Crown Boiler FSZ080, FSZ100, FSZ130, FSZ160 Installation Instructions Manual

Page 1
D ESIGNED TO L EAD
FSZ Series
Oil-Fired Steam Boilers
INSTALLATION INSTRUCTIONS
These instructions must be afxed on or adjacent to the boiler
Models:
FSZ080
FSZ100
FSZ130
FSZ160
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury, or loss of life. For assistance or additional
information, consult a qualied
installer, service agency or the oil supplier. Read these instructions carefully before installing.
Manufacturer of Hydronic Heating Products
P.O. Box 14818 3633 I. Street
Philadelphia, PA 19134
www.crownboiler.com
Page 2
Page 3
WARNINGS FOR THE HOMEOWNER
FOLLOW ALL INSTRUCTIONS and warnings printed in this manual and posted on the boiler.
INSPECT THE BOILER, BURNER AND CONTROLS ANNUALLY. To keep your boiler safe and efficient, have a service technician follow the Service checklist near the end of this manual.
IF YOU ARE NOT QUALIFIED to install or service boilers, do not install or service this one.
THE BOILER MAY LEAK WATER at the end of its useful life. Be sure to protect walls, carpets, and valuables from water that could leak from the boiler.
PROTECT YOUR HOME IN FREEZING WEATHER. A power outage, safety lockout, or component failure will prevent your boiler from lighting. In winter, your pipes may freeze and cause extensive property damage. Do not leave the heating system unattended during cold weather
unless alarms or other safeguards are in place to prevent such damage
DO NOT BLOCK AIR FLOW into or around the boiler. Insufficient air may cause the boiler to produce carbon monoxide or start a fire.
KEEP FLAMMABLE LIQUIDS AWAY from the boiler, including paint, solvents, and gasoline. The boiler may ignite the vapors from the liquids causing explosion or fire.
KEEP CHILDREN AND PETS away from hot surfaces of the boiler, boiler piping, and vent pipe.
CARBON MONOXIDE (CO) is an odorless, deadly gas that may be introduced into your home by any malfunctioning fuel-burning product or vent system failure. Consider installing CO alarms near bedrooms in all levels of the building to warn you and your family of potential CO exposure.
WARNINGS FOR THE INSTALLER
READ THIS ENTIRE MANUAL before attempting installation, start-up, or service. Improper installation, adjustment, alteration, service, or maintenance may cause serious property damage, personal injury, or death.
DO NOT DISCONNECT PIPE FITTINGS on the boiler or in the heating system without first verifying that the system is cool and free of pressure and that your clothing will protect you from a release of hot water or steam. Do not rely solely on the boiler’s temperature and pressure gage when making this judgment.
USE PROPER PERSONAL PROTECTION EQUIPMENT when servicing or working near the boiler. Materials of construction, flue products, and fuel contain alumina, silica, heavy metals, carbon monoxide, nitrogen oxides, and/or other toxic or harmful substances that can are hazardous to health and life and that are known to the State of California to cause cancer, birth defects, and other reproductive harm.
INSTALL ALL GUARDS, cover plates, and enclosures before operating the boiler.
SIZE THE BOILER PROPERLY relative to the design heat load or, if using domestic hot water priority, the peak hot water load, whichever is larger. A grossly oversized boiler will cycle excessively and this will lead to premature failure of the boiler and its components. Our warranty does not apply to damage from excessive cycling.
ADHERE TO ALL LOCAL CODE REQUIREMENTS. Contact your local code inspector prior to installation. In the absence of a local code, adhere to the latest editions of the
Installation of Oil Burning Equipment ANSI/NFPA 31 in the USA or CAN/CSA B139, Installation Code for Oil Burning Equipment in Canada.
ALL WIRING must comply with the National Electrical Code ANSI/NFPA 70 (in the USA) or the Canadian Electrical Code CSA C22.1 (in Canada)
and any local regulations.
1
Page 4
Table of Contents
I. Product Description ............................................................................... 3
II. Specications ......................................................................................... 3
III. Before Installing .................................................................................... 5
IV. Field Assembly ...................................................................................... 6
V. Locating the Boiler ................................................................................ 7
VI. Air for Combustion & Ventilation ......................................................... 8
VII. Venting ................................................................................................... 13
VIII. System Piping ........................................................................................ 15
IX. Indirect & Tankless Water Heater Piping ............................................... 19
X. Fuel Line Piping .................................................................................... 22
XI. Wiring .................................................................................................... 25
XII. Start-Up & Checkout ............................................................................. 30
XIII. Service & Maintenance .......................................................................... 34
XIV. Troubleshooting ..................................................................................... 38
XV. Parts ....................................................................................................... 40
Appendix A. Installation of Optional Gravity Return Piping Kit .................... 46
2
Page 5
I Product Description
The FSZ series boiler is a cast iron oil-red steam boiler designed for use in closed heating systems. This boiler must be vented by natural draft into a lined masonry or metal chimney, or Type L vent. An adequate supply of air for combustion, ventilation and dilution of ue gases must be available in the boiler room. This boiler has connections for use with an indirect domestic water heater.
The FSZ series boilers are not designed for use in process or other “open” steam systems.
II Specications
TABLE 2.1: GENERAL SPECIFICATIONS
BOILER MODEL
FSZ080 22-1/4” 24” 6” 15.3 14.9 20.29 607
FSZ100 22-1/4” 24” 6” 15.3 14.9 20.29 607
FSZ130 28-1/4” 30” 6” 19.7 19.3 27.29 744
FSZ160 34-1/4” 36” 7” 24.1 23.8 34.29 881
Maximum working pressure, Steam - 15psi
TABLE 2.2: RATING DATA
BURNER
BOILER MODEL
FSZ080 0.80 112 97 73 303 6 8 X 8 15 85.7
FSZ100 1.00 140 122 92 381 6 8 X 8 15 86.0
FSZ130 1.30 182 158 119 494 7 8 X 8 15 86.0
FSZ160 1.60 224 195 146 610 7 8 X 8 15 85.9
Burner Capacity Rating, GPH is based on #2 fuel oil with a Gross Heating Value equal to 140,000 BTU/Gal. AHRI Net Ratings are based on piping and pick-up allowances of 1.333.
INPUT
GPH MBH
DIMENSIONS
‘A’ ‘B’ ‘C’
HEATING
CAPACITY MBH
WATER CONTENT (TO NORMAL
WATER LINE) (GALLONS)
WITH TANKLESS
HEATER
AHRI NET RATINGS
STEAM
MBH
NON-HEATER
STEAM
SQ. FT.
ROUND IN. DIA.
HEAT TRANSFER
SURFACE AREA
(SQ FT)
MINIMUM CHIMNEY
REQUIREMENTS
RECTANGLE
IN. X IN.
HEIGHT
SHIPPING
WEIGHT
(LBS)
FT.
AFUE
%
TABLE 2.3: TANKLESS HEATER RATINGS
BOILER MODEL HEATER RATING (GPM) PRESSURE DROP THRU HEATER (PSI)
FSZ080 3.00 22.0
FSZ100 3.25 24.3
FSZ130 3.50 26.5
FSZ160 4.00 31.0
Ratings based on 40F inlet water, 140F outlet water, and 190F boiler water. Ratings are also based on 5 minute intermittent draws with 10 minutes between draws.
3
Page 6
OUT
COVER
CLEAN
SAFETY
VALVE
ARRANGEMENT.
* NOTE: THIS DIMENSION INCREASES AND
IS CONTROLLED BY SMOKEPIPE
CONTROL
FOR HEATER
REAR
SERVICE
* 12" MIN
TEMPERATURE
CLEARANCE
'C' DIA
COLLAR
SMOKEBOX
COLLAR
21 3/8"
DRAIN
VALVE
LINE
FLOOR
REAR VIEW
2" REAR SUPPLY
1-1/2" RETURN
11-1/4"
2" FRONT SUPPLY
'A'
'B' MIN.
/RELAY
TRANSFORMER
CLEARANCE
FRONT SERVICE
(FLUEWAY CLEANING)
TOP VIEW
N.W.L.
GLASS
WATER
GAUGE
31 1/8"
38 1/2"
BURNER
SWING
SPANNER BAR
RIGHT VIEWFRONT VIEW
DOOR
22 1/2"
5-11/16"
4-9/16"
19"
(FULLY OPEN)
STEAM
PRESSURE LIMIT
PRESSURE GAUGE
PROBE LOW
WATER CUT-OFF
FLAME
OBSERVATION
PORT
BURNER
BECKETT AFG
BURNER SWING
DOOR CLEARANCE
FIGURE 2.3: GENERAL CONFIGURATION
4
Page 7
III Before Installing
1) Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict accordance with this manual and the requirements of the authority having jurisdiction.
In the absence of an authority having jurisdiction, installation must be in accordance with this manual and the latest
edition of Installation of Oil Burning Equipment (ANSI/NFPA31). Installations in Canada comply with the requirements of CSA B139-04 – Installation Code for Oil-burning Equipment.
