P/N: MO-426 (Printed Instruction Manual)
Note: This page is not to be included as part of printed hard copy.
Overall Specifications:
Material: white plain paper
Printed text: black
Binder: staple upper left corner
Individual page specifications:
Cover page: printed single-side up
The balance of instruction manual pages to be printed utilizing both front and back side of paper.
OIL-FIRED CENTRAL FURNACE
Installation, Operation, And Service Manual
With Users Information Section
Models:
CHB68-112 CHC68-96 CLBF68-112
CLBR68-112
• Do NOT store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance.
• Improper installation, adjustment, alteration, service, or maintenance can
cause a fire or explosion resulting in property damage, personal injury, or
loss of life. For assistance or additional information consult a qualified
installer or service agency.
These instructions should be:
• read prior to installing the furnace.
• retained for reference by qualified service personnel.
• reviewed before performing any service or maintenance.
c WARNING:
Crown Boiler Company
3633 “I” Street
Philadelphia, Pennsylvania 19134
Made in USA
MO-426
ECN 5079-MA
Contents
SECTIONPAGE
Notice to the Installer .................................................................................................. 4
APPENDIX D: REPLACEMENT PARTS ....................................................................... 46
3
Notice to the Installer
Installation of this oil-fired furnace must be performed by a qualified installer in accordance
with all local codes and authorities having jurisdiction. In the absence of local governing codes,
installation shall conform to these instructions and to the regulations of the National Fire
Protection Association’s
2001, and the National Electrical Code, ANSI/NFPA 70-2002, or the latest editions thereof.
A qualified installer, also referred to in this instruction manual as a “qualified heating
contractor”, is an individual, or agency, properly licensed and experienced to install and
service oil-burning equipment in accordance with all local codes and ordinances.
Material and Workmanship
This furnace was built with the highest quality materials and attention to workmanship.
However, omissions and defects occasionally occur. Before installing the furnace,
inspect the furnace thoroughly. If missing parts, defective material, or poor workmanship
are evident, report the model and serial numbers imprinted on the furnace rating label
to the seller for adjustment.
Packaging
A complete furnace is contained within two (2) packages. The factory completed all
feasible assembly. However certain components including oil burner and draft regulator
and, if supplied, door handle, air filter(s), and air filter rack(s), must be assembled to the
furnace, or the venting system, in the field. Refer to the assembly instructions.
Shipping Damage
If this furnace was damaged during transit, please immediately request the
transportation company inspect the furnace and issue a concealed damage report.
The party receiving the furnace should file the claim for shipping damage. Report any shipping damage immediately.
It is absolutely essential that a damage report be obtained. If a concealed damage
report is not obtained, we cannot provide assistance in recovering your claim against
the transportation company.
Warranties
c WARNING: The manufacturer of this equipment assumes no liability for any
damages resulting from unauthorized modifications made to the furnace, or any
components thereof, or improper installation of the furnace in the field.
Furthermore, any such field modifications VOID THE WARRANTY and place
responsibility for safe and reliable operation of the furnace on those who
performed the modification(s).
Complete and return any enclosed warranty cards. These must be on file to verify
installation dates for replacement of any warrantied part(s).
Standard for the Installation of Oil-Burning Equipment, NFPA 31-
4
Codes
All local codes and regulations take precedence over the instructions in this manual and
shall be followed accordingly. In the absence of local codes, this installation must
conform to these instructions and to the regulations of the National Fire Protection
Association (NFPA) publications, the Standard for the Installation of Oil-Burning
Equipment, NFPA 31-2001, and the National Electrical Code, ANSI/NFPA 70-2002, or
the latest editions thereof. To obtain copies of these publications for a fee, contact the
NFPA at the address given in Appendix A of this manual.
Installation Location
c WARNING:
• These furnaces are designed for indoor installation ONLY.
• These furnaces are NOT to be used as construction heaters.
• DO NOT hang the horizontal / counterflow furnace from a structure, or
surface, by any integral part or fastener of the furnace. The furnace was
not designed to support itself in this manner.
In as much as practical, the furnace should be positioned near a chimney or vent and
should be centralized with respect to the air distribution system.
For a utility room installation, the entrance door must be wide enough to permit the
largest part of the furnace to pass through the doorway or allow sufficient clearance to
permit the replacement of another appliance, e.g. a water heater, in the room.
