of airborne dust will be present, such as a workshop.
FIGURE 5.1: INSTALLATION OVER A COMBUSTIBLE FLOOR
VI Air for Combustion and Ventilation
Sucient fresh air must be supplied for combustion and ventilation. Provisions for combustion and ventilation air for oil
burning equipment must be made in accordance with the Standard for the Installation of Oil Burning Equipment (ANSI/NFPA
31).
To ensure an adequate supply of air for combustion, ventilation and ue gas dilution, start by determining whether adequate
combustion and ventilation air can be obtained through natural inltration (air leaking into the building through cracks around
windows, doors, etc). Examples of construction features which could prevent adequate natural inltration include:
• Walls and ceilings exposed to outside atmosphere having a continuous water vapor retarder with a rating of 1 perm or
less with openings gasketed and sealed
• Weather stripping added on openable windows and doors
• Caulking and sealants are applied to areas such as joints around window and door frames, between sole plates and oors,
between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other
openings.
• Large exhaust fans
In this manual, buildings where natural inltration will not provide adequate air for combustion, and ventilation are referred to
as “buildings of unusually tight constuction”. If in doubt, assume that the building in which the boiler is installed is of unusually
tight construction.
12
Page 15
A. For Buildings of Other than Unusually Tight Construction
1) Determine whether the boiler is to be installed in a conned space - A conned space is dened as having a volume less
than 50 cubic feet per 1000 BTU/hr input of all appliances installed in that space. To determine whether the boiler room is a
conned space:
a) Total the input of all appliances in the boiler room in thousands of BTU/hr. Round the result to the next highest 1000
BTU/hr.
b) Find the volume of the room in cubic feet. The volume of the room in cubic feet is:
Length (ft) x width (ft) x ceiling height (ft)
In calculating the volume of the boiler room, consider the volume of adjoining spaces only if no doors are installed
between them. If doors are installed between the boiler room and an adjoining space, do not consider the volume of the
adjoining space, even if the door is normally left open.
c) Divide the volume of the boiler room by the input in thousands of BTU/hr. If the result is less than 50, the boiler room is
a conned space.
Example:
An FWZ080 and a water heater are to be installed in a room measuring 6 ft - 3 in x 7 ft with an 8 ft ceiling. The
water heater has an input of 30000 BTU/hr:
Input of FWZ080 = 0.80 Gal/hr x 140000 BTU/Gal = 112000BTU/hr
Total input in thousands of BTU/hr = (112000 BTU/hr + 30000 BTU/hr)/1000 = 142
Volume of room = 6.25 ft x 7 ft x 8 ft = 350 ft
350/142 = 2.46. Since 2.46 is less than 50, the boiler room is a conned space.
3
2) Unconned Space - Natural inltration into the boiler room will normally provide adequate air for combustion and ventilation without additional louvers or openings into boiler room.
3) Conned Space - Provide two openings into the boiler room, one near the oor and one near the ceiling. The top edge of the
upper opening must be within 12” of the ceiling and the bottom edge of the lower opening must be within 12” of the oor
(Figure 6.0).
• Each opening must have a free area of 1 square inch per 1000 BTU/hr input of all fuel burning appliances in the boiler
room. The minimum opening dimension is 3 inches. Minimum opening free area is 100 square inches per opening.
• If the total volume of both the boiler room and the room to which the openings connect is less than 50 cubic feet per
1000 BTU/hr of total appliance input, install a pair of identical openings into a third room. Connect additional rooms
with openings until the total volume of all rooms is at least 50 cubic feet per 1000 BTU/hr of input.
• The “free area” of an opening takes into account the blocking eect of mesh, grills, and louvers. Where screens are
used, they must be no ner than ¼” (4 x 4) mesh.
B. For Buildings of Unusually Tight Construction
1) Openings must be installed between the boiler room and the outdoors or a ventilated space, such as an attic or crawl space,
which communicates directly with the outdoors.
2) Two openings are required. The top edge of the upper opening must be within 12 inches of the ceiling. The bottom edge of
the lower opening must be within 12 inches of the oor.
3) Size openings and ducts as follows:
• Vertical ducts or openings directly outdoors (Figure 6.1, Figure 6.2, and Figure 6.3) - Each opening must have a free
cross sectional area of 1 square inch per 4000 BTU/hr of the total input of all fuel red appliances in the boiler room but
not less than 100 square inches. Minimum opening size is 3 inches.
• Openings to outdoors via horizontal ducts (Figure 6.4) - Each opening must have a free cross sectional area of 1 square
inch per 2000 BTU/hr of the total input of all fuel red appliances in the boiler room but not less than 100 square inches.
Minimum opening size is 3 inches.
• The “free area” of an opening takes into account the blocking eect of mesh, grills, and louvers. Where screens are
used, they must be no ner than ¼” (4 x 4) mesh.
13
Page 16
FIGURE 6.0: BOILER INSTALLED IN CONFINED SPACE, ALL AIR FROM INSIDE
FIGURE 6.1: ALL AIR FROM OUTDOORS, VENTILATED CRAWL SPACE AND ATTIC
14
Page 17
FIGURE 6.2: ALL AIR FROM OUTDOORS, VIA VENTILATED ATTIC
FIGURE 6.3: ALL AIR FROM OUTDOORS, USING OPENINGS INTO BOILER ROOM
15
Page 18
FIGURE 6.4: ALL AIR FROM OUTDOORS, USING HORIZONTAL DUCTS INTO BOILER ROOM
VII Venting
WARNING
• Improper venting may result in property damage and/or the release of flue gases, which
contain deadly carbon monoxide (CO), into the home, which can cause severe personal
injury or death.
• Inspect existing chimney before installing boiler. Failure to clean or replace damaged pipe
or tile lining will cause property damage, severe personal injury or death.
• Do not de-rate the appliance. Failure to fire the unit at it’s designed input may cause
excessive condensation upon the interior walls of the chimney. In addition, the lower input
may not create enough draft to adequately evacuate the products of combustion.
• Do not omit the blanket when called for in the table above.
• Do not add any extra baffles beyond those prescribed for the model/burner combination
shown in Table 4.1.
Doing either of these things could cause accelerated chimney deterioration due to condensation or inadequate draft resulting in severe property damage, personal injury or death.
16
Page 19
The vent installation must be in accordance with local building codes, or the local authority having jurisdiction. Contact your
local re and building ocials on specic requirements for restrictions and the installation of fuel oil burning equipment. In
the absence of other applicable codes, the vent system installation must meet the requirements of NFPA 31 – Standard for the
Installation of Oil-Burning Equipment and NFPA 211 - Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning
Appliances. Vent systems in Canada must comply with CSA B139-04 – Installation Code for Oil-burning Equipment.
A typical vent system is illustrated in Figure 7.0. The components of the vent installation are the vent connector (breeching),
barometric draft regulator, and chimney.
1) Acceptable Chimneys - The following chimneys may be used to vent a FWZ series boiler:
• Listed Type L vent - Install in accordance with the manufacturer’s instructions, the terms of its listing, and applicable
codes.
• Masonry Chimney - The masonry chimney must be constructed in accordance with the latest edition of Standard for
Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances (NFPA 211) and lined with a clay liner or other listed
lining system. Do not vent a FWZ series boiler into an unlined chimney.
2) Acceptable Vent Connectors - The following may be used for vent connectors:
• Listed Type L vent.
• Single Wall Galvanized Pipe - Use 0.018” (26 gauge) or heavier.
3) Chimney and Vent Connector Sizing - See Table 7.1 for minimum vent connector and chimney sizing. The vent connector
size must not be smaller than boiler ue collar diameter.
4) Do not vent this appliance into any portion of a mechanical vent system operating under positive pressure.
5) Do not connect the boiler into a chimney ue serving an open replace or other solid fuel appliance.
6) Prior to boiler installation, an existing chimney must be inspected by a qualied person in accordance with the requirements
of Chapter 11 of NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances. This inspection is
intended to identify safety problems with the chimney such as obstructions, a missing or damaged liner, or leak points. Clean
chimney as necessary and correct any other chimney defects before installing the boiler.