Where required by the authority having jurisdiction, this installation must conform to the latest edition of Standard for
Controls and Safety Devices for Automatically Fired Boilers (ANSI/ASME CSD-1).
2) Make sure that a properly sized chimney is available which is in good condition. Consult the authority having jurisdiction, Part VII of this manual, and ANSI/NFPA31 for additional information on venting requirements.
3) Make sure that the boiler is correctly sized. Do this by totalling the surface area of all radiators in the system (in sq. feet). To this, add any other space heating (not DHW) loads. Select a boiler having a net rating just larger than this total heating load. Note: 1 sq. ft of radiation is equal to 240 BTU/hr.
4) In some cases, boilers installed at altitudes above 2000ft may require a different burner conguration from that at sea level. Consult the local Crown representative for more information.
Power (“Side Wall”) Venting - Important Note
Two problems arise when any oil-fired appliance is power vented:
There is sometimes an accelerated rate of soot buildup on the oil burner cad-cell, spinner etc.
There is a potential for severe damage to the side of the structure in the event that the boiler operates at a high smoke level. This can happen for many reasons, some of which are out of the control of both the installer and appliance manufacturer.
Crown Boiler Company recommends the use of a chimney to vent the FSZ series boilers. If a power venter must be used, it is the responsibility of the installer and power vent manufacturer to “engineer” the power vent system. Crown Boiler Company will assume no responsibility for damage to siding, etc. from a power vented oil-fired boiler. This applies regardless of the cause of the sooting.
5
Page 8
IV Field Assembly
This boiler is shipped in two pieces:
a) The crated boiler itself b) The burner carton consisting of the following items:
Oil Burner assembly
Barometric Draft Regulator (if supplied)
Safety valve
Drain valve
Pipe ttings
WARNING
Installation of burners on the FSZ other than those provided by Crown, and marked for use with this boiler, may result in unreliable operation, property damage, personal injury, or loss of life.
It is recommended that the boiler be moved to its nal location before the items in the burner carton are installed. To complete eld assembly:
1) Make sure that the burner carton supplied is the correct one for the boiler. The crate tag on the boiler lists the Crown part numbers for the Beckett and Riello burner cartons that may be used with it.
2) Remove the burner mounting bolts and washers from the front door. Make sure that the burner gasket is in place and undam­aged and mount the burner to the door as shown in Figure 4.0.
3) Plug the burner cord into the receptacle on the lower right front corner of the boiler.
4) The FSZ100 uses a pair of second pass bafes which are included in the burner carton and which must be installed in the eld. Install these as shown in Figure 4.0. All bafes are factory installed on other models.
5) Install the barometric draft regulator, and other piping/trim, as described in the Venting and Piping sections of this manual.
FIGURE 4.0: BOILER FIELD ASSEMBLY
6
Page 9
V Locating the Boiler
WARNING
Failure to observe the following location requirements could result in property damage, a fire, explosion or carbon monoxide (CO) hazard.
1) Clearances:
Observe the minimum clearances shown below. Except as noted, these clearances apply to all combustible construction, as well as noncombustible walls, ceilings and doors. Also see Figure 5.0.
Front - 24” (from front jacket surface) Left Side – 6” Right Side – 6” (18” is required for tankless heater service) Rear – 12” Top – 6” Single Wall Chimney Connector (to combustible construction) - 18”
A 24” service clearance is recommended above the top of the boiler, as well as on the side to which the burner swing door opens (the left side as the boiler is shipped). See also dimension ‘B’ in Table 2.0 for recommended service clear­ances to the front of the boiler. These clearances may be reduced to those shown above; however, servicing the boiler will become increasingly difcult as these clearances are reduced.
FIGURE 5.0: CLEARANCES
7
Page 10
1) Do not install this boiler directly on a combustible oor. Where it is desired to install an FSZ on a non-carpeted combustible oor, install the boiler on a base constructed as shown in Figure 5.1
2) If listed Type L vent is used, follow vent pipe manufacturer recommendations for minimum clearances.
3) Do not install this boiler in a location where gasoline or other ammable vapors or liquids will be stored or used. Do not install this boiler in an area where large amounts of airborne dust will be present, such as a workshop.
FIGURE 5.1: INSTALLATION OVER A COMBUSTIBLE FLOOR
VI Air for Combustion and Ventilation
Sufcient fresh air must be supplied for combustion and ventilation. Provisions for combustion and ventilation air for oil burning equipment must be made in accordance with the Standard for the Installation of Oil Burning Equipment (ANSI/NFPA
31).
To ensure an adequate supply of air for combustion, ventilation and ue gas dilution, start by determining whether adequate combustion and ventilation air can be obtained through natural inltration (air leaking into the building through cracks around windows, doors, etc). Examples of construction features which could prevent adequate natural inltration include:
Walls and ceilings exposed to outside atmosphere having a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed and sealed
Weather stripping added on openable windows and doors
Caulking and sealants are applied to areas such as joints around window and door frames, between sole plates and oors,
between wall-ceiling joints, between wall panels, at penetrations for plumbing, electrical, and gas lines, and at other openings.
Large exhaust fans
In this manual, buildings where natural inltration will not provide adequate air for combustion, and ventilation are referred to as “buildings of unusually tight constuction”. If in doubt, assume that the building in which the boiler is installed is of unusually tight construction.
8
Page 11
A. For Buildings of Other than Unusually Tight Construction
1) Determine whether the boiler is to be installed in a conned space - A conned space is dened as having a volume less than 50 cubic feet per 1000 BTU/hr input of all appliances installed in that space. To determine whether the boiler room is a conned space:
a) Total the input of all appliances in the boiler room in thousands of BTU/hr. Round the result to the next highest 1000
BTU/hr.
b) Find the volume of the room in cubic feet. The volume of the room in cubic feet is:
Length (ft) x width (ft) x ceiling height (ft)
In calculating the volume of the boiler room, consider the volume of adjoining spaces only if no doors are installed between them. If doors are installed between the boiler room and an adjoining space, do not consider the volume of the adjoining space, even if the door is normally left open.
c) Divide the volume of the boiler room by the input in thousands of BTU/hr. If the result is less than 50, the boiler room is
a conned space.
Example: An FSZ080 and a water heater are to be installed in a room measuring 6 ft - 3 in x 7 ft with an 8 ft ceiling. The water heater has an input of 30000 BTU/hr: Input of FSZ080 = 0.80 Gal/hr x 140000 BTU/Gal = 112000BTU/hr Total input in thousands of BTU/hr = (112000 BTU/hr + 30000 BTU/hr)/1000 = 142 Volume of room = 6.25 ft x 7 ft x 8 ft = 350 ft
350/142 = 2.46. Since 2.46 is less than 50, the boiler room is a conned space.
3
2) Unconned Space - Natural inltration into the boiler room will normally provide adequate air for combustion and ventila­tion without additional louvers or openings into boiler room.
3) Conned Space - Provide two openings into the boiler room, one near the oor and one near the ceiling. The top edge of the upper opening must be within 12” of the ceiling and the bottom edge of the lower opening must be within 12” of the oor (Figure 6.0).
Each opening must have a free area of 1 square inch per 1000 BTU/hr input of all fuel burning appliances in the boiler
room. The minimum opening dimension is 3 inches. Minimum opening free area is 100 square inches per opening.
If the total volume of both the boiler room and the room to which the openings connect is less than 50 cubic feet per
1000 BTU/hr of total appliance input, install a pair of identical openings into a third room. Connect additional rooms with openings until the total volume of all rooms is at least 50 cubic feet per 1000 BTU/hr of input.
The “free area” of an opening takes into account the blocking effect of mesh, grills, and louvers. Where screens are
used, they must be no ner than ¼” (4 x 4) mesh.
B. For Buildings of Unusually Tight Construction
1) Openings must be installed between the boiler room and the outdoors or a ventilated space, such as an attic or crawl space, which communicates directly with the outdoors.
2) Two openings are required. The top edge of the upper opening must be within 12 inches of the ceiling. The bottom edge of the lower opening must be within 12 inches of the oor.
3) Size openings and ducts as follows:
Vertical ducts or openings directly outdoors (Figure 6.1, Figure 6.2, and Figure 6.3) - Each opening must have a free
cross sectional area of 1 square inch per 4000 BTU/hr of the total input of all fuel red appliances in the boiler room but not less than 100 square inches. Minimum opening size is 3 inches.
Openings to outdoors via horizontal ducts (Figure 6.4) - Each opening must have a free cross sectional area of 1 square
inch per 2000 BTU/hr of the total input of all fuel red appliances in the boiler room but not less than 100 square inches. Minimum opening size is 3 inches.
The “free area” of an opening takes into account the blocking effect of mesh, grills, and louvers. Where screens are
used, they must be no ner than ¼” (4 x 4) mesh.
