Crown Boiler CLBR68-112, CHB68-112, CHC68-96, CLBF68-112 User Manual

P/N: MO-426 (Printed Instruction Manual) Note: This page is not to be included as part of printed hard copy.
Overall Specifications:
Material: white plain paper Printed text: black Binder: staple upper left corner
Individual page specifications:
The balance of instruction manual pages to be printed utilizing both front and back side of paper.
OIL-FIRED CENTRAL FURNACE
Installation, Operation, And Service Manual
With Users Information Section
Models:
CHB68-112 CHC68-96 CLBF68-112
CLBR68-112
Do NOT store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
Improper installation, adjustment, alteration, service, or maintenance can
cause a fire or explosion resulting in property damage, personal injury, or loss of life. For assistance or additional information consult a qualified installer or service agency.
These instructions should be:
read prior to installing the furnace.
retained for reference by qualified service personnel.
reviewed before performing any service or maintenance.
c WARNING:
Crown Boiler Company
3633 “I” Street
Philadelphia, Pennsylvania 19134
Made in USA
MO-426
ECN 5079-MA
Contents
SECTION PAGE
Notice to the Installer .................................................................................................. 4
INSTALLATION GUIDELINES ...................................................................................... 5
Codes ................................................................................................................. 5
Installation Location ............................................................................................ 5
Closet and Alcove Installation ............................................................................. 6
Standard Clearances .......................................................................................... 6
Air for Combustion and Ventilation ..................................................................... 7
Chimney Inspection ............................................................................................ 10
Flue / Chimney / Vent Connector ........................................................................ 10
Power (Side-Wall) Venting – Important Note Regarding ..................................... 11
Draft Regulator .................................................................................................... 11
Duct Work and Air Conditioning .......................................................................... 12
Air Filter Mounting ............................................................................................... 12
Electrical Connections ........................................................................................ 14
Room Thermostat ............................................................................................... 14
Combustion Chamber ......................................................................................... 15
Oil Burner and Oil Nozzle Installation .................................................................. 15
Fuel System Installation ....................................................................................... 18
Horizontal / Counterflow Furnace Setup ............................................................. 19
INITIAL OPERATION OF THE FURNACE .................................................................... 21
Initial Burner Operation ....................................................................................... 21
Supply/Return Airflow and Air Temperature ........................................................ 23
Furnace Limit and Blower Controls ..................................................................... 25
Room Thermostat ............................................................................................... 26
Instructions to Our Customer / End User ............................................................. 26
SERVICE ....................................................................................................................... 27
Troubleshooting .................................................................................................. 27
Flame Sensor (“Cad Cell”) Checkout Procedure ................................................ 31
Replacement Parts ............................................................................................. 32
MAINTENANCE ............................................................................................................. 33
Air Filter(s) ........................................................................................................... 33
Oil Burner ............................................................................................................ 33
Blower and Motor ................................................................................................ 33
Heat Exchanger .................................................................................................. 33
Flue and Chimney ............................................................................................... 35
USERS INFORMATION ................................................................................................. 36
Operating Instructions ........................................................................................ 36
Oil Supply ........................................................................................................... 37
Extended Shutdown ........................................................................................... 38
Combustion Air and Ventilation Supply ................................................................ 38
Inspection Areas ................................................................................................. 38
2
APPENDIX A: SOURCES FOR REFERENCED STANDARDS ................................... 40
APPENDIX B: ELECTRICAL DIAGRAMS ..................................................................... 41
APPENDIX C: SPECIFICATION SHEETS .................................................................... 43
APPENDIX D: REPLACEMENT PARTS ....................................................................... 46
3
Notice to the Installer
Installation of this oil-fired furnace must be performed by a qualified installer in accordance with all local codes and authorities having jurisdiction. In the absence of local governing codes, installation shall conform to these instructions and to the regulations of the National Fire Protection Association’s 2001, and the National Electrical Code, ANSI/NFPA 70-2002, or the latest editions thereof.
A qualified installer, also referred to in this instruction manual as a “qualified heating contractor”, is an individual, or agency, properly licensed and experienced to install and
service oil-burning equipment in accordance with all local codes and ordinances. Material and Workmanship
This furnace was built with the highest quality materials and attention to workmanship. However, omissions and defects occasionally occur. Before installing the furnace, inspect the furnace thoroughly. If missing parts, defective material, or poor workmanship are evident, report the model and serial numbers imprinted on the furnace rating label to the seller for adjustment.
Packaging
A complete furnace is contained within two (2) packages. The factory completed all feasible assembly. However certain components including oil burner and draft regulator and, if supplied, door handle, air filter(s), and air filter rack(s), must be assembled to the furnace, or the venting system, in the field. Refer to the assembly instructions.