7) Vent connector must slope upward from boiler not less than one inch in four feet. No portion of vent pipe should run
downward or have sags. Vent connector must be securely supported.
8) The vertical section of vent connector coming o the boiler should be as tall as possible, while still maintaining the proper
clearance from the horizontal vent connector to combustibles and the proper pitch called for in (7) above.
9) Vent connector must be installed above the bottom of the chimney to minimize risk of blockage.
10) Vent connector must be inserted ush with inside face of the chimney liner and the space between vent connector and
chimney sealed tight. A thimble permanently cemented in place can be used to facilitate removal of vent connector for
cleaning.
11) Install the barometric draft regulator supplied with this boiler in accordance with the regulator manufacturer’s instructions.
No other draft regulator shall be used. Mount the barometric draft regulator in the side connection of a tee (not supplied).
12) Secure all joints in the vent connector system with sheet metal screws. This includes the joint between the vent connector and
the boiler collar (see Figure 7.0, Detail ‘A’), as well as the barometric draft regulator. Use at least three screws at each joint.
17
Page 20
FIGURE 7.0: TYPICAL VENT SYSTEM INSTALLATION AND COMPONENTS
TABLE 7.1: MINIMUM RECOMMENDED BREECHING AND CHIMNEY SIZE
BOILER
MODEL
FWZ060568 X 815
FWZ080568 X 815
FWZ081568 X 815
FWZ100668 X 815
FWZ130678 X 815
FWZ160778 X 815
MINIMUM
BREECHING
DIA. (INCHES)
MINIMUM CHIMNEY REQUIREMENTS
ROUND I.D.
(IN.)
SQUARE. TILE
SIZE (NOMINAL)
18
HEIGHT (FT.)
Page 21
VIII System Piping
WARNING
• Install boiler so that the electrical components are protected from water (dripping, spraying,
rain, etc.) During appliance operation and service (circulator replacement, etc.).
• Operation of this boiler with continuous return temperatures below 135°f can cause severe
boiler or chimney damage.
• Do not operate this boiler at a flow rate less than the minimum shown in Table 8.0, Column
(a).
• Operation of this boiler in a system having significant amounts of dissolved oxygen can
cause severe heat exchanger corrosion damage.
• Do not use toxic additives, such as automotive antifreeze, in a hydronic system.
• Pipe relief valve discharge to a safe location. The relief valve may discharge scalding hot
water.
• Do not install a valve in the relief valve discharge line.
• Do not move relief valve from factory location.
• Do not plug relief valve discharge. Blocking the relief valve may result in boiler explosion.
A. Standard Piping
Figure 8.2 shows typical boiler system connections on a single zone system. Additional information on hydronic system design
may be found in the I=B=R Guide RHH published by the Air-Conditioning, Heating and Refrigeration Institute (AHRI). The
components in this system and their purposes are as follows:
1) Relief valve (Required) - Mount the relief valve on the rear of the boiler as shown in Figure 8.1 using the ttings provided.
The relief valve shipped with the boiler is set to open at 30 psi. This valve may be replaced with one having a pressure up to
the “Maximum Allowable Working Pressure” shown on the rating plate. If the valve is replaced, the replacement must have a
relief capacity in excess of the heating capacity for the boiler.
Pipe the discharge of the relief valve to a location where water or steam will not create a hazard or cause property damage
if the valve opens. The end of the discharge pipe must terminate in an unthreaded pipe. If the relief valve discharge is not
piped to a drain, it must terminate at least 6 inches above the oor. Do not run relief valve discharge piping through an area
that is prone to freezing. The termination of the relief valve discharge piping must be in an area where it is not likely to
become plugged by debris.
2) Return Injector Pipe - The return injector distributes water evenly throughout the heat exchanger and also helps to minimize
the possibility of thermal shock. Install it in the upper-rear tapping as shown in Figure 8.1. The 2 x 1-1/2” reducing elbow can
be oriented in any direction.
3) Circulator (Required) - Figure 8.2 shows the ideal location of the circulator which is in the supply piping immediately
downstream of the expansion tank. A less ideal, but acceptable, location for most residential circulators is in the return. The
circulator/s and connected piping should be sized so that the temperature rise across the boiler is 20F. Burner operation while
the ow through the boiler is less than that shown in Table 8.0, column (a) could result in problems regulating the supply
temperature. If the system is zoned, the ow rate through the boiler should be greater than that shown in Table 8.0 when only
the zone having the lowest ow rate is on. If this requirement cannot otherwise be met, use a bypass, or primary-secondary
piping. Boiler head loss data at the minimum ow and the ow corresponding to a 20F rise are shown in Table 8.0.
4) Expansion Tank (Required) - If this boiler is replacing an existing boiler with no other changes in the system, the old
expansion tank can generally be reused. If the expansion tank must be replaced, consult the expansion tank manufacturer’s
literature for proper sizing.
19
Page 22
5) Fill Valve (Required) - Either a manual or automatic ll valve may be used. The ideal location for the ll is at the expansion
tank.
6) Automatic Air Vent (Required) - At least one automatic air vent is required. Manual vents will usually be required in other
parts of the system to remove air during initial ll.
7) Low Water Cut-O (Required in some situations) - A low water cut-o is required when the boiler is installed above
radiation. In addition, some codes such as ASME CSD-1, require low water cut-os. Codes may also require that this low
water cut-o have a manual reset function. The low water cut-o may be a oat type or probe type, but must be designed
for use in a hot-water system. The low water cut-o should be piped into the boiler supply just above the boiler with no
intervening valves between it and the boiler. Use a low water cut-o that breaks the 120 VAC supply to the boiler. Do not
attempt to wire a 24-volt low water cut-o into the boiler factory wiring.
8) Manual Reset High Limit (Required by some codes) - This control is required by ASME CSD-1 and some other codes. Install
the high limit in the boiler supply piping just beyond the boiler with no intervening valves. Set the manual reset high limit as
far above the operating limit setting as possible, but not over 240°F. Wire the control to break the 120 VAC electrical supply
to the boiler.
9) Flow Control Valve (Required under some conditions) - The ow control valve prevents ow through the system unless the
circulator is operating. A ow control valve may be necessary on converted gravity systems to prevent gravity circulation.
Flow control valves are also used to prevent “ghost ows” in circulator zone systems through zones that are not calling for
heat.
10) Isolation Valves (Optional) - Isolation valves are useful if the boiler must be drained, as they will eliminate having to drain
and rell the entire system.
11) Drain Valve - The drain valve is shipped in the boiler parts bag. Install it in the bottom-rear of the boiler return as shown in
Figure 8.1.
Table 8.0 Minimum Flow Rate Requirements
Minimum Flow
(Approx 35F Rise)*
Flow at 20F Rise
(a)(c)(d)(e)
Model
Min. Flow
(Gal /Min)
Boiler Head
Loss (ft w.c.)
Flow
(GPM)
Boiler Head
Loss (ft w.c.)
FWZ0604.50.107.30.22
FWZ0806.00.169.70.38
FWZ0818.00.279.90.40
FWZ1008.00.2712.30.61
FWZ13010.00.4216.00.88
FWZ16012.00.6119.71.45
* Approximate 25°F Rise for FWZ081
20
Page 23
FIGURE 8.1: INSTALLATION OF FACTORY SUPPLIED PIPING
FIGURE 8.2: STANDARD BOILER PIPING
21
Page 24
B. Piping for Special Situations
Certain types of heating systems have additional requirements. Some of the more common variations follow:
1) Indirect Water Heaters - Figure 8.3 shows typical indirect water heater piping. Boiler piping is the same as for any two zone
system. Figure 8.3 shows circulator zoning, which is usually preferred for indirect water heaters. Size the circulator and
indirect water heater piping to obtain the boiler water ow through the indirect water heater called for by the indirect water
heater manufacturer.
2) Large Water Volume Systems - The piping shown in Figure 8.4 will minimize the amount of time that the boiler operates
with return temperatures below 135°F on these systems. A bypass is installed as shown to divert some supply water directly
into the return water. The bypass pipe should be the same size as the supply. The two throttling valves shown are adjusted so
that the return temperature rises above 135°F during the rst few minutes of operation. A three-way valve can be substituted
for the two throttling valves shown. A bypass can also be used to ensure that the minimum ow requirement in Table 8.0 is
met.