9
Page 12
FIGURE 6.0: BOILER INSTALLED IN CONFINED SPACE, ALL AIR FROM INSIDE
FIGURE 6.1: ALL AIR FROM OUTDOORS, VENTILATED CRAWL SPACE AND ATTIC
10
Page 13
FIGURE 6.2: ALL AIR FROM OUTDOORS, VIA VENTILATED ATTIC
FIGURE 6.3: ALL AIR FROM OUTDOORS, USING OPENINGS INTO BOILER ROOM
11
Page 14
FIGURE 6.4: ALL AIR FROM OUTDOORS, USING HORIZONTAL DUCTS INTO BOILER ROOM
12
Page 15
VII Venting
WARNING
Improper venting may result in property damage and/or the release of flue gases, which contain deadly carbon monoxide (CO), into the home, which can cause severe personal injury or death.
Inspect existing chimney before installing boiler. Failure to clean or replace damaged pipe or tile lining will cause property damage, severe personal injury or death.
Do not de-rate the appliance. Failure to fire the unit at it’s designed input may cause excessive condensation upon the interior walls of the chimney. In addition, the lower input may not create enough draft to adequately evacuate the products of combustion.
The vent installation must be in accordance with local building codes, or the local authority having jurisdiction. Contact your local re and building ofcials on specic requirements for restrictions and the installation of fuel oil burning equipment. In the absence of other applicable codes, the vent system installation must meet the requirements of NFPA 31 – Standard for the
Installation of Oil-Burning Equipment and NFPA 211 - Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances. Vent systems in Canada must comply with CSA B139-04 – Installation Code for Oil-burning Equipment.
A typical vent system is illustrated in Figure 7.0. The components of the vent installation are the vent connector (breeching), barometric draft regulator, and chimney.
1) Acceptable Chimneys - The following chimneys may be used to vent a FSZ series boiler:
Listed Type L vent - Install in accordance with the manufacturer’s instructions, the terms of its listing, and applicable codes.
Masonry Chimney - The masonry chimney must be constructed in accordance with the latest edition of Standard for Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances (NFPA 211) and lined with a clay liner or other listed
lining system. Do not vent a FSZ series boiler into an unlined chimney.
2) Acceptable Vent Connectors - The following may be used for vent connectors:
Listed Type L vent.
Single Wall Galvanized Pipe - Use 0.018” (26 gauge) or heavier.
3) Chimney and Vent Connector Sizing - See Table 7.1 for minimum vent connector and chimney sizing. The vent connector size must not be smaller than boiler ue collar diameter.
4) Do not vent this appliance into any portion of a mechanical vent system operating under positive pressure.
5) Do not connect the boiler into a chimney ue serving an open replace or other solid fuel appliance.
6) Prior to boiler installation, an existing chimney must be inspected by a qualied person in accordance with the requirements of Chapter 11 of NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances. This inspection is intended to identify safety problems with the chimney such as obstructions, a missing or damaged liner, or leak points. Clean chimney as necessary and correct any other chimney defects before installing the boiler.
7) Vent connector must slope upward from boiler not less than one inch in four feet. No portion of vent pipe should run downward or have sags. Vent connector must be securely supported.
8) The vertical section of vent connector coming off the boiler should be as tall as possible, while still maintaining the proper clearance from the horizontal vent connector to combustibles and the proper pitch called for in (7) above.
9) Vent connector must be installed above the bottom of the chimney to minimize risk of blockage.
13
Page 16
10) Vent connector must be inserted ush with inside face of the chimney liner and the space between vent connector and chimney sealed tight. A thimble permanently cemented in place can be used to facilitate removal of vent connector for cleaning.
11) Install the barometric draft regulator supplied with this boiler in accordance with the regulator manufacturer’s instructions. No other draft regulator shall be used.
12) Secure all joints in the vent connector system with sheet metal screws. This includes the joint between the vent connector and the boiler collar (see Figure 7.0, Detail ‘A’), as well as the barometric draft regulator. Use at least three screws at each joint.
FIGURE 7.0: TYPICAL VENT SYSTEM INSTALLATION AND COMPONENTS
TABLE 7.1: MINIMUM RECOMMENDED BREECHING AND CHIMNEY SIZE
BOILER MODEL
FSZ080 6 6 8 X 8 15
FSZ100 6 6 8 X 8 15
FSZ130 6 7 8 X 8 15
FSZ160 7 7 8 X 8 15
MINIMUM
BREECHING
DIA. (INCHES)
MINIMUM CHIMNEY REQUIREMENTS
ROUND I.D.
(IN.)
SQUARE. TILE
SIZE (NOMINAL)
14
HEIGHT (FT.)
Page 17
VIII System Piping
WARNING
Install boiler so that the electrical components are protected from water (dripping, spraying, rain, etc.) During appliance operation and service (circulator replacement, etc.).
Operation of this boiler in a system having significant amounts of dissolved oxygen can cause severe heat exchanger corrosion damage.
Do not use toxic additives, such as automotive antifreeze, in a hydronic system.
Pipe safety valve discharge to a safe location. The safety valve may discharge steam or scalding hot water.
Do not install a valve in the safety valve discharge line.
Do not move safety valve from factory location.
Do not plug safety valve discharge. Blocking the safety valve may result in boiler explosion.
Figure 8.1 shows recommended near boiler piping for most common types of gravity return steam systems. Additional information on steam system design may be found in the I=B=R Guide RHH published by the Air-Conditioning, Heating and Refrigeration Institute (AHRI).
One of the primary purposes of this near boiler piping is to separate tiny water droplets from the steam exiting the boiler so that “dry” steam is sent to the system. If the near boiler piping is not correct, wet steam will enter the system and the following problems may occur:
Short cycling on low water
Boiler or system Flooding
Hammering
Failure to heat one or more radiators
Avoid the common piping mistakes shown in Figure 8.2. This applies even if the existing boiler has one of the piping mistakes shown in Figure 8.2 and appears to be working. If two or more steam mains must be connected to the boiler, connect a separate take-off for each main into the header between the riser(s) and equalizer. Also note the following points:
1) A size reduction must be made to connect the header to the equalizer. This reduction must be made in the vertical equalizer line. Do not make this size reduction in the horizontal header.
2) One-pipe steam systems require air vents on each radiator, as well as at the end of each main. For the system to work properly, these vents must be properly installed, sized, and be in good condition. Inspect and replace any defective vents. If there are no vents at the ends of the mains, install them.
3) Do not attempt to manifold multiple FSZ boilers with gravity returns.
4) For installations with condensate or boiler feed pumps, follow the pump manufacturer’s piping instructions. Such systems generally do not require Hartford loops.
5) Do not use a check valve in place of, or in addition to, a Hartford loop on a gravity return system.
6) Pipe the ll connection from a clean source of cold water. When the water supply is from a well, make sure that a strainer is installed in the well system.
7) The “drop header” arrangement shown as “Alternate Piping Method” in Fig 8.1 is useful when there is limited vertical clearance above the boiler.
15
Page 18
FIGURE 8.1: STEAM BOILER PIPING FOR GRAVITY RETURN
16
Page 19
FIGURE 8.2: NEAR BOILER PIPING MISTAKES
Piping Installation
1) Remove parts bag from boiler crate.
2) Install safety valve as shown in Figure 8.1 into the 3/4” tapping “F” on rear of the boiler (spindle must be in vertical position).
3) Pipe the discharge of the safety relief valve to a location where water or steam will not create a hazard or cause property damage if the valve opens. The end of the discharge pipe must terminate in an unthreaded pipe. If the safety valve discharge is not piped to a drain, it must terminate at least 6 inches above the oor. The termination of the safety valve discharge piping must be in an area where it is not likely to become plugged by debris or subjected to freezing.
4) Install drain valve provided into the return piping. See Figure 8.1.
5) Connect system supply and return to boiler. See Figure 8.1.
17
Page 20
FIGURE 8.3: PURPOSE OF TAPPINGS AND BOSSES
TABLE 8.4 PURPOSE OF TAPPINGS
Tapping Location Size (NPT)
A 1/4” Pressure Gauge
B 1/4” Pressure Limit
C 3/4” Probe LWCO
D 1/2” Water Gauge Glass
E 2” Supply (Front & Rear Tappings)
F 3/4” Safety Valve
G 1-1/2”
H 1-1/4” Optional Front Return (Plugged)
J 1-1/2” Surface Blowoff (Plugged)
K 1” Indirect Water Heater Supply (Plugged)
L 1/2” Indirect Water Heater Limit (Plugged)
R 1/2”
Steam Boiler
Less Heater With Heater
Condensate Return (Reduced to 1-1/4”
on FSZ080,100 & 130)
L4006 Operating
Control
Plugged
18
Page 21
IX INDIRECT & TANKLESS WATER HEATER PIPING
INDIRECT WATER HEATER PIPING
All FSZ series boilers are equipped with tappings to permit the connection of a Crown Mega-Stor, or other indirect water heater. In this type of system, hot boiler water is drawn from below the water line and passed through the heat exchanger in the indirect water heater. This section describes boiler-side piping only. Refer to the indirect water heater instruction manual for domestic water piping. The components in this system and their functions are as follows:
1) Circulator - Mount the circulator as shown in Figure 9.1. The circulator should be located as low and as close to the boiler as practical. Do not install valves, or other devices having a signicant pressure drop between the boiler and the circulator inlet. All piping between the boiler and the circulator inlet should be 1”, regardless of the size of the piping required in the rest of the system. See Figure 11.2 in Part XI for wiring information.