Shipping Damage
If this furnace was damaged during transit, please immediately request the transportation company inspect the furnace and issue a concealed damage report. The party receiving the furnace should file the claim for shipping damage. Report any shipping damage immediately.
It is absolutely essential that a damage report be obtained. If a concealed damage report is not obtained, we cannot provide assistance in recovering your claim against the transportation company.
Warranties
c WARNING: The manufacturer of this equipment assumes no liability for any damages resulting from unauthorized modifications made to the furnace, or any components thereof, or improper installation of the furnace in the field. Furthermore, any such field modifications VOID THE WARRANTY and place responsibility for safe and reliable operation of the furnace on those who performed the modification(s).
Complete and return any enclosed warranty cards. These must be on file to verify installation dates for replacement of any warrantied part(s).
Standard for the Installation of Oil-Burning Equipment, NFPA 31-
4
Codes
All local codes and regulations take precedence over the instructions in this manual and shall be followed accordingly. In the absence of local codes, this installation must conform to these instructions and to the regulations of the National Fire Protection Association (NFPA) publications, the Standard for the Installation of Oil-Burning Equipment, NFPA 31-2001, and the National Electrical Code, ANSI/NFPA 70-2002, or the latest editions thereof. To obtain copies of these publications for a fee, contact the NFPA at the address given in Appendix A of this manual.
Installation Location c WARNING:
These furnaces are designed for indoor installation ONLY.
These furnaces are NOT to be used as construction heaters.
DO NOT hang the horizontal / counterflow furnace from a structure, or
surface, by any integral part or fastener of the furnace. The furnace was not designed to support itself in this manner.
In as much as practical, the furnace should be positioned near a chimney or vent and should be centralized with respect to the air distribution system.
For a utility room installation, the entrance door must be wide enough to permit the largest part of the furnace to pass through the doorway or allow sufficient clearance to permit the replacement of another appliance, e.g. a water heater, in the room.
If the furnace is installed in a residential garage, it must be installed so the burner is located higher than 18 inches above the floor, unless the required combustion air is taken from the exterior of the garage. Also, the furnace must be located or protected to avoid physical damage from impacts by vehicles.
Highboy and lowboy furnace models must rest on sturdy, stable, and level surfaces. The horizontal / counterflow model may be mounted on a level surface, as described
above, or it may be suspended from an overhead structure or surface. If this model is suspended from hanger rods, support the furnace from the bottom casing surface at three (3) places, across both ends of the casing and across the casing, near the middle of the furnace. Generally, a simple support frame for the furnace can be fabricated from structural steel angle, threaded steel rod, and fastener hardware, refer to Figure 1. Adjust the height of the support angles to level the unit in position.
INSTALLATION GUIDELINES
5
Figure 1: Recommended Support Frame for Horizontal / Counterflow Furnaces
Closet and Alcove Installation
All furnace models may be installed in a closet or alcove on combustible flooring with specified (standard) clearances to combustible construction. The horizontal /
counterflow furnace model requires an optional combustible surface-mounting base (model # CSFB-HC68) for vertical installation (i.e., counterflow configuration) directly on combustible materials, refer to Figure 2.
Figure 2: Counterflow Furnace Combustible Surface-Mounting Base
Standard Clearances
Standard clearances are mandatory minimum clearances from heated surfaces of the furnace to combustible materials to assure protection from fire hazard during furnace operation. (Refer to the Standard for the Installation of Oil-Burning Equipment, NFPA 31-2001, for definitions of combustible and non-combustible materials.)
6
Accessibility clearances, which are typically greater, may exceed fire protection clearances. Therefore, consider providing at least 24 inches of clearance from the front (and the rear, for lowboy furnaces) of the furnace to obstructions and surfaces for adequate service and maintenance access.
The minimum clearances from furnace casing surfaces to combustible materials are:
3 inches from casing sides and rear
8 inches from front casing of furnace to the closet door, with exception of:
o the lowboy rear flue model only requires 3 inches from front casing of the
furnace to the closet door
o the horizontal / counterflow furnace requires 22 inches from front casing of
the furnace to the closet door
9 inches from flue pipe/vent connector
3 inches from casing top
3 inches from any side of supply air plenum
3 inches above supply air ducts, within 6 feet of furnace
For the horizontal / counterflow furnace only, when the optional combustible
surface-mounting base is used with the furnace in the counterflow configuration, adequate clearances from the supply end surface of the furnace casing to combustible surfaces are provided by the design of the mounting base.