3) Systems Containing Oxygen - Many hydronic systems contain enough dissolved oxygen to cause severe corrosion damage to
a cast iron boiler such as the FWZ. Some examples include:
• Radiant systems that employ tubing without an oxygen barrier.
• Systems with routine additions of fresh water.
• Systems which are open to the atmosphere.
If the boiler is to be used in such a system, it must be separated from the oxygenated water being heated with a heat
exchanger as shown in Figure 8.5. Consult the heat exchanger manufacturer for proper heat exchanger sizing as well as ow
and temperature requirements. All components on the oxygenated side of the heat exchanger, such as the pump and expansion
tank, must be designed for use in oxygenated water.
4) Air Handlers - Where the boiler is connected to air handlers through which refrigerated air passes, use ow control valves in
the boiler piping or other automatic means to prevent gravity circulation during the cooling cycle.
FIGURE 8.3: INDIRECT WATER HEATER BOILER SIDE PIPING
22
Page 25
FIGURE 8.4: BYPASS PIPING
FIGURE 8.5: ISOLATION OF BOILER FROM SYSTEM WITH A HEAT EXCHANGER
23
Page 26
IX Fuel Line Piping
WARNING
• Under no circumstances can copper with sweat style connectors be used.
• Do not use compression fittings.
• Oil piping must be absolutely airtight or leaks or loss of prime may result.
• Some jurisdictions require the use of a fusible shutoff valve at the tank and/or the burner.
In addition, some jurisdictions require the use of a fusible electrical interlock with the
burner circuit. Check your local codes for special requirements.
Fuel line piping design, materials and construction must be in accordance with local building codes, requirements of the local
authority having jurisdiction, and, the latest edition of the Standard for the Installation of Oil-Burning Equipment (ANSI/NFPA
31) in the United States and CSA B139-04 for installation in Canada. Refer also to the instruction manuals provided with the
burner and oil pump.
Depending on the location of the fuel oil storage tank in relation to an oil burner, there are four types of oil piping systems that
may be encountered:
a) ONE-PIPE GRAVITY SYSTEM - Used when a fuel oil storage tank is positioned above an oil burner fuel pump. See
Figure 9.0. A vertical distance from top of the tank to center line of the pump (Dimension ‘H’) over 8 feet will result in a
pump inlet pressure in excess of the 3-psi limit in NFPA-31.
b) ONE-PIPE LIFT SYSTEM (not recommended) - Used when a fuel oil storage tank is located below an oil burner fuel
pump. See Figure 9.1. The vertical distance from bottom of the tank to center line of the pump (Dimension ‘H’) must not
exceed that shown in the pump manufacturer’s instructions. Although all oil piping systems must be airtight, one-pipe lift
systems are particularly susceptible to nuisance lockout problems if the suction line is not completely airtight. A two-pipe
lift system is therefore preferred to a one-pipe lift system.
c) TWO-PIPE GRAVITY SYSTEM (not recommended) - A vertical distance from top of the tank to center line of the pump
(Dimension ‘H’) over 8 feet will result in a pump inlet pressure in excess of the 3-psi limit in NFPA-31. This type of
system should be converted to a one-pipe gravity system, as doing so will result in lower inlet line ow and longer lter
life.
d) TWO-PIPE LIFT SYSTEM - Used when a fuel oil storage tank is located below an oil burner fuel pump suction port.
See Figure 9.3. The vertical distance from bottom of the tank to center line of the pump (Dimension ‘H’) must not
exceed that shown in the pump manufacturer’s instructions. The maximum permissible distance ‘H’ allowed is reduced
by the number of ttings, lters and valves installed in the line.
Once the type of system has been selected, observe the following:
1) Fuel line piping must be airtight. Do not use compression type ttings for tubing connections in fuel line piping. Use only
listed are type ttings. Cast iron threaded ttings shall not be used.
2) Piping shall be substantially supported and protected against physical damage and corrosion.
3) Refer to supplied oil pump instruction manual for proper connections. On one-pipe systems, ensure that the fuel pump return
port plug is tightened securely.
4) Some fuel pumps, such as the Suntec A and B series, are supplied with a loose bypass plug which must be installed on twopipe systems. If such a plug is supplied, install it as shown in the pump manufacturer’s instructions. Do not install this bypass
plug on one-pipe systems as pump seal damage will result.
5) Do not use check valves, especially on gravity feed systems.
6) Do not use Teon tape for threaded connections. Use a non-hardening thread sealant listed for use with #2 fuel oil .
24
Page 27
7) Attach required piping between burner fuel pump and fuel oil storage tank. Install one fuel shut-o valve near the storage
tank and second fuel shut-o valve near the oil burner fuel pump. Use a continuous run of copper tubing having a minimum
wall thickness of 0.032”. On two-pipe systems, the return line should terminate 3” - 4” above suction line depth within the
storage tank. Refer to the pump manufacturer’s instructions for tube sizing information.
8) Never install manual shut-o valves in the return piping of a two-pipe system.
9) Install a listed exible oil line/s at the burner to facilitate opening of the boiler’s swing door.
10) All systems require an oil lter. Use of a high eciency micron lter (Garber or equivalent) in addition to a conventional
lter is highly recommended, particularly on FWZ060 and FWZ080.
11) Use only #2 Fuel Oil with physical and chemical characteristics meeting the requirements of ASTM D-396.
FIGURE 9.0: ONE-PIPE GRAVITY SYSTEM
FIGURE 9.1: ONE-PIPE LIFT SYSTEM
25
Page 28
FIGURE 9.2: TWO-PIPE GRAVITY FEED SYSTEM (NOT RECOMMENDED)
FIGURE 9.3: TWO-PIPE LIFT SYSTEM
26
Page 29
X Wiring
WARNING
• All wiring and grounding must be done in accordance with the authority having jurisdiction
or, in the absence of such requirements, with the
• Disconnect electrical power to the boiler and heating system before servicing. Positively
assure that no voltage is present. Lock electrical boxes to prevent someone from
inadvertently restoring power before the heating system is safe to operate.
• Never defeat or jump out safety devices.
• Protect each boiler circuit with a properly sized over-current protection device.
• Make electrical connections carefully according to the boiler’s wiring diagram and
instructions.
• Wire additional field supplied safety limits, such as low water cutoffs and temperature limit
devices, in series with the 120V circuit used to power the boiler. Do not alter the boiler’s
factory wiring when adding an additional limit device.
1) 120 Volt Wiring - The boiler should be provided with its own 15A branch circuit with fused disconnect. 120VAC power connections are made inside the Hydrolevel 3250-Plus hot water boiler control as follows (also see Figures. 10.0 and 10.1):
National Electrical Code (ANSI/NFPA 70).
• Hot (“black”) - Terminal “L1”
• Neutral (“white”) - Terminal “L2”
• Ground (“green” or bare) - Ground screw on case of 3250-Plus.
The heating circulator is factory wired to the 3250-Plus circulator connections or the boiler is provided with a exible conduit
“whip” that is to be wired to the 3250-Plus circulator connections. If the circulator is not already wired to the control, connect
it as follows:
• Circulator “Hot” - Black wire lead from “whip” to C1
• Circulator “Neutral” - White wire lead from “whip” to C2
2) Low Voltage Connections – Low voltage eld connections are located as shown in Figure 10.0 and 10.1 and are as follows:
• T-T - Connect to a 24 volt heating thermostat or other “dry contacts” (such as a zone panel end switch) that close upon
a call for heat. Follow thermostat manufacturer’s instructions. To insure proper thermostat operation, avoid installation
in areas of poor air circulation, hot spots (near any heat source or in direct sunlight), cold spots (outside walls, walls
adjacent to unheated areas, locations subject to drafts). Provide Class II circuit between thermostat (or zone controls) and
boiler.
3) Adding a Second Circulator Zone - The control provided on this boiler can be used to control a second heating or DHW
circulator zone. If this is done, make the following 120VAC connections in addition to those described above (also see Figure
10.0):
• Connect a 120VAC heating or DHW thermostat for the second zone between ZC and ZR.