2) “Y” Strainer - Install a “Y” strainer to prevent sediment from accumulating inside the indirect water heater.
3) Check Valve - Prevents gravity circulation through the indirect water heater when the boiler is responding to a call for heat.
4) Boiler Limit Control - Use a SPST break-on-rise temperature limit control such as the Honeywell L4006A. Do not set the limit above 180F as doing so may cause the boiler to steam when there is no call for heat. See Figure 11.2 for wiring information.
5) Valves and Unions - Install shut-off valves, drain valves, and unions in locations that will facilitate maintenance of the system. Do not install any valves between the boiler and circulator inlet.
FIGURE 9.1: INDIRECT WATER HEATER BOILER-SIDE PIPING
19
Page 22
IMPORTANT
Some indirect water heaters may not be suitable for use with a steam boiler. Consult the water heater
manufacturer’s guidelines before installing it in this type of system.
Boiler water temperatures and ow rates in this type of system may be considerably lower than those upon which the
water heater manufacturer’s ratings are based. This may result in substantially longer water heater recovery times.
TANKLESS HEATER PIPING
FSZ Series boilers equipped with tankless heaters are supplied with a Honeywell L4006A limit control and a 1/2” NPT well. These components are shipped unmounted. This control is mounted in the 1/2” tapping “R” in the center of the tankless coil. Make the piping connections to the coil before installing the L4006A, making sure that these connections are routed so that they will not interfere with the L4006A. Pipe the heater as shown in Figure 9.2. The components in this system and their functions are as follows:
1) Mixing Valve (Required) - During the heating season, the water exiting the tankless heater may be 180 degrees or more. The mixing valve blends hot water leaving the tankless heater with cold water so as to maintain the hot water supplied to the xtures at a xed temperature. This saves energy, increases the amount of usable hot water available to the homeowner, and reduces the risk of scalding.
Install a mixing valve with a setting range of approximately 110 to 130F. Follow the manufacturer’s instructions for
installing this valve. Usually a “heat trap” will be required between the coil and the “hot” connection on the mixing valve.
WARNING
A mixing valve does not eliminate the risk of scalding.
Set the mixing valve and boiler low limit adjustments as low as possible.
Feel water before showering or bathing.
If anti-scald or anti-chill protection is required, use devices specifically designed for such service. Install and maintain these devices in accordance with the manufacturer’s instructions. Do not use the mixing valve as a substitute for pressure balancing valves or other devices required by plumbing codes to protect against scalding.
2) Flow Restrictor (Recommended) - If water is drawn from the tankless coil at a rate in excess of the rating in Table 2.3, the temperature of the hot water may be too low to be of use. The use of a ow restrictor will prevent this problem by limiting the rate at which water can pass through the tankless heater. If a restrictor is used, select one having a rating in GPM approximately equal to the rating shown in Table 2.3. If possible, locate this restrictor at least 3 feet from the tankless heater inlet so that it is not subjected to excessive temperatures when no water is owing through the coil.
3) Pressure Relief Valve (Required) - Limits the pressure in the tankless heater and piping. Use an ASME constructed valve designed for domestic water service, such as the Watts #3L. Note that this is a pressure relief valve, not a T&P valve. Select a valve with a pressure setting less than or equal to the working pressure marked on the tankless coil. Pipe the discharge to a safe location using piping the same size as the discharge connection on the valve.
4) Hose Bib Valves (Recommended) - These valves permit the coil to be periodically “backushed” to remove sediment.
5) Globe or Ball Valve (Recommended) - Used to adjust the ow through the entire tankless heater system if needed.
20
Page 23
6) Unions (Required) - Tankless heaters may require periodic gasket replacement or other maintenance which requires removal of the heater from the boiler. Install unions anywhere in the tankless heater piping that will facilitate removal of the heater.
FIGURE 9.2: TANKLESS HEATER PIPING
21
Page 24
X Fuel Line Piping
WARNING
Under no circumstances can copper with sweat style connectors be used.
Do not use compression fittings.
Oil piping must be absolutely airtight or leaks or loss of prime may result.
Some jurisdictions require the use of a fusible shutoff valve at the tank and/or the burner. In addition, some jurisdictions require the use of a fusible electrical interlock with the burner circuit. Check your local codes for special requirements.
Fuel line piping design, materials and construction must be in accordance with local building codes, requirements of the local authority having jurisdiction, and, the latest edition of the Standard for the Installation of Oil-Burning Equipment (ANSI/NFPA
31) in the United States and CSA B139-04 for installation in Canada. Refer also to the instruction manuals provided with the burner and oil pump.
Depending on the location of the fuel oil storage tank in relation to an oil burner, there are four types of oil piping systems that may be encountered:
a) ONE-PIPE GRAVITY SYSTEM - Used when a fuel oil storage tank is positioned above an oil burner fuel pump. See
Figure 10.0. A vertical distance from top of the tank to center line of the pump (Dimension ‘H’) over 8 feet will result in a pump inlet pressure in excess of the 3-psi limit in NFPA-31.
b) ONE-PIPE LIFT SYSTEM (not recommended) - Used when a fuel oil storage tank is located below an oil burner fuel
pump. See Figure 10.1. The vertical distance from bottom of the tank to center line of the pump (Dimension ‘H’) must not exceed that shown in the pump manufacturer’s instructions. Although all oil piping systems must be airtight, one­pipe lift systems are particularly susceptible to nuisance lockout problems if the suction line is not completely airtight. A two-pipe lift system is therefore preferred to a one-pipe lift system.
c) TWO-PIPE GRAVITY SYSTEM (not recommended) - A vertical distance from top of the tank to center line of the pump
(Dimension ‘H’) over 8 feet will result in a pump inlet pressure in excess of the 3-psi limit in NFPA-31. This type of system should be converted to a one-pipe gravity system, as doing so will result in lower inlet line ow and longer lter life. See Figure 10.2
d) TWO-PIPE LIFT SYSTEM - Used when a fuel oil storage tank is located below an oil burner fuel pump suction port.
See Figure 10.3. The vertical distance from bottom of the tank to center line of the pump (Dimension ‘H’) must not exceed that shown in the pump manufacturer’s instructions. The maximum permissible distance ‘H’ allowed is reduced by the number of ttings, lters and valves installed in the line.
Once the type of system has been selected, observe the following:
1) Fuel line piping must be airtight. Do not use compression type ttings for tubing connections in fuel line piping. Use only listed are type ttings. Cast iron threaded ttings shall not be used.
2) Piping shall be substantially supported and protected against physical damage and corrosion.
3) Refer to supplied oil pump instruction manual for proper connections. On one-pipe systems, ensure that the fuel pump return port plug is tightened securely.
4) Some fuel pumps, such as the Suntec A and B series, are supplied with a loose bypass plug which must be installed on two­pipe systems. If such a plug is supplied, install it as shown in the pump manufacturer’s instructions. Do not install this bypass plug on one-pipe systems as pump seal damage will result.
5) Do not use check valves, especially on gravity feed systems.
6) Do not use Teon tape for threaded connections. Use a non-hardening thread sealant listed for use with #2 fuel oil .
22
Page 25
7) Attach required piping between burner fuel pump and fuel oil storage tank. Install one fuel shut-off valve near the storage
tank and second fuel shut-off valve near the oil burner fuel pump. Use a continuous run of copper tubing having a minimum wall thickness of 0.032”. On two-pipe systems, the return line should terminate 3” - 4” above suction line depth within the storage tank. Refer to the pump manufacturer’s instructions for tube sizing information.
8) Never install manual shut-off valves in the return piping of a two-pipe system.
9) Install a listed exible oil line/s at the burner to facilitate opening of the boiler’s swing door.
10) All systems require an oil lter. Use of a high efciency micron lter (Garber or equivalent) in addition to a conventional
lter is highly recommended, particularly on the FSZ080.
11) Use only #2 Fuel Oil with physical and chemical characteristics meeting the requirements of ASTM D-396.
FIGURE 10.0: ONE-PIPE GRAVITY SYSTEM
FIGURE 10.1: ONE-PIPE LIFT SYSTEM
23
Page 26
FIGURE 10.2: TWO-PIPE GRAVITY FEED SYSTEM (NOT RECOMMENDED)
FIGURE 10.3: TWO-PIPE LIFT SYSTEM
24
Page 27
XI Wiring
WARNING
All wiring and grounding must be done in accordance with the authority having jurisdiction or, in the absence of such requirements, with the
70).
Disconnect electrical power to the boiler and heating system before servicing. Positively assure that no voltage is present. Lock electrical boxes to prevent someone from inadvertently restoring power before the heating system is safe to operate.