If the furnace is installed in a residential garage, it must be installed so the burner is
located higher than 18 inches above the floor, unless the required combustion air is
taken from the exterior of the garage. Also, the furnace must be located or protected to
avoid physical damage from impacts by vehicles.
Highboy and lowboy furnace models must rest on sturdy, stable, and level surfaces.
The horizontal / counterflow model may be mounted on a level surface, as described
above, or it may be suspended from an overhead structure or surface. If this model is
suspended from hanger rods, support the furnace from the bottom casing surface at three (3) places, across both ends of the casing and across the casing, near the
middle of the furnace. Generally, a simple support frame for the furnace can be
fabricated from structural steel angle, threaded steel rod, and fastener hardware, refer
to Figure 1. Adjust the height of the support angles to level the unit in position.
INSTALLATION GUIDELINES
5
Figure 1: Recommended Support Frame for Horizontal / Counterflow Furnaces
Closet and Alcove Installation
All furnace models may be installed in a closet or alcove on combustible flooring with
specified (standard) clearances to combustible construction. The horizontal /
counterflow furnace model requires an optional combustible surface-mounting
base (model # CSFB-HC68) for vertical installation (i.e., counterflow
configuration) directly on combustible materials, refer to Figure 2.
Figure 2: Counterflow Furnace Combustible Surface-Mounting Base
Standard Clearances
Standard clearances are mandatory minimum clearances from heated surfaces of the
furnace to combustible materials to assure protection from fire hazard during furnace
operation. (Refer to the Standard for the Installation of Oil-Burning Equipment, NFPA
31-2001, for definitions of combustible and non-combustible materials.)
6
Accessibility clearances, which are typically greater, may exceed fire protection
clearances. Therefore, consider providing at least 24 inches of clearance from the front
(and the rear, for lowboy furnaces) of the furnace to obstructions and surfaces for
adequate service and maintenance access.
The minimum clearances from furnace casing surfaces to combustible materials are:
• 3 inches from casing sides and rear
• 8 inches from front casing of furnace to the closet door, with exception of:
o the lowboy rear flue model only requires 3 inches from front casing of the
furnace to the closet door
o the horizontal / counterflow furnace requires 22 inches from front casing of
the furnace to the closet door
• 9 inches from flue pipe/vent connector
• 3 inches from casing top
• 3 inches from any side of supply air plenum
• 3 inches above supply air ducts, within 6 feet of furnace
• For the horizontal / counterflow furnace only, when the optional combustible
surface-mounting base is used with the furnace in the counterflow configuration,
adequate clearances from the supply end surface of the furnace casing to
combustible surfaces are provided by the design of the mounting base.
Though these are approved clearances for these furnaces, space must be provided at
the front (18 inches minimum, 24 inches recommended) and at the rear of the furnace
for access, service, and replacement of the oil burner, air filter(s), circulating air blower,
and fan motor.
Air for Combustion and Ventilation
c CAUTION: Relief openings in the front or top of the furnace casing should not
be obstructed or blocked. These openings supply combustion and ventilation air
to the furnace.
Chloride, fluoride, iodide, and bromide bearing compounds when present, even in low
concentrations, in air supplied for combustion to the furnace, can result in accelerated
and severe corrosion of the heat exchanger and/or the venting system. This condition
can occur with less efficient furnaces, but is more likely to happen on furnaces with
efficiencies of 80% or greater.
7
Often, household chemicals contain chloride-bearing compounds. There are many
compounds representative of this classification of chemicals. A few common examples
are listed below.
• Cleaning solvents
• Varnish and paint removers
• Bleaches
• Fabric softeners
• Water softener salt
• Tile adhesives
Avoid storing or using these chemicals within close proximity to the furnace. In addition,
avoid storing or using any chemicals, of an unknown and possibly flammable nature, in
close proximity to the furnace. If it is necessary to store or use chemicals in the same
space as the furnace, the area should be well-ventilated and all containers should be
sealed when not in use. If possible, keep chemicals in a separate, well ventilated, room
closed off from the furnace with a door.
The furnace shall be installed in a location within the building that permits a satisfactory
supply of air for combustion, ventilation, and proper operation of the venting system.