• Connect the DHW circulator or the second heating zone circulator between ZR and L2.
See Part XII of this manual for information on conguring the control to respond properly to the DHW or second heating
zone circulator.
27
Page 30
NOTICE
• When making low voltage connections, make sure that no external power source is
present in the thermostat circuits. If such a power source is present, it could destroy the
boiler’s control. One example of an external power source that could be inadvertently
connected to the low voltage connections is a transformer in old thermostat wiring.
• Do not use the transformer provided on the boiler to power external devices such as
zone valves. Doing so may cause damage to the transformer.
28
Page 31
FIGURE 10.0: WIRING CONNECTIONS DIAGRAM FOR HYDROSTAT 3250-PLUS CONTROL
29
Page 32
FIGURE 10.1: CONNECTIONS WIRING DIAGRAM FOR BURNER SPECIFIC PRIMARY CONTROL
30
Page 33
XI Start-up and Checkout
Use the following procedure for initial start-up of the boiler:
WARNING
• Never attempt to fill a hot empty boiler.
• Make sure that the area around the boiler is clear and free from combustible materials,
gasoline, and other flammable vapors and liquids.
• Safe reliable operation of this boiler requires that the burner be checked and adjusted by a
qualified oil serviceman using combustion test instruments.
• Failure to perform all of the checks outlined in the following procedure could result in
unreliable operation, damage to the boiler not covered under warranty, property damage, or
unsafe operation.
• All boilers equipped with burner swing door have a potential hazard which can cause severe
property damage, personal injury or loss of life if ignored. Before opening swing door, turn
off service switch to boiler to prevent accidental firing of burner outside the combustion
chamber. Be sure to tighten swing door fastener completely when service is completed. In
addition, the burner power cord will have to be disconnected from the receptacle in the front
jacket.
1) Ensure that the boiler and entire heating system are lled with water.
2) Check all new piping for leaks and purge all heating system piping of air. Clean heating system if system water is dirty.
3) Verify that the venting system is properly installed and free of obstructions prior to start-up of the boiler. Refer to Section
VII for more information.
4) Inspect all wiring for loose or uninsulated connections, proper size fuses installed, etc.
5) Verify that oil tank is lled with #2 fuel oil meeting ASTM D396 specications, oil piping has been tested and is air
tight, and shuto valve(s) are closed.
6) Check initial settings of oil burner air band and air shutter, head setting etc., and readjust if needed. See Table 11.1 for
setup and combustion data pertaining to a particular boiler/ burner combination.
7) Ensure that burner is tightly secured to the burner swing door creating an airtight seal.
8) Attach plastic hose to oil pump vent tting and provide a container to catch oil during oil pump bleeding procedure.
13) Crack open vent tting on the oil pump and allow burner to run until a solid oil stream, free of air bubbles, ows for
15 seconds into container. As the vent tting is closed, the burner should re and ame should be visible through
observation port immediately (or after prepurge timing has expired, if a burner is so equipped). Refer to burner
instructions for more details.
14) Immediately upon ring the boiler, check the smoke level. If the smoke level is in excess of a #1, open the air adjustment
to bring the smoke level below a #1.
15) Make sure that the oil pressure matches that shown in Table 11.1 for the burner supplied. Adjust pressure if required.
16) Check the vacuum at the inlet of the fuel pump. Make sure that the vacuum does not exceed the fuel pump
manufacturer’s limit (consult the pump manufacturer’s instructions).
17) Close the ame observation cover.
31
Page 34
FIGURE 11.0: FLUE DRAFT TAPPING
18) After chimney has warmed-up for at least 5 minutes, adjust barometric draft regulator to obtain a draft at the 1/4” tapping
shown in Figure 11.0 that is within the range shown in Table 11.1. DRAFT AT THIS LOCATION MUST NEVER BE
POSITIVE.
19) Check the CO2 and conrm that it is between the minimum and maximum limits shown in Table 11.1. Adjust if
necessary.
20) Verify that the smoke level still does not exceed #1 and that the draft in the breech still within the range prescribed by
Table 11.1.
21) Turn o the burner and remove pressure gauge. Install and tighten gauge port plug, then restart the burner.
22) Check for clean cuto of the burner. Air in the oil line between fuel pump and nozzle will compress, while burner is
running, and expand when burner shuts o, causing nozzle drip after burner stops. Cycle burner on and o 5 to 10 times
to purge air completely.
23) Check thermostat operation by raising or lowering its set point as required, cycling burner on and o.
24) Verify primary control operation and safety features according to procedure outlined in the instructions furnished with
the burner.
25) Check high limit control operation. Jump thermostat terminals and allow burner to run until boiler water temperature
exceeds high limit setting. The burner should shut down, and circulator continue running. Allow the temperature to drop
below the control setting. The burner must restart. Boiler installation is not complete unless these checks are made and
are satisfactory. Remove thermostat jumper and reconnect thermostat upon check completion.
26) After the boiler has operated for approximately 30 minutes, check the boiler and heating system for leaks. Repair any
leaks found at once.
27) After the above checks have been completed, leave thermostat(s) at desired setting. Leave all instructions provided with
the boiler with owner or in boiler room, displayed near boiler.
32
Page 35
WARNING
Attempts to use burners or burner configurations other than those shown in Table 11.1 could
result in reliability problems, property damage, personal injury or loss of life.
TABLE 11.1a: BECKETT BURNER CONFIGURATION AND SETUP DATA
BOILER MODELFWZ060FWZ080FWZ081FWZ100FWZ130FWZ160
BURNER MODELAFGAFGAFGAFGAFGAFG
AIR TUBE COMBO70MQASN70MMAQN70MMAQN70MMAQN70MLASN70MLASN
HEAD TYPEL2L1L1L1V1V1
STATIC PLATE3-3/8U3-3/8U3-3/8U3-3/8UNONE2-3/4M
LOW FIRING RATE BAFFLE
INSERTION LENGTH2.0”2.0”2.0”2.0”2.0”2.0”
PITCH ANGLE000000
STANDARD NOZZLE
PUMP PRESSURE (psi)180150150150150150
HEAD SETTINGFIXEDFIXEDFIXEDFIXED01
STARTING:
SHUTTER SETTING
BAND SETTING
DRAFT IN FLUE (in w.c.)0 to -0.020 to -0.020 to -0.020 to -0.020 to -0.020 to -0.02
MAX SMOKE
(Bacharach Scale)
FLUE CO
MIN.
MAX.
(%)
2
BECKETT
SILVER (5880)
DELAVAN
0.50 X 45W
8
0
#1#1#1#1#1#1
11.5
12.8
BECKETT
SILVER (5880)
DELAVAN
0.65 X 60A
10
1
11.5
12.8
BECKETT
SILVER (5880)
DELAVAN
0.65 X 60A
10
1
11.5
12.8
NONENONENONE
DELAVAN
0.85 X 60B
7
1
11.5
12.8
DELAVAN
1.10 X 60B
8
2
11.5
12.8
DELAVAN
1.35 X 60B
9
5
11.5
12.8
TABLE 11.1b: RIELLO BURNER CONFIGURATION AND SETUP DATA
1.35 X 60B
INSERTION LENGTH2.5”10”3.5”2.25”
PUMP PRESSURE (psi)175145150145
TURBULATOR SETTING3.02.04.04.0
AIR GATE SETTING2.42.53.754.0
DRAFT IN FLUE (in w.c.)0 to -0.020 to -0.020 to -0.020 to -0.02
MAX SMOKE
(Bacharach Scale)
FLUE CO
(%)
2
MIN.
MAX.
#1#1#1#1
11.5
12.8
11.5
12.8
11.5
12.8
11.5
12.8
33
Page 36
TABLE 11.1c: CARLIN BURNER CONFIGURATION AND SETUP DATA
BOILER MODELFWZ081FWZ100FWZ130FWZ160
BURNER MODELEZ1-LFEZ1-LFEZ1-LFEZ-66
BLENDER28 HOLENONENONENONE
CARLIN AIR TUBE NUMBER50989509895098951198
STANDARD NOZZLE
DANFOSS
0.60 X 60AS
HAGO
0.75 X 60B
HAGO
1.00 X 45B
HAGO
1.35 X 45B
INSERTION LENGTH2.62”2.62”2.62”2.62”
PITCH ANGLE1°1°1°1°
PUMP PRESSURE (psi)175175175140
HEAD SETTING2235
STARTING AIR BAND SETTING45%35%45%60%
DRAFT IN FLUE (in w.c.)0 to -0.020 to -0.020 to -0.020 to -0.02
MAX SMOKE
(Bacharach Scale)
#1#1#1#1
FLUE CO
MIN.