Never defeat or jump out safety devices.
Protect each boiler circuit with a properly sized over-current protection device.
Make electrical connections carefully according to the boiler’s wiring diagram and instructions.
Wire additional field supplied safety limits, such as low water cutoffs and temperature limit devices, in series with the 120V circuit used to power the boiler. Do not alter the boiler’s factory wiring when adding an additional limit device.
National Electrical Code (ANSI/NFPA
1) 120 Volt Wiring - The boiler should be provided with its own 15A branch circuit with fused disconnect. 120VAC power con­nections are made inside the junction box on the right side of the boiler as follows (also see Figures. 11.0 and 11.1):
Connect Hot (“black”) to black pigtail in junction box.
Connect Neutral (“white”) to white pigtail in junction box.
Connect Ground (“green” or bare) to green pigtail in junction box.
2) Install R8285D Control – The R8285D (“transformer/relay”) control is shipped loose inside the accessory carton. Connect the plug on the back of this control into the receptical inside the junction box and mount the R8285D on the junction box as shown in Figure 2.3.
3) 24 Volt Thermostat Wiring - Connect to a 24 volt heating thermostat to Terminals R and G on the R8285 (Figure 11.1). Follow thermostat manufacturer’s instructions. To insure proper thermostat operation, avoid installation in areas of poor air circulation, hot spots (near any heat source or in direct sunlight), cold spots (outside walls, walls adjacent to unheated areas, locations subject to drafts). Provide Class II circuit between thermostat (or zone controls) and boiler.
3) Optional Tankless Heater Wiring - Route the wire harness from this control to the “R” and “G” (thermostat) terminals on the R8285D control so that they are in parallel with the space heating thermostat (Figure 11.1).
25
Page 28
Indirect Water Heater Wiring
Figure 11.2 shows eld wiring for an indirect water heater. A Honeywell R845A or equivalent DPST relay and transformer is required. The high limit described in Part VIII must also be supplied by the installer. A call for heat from the indirect water heater thermostat will energize the relay making both sets of contacts. One set of these contacts then energizes the cir­culator. The other set of contacts will make the “R” and “G” contacts on the R8285D control, ring the burner. If the boiler water temperature exceeds the high limit setting of 180F, the high limit will open the “R” - “G” circuit and the burner will shut down. If there is a call for space heat, the heating thermostat will make the “R”-”G” circuit and the boiler will re without regard to the status of the indirect water heater. The low water cut-off and pressure limit control will interrupt 120 volt power to the burner in the event of a low water or excessive pressure condition.
Feeder Wiring for Boilers Equipped with Hydrolevel CG450 Low Water Cut-offs
1) Using Hydrolevel VXT-120 feeder - Do not alter factory boiler wiring. Connect VXT-120 to CG450 as follows:
Connect the BLACK lead on the feeder to terminal A on the CG450.
Connect the WHITE lead on the feeder to terminal 2 on the CG450.
CAUTION
When making low voltage connections, make sure that no external power source is present in the thermostat circuits. If such a power source is present, it could destroy the boiler’s control. One example of an external power source that could be inadvertently connected to the low voltage connections is a transformer in old thermostat wiring.
Do not use the transformer provided on the boiler to power external devices such as zone valves. Doing so may cause damage to the transformer.
26
Page 29
FIGURE 11.0: WIRING CONNECTIONS DIAGRAM, STEAM, CG450 PROBE LWCO
27
Page 30
FIGURE 11.1: CONNECTIONS WIRING DIAGRAM FOR BURNER SPECIFIC PRIMARY CONTROL
28
Page 31
FIGURE 11.2: INDIRECT WATER HEATER FIELD WIRING
29
Page 32
XII Start-up and Checkout
WARNING
Never attempt to fill a hot empty boiler.
Make sure that the area around the boiler is clear and free from combustible materials, gasoline, and other flammable vapors and liquids.
Safe reliable operation of this boiler requires that the burner be checked and adjusted by a qualified oil serviceman using combustion test instruments.
Failure to perform all of the checks outlined in the following procedure could result in unreliable operation, damage to the boiler not covered under warranty, property damage, or unsafe operation.
All boilers equipped with burner swing door have a potential hazard which can cause severe property damage, personal injury or loss of life if ignored. Before opening swing door, turn off service switch to boiler to prevent accidental firing of burner outside the combustion chamber. Be sure to tighten swing door fastener completely when service is completed. In addition, the burner power cord will have to be disconnected from the receptacle in the front jacket.
Use the following procedure for initial start-up of the boiler:
1) Ensure that the boiler is lled to the normal water level.
2) Verify that the vent system is properly installed and free of obstructions prior to start-up of the boiler. Refer to Section VII
for more information.
3) Inspect all wiring for loose or uninsulated connections, proper size fuses installed, etc.
4) Verify that oil tank is lled with #2 fuel oil meeting ASTM D396 specications, oil piping has been tested and is air tight,
and shutoff valve(s) are closed.
5) Check initial settings of oil burner air band and air shutter, head setting etc., and readjust if needed. See Table 12.1 for
setup and combustion data pertaining to a particular boiler/ burner combination.
6) Ensure the burner is tightly secured to the burner swing door creating an airtight seal.
7) Attach plastic hose to oil pump vent tting and provide a container to catch oil during oil pump bleeding procedure.
8) Install 0-200 PSI pressure gauge into oil pump gauge port.
9) Open all oil line shutoff valves.
10) Open ame observation port cover on burner swing door to see ame.
11) Adjust system thermostat to highest setting.
12) Set pressure limit control to suit individual requirements of the installation. For most systems, the cut-in pressure should
be set at 0.5 psi with a 1 psi differential.
13) Turn the line service switch to “ON” position.
14) Crack open vent tting on the oil pump and allow burner to run until a solid oil stream, free of air bubbles, ows for 15
seconds into container. As the vent tting is closed, the burner should re and ame should be visible through observation
port immediately (or after prepurge timing has expired, if a burner is so equipped). Refer to burner instructions for more
details.
15) Immediately upon ring the boiler, check the smoke level. If the smoke level is in excess of a #1, open the air adjustment
to bring the smoke level below a #1.
16) Make sure that the oil pressure matches that shown in Table 12.1 for the burner supplied. Adjust pressure if required.
30
Page 33
FIGURE 12.0: FLUE DRAFT TAPPING
17) Check the vacuum at the inlet of the fuel pump. Make sure that the vacuum does not exceed the fuel pump manufacturer’s
limit (consult the pump manufacturer’s instructions).
18) Close the ame observation cover.
19) After chimney has warmed-up for at least 5 minutes, adjust barometric draft regulator to obtain a draft at the 1/4” tapping
shown in Figure 12.0 that is within the range shown in Table 12.1. DRAFT AT THIS LOCATION MUST NEVER BE
POSITIVE.
20) Check the CO2 and conrm that it is between the minimum and maximum limits shown in Table 12.1. Adjust if
necessary.
21) Verify that the smoke level still does not exceed #1 and that the draft in the breech is still within the range prescribed by
Table 12.1.
22) Turn off the burner and remove pressure gauge. Install and tighten gauge port plug, then restart the burner.
23) Check for clean cutoff of the burner. Air in the oil line between fuel pump and nozzle will compress, while burner is
running, and expand, when burner shuts off, causing oil line pressure to drop and nozzle drip after burner stops. Cycle burner
on and off 5 to 10 times to purge air completely.
24) Check thermostat operation by raising or lowering its set point as required, cycling burner on and off.
25) Verify primary control operation and safety features according to procedure outlined in the instructions furnished with
the burner.
26) Check pressure limit control operation. Jump thermostat terminals and allow burner to run until boiler pressure exceeds
cut-in pressure plus the differential. The burner should shut down.
27) Check low water cut-off operation. With the thermostat still jumped, re the boiler and crack the boiler drain valve so that
water is slowly drained from the boiler. Conrm that the burner shuts down before the water level drops below the bottom
of the sight glass. Do not permit the boiler to re without water visible in the sight glass. Add water to the boiler and
conrm that the burner restarts. Remove thermostat jumper and reconnect thermostat upon check completion.
28) After the boiler has operated for approximately 30 minutes, check the boiler and heating system for leaks. Repair any
leaks found at once.
29) After the above checks have been completed, leave thermostat(s) at desired setting. Leave all instructions provided with
31
Page 34
the boiler with owner or in boiler room, displayed near boiler.
30) After new boiler has been installed and put into continuous operation for several days, clean the boiler of oil, grease,
sludge, and other contaminants that may have been present in existing piping. This will prevent unsteady water line and water
carry over into supply main. The boiler boil-out should be done as follows:
a) Turn off the burner.
b) Drain water from boiler until about one inch of water is visible in gauge glass.
c) Run a hose or temporary piping from the boiler drain valve to a location where hot water can be safely discharged.