While all forms of building construction cannot be covered in detail in this manual, this
requirement may usually be met by application of one of the following methods in
ordinary building construction. However, applicable local installation codes always take
precedence and shall be followed.
The content of certain pertinent passages of NFPA 31-2001 on methods to obtain and
ensure adequate airflow to the furnace has been excerpted and, in some cases,
paraphrased below for reference purposes. Consult the Standard for the Installation of
Oil-Burning Equipment, NFPA 31-2001, for special cases and further details.
1. Utility Room (example of a confined space)
a. In buildings of conventional construction with normal air infiltration, two (2)
permanent openings connecting to a well-ventilated crawl space, attic, or
another large, well-ventilated internal area shall be provided. Each opening
shall have a minimum free area of one (1) square inch per 1000 BTUH of total
input rate (sum of the individual appliance input rates) of all appliances to be
installed in the utility room. One opening should be located near, or in, the
ceiling of the room and the other should be located near, or in, the floor.
b. In buildings of unusually tight construction (e.g. those having continuous
water vapor barriers; tightly-fitting, or weather-stripped, doors and windows;
and gasketed, caulked, or sealed outer wall joints and penetrations), wherein
infiltration and air exchange with the outdoors is very limited (0.35 air changes
per hour, or less), provision must be made to provide sufficient air for
combustion. The following method will usually be adequate to ensure
sufficient airflow into the space.
8
Provide two (2) permanent openings, one (1) located within 12 inches of the
floor and one (1) within 12 inches of the ceiling, or roof, of the room. These
openings shall allow for direct exchange of air between the room and
outdoors. If required, ducting between the room and the outdoors shall be
provided.
• For horizontally -oriented ducts, each opening shall have a minimum free
area of one (1) square inch per 2000 BTUH of the total input rate (sum of
the individual appliance input rates) of all appliances to be installed in the
room.
• For vertically -oriented ducts, the minimum free area may be reduced to
one (1) square inch per 4000 BTUH of the total input rate (sum of the
individual appliance input rates) of all appliances to be installed in the
room.
• The minimum dimension of any air opening shall not be less than 3inches.
• When an opening in the outside wall must be provided, it should be
furnished with properly screened metal sleeves.
2. Full Basement (example of an unconfined space)
a. Where a furnace is installed in a full basement, in a building of conventional
construction with normal air infiltration, infiltration is normally adequate to
provide air for combustion and ventilation.
b. In buildings of unusually tight construction (such as those where weather
stripping and storm sash windows are used, and where basement windows
are also weather-stripped), one (1) permanent opening connecting to a wellventilated attic, or with the outdoors shall be provided, using a duct, if
necessary. This opening shall have a minimum free area of one (1) square
inch per 5000 BTUH of total input rate (sum of the individual appliance input
rates) of all appliances to be installed in the basement.
When an opening in the outside wall must be provided, it should be furnished
with properly screened metal sleeves.
If an exhaust fan, additional air consuming machines (e.g. an air compressor), or a
return air grill is present in the furnace room, there should be increased concern about
providing adequate airflow to the furnace. Additional efforts may be required to assure
an adequate supply of combustion and ventilation air is available to the furnace under
all conditions.
9
Chimney Inspection
The chimney, vent, or any passageway for the stack gases to flow to the outdoor
atmosphere is a very important part of the heating system. No furnace, regardless of the
efficiency of the design, can perform satisfactorily when the chimney to which it is
connected is inadequate or in poor condition. Any of the following symptoms may
indicate a chimney has severe structural damage and is unsuitable for use.
• Chimney appears to be leaning to the side.
• Chimney appears to have structural damage, i.e. loose or missing blocks or
bricks, or excessive deterioration at mortar joints.
• Tile liner damaged or missing.
• Flue gas leakage along the length of the chimney between the chimney
connector and discharge termination.
• Excessive corrosion at the cleanout port or at the chimney connector entrance
into the chimney.
• Structural debris, i.e. mortar or tile liner flakes, in base of the flue way.
A qualified person shall inspect the chimney to confirm it is correctly sized for the
application, properly constructed, and in sound condition. Refer to the Standard for the
Installation of Oil-Burning Equipment, NFPA 31-2001, for details on proper chimney
sizing and construction. If needed, the chimney should be cleaned before installing the
furnace. Any accumulation of dirt or debris at the bottom of the flue should be removed.