MAX.
(%)
2
11.5
12.8
11.5
12.8
11.5
12.8
11.5
12.8
34
Page 37
XII Operation
A. General Information
This boiler uses the Hydrolevel Hydrostat® model 3250-Plus control to provide control of boiler water temperature, as well as to
manage demands for up to two circulator zones. In addition, this control also provides protection against low water conditions.
This boiler complies with the 2007 Energy and Independence Security Act, using an “Economy” feature, which raises or lowers
the target boiler water temperature during a call for space heat based on thermostat cycling patterns. For additional information
see Part B of this section.
IMPORTANT
This boiler is equipped with a feature that saves energy by reducing the boiler water
temperature as the heating load decreases. This feature is equipped with an override which
is provided primarily to permit the use of an external energy management system that serves
the same function. THIS OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE
FOLLOWING CONDITIONS IS TRUE:
• An external energy management system is installed that reduces the boiler water
temperature as the heating load decreases.
• This boiler is not used for any space heating.
• This boiler is part of a modular or multiple boiler system having a total input of
300,000 BTU/hr or greater.
• This boiler is equipped with a tankless coil.
FIGURE 12.0 HYDROSTAT 3250-PLUS CONTROL COMPONENT LAYOUT
35
Page 38
B. Setting the Control
NOTE: Settings can be checked using the TEST/SETTINGS button located on the top right of the control. See page 33 for
details.
1) Setting the High Limit - The high limit is factory set at 190°F. To adjust, turn the HI TEMP dial A until the desired setting
is displayed. (Setting range: 100°-220°F) See Figure 12.0.
2) Setting the Low Limit - The low limit is factory set to OFF and should not be adjusted.
NOTICE
For proper operation low limit setting must be at least 10F below high limit setting.
3) Setting the Economy Feature - The Economy Feature is factory set for a 1 zone heating system. To adjust, turn the
ECONOMY Dial D until the number displayed equals the number of heating zones. Do not include indirect water heaters
in the number of heating zones. The Economy Feature conserves fuel by analyzing thermostat activity and continually
evaluating how much heat the house requires. When it is very cold outside, the heat demand is high and the control will
raise the boiler’s target temperature to provide needed heat to the home. When the outside temperature is milder, the heat
demand is lower. During these periods, the control will lower the boiler’s target temperature – saving fuel – while continuing
to provide comfort to the house. If the heating system is unable to supply needed heat to the house, the ECONOMY Dial
should be turned to a lower setting (example: In a three zone house, turn the dial to 2 or 1). Conversely, if the boiler provides
adequate heat, added fuel savings can be achieved by selecting a higher setting (example: 4 or 5). If the heating and indirect
water heater signals were not separated when wiring the control, the Economy Feature should be turned OFF to ensure the
boiler supplies adequate temperature to heat the indirect tank. See Figure 12.0 & Table 12.1.
SETTING
OFF
LO
1
2
3
4
5
HI
4) Setting the Zone/Indirect Switch - See Figure 10.0.
TABLE 12.1 ECONOMY SETTING RECOMMENDATIONS
Disables economy function. Will allow boiler to re until hi limit
temp is reached and re-re with a 10° subtractive dierential.
Provides lowest level of fuel savings. Use this setting only if the
house does not stay warm at higher settings.
Recommended setting for single zone systems
Recommended setting for two zone systems
Recommended setting for three zone systems
Recommended setting for four zone systems
Recommended setting for ve zone systems
Provides highest level of fuel savings
NOTICE
IMPORTANT: When installing with an indirect water heater, the Zone/Indirect Switch must
be set in the I position. When set in the I position, calls to ZC-ZR will bypass the thermal
targeting feature and allow the boiler to fire to the high limit setting to heat the indirect tank.
The indirect signal must be separate from all heating zone signals.
36
Page 39
NOTE: DHW Priority: During a call from an indirect water heater, the control will de-energize the circulator contacts
(C1/C2) to heat only the indirect tank ensuring an adequate supply of domestic hot water. The control will re-energize the circulator when the indirect tank is satised or if the boiler temperature reaches 170°F. If the indirect call continues for 45
minutes, the control will override the priority function energizing the circulator to provide space heating.
C. Optional Features
NOTE: The Program Mode - Pro - is accessed by turning the LO TEMP dial to a position just above OFF.
1) Thermal Pre-Purge - Thermal Pre-Purge is designed to maximize boiler eciency. When activated, the control will supply
latent heat that may remain in the boiler from a previous run cycle to the heating zone that is now calling. The control
monitors how quickly the boiler temperature is declining and activates the burner only when it determines that the latent heat
is insucient to satisfy the call. During the purge cycle, the display will indicate Pur. This feature works with single-zone
and multi-zone heating systems utilizing circulators or zone valves. No change in wiring is needed.
To activate Thermal Pre-Purge
1. Turn the LO TEMP dial to access the Program Mode – indicated in the display as Pro
2. Turn the HI TEMP dial to select feature 1
3. Push the Test/Settings Button to turn Thermal Pre-Purge on or OFF
4. Reset LO TEMP and HI TEMP settings to desired temperatures (see page 28)
2) Degrees Fahrenheit or Celsius - The control has the ability to operate in degrees Fahrenheit or Celsius. When operating in
Celsius, a c will appear in the display next to the temperature whenever the temperature is below 100 degrees.
To change between degrees Fahrenheit and degrees Celsius
1. Turn the LO TEMP dial to access the Program Mode – indicated in the display as Pro
2. Turn the HI TEMP dial to select feature 2
3. Push the Test/Settings Button to c for Celsius or F for Fahrenheit
1. Reset LO TEMP and HI TEMP settings to desired temperatures (see page 28)
3) Manual Reset Low Water Cut-O - The low water cut-o operation on the HydroStat can be set to operate in automatic
(default) or manual reset mode. When in manual reset mode, the control will shut-down the burner immediately when a low
water condition is detected. If the low water condition is sustained for 30 seconds, the low water light will blink, indicating
that the control has locked out the burner. The control can only be reset by pushing the Test Settings button on the top of the
control. The manual reset feature meets CSD-1 code requirements.
To activate Manual Reset LWCO mode
1. Turn the LO TEMP dial to access the Program Mode – indicated in the display as Pro
2. Turn the HI TEMP dial to select feature 3
3. Push the Test/Settings Button to A for Automatic Reset Mode or b for Manual Reset Mode
4. Reset LO TEMP and HI TEMP settings to desired temperatures (see page 28)
To Test the Manual Reset Feature: Press and hold the Test/Settings button located on the top of the control for
30 seconds to simulate a low water condition. After 30 seconds, the Low Water light will blink indicating that the
control is locked out. To reset the lock-out condition, press the Test/Settings button momentarily.
4) Circulator Activation Options - When in the default mode, the control activates the circulator (C1/C2 contacts) on calls to
TT. The control can be programmed to activate the circulator on calls to ZC/ZR in place of, or in addition to, calls to TT.
To change how the Circulator is activated
1. Turn the LO TEMP dial to access the Program Mode – indicated in the display as Pro
2. Turn the HI TEMP dial to select feature 4
3. Push the Test/Settings Button to select between the following options:
A - Circulator on TT call only
b - Circulator on ZC/ZR call only
C - Circulator on both TT & ZC/ZR calls
4. Reset LO TEMP and HI TEMP settings to desired temperatures (see page 28)
37
Page 40
5) Circulator Hold O (Enhanced Condensing Protection) - To reduce the potential for condensing, on a call for heat the control
will allow the boiler to heat to 125°F prior to energizing the circulator. Once energized, the circulator will remain on for the
duration of the heating call unless the boiler temperature drops below 115°F. If this occurs, the circulator will re-energize
when the boiler returns to 125°F. Circulator Hold O will expire after 15 minutes.