Drain approximately ve gallons of water from the boiler and mix-in an appropriate amount of an approved boil-out
compound. Remove safety valve and rell the boiler with prepared solution through funnel. Replace safety valve.
d) Run a hose or temporary piping from the 1-1/2” skimmer tap on the upper rear section to a location where hot water
can be safely discharged.
e) Start the burner. Run boiler for several hours, boiling the water, without generating steam pressure. Open the water
feed valve sufciently to allow a slight overow of water through the skimmer tapping drain line. Continue boiling
until water coming out is clear.
f) Turn off the burner. Drain hot water from boiler through boiler drain valve to a location where hot water can be
safely discharged. Rell the boiler to normal water line level. If water in the gauge glass does not look clear, repeat
above boil-out procedure again until water clears out.
g) Reinstall safety valve and related piping.
h) Conduct pH and Alkalinity test of water in the system. The pH reading should be in 7 to 11 range.
NOTE
When substantial amount of make-up water is used due to lost condensate, or when make-up water is hard or corrosive, water treatment is required. Contact qualied water treatment company for recommended water treatment compounds and procedure.
WARNING
Attempts to use burners or burner configurations other than those shown in Table 12.1 could result in reliability problems, property damage, personal injury or loss of life
32
Page 35
TABLE 12.1a: BECKETT BURNER CONFIGURATION AND SETUP DATA
BOILER MODEL FSZ080 FSZ100 FSZ130 FSZ160
BURNER MODEL AFG AFG AFG AFG
AIR TUBE COMBO 70MMAQN 70MMAQN 70MLASN 70MLASN
HEAD TYPE L1 L1 V1 V1
STATIC PLATE 3-3/8U 3-3/8U NONE 2-3/4M
LOW FIRING RATE BAFFLE
INSERTION LENGTH 2.0 2.0 2.0 2.0
PITCH ANGLE 0 0 0 0
STANDARD NOZZLE
PUMP PRESSURE (psi) 150 150 150 150
HEAD SETTING FIXED FIXED 0.0 3.0
STARTING: SHUTTER SETTING BAND SETTING
DRAFT IN FLUE (in w.c.) 0 to -0.02 0 to -0.02 0 to -0.02 0 to -0.02
MAX SMOKE (Bacharach Scale)
FLUE CO
(%)
2
MIN. MAX.
Beckett Silver
(5880)
DELAVAN
.65 X 60A
10
1
NONE NONE NONE
DELAVAN
.85 X 60B
7
1
HAGO
1.10 X 60B
8
2
#1 #1 #1 #1
11.5
12.8
11.5
12.8
11.5
12.8
HAGO
1.35 X 60B
9 5
11.5
12.8
TABLE 12.1b: RIELLO BURNER CONFIGURATION AND SETUP DATA
BOILER MODEL FSZ080 FSZ100 FSZ130 FSZ160
BURNER MODEL F3 F5 F5 F5
TURBULATOR DISK 5 SLOT 9 SLOT 9 SLOT 9 SLOT
COMBUSTION HEAD VSBT 10” LBT 6” SBT VSBT
STANDARD NOZZLE
DELAVAN
.65 X 70A
INSERTION LENGTH 2.25 10 3.5 2.25
PUMP PRESSURE (psi) 145 145 150 145
TURBULATOR SETTING 3.0 2.0 4.0 4.0
AIR GATE SETTING 2.75 2.5 3.75 4.0
DRAFT IN FLUE (in w.c.) 0 to -0.02 0 to -0.02 0 to -0.02 0 to -0.02
MAX SMOKE (Bacharach Scale)
FLUE CO
(%)
2
MIN. MAX.
#1 #1 #1 #1
11.5
12.8
DELAVAN
.85 X 60B
11.5
12.8
DELAVAN
1.10 X 60B
11.5
12.8
DELAVAN
1.35 X 60B
11.5
12.8
33
Page 36
XIII Service and Maintenance
A. Water Side Maintenance
The following procedure should be performed on an annual basis:
1) Turn off electrical power and oil supply to the boiler.
2) Inspect the low water cut-off:
For Hydrolevel CG450 low water cut-offs - Remove and inspect the probe for scale and sediment buildup. Clean
any sediment or scale from the probe with a scouring pad or steel wool. Consult the Hydrolevel CG450 manual for any additional maintenance information. Test the low water cut-off before placing the boiler back into service.
3) Allow the boiler to cool to room temperature and drain the boiler. Remove the 1-1/4” plug from the unused return tapping. Use a ashlight to inspect the bottom row of pushnipples for accumulated scale or mud. If a signicant amount is present, use the following procedure to clean the inside of the heat exchanger:
a) Temporarily install a 1-1/4” inch or larger full port ball valve in place of the 1-1/4” plug. Temporarily pipe the outlet
of this valve to a location where hot water and steam can be safely discharged. b) Make sure that this valve is closed and that the water level is at the normal water line. c) If a king valve is present in the steam main takeoff, close it. Alternatively, temporarily replace enough of the vents
on the mains and/or radiators with plugs so that 2-5 psi can be developed when the boiler is red. d) Fire the boiler and allow it to steam until 2-5 psi is registered on the gauge. e) Turn off the burner and immediately fully open the 1-1/4” valve. f) Allow the boiler to blow down until either the water runs clear or the water level reaches the bottom of the gauge
glass. g) Allow all parts of the boiler to cool to room temperature. Drain the boiler completely and remove the 1-1/4” valve. h) If signicant mud or scale is still present in the bottom of the boiler, repeat steps (b) through (g) until all mud or
scale is removed. i) Once all mud or scale is removed, replace the 1-1/4” valve and temporary blow-down piping with the standard plug. j) After all parts of the boiler are at room temperature, rell the boiler to the normal water line.
NOTE
A large accumulation of mud or scale in the bottom of the heat exchanger is usually a sign of excessive feedwater make-up. Such accumulations can cause severe heat exchanger damage. If mud or scale accumulations are found:
Make sure that all vents are in working order. Vents should not permit any passage of steam or water.
Check all steam and return piping for leaks. Be aware that buried return piping can leak and go undetected
during normal operation.
TANKLESS HEATER MAINTENANCE
During the warm months, make sure that the water level in the boiler is 30 to 31-1/2 inches above the surface on
which the boiler is installed. Failure to do this may result in inadequate hot water and/or steaming when there is no call
for heat.
Maintain the mixing valve in accordance with the valve manufacturer’s instructions.
34
Page 37
B. Fire Side Maintenance
WARNING
All boiler cleaning must be completed with the burner service switch turned off. Boilers equipped with burner swing door have a potential hazard which can cause severe property damage, personal injury or loss of life if ignored. Before opening swing door, turn off service switch to boiler to prevent accidental firing of burner outside the combustion chamber. Disconnect the burner plug from the receptacle in the front jacket. Be sure to tighten the swing door fastener completely when service is completed.
The following procedure should be performed on an annual basis:
1) Turn off electrical power and oil supply to the boiler.
2) Clean the boiler as follows:
a) Remove the two 3/8” bolts from either side of the swing door and open the door to access the combustion chamber.
b) Remove the two smoke box clean-out covers from the rear smoke box by removing the four 5/16” bolts. It is
not necessary to remove the vent connector from the smoke box to clean boiler however if there is heavy soot accumulation in the boiler remove the vent connector to inspect the base of the chimney for condensate or accumulation of debris.
c) Remove the bafes (if installed) from the ue passages.
d) Clean the 3rd Pass - Insert a 2” dia x 42” long wire or ber bristle brush into one of the two 3rd ue passes. Using
long strokes push the brush all the way through the boiler until the brush has exited the smoke box opening. Pull the brush all the way forward until it has exited the front of the boiler. Continue this operation for the entire height of the ue way until clean. Repeat the operation for the other 3rd pass ue way.
e) Clean the 2nd Pass - Insert a 2” dia x 42” long wire or ber bristle brush into one of the two 2nd ue passes. Using
long strokes push the brush all the way through the boiler until the brush hits the back wall of the reversing chamber. Pull the brush all the way forward until it has exited the front of the boiler. Continue this operation for the entire height of the ue way until clean. Repeat the operation for the other 2nd pass ue way.
f) Vacuum to loose debris in the bottom of the combustion chamber and smoke box
g) Clean the Combustion Chamber - Use a wire or ber bristle brush to clean the surfaces of the combustion chamber.
Vacuum all loose debris in the chamber.
h) Check condition of the burner swing door insulation and rope gaskets for signs of damage; replace if required.
i) Check burner head for signs of deterioration. Clean the head of any deposits.
j) Insert bafes (if originally installed) into the correct ueways.
k) Attach the smoke box clean-out covers onto the rear of the boiler using the 5/16” bolts originally removed. Verify
that the rope gasket is in good order before assembly. Replace rope gasket if necessary. Do not over tighten. The bolts should be snug but not bottomed out.
l) Close the swing door and tighten it with the 3/8” bolts originally removed. When securing the burner swing door
make sure the door is drawn-in equally on both sides by alternating the tightening method for right side to left side. Do not over tighten. The rope gasket will provide sufcient seal when door is snugged into place.