Though these are approved clearances for these furnaces, space must be provided at the front (18 inches minimum, 24 inches recommended) and at the rear of the furnace for access, service, and replacement of the oil burner, air filter(s), circulating air blower, and fan motor.
Air for Combustion and Ventilation
c CAUTION: Relief openings in the front or top of the furnace casing should not be obstructed or blocked. These openings supply combustion and ventilation air to the furnace.
Chloride, fluoride, iodide, and bromide bearing compounds when present, even in low concentrations, in air supplied for combustion to the furnace, can result in accelerated and severe corrosion of the heat exchanger and/or the venting system. This condition can occur with less efficient furnaces, but is more likely to happen on furnaces with efficiencies of 80% or greater.
7
Often, household chemicals contain chloride-bearing compounds. There are many compounds representative of this classification of chemicals. A few common examples are listed below.
Cleaning solvents
Varnish and paint removers
Bleaches
Fabric softeners
Water softener salt
Tile adhesives
Avoid storing or using these chemicals within close proximity to the furnace. In addition, avoid storing or using any chemicals, of an unknown and possibly flammable nature, in close proximity to the furnace. If it is necessary to store or use chemicals in the same space as the furnace, the area should be well-ventilated and all containers should be sealed when not in use. If possible, keep chemicals in a separate, well ventilated, room closed off from the furnace with a door.
The furnace shall be installed in a location within the building that permits a satisfactory supply of air for combustion, ventilation, and proper operation of the venting system. While all forms of building construction cannot be covered in detail in this manual, this requirement may usually be met by application of one of the following methods in ordinary building construction. However, applicable local installation codes always take precedence and shall be followed.
The content of certain pertinent passages of NFPA 31-2001 on methods to obtain and ensure adequate airflow to the furnace has been excerpted and, in some cases, paraphrased below for reference purposes. Consult the Standard for the Installation of Oil-Burning Equipment, NFPA 31-2001, for special cases and further details.
1. Utility Room (example of a confined space)
a. In buildings of conventional construction with normal air infiltration, two (2)
permanent openings connecting to a well-ventilated crawl space, attic, or another large, well-ventilated internal area shall be provided. Each opening shall have a minimum free area of one (1) square inch per 1000 BTUH of total input rate (sum of the individual appliance input rates) of all appliances to be installed in the utility room. One opening should be located near, or in, the ceiling of the room and the other should be located near, or in, the floor.
b. In buildings of unusually tight construction (e.g. those having continuous
water vapor barriers; tightly-fitting, or weather-stripped, doors and windows; and gasketed, caulked, or sealed outer wall joints and penetrations), wherein infiltration and air exchange with the outdoors is very limited (0.35 air changes per hour, or less), provision must be made to provide sufficient air for combustion. The following method will usually be adequate to ensure sufficient airflow into the space.
8
Provide two (2) permanent openings, one (1) located within 12 inches of the floor and one (1) within 12 inches of the ceiling, or roof, of the room. These openings shall allow for direct exchange of air between the room and outdoors. If required, ducting between the room and the outdoors shall be provided.
For horizontally -oriented ducts, each opening shall have a minimum free area of one (1) square inch per 2000 BTUH of the total input rate (sum of the individual appliance input rates) of all appliances to be installed in the room.
For vertically -oriented ducts, the minimum free area may be reduced to one (1) square inch per 4000 BTUH of the total input rate (sum of the individual appliance input rates) of all appliances to be installed in the room.
The minimum dimension of any air opening shall not be less than 3­inches.
When an opening in the outside wall must be provided, it should be furnished with properly screened metal sleeves.
2. Full Basement (example of an unconfined space) a. Where a furnace is installed in a full basement, in a building of conventional
construction with normal air infiltration, infiltration is normally adequate to provide air for combustion and ventilation.
b. In buildings of unusually tight construction (such as those where weather
stripping and storm sash windows are used, and where basement windows are also weather-stripped), one (1) permanent opening connecting to a well­ventilated attic, or with the outdoors shall be provided, using a duct, if necessary. This opening shall have a minimum free area of one (1) square inch per 5000 BTUH of total input rate (sum of the individual appliance input rates) of all appliances to be installed in the basement.
When an opening in the outside wall must be provided, it should be furnished with properly screened metal sleeves.
If an exhaust fan, additional air consuming machines (e.g. an air compressor), or a return air grill is present in the furnace room, there should be increased concern about providing adequate airflow to the furnace. Additional efforts may be required to assure an adequate supply of combustion and ventilation air is available to the furnace under all conditions.