To activate Circulator Hold O
1. Turn the LO TEMP dial to access the Program Mode – indicated in the display as Pro
2. Turn the HI TEMP dial to select feature 5
3. Push the Test/Settings Button to turn Circulator Hold O on or OFF
4. Reset LO TEMP and HI TEMP settings to desired temperatures (see page 28)
6) Not available on this control.
7) Not available on this control.
8) Well Type - Hydrolevel Electro-Well (factory installed on boiler).
9) High Limit Dierential - When the Economy feature is on, the control’s Thermal Targeting feature actively sets varying
dierentials based on system conditions. This option allows for selecting a 10, 20 or 30 degree xed dierential when the
Economy feature is turned OFF. These optional dierential settings are subtractive from the HIGH LIMIT setting. Note: If
the Economy feature is on, this setting will be overridden by the control’s Thermal Targeting function.
To change the High Limit Dierential
1. Turn the LO TEMP dial to access the Program Mode –indicated in the display as Pro
2. Turn the HI TEMP dial to select feature 9
3. Push the Test/Settings Button to select a high limit dierential of 10, 20, or 30
4. Reset LO TEMP and HI TEMP settings to desired temperatures (see page 28)
dEF) Restore Factory Default Settings
To restore all features to the factory default settings (see Table 12.2 for default settings)
1. Turn the LO TEMP dial to access the Program Mode – indicated in the display as Pro
2. Turn the HI TEMP dial to select feature dEF
3. Push the Test/Settings Button to Y to reset all features to the default settings.
4. Reset LO TEMP and HI TEMP settings to desired temperatures (see page 28)
38
Page 41
TABLE 12.2 DEFAULT SETTINGS
Dial
Setting
1
2
3
4
5
6
7
8
9
def
FeatureOptionsDescription
Thermal Pre-Purge
Fahrenheit or Celsius
LWCO Manual or Auto-
matic Reset
Circulator Options
Circulator Hold O
Not available on this
control
Not available on this
control
Well Type
High Limit
Dierential
Restore Factory
Defaults
Off
on
F
c
A
b
A
b
c
on
Off
A
b
10
20
30
y
n
Purge Inactive
Purge Active
Degrees Fahrenheit
Degrees Celsius
Automatic Reset
Manual Reset
Circulator operation on TT call only
Circulator operation on ZC/ZR call only
Circulator operation on call from either
Circulator Hold O - Active
Circulator Hold O - Inactive
Hydrolevel Electro-Well (supplied with boiler)
Standard Immersion Well
10° Dierential
20° Dierential
30° Dierential
Restore Defaults
Do Not Restore Defaults
Default
Setting
Off
F
A
A
on
A
10
n
D. LED Legend and TEST/SETTINGS Button (Figure 12.3)
1) TEMP - ACTIVE - Indicates that the control is powered and that the temperature function is active.
2) TEMP - HI TEMP - Illuminates when the boiler water temperature reaches the high limit setting. It will remain lit until the
water temperature falls 10°. The control prevents burner operation while this LED is on. See Dierential explanation on page
28.
3) LWCO - ACTIVE - Indicates that the low water cut-o (LWCO) function of the control is active.
4) LWCO - LOW WATER - Indicates that the boiler is in a low water condition. The control will prevent burner operation
during this condition. If the LOW WATER light is blinking, the control has been programmed to provide lock- out protection
in the event a low water condition is detected (see Manual Reset Low Water Cut-O on page 30). Pressing the TEST/
SETTINGS button will reset the control.
WARNING
If the Hydrostat is found to be in a low water condition:
• Have the system checked by a qualified HVAC service technician before attempting to
restore operation.
• Do not add water to the boiler until it has fully cooled.
39
Page 42
FIGURE 12.3 LED Legend and TEST/SETTINGS Button
5) ECONOMY - ACTIVE - Indicates that the thermal targeting function is active and the control will reduce boiler temperature
to conserve fuel. The Economy feature is activated using the ECONOMY dial. (See “Setting the Economy Feature” on page
29 for more information).
6) ECONOMY - TARGET - When the Economy feature is active, the control continually sets target temperatures below the
high limit setting to maximize fuel eciency. When the boiler water reaches the target temperature, the LED illuminates
and the burner will shut down. The boiler water will continue to circulate and heat the house as long as the thermostat call
continues. The LED will stay lit until the boiler temperature drops below the dierential set point at which point the boiler
will be allowed to re again. See Dierential explanation on page 31. NOTE: This LED illuminates regularly during normal
boiler operation.
7) TEST/SETTINGS BUTTON - To Test Low Water Cut-O: Press and hold the Test/ Settings button for 5 seconds. The
display will read LCO. The red Low Water light should illuminate and the burner circuit (B1 and B2) should de-energize.
NOTE: The control must be installed with a Hydrolevel Electro-Well™ for low water cut-o functionality (see page 28 for
more details). To View Current Settings: Press and release the Test/Settings Button in short intervals to sequentially display
the following settings:
HIGH LIMIT SETTING HL
LOW LIMIT SETTING LL
ECONOMY SETTING ECO
CURRENT TARGET TEMPERATURE ooo
The display will return to boiler temperature (default) if Test/Settings Button in not pressed for 5 seconds.
40
Page 43
XIII Service and Maintenance
WARNING
All boiler cleaning must be completed with the burner service switch turned off. Boilers
equipped with burner swing door have a potential hazard which can cause severe property
damage, personal injury or loss of life if ignored. Before opening swing door, turn off service
switch to boiler to prevent accidental firing of burner outside the combustion chamber.
Disconnect the burner plug from the receptacle in the front jacket. Be sure to tighten the
swing door fastener completely when service is completed.
The following procedure should be performed on an annual basis:
1) Turn o electrical power and oil supply to the boiler.
2) Clean the boiler as follows:
a) Remove the two 3/8” bolts from either side of the swing door and open the door to access the combustion chamber.
b) Remove the two smoke box clean-out covers from the rear smoke box by removing the four 5/16” bolts. It is
not necessary to remove the vent connector from the smoke box to clean boiler however if there is heavy soot
accumulation in the boiler remove the vent connector to inspect the base of the chimney for condensate or
accumulation of debris.
c) Remove the baes (if installed) from the ue passages.
d) Clean the 3rd Pass - Insert a 2” dia x 42” long wire or ber bristle brush into one of the two 3rd ue passes. Using
long strokes push the brush all the way through the boiler until the brush has exited the smoke box opening. Pull the
brush all the way forward until it has exited the front of the boiler. Continue this operation for the entire height of
the ue way until clean. Repeat the operation for the other 3rd pass ue way.
e) Clean the 2nd Pass - Insert a 2” dia x 42” long wire or ber bristle brush into one of the two 2nd ue passes. Using
long strokes push the brush all the way through the boiler until the brush hits the back wall of the reversing chamber.
Pull the brush all the way forward until it has exited the front of the boiler. Continue this operation for the entire
height of the ue way until clean. Repeat the operation for the other 2nd pass ue way.
f) Vacuum to loose debris in the bottom of the combustion chamber and smoke box
g) Clean the Combustion Chamber - Use a wire or ber bristle brush to clean the surfaces of the combustion chamber.
Vacuum all loose debris in the chamber.
h) Check condition of the burner swing door insulation and rope gaskets for signs of damage; replace if required.
i) Check burner head for signs of deterioration. Clean the head of any deposits.
j) Insert baes (if originally installed) into the correct ueways.
k) Attach the smoke box clean-out covers onto the rear of the boiler using the 5/16” bolts originally removed. Verify
that the rope gasket is in good order before assembly. Replace rope gasket if necessary. Do not over tighten. The
bolts should be snug but not bottomed out.
l) Close the swing door and tighten it with the 3/8” bolts originally removed. When securing the burner swing door
make sure the door is drawn-in equally on both sides by alternating the tightening method for right side to left side.
Do not over tighten. The rope gasket will provide sucient seal when door is snugged into place.
m) Ensure all vent piping joints are gas tight and secured with sheet metal screws.
Clean the boiler even if there are no significant soot deposits. Failure to remove all sulfur and
ash deposits annually can cause severe corrosion damage.