Clean The Boiler Even If There Are No Significant Soot Deposits. Failure To Remove All Sulfur And Ash Deposits Annually Can Cause Severe Corrosion Damage.
IMPORTANT
35
Page 38
WARNING
The boiler must be connected to an approved chimney in good condition. Serious property damage could result if the boiler is connected to a dirty or inadequate chimney. The interior of the chimney flue must be inspected and cleaned before the start of the heating season and should be inspected periodically throughout the heating season for any obstructions. A clean and unobstructed chimney flue is necessary to allow noxious fumes that could cause injury or loss of life to vent safely and will contribute toward maintaining the boiler’s efficiency.
3) Inspect the vent system:
a) Make sure that the vent system is free of obstructions and soot.
b) Make sure that all vent system supports are intact.
c) Inspect joints for signs of condensate or ue gas leakage.
d) Inspect venting components for corrosion or other deterioration. Replace any defective vent system components.
e) Ensure all vent piping joints are gas tight and secured with sheet metal screws.
4) Service the oil burner:
a) Replace oil nozzle with identical make and model (see Table 12.1).
b) Inspect the electrodes. Replace if they are deteriorated. Make sure that the electrode position is set according to the
burner manufacturer’s instructions.
c) Remove and clean fuel pump strainer.
d) Remove any accumulations of dust, hair, etc. from the air shutter, blower wheel, and other air handling parts of the
burner.
e) Replace the fuel oil line lter element and gaskets.
6) Inspect all oil piping and ttings for kinks and leaks. Repair any found.
7) Inspect the hydronic piping and boiler for water leaks. Repair any leaks found immediately.
8) Verify operation of relief valve by manually lifting lever; replace relief valve immediately if valve fails to relieve pressure.
9) Open fuel line shut-off valve(s) and restore electrical power to the boiler.
10) Fire the boiler and check it out using the procedure outlined in “Start-up and Checkout” . This must include checking the burner adjustments using instruments. Check for proper operation of all controls.
Water leaks can cause severe corrosion damage to the boiler or other system components. Repair any leaks found immediately.
WARNING
36
Page 39
Important Product Safety Information
Refractory Ceramic Fiber Product
Warning:
The Parts list designates parts that contain refractory ceramic fibers (RCF). RFC has been classified as a possible human carcinogen. When exposed to temperatures about 1805°F, such as during direct flame contact, RFC changes into crystalline silica, a known carcinogen. When disturbed as a result of servicing or repair, these substances become airborne and, if inhaled, may be hazardous to your health.
AVOID Breathing Fiber Particulates and Dust
Precautionary Measures:
Do not remove or replace RCF parts or attempt any service or repair work involving RCF without wearing the following protective gear:
1. A National Institute for Occupational Safety and Health (NIOSH) approved respirator
2. Long sleeved, loose fitting clothing
3. Gloves
4. Eye Protection
Take steps to assure adequate ventilation.
Wash all exposed body areas gently with soap and water after contact.
Wash work clothes separately from other laundry and rinse washing machine after use to avoid contaminating other clothes.
Discard used RCF components by sealing in an airtight plastic bag. RCF and crystalline silica are not classified as hazardous wastes in the United States and Canada.
First Aid Procedures:
If contact with eyes: Flush with water for at least 15 minutes. Seek
immediate medical attention if irritation persists.
If contact with skin: Wash affected area gently with soap and water.
Seek immediate medical attention if irritation persists.
If breathing difficulty develops: Leave the area and move to a location
with clean fresh air. Seek immediate medical attention if breathing difficulties persist.
Ingestion: Do not induce vomiting. Drink plenty of water. Seek
immediate medical attention.
37
Page 40
XIV Trouble Shooting
A. Combustion
1) Nozzles - The selection of the nozzle supplied with the FSZ boiler is the result of extensive testing to obtain the best ame shape and efcient combustion. Other brands of the same spray angle and pattern may be used but may not perform at the expected level of CO2 and smoke. Nozzles are delicate and should be protected from dirt and abuse. Nozzles are mass­produced and can vary from sample to sample. For all of those reasons a spare nozzle should be part of a serviceman’s replacement parts inventory.
2) Flame Shape - As seen for the observation port, the ame should appear straight with no sparklers rolling up toward the crown of the chamber. If the ame drags to the right or left, sends sparklers upward or makes wet spots on the chamber walls, the nozzle should be replaced. If the condition persists look for fuel leaks, air leaks, water or dirt in the fuel as described below.
3) Fuel Leaks - Any fuel leak between the pump and the nozzle will be detrimental to good combustion results. Look for wet surfaces in the air tube, under the ignitor and around the air inlet. Any such leaks should be repaired as they may cause erratic burning of the fuel and in the extreme case may become a re hazard.
4) Air Leaks - Any such leaks should be repaired as they may cause erratic burning of fuel and in extreme cases may become a re hazard.
5) Gasket Leaks - If CO2 readings between 11.5% and 12.8% with a #1 smoke cannot be obtained in the breeching, or if odors are observed, look for leaks around the burner mounting gasket, observation door and canopy gasket, or in the breeching below the point where the ue gas sample is taken. Air leakage into the boiler or breeching can cause low CO2 readings (the lower the ring rate, the greater effect an air leak can have on CO2 readings). Such leaks can also cause ue gas leakage into the building, resulting in odor complaints.
6) Dirt - The use of a fuel lter is good practice. Accidental accumulation of dirt in the fuel system can clog the nozzle or nozzle strainer and produce a poor spray pattern from the nozzle. The smaller the ring rate, the smaller the slots in the nozzle and the more prone to plugging it becomes.
7) Water - Water in the fuel in large amounts will stall the fuel pump. Water in the fuel in smaller amounts will cause excessive wear on the pump. More importantly it chills the ame and causes smoke and unburned fuel to pass through the combustion chamber and clog the ueways of the boiler.
8) Cold Oil - If the oil temperature near the fuel pump is 40°F or lower, poor combustion or delayed ignition may result. Cold oil is harder for the nozzle to atomize, thus the oil droplets get larger and travel further creating a longer ame. An outside fuel tank that is above grade or has fuel lines in a shallow bury is a good candidate for cold oil. The best solution is to bury the tank and lines deep enough to keep the oil above 40°F. Be sure to follow any state and local codes when burying fuel oil tanks and/or fuel oil lines.
9) Start-Up Noise - Delayed ignition is the cause of start-up noises. If it occurs recheck for electrode settings, ame shape, air or water in the fuel lines.
10) Shut Down Noise - If the ame runs out of air before it runs out of fuel, an after burn with noise may occur. That may be the result of a faulty cut-off valve in the fuel pump, or it may be air trapped in the nozzle line. It may take several ring cycles for that air to be fully vented through the nozzle. Water in the fuel or poor ame shape can also cause shut down noises.
TEST PROCEDURE FOR FUEL SIDE PROBLEMS
A good test for isolating fuel side problems is to disconnect the fuel system and with a 24” length of tubing, fire the burner out of an auxiliary five gallon pail of clean, fresh, warm #2 fuel oil from another source. If the burner runs successfully when drawing out of the auxiliary pail then the problem is isolated to the fuel or fuel lines being used on the installation.