9
Chimney Inspection
The chimney, vent, or any passageway for the stack gases to flow to the outdoor atmosphere is a very important part of the heating system. No furnace, regardless of the efficiency of the design, can perform satisfactorily when the chimney to which it is connected is inadequate or in poor condition. Any of the following symptoms may indicate a chimney has severe structural damage and is unsuitable for use.
Chimney appears to be leaning to the side.
Chimney appears to have structural damage, i.e. loose or missing blocks or
bricks, or excessive deterioration at mortar joints.
Tile liner damaged or missing.
Flue gas leakage along the length of the chimney between the chimney
connector and discharge termination.
Excessive corrosion at the cleanout port or at the chimney connector entrance into the chimney.
Structural debris, i.e. mortar or tile liner flakes, in base of the flue way.
A qualified person shall inspect the chimney to confirm it is correctly sized for the application, properly constructed, and in sound condition. Refer to the Standard for the Installation of Oil-Burning Equipment, NFPA 31-2001, for details on proper chimney sizing and construction. If needed, the chimney should be cleaned before installing the furnace. Any accumulation of dirt or debris at the bottom of the flue should be removed.
Flue / Chimney / Vent Connector
c CAUTION:
DO NOT install a manual damper in the chimney or vent connector.
Motorized and thermally- activated type vent dampers are NOT
recommended for use on these furnaces.
It is desirable to install the shortest vent connector (also referred to as a flue or chimney connector) possible with the fewest number of fittings, i.e. transitions and elbows. Generally, 6-inch diameter, 24 Ga. or heavier, single wall, lock seam-type, galvanized steel vent pipe and fittings are satisfactory materials for the fabrication of a vent connector. However, always consult local codes and authorities for specific minimum requirements.
For some installations, it may be prudent to turn the furnace flue elbow 90 degrees clockwise, with respect to the front of the furnace, such that the elbow is open to the right-hand side of the unit, rather than upward. Turning the flue elbow may better facilitate connection of the vent connector piping to the flue elbow on the highboy and front flue, lowboy furnaces. Due to the presence of the fan and limit control and the wiring harness, the elbow may not be rotated 90 degrees counterclockwise. The installer must carefully mark and cut a hole in the furnace housing to allow the vent connector to pass through the housing.
10
If desired, with the furnace flue elbow turned to the right, the standard furnace top front panel (p/n 52-17346-1) may be replaced with the top front panel from the rear flue lowboy model (p/n 52-17383-1). Refer to Appendix D: Replacement Parts for sketches of these parts. Contact your Crown distributor to purchase this part.
All horizontal sections of the vent connector must slope upward not less than ¼ inch per foot from the furnace to the vent termination. Long horizontal sections of the venting system must be supported at least every five (5) feet with metal straps to prevent sagging of the vent piping. Secure all joints in the vent connector with sheet metal screws or equivalent fasteners. Vent piping must not be inserted beyond the inside wall of the chimney flue.
Power (Side-Wall) Venting – Important Note Regarding
c CAUTION: Crown Boiler Company will NOT assume responsibility for damage to, and deterioration of, exterior building materials, e.g. brick, siding, clapboards, and etc., in close proximity to the vent terminal due to operation of a power vented, oil furnace. This policy is applicable regardless of the cause of sooting.
Two (2) problems typically arise when power venting any oil-fired appliance.
1) Soot buildup may occur at an accelerated rate on critical components of the furnace oil burner, e.g. the primary control flame sensor (“cad cell”), the burner head, and oil nozzle.
2) Severe damage may occur to external surfaces of the structure in the event the furnace continually produces a high level of smoke in the flue gases. Excess smoke and soot can be produced for many reasons, some of which cannot be successfully controlled by the installer and the appliance manufacturer.
NOTICE: Crown Boiler recommends the use of a chimney to vent residential oil furnaces. If a power venter must be used, it is the responsibility of the installer and power venter manufacturer to design, assemble, and demonstrate proper operation of the power venting system with the furnace.
Draft Regulator
A barometric-type, draft regulator is supplied with the furnace. Installation or operating conditions that produce excess amounts of draft can reduce the heating efficiency of the furnace. The purpose of the regulator is to adjust and control the flow of flue gases from the furnace by stabilizing the amount of chimney draft to which the furnace is subjected.
Generally, install the barometric draft regulator in the vent connector as close as possible to the flue outlet collar of the furnace. However, always refer to the draft regulator manufacturer’s installation instructions for application specific recommendations.