IMPORTANT
41
Page 44
WARNING
The boiler must be connected to an approved chimney in good condition. Serious property
damage could result if the boiler is connected to a dirty or inadequate chimney. The interior
of the chimney flue must be inspected and cleaned before the start of the heating season and
should be inspected periodically throughout the heating season for any obstructions. A clean
and unobstructed chimney flue is necessary to allow noxious fumes that could cause injury or
loss of life to vent safely and will contribute toward maintaining the boiler’s efficiency.
3) Inspect the vent system:
a) Make sure that the vent system is free of obstructions and soot.
b) Make sure that all vent system supports are intact.
c) Inspect joints for signs of condensate or ue gas leakage.
d) Inspect venting components for corrosion or other deterioration. Replace any defective vent system components.
4) Service the oil burner:
a) Replace oil nozzle with identical make and model (see Table 11.1).
b) Inspect the electrodes. Replace if they are deteriorated. Make sure that the electrode position is set according to the
burner manufacturer’s instructions.
c) Remove and clean fuel pump strainer.
d) Remove any accumulations of dust, hair, etc. from the air shutter, blower wheel, and other air handling parts of the
burner.
e) Replace the fuel oil line lter element and gaskets.
6) Inspect all oil piping and ttings for kinks and leaks. Repair any found.
7) Inspect the hydronic piping and boiler for water leaks. Repair any leaks found immediately.
8) Verify operation of relief valve by manually lifting lever; replace relief valve immediately if valve fails to relieve
pressure.
9) Open fuel line shut-o valve(s) and restore electrical power to the boiler.
10) Fire the boiler and check it out using the procedure outlined in “Start-up and Checkout” . This must include checking the
burner adjustments using instruments. Check for proper operation of all controls.
Water leaks can cause severe corrosion damage to the boiler or other system components.
Repair any leaks found immediately.
WARNING
42
Page 45
Important Product Safety Information
Refractory Ceramic Fiber Product
Warning:
The Parts list designates parts that contain refractory ceramic fibers (RCF).
RFC has been classified as a possible human carcinogen. When exposed to
temperatures about 1805°F, such as during direct flame contact, RFC changes
into crystalline silica, a known carcinogen. When disturbed as a result of
servicing or repair, these substances become airborne and, if inhaled, may be
hazardous to your health.
AVOID Breathing Fiber Particulates and Dust
Precautionary Measures:
Do not remove or replace RCF parts or attempt any service or repair work
involving RCF without wearing the following protective gear:
1. A National Institute for Occupational Safety and Health (NIOSH)
approved respirator
2. Long sleeved, loose fitting clothing
3. Gloves
4. Eye Protection
• Take steps to assure adequate ventilation.
• Wash all exposed body areas gently with soap and water after contact.
• Wash work clothes separately from other laundry and rinse washing
machine after use to avoid contaminating other clothes.
• Discard used RCF components by sealing in an airtight plastic bag. RCF
and crystalline silica are not classified as hazardous wastes in the United
States and Canada.
First Aid Procedures:
• If contact with eyes: Flush with water for at least 15 minutes. Seek
immediate medical attention if irritation persists.
• If contact with skin: Wash affected area gently with soap and water.
Seek immediate medical attention if irritation persists.
• If breathing difficulty develops: Leave the area and move to a location
with clean fresh air. Seek immediate medical attention if breathing
difficulties persist.
• Ingestion: Do not induce vomiting. Drink plenty of water. Seek
immediate medical attention.
43
Page 46
XIV Trouble Shooting
A. Combustion
1) Nozzles - The selection of the nozzle supplied with the FWZ boiler is the result of extensive testing to obtain the best ame
shape and ecient combustion. Other brands of the same spray angle and pattern may be used but may not perform at the
expected level of CO2 and smoke. Nozzles are delicate and should be protected from dirt and abuse. Nozzles are massproduced and can vary from sample to sample. For all of those reasons a spare nozzle should be part of a serviceman’s
replacement parts inventory.
2) Flame Shape - As seen for the observation port, the ame should appear straight with no sparklers rolling up toward the
crown of the chamber. If the ame drags to the right or left, sends sparklers upward or makes wet spots on the chamber
walls, the nozzle should be replaced. If the condition persists look for fuel leaks, air leaks, water or dirt in the fuel as
described below.
3) Fuel Leaks - Any fuel leak between the pump and the nozzle will be detrimental to good combustion results. Look for wet
surfaces in the air tube, under the ignitor and around the air inlet. Any such leaks should be repaired as they may cause
erratic burning of the fuel and in the extreme case may become a re hazard.
4) Air Leaks - Any such leaks should be repaired as they may cause erratic burning of fuel and in extreme cases may become a
re hazard.
5) Gasket Leaks - If CO2 readings between 11.5% and 12.8% with a #1 smoke cannot be obtained in the breeching, or if odors
are observed, look for leaks around the burner mounting gasket, observation door and canopy gasket, or in the breeching
below the point where the ue gas sample is taken. Air leakage into the boiler or breeching can cause low CO2 readings (the
lower the ring rate, the greater eect an air leak can have on CO2 readings). Such leaks can also cause ue gas leakage into
the building, resulting in odor complaints.
6) Dirt - The use of a fuel lter is good practice. Accidental accumulation of dirt in the fuel system can clog the nozzle or
nozzle strainer and produce a poor spray pattern from the nozzle. The smaller the ring rate, the smaller the slots in the
nozzle and the more prone to plugging it becomes.
7) Water - Water in the fuel in large amounts will stall the fuel pump. Water in the fuel in smaller amounts will cause excessive
wear on the pump. More importantly it chills the ame and causes smoke and unburned fuel to pass through the combustion
chamber and clog the ueways of the boiler.
8) Cold Oil - If the oil temperature near the fuel pump is 40°F or lower, poor combustion or delayed ignition may result. Cold
oil is harder for the nozzle to atomize, thus the oil droplets get larger and travel further creating a longer ame. An outside
fuel tank that is above grade or has fuel lines in a shallow bury is a good candidate for cold oil. The best solution is to bury
the tank and lines deep enough to keep the oil above 40°F. Be sure to follow any state and local codes when burying fuel oil
tanks and/or fuel oil lines.
9) Start-Up Noise - Delayed ignition is the cause of start-up noises. If it occurs recheck for electrode settings, ame shape, air
or water in the fuel lines.
10) Shut Down Noise - If the ame runs out of air before it runs out of fuel, an after burn with noise may occur. That may be the
result of a faulty cut-o valve in the fuel pump, or it may be air trapped in the nozzle line. It may take several ring cycles
for that air to be fully vented through the nozzle. Water in the fuel or poor ame shape can also cause shut down noises.
TEST PROCEDURE FOR FUEL SIDE PROBLEMS
A good test for isolating fuel side problems is to disconnect the fuel system and with a 24”
length of tubing, fire the burner out of an auxiliary five gallon pail of clean, fresh, warm #2 fuel
oil from another source. If the burner runs successfully when drawing out of the auxiliary pail
then the problem is isolated to the fuel or fuel lines being used on the installation.
44
Page 47
B. Control System
The following pages contain a trouble shooting table and ow charts for use in diagnosing control problems. When using these
materials the following should be kept in mind:
1) This information is only meant to be used by a professional heating technician as an aid in diagnosing boiler problems.
2) Where applicable, follow all precautions outlined in the Section XI (Start-up and Checkout).
3) In general, this table and ow charts assume that there are no loose or miswired electrical connections. Before using these
tables inspect all electrical connections on the boiler to make sure that they are tight. Also, check the wiring on the boiler
against the wiring diagram in Figures 10.0 and 10.1. Ensure that incoming 120 VAC power polarity is correct and that the
boiler is properly grounded.
4) All controls on the boiler are tested at least once in the manufacturing process and a defective control or component is
generally the least likely cause. Before replacing a component, try to rule out all other possible causes.