Flue / Chimney / Vent Connector
c CAUTION:
• DO NOT install a manual damper in the chimney or vent connector.
• Motorized and thermally- activated type vent dampers are NOT
recommended for use on these furnaces.
It is desirable to install the shortest vent connector (also referred to as a flue or chimney
connector) possible with the fewest number of fittings, i.e. transitions and elbows.
Generally, 6-inch diameter, 24 Ga. or heavier, single wall, lock seam-type, galvanized
steel vent pipe and fittings are satisfactory materials for the fabrication of a vent
connector. However, always consult local codes and authorities for specific minimum
requirements.
For some installations, it may be prudent to turn the furnace flue elbow 90 degrees
clockwise, with respect to the front of the furnace, such that the elbow is open to the
right-hand side of the unit, rather than upward. Turning the flue elbow may better
facilitate connection of the vent connector piping to the flue elbow on the highboy and
front flue, lowboy furnaces. Due to the presence of the fan and limit control and the
wiring harness, the elbow may not be rotated 90 degrees counterclockwise. The
installer must carefully mark and cut a hole in the furnace housing to allow the vent
connector to pass through the housing.
10
If desired, with the furnace flue elbow turned to the right, the standard furnace top front
panel (p/n 52-17346-1) may be replaced with the top front panel from the rear flue
lowboy model (p/n 52-17383-1). Refer to Appendix D: Replacement Parts for sketches
of these parts. Contact your Crown distributor to purchase this part.
All horizontal sections of the vent connector must slope upward not less than ¼ inch per
foot from the furnace to the vent termination. Long horizontal sections of the venting
system must be supported at least every five (5) feet with metal straps to prevent
sagging of the vent piping. Secure all joints in the vent connector with sheet metal
screws or equivalent fasteners. Vent piping must not be inserted beyond the inside wall
of the chimney flue.
Power (Side-Wall) Venting – Important Note Regarding
c CAUTION: Crown Boiler Company will NOT assume responsibility for damage
to, and deterioration of, exterior building materials, e.g. brick, siding, clapboards,
and etc., in close proximity to the vent terminal due to operation of a power
vented, oil furnace. This policy is applicable regardless of the cause of sooting.
Two (2) problems typically arise when power venting any oil-fired appliance.
1) Soot buildup may occur at an accelerated rate on critical components of the
furnace oil burner, e.g. the primary control flame sensor (“cad cell”), the burner
head, and oil nozzle.
2) Severe damage may occur to external surfaces of the structure in the event the
furnace continually produces a high level of smoke in the flue gases. Excess
smoke and soot can be produced for many reasons, some of which cannot be
successfully controlled by the installer and the appliance manufacturer.
NOTICE: Crown Boiler recommends the use of a chimney to vent residential oil
furnaces. If a power venter must be used, it is the responsibility of the installer
and power venter manufacturer to design, assemble, and demonstrate proper
operation of the power venting system with the furnace.
Draft Regulator
A barometric-type, draft regulator is supplied with the furnace. Installation or operating
conditions that produce excess amounts of draft can reduce the heating efficiency of the
furnace. The purpose of the regulator is to adjust and control the flow of flue gases from
the furnace by stabilizing the amount of chimney draft to which the furnace is subjected.
Generally, install the barometric draft regulator in the vent connector as close as
possible to the flue outlet collar of the furnace. However, always refer to the draft
regulator manufacturer’s installation instructions for application specific
recommendations.
11
Duct Work and Air Conditioning
Design and installation of the duct system should follow the current guidelines of the Air
Conditioning Contractors of America (ACCA) or the American Society of Heating,
Refrigeration and Air Conditioning Engineers, Inc. (ASHRAE). Refer to the Residential
Duct Systems, Manual D, from the ACCA, and the ASHRAE Handbook Fundamentals
volume, from ASHRAE, for recommended practices in duct system design and
installation. To obtain copies of these publications for a fee, contact the ACCA and the
ASHRAE at the addresses given in Appendix A of this manual.