38
Page 41
Notes
39
Page 42
XV Parts
KEY # DESCRIPTION
HEAT EXCHANGER ASSEMBLY WITH
1
HEATER OPENING
HEAT EXCHANGER ASSEMBLY WITH NO
*
HEATER OPENING
2 SPANNER BAR 2 410403 410403 410404 410405
3 NYLON GLIDE 700111 4 4 4 4
4 HEX HD CAP SCREW 5/16-18 X 7/8” 900109 10 10 10 10
5 FLAT WASHER 5/16” 900102 10 10 10 10
6 HEX JAM NUT 5/16-18 900103 4 4 4 4
7 HINGE BRACKET 410010 1 1 1 1
8 HEX HD CAP SCREW 5/16-18 X 7/8” 900109 2 2 2 2
9 SWING DOOR 410020 1 1 1 1
10 SWING DOOR INSULATION LESS POCKETS 410021 1 1 1
10 SWING DOOR INSULATION WITH POCKETS 410023 1
11 1/2” DIA ROPE GASKET - SWING DOOR 410024 1 1 1 1
12 1/8” DIA ROPE GASKET - OBSERVATION PORT 410032 1 1 1 1
QTY. OR
CROWN PN
1 420013 420013 420014 420015
1 4200135 4200135 4200145 4200155
QUANTITY PER BOILER OR CROWN PART NUMBER
FSZ080 FSZ100 FSZ130 FSZ160
13 OBSERVATION PORT COVER 410022 1 1 1 1
14 SOCKET HD CAP SCREW 5/16”-18 X 3/4” 900108 2 2 2 2
15 HEX HD TAP BOLT 3/8”-16 X 1-3/4” 900170 2 2 2 2
16 USS FLAT WASHER 3/8” 90-036 2 2 2 2
17 SMOKEBOX 410006 1 1 1 1
18 BRASS SQUARE HD PIPE PLUG 1/4” NPT 950041 1 1 1 1
19 SMOKEBOX COLLAR - 6” DIA. 410026 1 1 1
19 SMOKEBOX COLLAR - 7” DIA. 410027 1
20 CLEAN OUT COVER 410004 2 2 2 2
21 1/2” DIA ROPE GASKET - CLEAN OUT COVER 410005 EA EA EA EA
23 SECOND PASS BAFFLE - 100/130/160 410008 2 2 2
24 HEATER GASKET 270001 1 1 1 1
26 HEATER ASSEMBLY 420002 1 1 1 1
27 USS FLAT WASHER 3/8” 90-036 6 6 6 6
28 CAP SCREW 3/8”-16 X 7/8” 900450 6 6 6 6
* NOT SHOWN
40
Page 43
41
Page 44
KEY # DESCRIPTION
29 RECEPTACLE ENCLOSURE 410090 1 1 1 1
30 FRONT JACKET PANEL 420310 1 1 1 1
31 RIGHT SIDE JACKET PANEL 1 420303 420303 420304 420305
32 LEFT SIDE JACKET PANEL 1 420313 420313 420314 420315
33 REAR JACKET PANEL 420301 1 1 1 1
34 TOP JACKET PANEL 1 420323 420323 420324 420325
35 JUNCTION BOX 960155 1 1 1 1
37 FIBERGLASS INSULATION WRAPPER 1 422303 422303 422304 422305
40 POWER RECEPTACLE 960041 1 1 1 1
41 CROWN NAMEPLATE 98-004 1 1 1 1
42 #10 X 1/2” SHEET METAL SCREW 900120 15 15 15 15
43 5/16”-18 X 1/2” PAN HEAD SCREW 900420 4 4 4 4
44 5/16”-18 X 3” THREADED STUD 900111 2 2 2 2
45 5/8”O.D. X 2-5/32” LONG JACKET SPACER 410200 2 2 2 2
46 5/16”-18 ACORN NUT 146-95-042 2 2 2 2
QTY. OR
CROWN PN
QUANTITY PER BOILER OR CROWN PART NUMBER
FSZ080 FSZ100 FSZ130 FSZ160
* NOT SHOWN
42
Page 45
43
Page 46
KEY # DESCRIPTION
QTY. OR
CROWN PN
50 BECKETT OIL BURNER ASSY (NOTE 1) 1 42080B 42100B
50 RIELLO OIL BURNER ASSY (NOTE 1) 1 42080R 42100R
QUANTITY PER BOILER OR CROWN PART NUMBER
FSZ080 FSZ100 FSZ130 FSZ160
2
41130B 41160B
2
41130R 41160R
51 HONEYWELL R8285D5001 W/ MOLEX CONNECTOR 9601913 1 1 1 1
52 PRESSURE GAUGE 95-070 1 1 1 1
53 PRESSURE LIMIT, HONEYWELL L404F1367 3503800 1 1 1 1
54 SYPHON, 1/ 4” NPT X 1-7/8” X 3-1/2” X 90 950058 1 1 1 1
55 CG450 PROBE LOW WATER CUT-OFF 450450 1 1 1 1
56 GAUGE GLASS SET, 6” CONBRACO 21-104-10 950079 1 1 1 1
57 LIMIT, HONEYWELL L4006A2015 35-3510 1 1 1 1
58 WELL, 1/2” NPT X 3” 35-1006 1 1 1 1
60 3/4” NPT X 3” LONG NIPPLE 95-027 1 1 1 1
61 3/4” NPT 90° ELBOW 95-057 1 1 1 1
62 3/4” NPT X 8” LONG NIPPLE 950008 1 1 1 1
63 3/4” NPT SAFETY VALVE, 15 PSI, CONBRACO 13-512-B15 95-079 1 1 1 1
64 1-1/2” NPT X 3” NIPPLE 950023 1 1 1 1
65 1-1/2” NPT CAP 950107 1 1 1 1
66 1-1/4”NPT X 5” NIPPLE 95-043 1 1 1
66 1-1/2” NPT X 5” NIPPLE 950025 1
67 1-1/4” X 1-1/4” X 3/4” NPT REDUCING TEE 95-100 1 1 1
67 1-1/2” X 1-1/2” x 3/4” NPT REDUCING TEE 950019 1
68 3/4” NPT DRAIN VALVE 95-041 1 1 1 1
* BAROMETRIC DRAFT CONTROL 1 13-020 13-020 13-020 13-018
* FSZ STANDARD WIRING HARNESS 9601910 1 1 1 1
* FSZ PRESSURE LIMIT HARNESS 9601911 1 1 1 1
* FSZ LWCO HARNESS 9601912 1 1 1 1
* NOT SHOWN
1. PART NUMBERS PROVIDED ARE FOR FULLY CONFIGURED BURNERS AND INCLUDE PRIMARY SAFETY CONTROL, NOZZLES, BURNER CORD ASSEMBLIES AND (WHERE APPLICABLE) LOW FIRING RATE BAFFLES.
2. BURNER ASSEMBLIES FOR THE FSZ100 ARE PACKAGED WITH 2 SECOND PASS BAFFLES PN 410008.
44
Page 47
45
Page 48
Appendix A: Optional Dropped Header Gravity Return Piping Kit
The following near-boiler piping kits are available from Crown for use with FSZ boilers installed in gravity return systems:
421095 - Dropped Header Gravity Return Near Boiler Piping Kit (FSZ080,100,130)
421096 - Dropped Header Gravity Return Near Boiler Piping Kit (FSZ160)
These kits provide the pipe and ttings needed for the “drop header” piping as listed in Table A.1 for the FSZ080, FSZ100 and FSZ130 and in Table A.3 for the FSZ160.
Installation of Dropped Header Gravity Return Piping Kit
1) Assemble Dropped Header Gravity Return Piping Kit for the FSZ080, FSZ100 and FSZ130 as shown in Figure A.2.
2) Assemble Dropped Header Gravity Return Piping Kit for the FSZ160 as shown in Figure A.4.
3) Tighten unions only after all piping is in the proper position. Use of pipe dope or teon tape on all threaded surfaces is
reommended.
WARNING
Difference in piping compound and or method may effect pipe alignment.
46
Page 49
TABLE A.1: Dropped Header Material List for FSZ080, FSZ100 and FSZ130 Boilers
Item Fitting Description Quantity
1 2” x 12” Nipple 2
2 2” Union 3
3 2” x 6” Nipple 2
4 2” Elbow 5
5 2” x 15” Nipple 2
6 2” x 7” Nipple 2
2” x 3” Nipple (FSZ080 and FSZ100)
7
8 2” x 4-1/2” Nipple 3
9 2” Tee 2
10 2” - 1-1/2” Reducing Elbow 1
11 1-1/2” x 8” Nipple 1
12 1-1/2” Union 1
13 1-1/2” x 5-1/2” Nipple 1
14 1-1/2” Wye 1
15 1-1/2” - 1-1/4” Bushing 1
16 1-1/4” x 22” Nipple 1
17 1-1/4” x 3/4” x 1-1/4” Tee 2
18 1-1/4” x 12” Nipple 1
19 1-1/4” x 1-1/4” x 3/4” Tee 1
20 1-1/4” x 7” Nipple 1
21 1-1/4” x Close Nipple 2
22 1-1/4” Union 1
23 3/4” Plug 1
NOTE: Item 15 shown at boiler is installed on the boiler at the factory.
or
2” x 9” Nipple (FSZ130)
1
FIGURE A.2: Dropped Header Gravity Return Diagram for FSZ080, FSZ100 and FSZ130
47
Page 50
TABLE A-3: Dropped Header Material List for FSZ160 Boilers
Item Fitting Description Quantity
1 2” x 12” Nipple 2
2 2” Union 3
3 2” x 6” Nipple 2
4 2” Elbow 4
5 2” x 15” Nipple 2
6 2” x 7” Nipple 2
7 3” x 2” Reducing Elbow 2
8 3” x 9” Nipple 1
8A 3” x 10” Nipple 1
9 3” Union 1
10 3” x 5” Nipple 2
11 3” x 3” x 2” Tee 1
12 3” Tee 1
13 2” x 7” Nipple 1
13A 2” x 5” Nipple 1
14 2” Wye 1
15 2” - 1-1/2” Bushing 1
16 1-1/2” x 20-3/4” Nipple 1
17 1-1/2” x 1-1/2” x 3/4 Tee 1
18 1-1/2” x 5” Nipple 1
19 1-1/2” x 3/4” x 1-1/2” Tee 2
20 1-1/2” x 4” Nipple 1
21 1-1/2” Union 1
22 1-1/2” x 8” Nipple 2
23 3/4” Plug 1
FIGURE A.4: Dropped Header Gravity Return Diagram for FSZ160
48
Page 51
Notes
Page 52
Manufacturer of Hydronic Heating Products
P.O. Box 14818 3633 I. Street
Philadelphia, PA 19134
www.crownboiler.com
PN: 980265
FSZ
Rev 3 - 07/13