11
Duct Work and Air Conditioning
Design and installation of the duct system should follow the current guidelines of the Air Conditioning Contractors of America (ACCA) or the American Society of Heating, Refrigeration and Air Conditioning Engineers, Inc. (ASHRAE). Refer to the Residential Duct Systems, Manual D, from the ACCA, and the ASHRAE Handbook Fundamentals volume, from ASHRAE, for recommended practices in duct system design and installation. To obtain copies of these publications for a fee, contact the ACCA and the ASHRAE at the addresses given in Appendix A of this manual.
All furnaces are tested over a range of external static pressure that simulates the airflow resistance of the ductwork, fittings, and diffusers connected to the furnace for a typical (average) duct system. The furnace blower and blower motor have been selected to work successfully against the following range of duct system resistance.
Recommended range of duct system resistance for all models: 0.2 to 0.5 in. W.G. external static pressure.
Due to the need to maintain an adequate supply of combustion and ventilation air, the furnace shall not be installed in small room without return air duct system. A duct the full size of the furnace return air opening shall extend to a location outside the furnace room.
If the furnace is used in connection with summer air conditioning (cooling), the furnace should be installed in parallel with, or on the upstream side of, the evaporator coil to avoid water vapor condensation in the furnace heat exchanger. If the cooling unit is installed in a parallel flow arrangement, dampers (or other means used to control airflow) should be provided to prevent chilled air from entering the furnace. If such a damper is manually operated, it must be equipped with a means to prevent operation of either unit, unless the damper is placed in either the full heat or full cool position.
NOTICE: Return air grilles and supply registers in the air distribution system should never be obstructed.
Air Filter Mounting
c CAUTION: If cutting openings in the furnace casing is required, DO NOT cut any supporting clips or angles. Cut as close to the scribed line as possible, but DO NOT cut the base clip or blower pan support angle.
Lowboy furnaces are factory-equipped with permanent-type, air filters located above the blower compartment, in the rear of the furnaces.
NOTICE: Horizontal / counterflow furnaces are not factory-equipped with an air filter or filter rack. Furthermore, the furnace blower compartment does not contain
enough free space to permit an air filter to be mounted within the furnace casing. However, the installer should supply, or fabricate, a filter rack and mount an air filter in the return air plenum above, or upstream of, the furnace blower compartment.
12
On the highboy furnace, it is necessary to cut the return air opening in the lower side, or rear, of the casing depending upon the needs of the specific installation, refer to Figure
3.
Figure 3: Cutaway view of fan section of a typical highboy furnace.
The side casings have each been pre-punched with four (4), square, knockout openings for use in locating the proper position for the return air filter rack. On the side of the furnace, where the return air duct will attach, scribe a line connecting the outside edges of the knockout openings to form a rectangle. Using a punch, or a large screwdriver, and a hammer, remove the knockouts and cut the return air opening in the casing. Sheet metal shears, or a power metal cutting tool, will be required to cut the casing.
Position the open end of the filter rack to the front of the furnace to permit access for filter replacement. Align the filter rack with the rectangular hole and mark the locations on the casing of the pre-punched mounting holes in the filter rack flange. Drill pilot holes in the casing and permanently attach the filter rack to the furnace with screws, or pop­rivets (these fasteners are not included). Connect the return air plenum to the filter rack and slide the air filter into position.
13
Electrical Connections
NOTICE: All field wiring must conform to local, state, and national installation codes.
A disconnecting switch equipped with overcurrent protection rated at 15 A. (e.g. a time delay-type fuse or inverse time, circuit breaker) should be installed in the service line for shutting down and protecting the furnace and electrical system.
Since the furnace is entirely pre-wired at the factory, it is only necessary to connect the building electrical service lines to the two (2) pigtail wires extending from the fan center junction box. The fan center is mounted inside the furnace burner compartment or mounted on the front exterior of the furnace, in the case of the horizontal / counterflow model. The service lines to the furnace should be no smaller than 14 Ga., insulated copper wire with a temperature rating of 60ºC, or greater.
Connect an equipment ground wire to the furnace at the fan center junction box. If wiring is run through metal electrical conduit, it may not be necessary to run a separate equipment ground wire. Consult local codes and authorities for specific minimum requirements.
A two (2) wire connection to the room thermostat from the oil primary control is also necessary. This is typically a low voltage (24 VAC) circuit. Consult the National Electrical Code, ANSI/NFPA 70-2002, for guidelines for proper wiring methods and materials for this circuit.
Refer to the electrical diagrams contained in Appendix B of this manual for an electrical schematic, a connection diagram, and operating instructions.
Room Thermostat
A room thermostat is not furnished with this furnace. However, a thermostat is required to properly operate the furnace control system in a typical residential heating application.
14
Loading...
+ 35 hidden pages