45
Page 48
TABLE 14.0 - DIAGNOSTIC CONDITIONS
ConditionPossible Cause
Burner will not reSee Flow Chart 1, page 46
Burner will not shut downSee Flow Chart 2, page 47
Temperature display exceeds
high limit setting
No or insucient domestic hot
water
Low water light (Red LED) is on
or blinking
House will not get or stay warm
Circulator contacts
C1 and C2 not energized on call
for heat
All LED lights and temp display
are blinking
Under normal operation, boiler temperature will continue to rise after the control shuts o
the burner. This condition, known as “thermal stacking”, results from hot boiler surfaces
continuing to release heat into the boiler water.
For boilers equipped with a tankless coil, make sure the low limit setting on the control is
set properly. NOTE: If the low limit setting is dialed fully counterclockwise, it will shut
o the low temperature maintenance feature and will function as a cold start control. If
installed with an indirect water heater, check that the Zone/Indirect Switch is set in the
Indirect (I) position. Verify that the end switch in the relay box controlling the indirect water
heater is connected to the ZC-ZR terminals. This will ensure that the domestic water calls
are prioritized.
WARNING: A low water condition is a serious and potentially
dangerous condition. Do not attempt to add water to a hot boiler.
Allow the boiler to fully cool before adding water.
When the LOW WATER light is on, this indicates that the control is not detecting water
in the boiler. When the LOW WATER light is blinking, this indicates that the control has
been programmed to provide low water lock-out protection and is currently locked out (see
Manual Reset Low Water Cut-O). Pressing the TEST/SETTINGS button after the low
water condition is resolved will reset the lock-out condition.
1. If the light is on and the heating system is lled with water, pull the sensor out of the well
and inspect it. Make sure that the metal clip is protruding enough to come in contact with
the inside of the well tube. Check that the well does not have excessive build-up of heat
transfer grease that may interfere with the clip contacting the well.
2. Remove well and examine for excessive residue build-up. Clean and re-install.
1. Check for air-bound radiators.
2. Check thermostat settings including heat anticipator settings (common on non-digital
thermostats).
3. Check the Economy setting. The Economy feature, much like outdoor reset controls,
lowers average boiler temperature and can slow or, in some cases, prevent the house from
coming up to temperature. Move to a lower setting (see “Setting the Economy Feature”).
Check to see that boiler water is at or above 125°F. On a call for heat, the control will
not permit the circulator to operate if the boiler water temperature is below 125°F (see
“Circulator Hold O”).
If the LED lights and the temp display are blinking alternately, this indicates the control has
sensed a boiler temperature of 250°F. When this occurs, the control pulses the burner relay
and then shuts down and locks-out the burner. The system should be analyzed to determine
the cause of the overheating condition. Check that the sensor is inserted all the way into
the well so it can accurately sense the temperature of the boiler water. Check the load on
the burner contacts: If the load exceeds the 7.4 Amp rating, the contacts may have welded.
Correct the overloading condition and replace the control before reenergizing the system.
If the load on the contacts is below the rating, check system wiring and operation as well
as the control’s high limit setting. If the cause of the overheating is found and the system is
deemed safe, the control can be reset by removing power from the control and then repowering while simultaneously pressing the Test/Settings button on the top of the control. If the
cause of the overheating condition is not determined, the control should be replaced.
46
Page 49
Troubleshooting Flow Chart 1 – Burner Will Not Fire
Does the
Display Read
?
NO
Is
the
Green LED
O
YES
Is
NO
Is
Yellow
(HI
TEMP
On?
n?
the
the
LED
)
(TEMP ACTIVE)
Red LED (LOW
WATE R) On?
YES
NO
YES
YES
The
Control is
Purging Latent
Heat
from
B
oiler.
The Control
Not Power
The
Control is
S
ensing
Low
Water.
The Control
Sensing
T
emperature.
the
is
ed.
High
The Thermal Pre-Purge feature holds off the burner until the
control determines
the heat
call.
The Temp Active LED
powered.
�
Check
for
CAUTION – ALW
The burner
�
Check that the system
�
Check that the sensor
between
�
Check that the control
S
ee pages 38 and 39
The burner
is
high
limit
differential set-point
�
Check that the high temperature setting
if
the latent heat
will
be
on at all
120 VAC on terminals L1 and
AYS ALLOW A BOILER TO COOL BEFORE
will not
fire
until
the
is
filled with
is
its
spring clip and the copper well tube
will not
inserted fully into the well and
is
tightly clamped
for
additi
fire
until
the boiler water has dropped
in
times when the control
L2.
low
water condition
water.
onal
tr
oubl
eshooting i
(10°
below high
is correct.
the boiler can
ADDING WATER
to
the
limit setting).
is satisfied.
is made.
well.
nformation.
satisfy
cont
to the
is
act
NO
Is
the
Yellow
LED
(TARG
ET)
On?
NO
Is
the
Thermost
(T-T) Calling
for Heat?
YES
Is
There
120 VAC
Between B1
and B2?
NO
YES
The Boiler has
Reached
T
arget
T
emperature.
Is
at
NO
YES
the
External Zone
(ZC-ZR) Calling
for Heat?
YES
The Control
is Operat
Properly.
When the ECONOMY function
demand and establishes Target boiler temperatures below the
the
limit
setting
to
conserve fuel. The burner
t
emperature drops
D
ifferential.
Is
Low Limit Dial
Set
to OFF?
NO
NO
is
active, the control monitors heati
to
the automatically calculated Target Temp
the
YES
HydroStat
is
ing
�
supplying 120 VAC
Recheck wiring and operation
to
the burner
of
burner and other
will
not fire until the boiler
When the
low t
setting
HydroStat
start control. The
will not
a call
(T-T)
(
ZC-ZR).
Set thermostat
�
for
fire.
� If
less coil, set the
Temperature Limit
maintain t
emperature
is
set
to
will
act as a
fire unless there
from
the thermost
or
an external
heat. Burner should
the boiler has a t
emperature.
circuit.
limit controls.
OFF,
burner
to call
ng
high
the
cold
is
at
zone
ank-
Low
to
Replace
C
ontrol
If
both the red and yellow LEDs are
there
is
a call
to
120 VAC
� If
120 VAC
be
fire the burner, there
on
terminals B1 and B2.
is not
replaced.
present, the control should
47
off and
will be
Page 50
Troubleshooting Flow Chart 2 – Burner Will Not Shut Down
Is the
Red LED
(LOW WATER)
On?
NO
Is either
Yellow LED
On?
NO
Is the
Thermostat
(T-T) Calling
for Heat?
NO
Is the
External Zone
(ZC-ZR) Calling
for Heat?
YES
YES
YES
YES
The Control is
Sensing
Low Water.
The Control has
Reached Target
or High Limit
Temperature.
The Control is
Operating
Normally.
The Control is
Operating
Normally.
WARNING!
TURN OFF POWER TO BURNER IMMEDIATELY!
CAUTION – ALWAYS ALLOW A BOILER TO FULLY COOL
BEFORE ADDING WATER.
Recheck wiring. Make sure that burner is wired to
B1. Burner should never fire when red or yellow
LED is lit.
The burner will continue to fire when there is a call
from the thermostat or external zone.
NO
Is the
Low Limit Dial
Set to OFF?
YES
Is there
120 VAC between
B1 and B2?
YES
Replace
Control.
Check temperature display. When the Low Limit is
NO
set, the HydroStat will fire the burner until the
temperature reaches the Low Limit Setting.
NO
Recheck
Wiring.
If there is no call for heat (from T-T, ZC-ZR or Low
Limit), there should be 0 VAC between B1-B2.
If there is voltage between B1-B2, the control
should be replaced.
When there is no call to fire the burner, the voltage
should be 0 volts between B1 and B2.
1. PART NUMBERS PROVIDED ARE FOR FULLY CONFIGURED BURNERS AND INCLUDE PRIMARY SAFETY CONTROL, NOZZLES,
BURNER CORD ASSEMBLIES AND (WHERE APPLICABLE) LOW FIRING RATE BAFFLES. SOME BURNERS ARE ALSO SUPPLIED WITH
BLANKETS AND BAFFLES. SEE TABLE 4.1 FOR DETAILS.
52
Page 55
53
Page 56
Manufacturer of Hydronic Heating Products
P.O. Box 14818 3633 I. Street
Philadelphia, PA 19134
www.crownboiler.com