All furnaces are tested over a range of external static pressure that simulates the airflow
resistance of the ductwork, fittings, and diffusers connected to the furnace for a typical
(average) duct system. The furnace blower and blower motor have been selected to
work successfully against the following range of duct system resistance.
Recommended range of duct system resistance for all models: 0.2 to 0.5 in. W.G.
external static pressure.
Due to the need to maintain an adequate supply of combustion and ventilation air, the
furnace shall not be installed in small room without return air duct system. A duct the full
size of the furnace return air opening shall extend to a location outside the furnace
room.
If the furnace is used in connection with summer air conditioning (cooling), the furnace
should be installed in parallel with, or on the upstream side of, the evaporator coil to
avoid water vapor condensation in the furnace heat exchanger. If the cooling unit is
installed in a parallel flow arrangement, dampers (or other means used to control
airflow) should be provided to prevent chilled air from entering the furnace. If such a
damper is manually operated, it must be equipped with a means to prevent operation of
either unit, unless the damper is placed in either the full heat or full cool position.
NOTICE: Return air grilles and supply registers in the air distribution system
should never be obstructed.
Air Filter Mounting
c CAUTION: If cutting openings in the furnace casing is required, DO NOT cut
any supporting clips or angles. Cut as close to the scribed line as possible, but
DO NOT cut the base clip or blower pan support angle.
Lowboy furnaces are factory-equipped with permanent-type, air filters located above the
blower compartment, in the rear of the furnaces.
NOTICE: Horizontal / counterflow furnaces are not factory-equipped with an air
filter or filter rack. Furthermore, the furnace blower compartment does not contain
enough free space to permit an air filter to be mounted within the furnace casing.
However, the installer should supply, or fabricate, a filter rack and mount an air filter in
the return air plenum above, or upstream of, the furnace blower compartment.
12
On the highboy furnace, it is necessary to cut the return air opening in the lower side, or
rear, of the casing depending upon the needs of the specific installation, refer to Figure
3.
Figure 3: Cutaway view of fan section of a typical highboy furnace.
The side casings have each been pre-punched with four (4), square, knockout openings
for use in locating the proper position for the return air filter rack. On the side of the
furnace, where the return air duct will attach, scribe a line connecting the outside edges
of the knockout openings to form a rectangle. Using a punch, or a large screwdriver,
and a hammer, remove the knockouts and cut the return air opening in the casing.
Sheet metal shears, or a power metal cutting tool, will be required to cut the casing.
Position the open end of the filter rack to the front of the furnace to permit access for
filter replacement. Align the filter rack with the rectangular hole and mark the locations
on the casing of the pre-punched mounting holes in the filter rack flange. Drill pilot holes
in the casing and permanently attach the filter rack to the furnace with screws, or poprivets (these fasteners are not included). Connect the return air plenum to the filter rack
and slide the air filter into position.
13
Electrical Connections
NOTICE: All field wiring must conform to local, state, and national installation
codes.
A disconnecting switch equipped with overcurrent protection rated at 15 A. (e.g. a time
delay-type fuse or inverse time, circuit breaker) should be installed in the service line for
shutting down and protecting the furnace and electrical system.
Since the furnace is entirely pre-wired at the factory, it is only necessary to connect the
building electrical service lines to the two (2) pigtail wires extending from the fan center
junction box. The fan center is mounted inside the furnace burner compartment or
mounted on the front exterior of the furnace, in the case of the horizontal / counterflow
model. The service lines to the furnace should be no smaller than 14 Ga., insulated
copper wire with a temperature rating of 60ºC, or greater.
Connect an equipment ground wire to the furnace at the fan center junction box. If
wiring is run through metal electrical conduit, it may not be necessary to run a separate
equipment ground wire. Consult local codes and authorities for specific minimum
requirements.
A two (2) wire connection to the room thermostat from the oil primary control is also
necessary. This is typically a low voltage (24 VAC) circuit. Consult the National
Electrical Code, ANSI/NFPA 70-2002, for guidelines for proper wiring methods and
materials for this circuit.
Refer to the electrical diagrams contained in Appendix B of this manual for an electrical
schematic, a connection diagram, and operating instructions.
Room Thermostat
A room thermostat is not furnished with this furnace. However, a thermostat is required
to properly operate the furnace control system in a typical residential heating
application.
14
Loading...
+ 35 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.