Crown Boiler 32-380ECS, 32-475ECS User Manual

D e s i g n e D t o L e a D
Series 32ECS
Gas-Fired Natural Draft Steam or Water Boilers
32-380ECS 32-475ECS
EQUIPPED WITH 24 VOLT CONTROL SYSTEMS
WARNING: Improper installation,
adjustment, alteration, service or maintenance can cause property damage, injury, or loss of life. For assistance or additional information,
consult a qualied installer, service
agency or the gas supplier. Read these instructions carefully before installing.
Manufacturer of Hydronic Heating Products
P.O. Box 14818 3633 I. Street
Philadelphia, PA 19134
Tel: (215) 535-8900 • Fax: (215) 535-9736 • www.crownboiler.com
I Product Description
This supplement covers information not included in the standard Series 32 installation manual that is unique to the
following models:
32-380WNLECS, 32-475WNLECS 32-380WNTECS, 32-475WNTECS 32-380SNLECS, 32-475SNLECS
Follow the Series 32 installation instructions except where noted in this supplement.
II Specications
32-380ECS Dimensional Data (Refer to Figure 1 in Installation Manual):
Jacket Overall Length (“A”): 31 1/4” Vent Collar Dia. (“B”): 12” Vent Centerline (“N”): 15 5/8” Number of Flue Outlets: 1
32-380ECS Specications:
Number of Sections: 5 Input (MBH): 380 I=B=R Gross Output (MBH): 304 I=B=R Net Rating (MBH Water): 264 I=B=R Net Rating (MBH Steam): 228 I=B=R Net Rating (ft2 Steam): 950 Combustion Effy. (%): 80.5 Steam Water Volume to Normal Water Line (Gal): 24.51 Water Boiler Volume (Gal): 34.13 Output (BHP): 9.1
Arrangement of Steam Riser Connections, Draft Hoods, and Base Assemblies: The 32-380ECS has the same basic conguration as that shown for the 32-475 in gure 2A of the installation manual.
32-475ECS Specications - Refer to 32-475 specications in the installation manual.
III Before Installing
Refer to installation manual. Also note that a CSD-1 compliant gas train is not available for the 32-475ECS.
IV Locating the Boiler
Refer to installation manual. Minimum required room volume for 32-380ECS is 436 ft3 (Table 2).
V. Knockdown Boiler Assembly Instructions - Refer to installation manual
VI Air for Combustion and Ventilation - Refer to installation manual
1
VII Venting
Refer to installation manual. Vent sizing for the 32-380ECS should always be done in accordance with the National Fuel Gas Code. A vent damper can be installed on any 32-380ECS or 32-475ECS equipped with a 24 volt control system except for those with tankless heaters. If a vent damper is installed, the following components are required:
Efkal Model GVD-12 Vent Damper: Crown PN 96-038
Damper Harness (Steam Boilers): Crown PN 9601300
Damper Harness (Water Boilers): Crown PN 9601550
To install the damper:
1) Open vent damper carton and remove installation instructions. Read the instructions thoroughly before proceeding. Verify that vent damper is same size as draft diverter outlet (12”). Unpack vent damper carefully. Do not force closed damper blade. Forcing vent damper closed may result in damaged gear train.
2) Vent damper is factory shipped having approximately ¾” diameter hole in the vent damper blade, which must be left
open even though this boiler is equipped with an intermittent ignition system.
3) Mount the vent damper on the ue collar without modication to either and secure with sheet metal screws. Make sure screws do not interfere with damper blade operation. Vent damper blade position indicator must be visible to users. Maintain at least 6 inches between the vent damper device and combustible construction. Also make sure that there is adequate access to the vent damper for servicing. Figures D and F in the Wiring section show typical damper orientation.
4) Install vent connector pipe and vent ttings from vent damper outlet to chimney or gas vent. Secure with sheet metal screws and support as required.
WARNING
Install the vent damper directly on top of the boiler so that it is servicing only the boiler.
5) See the Wiring section of this supplement for instructions on making damper electrical connections.
VIII Steam Boiler Piping and Trim Installation
Refer to installation manual. The #67 low water cut-off (LWCO) cannot be used as the primary (operating) LWCO on the 380ECS or 475ECS. Instead, a Hydrolevel CG400 is installed in tapping “G” (Figure 22). A #67 LWCO can be used as a redundant LWCO (with or without manual reset) in tappings “E” along with the level glass. The CG400 supplied with this boiler uses the same angeless probe, and is mounted on the boiler in the same manner, as the CG450 described in the installation manual at the top of page 28. Install the 32-380ECS near boiler piping in accordance with that shown for the 32-475 in Figure 27a in the installation manual.
IX Water Boiler Piping
Refer to installation manual. Boilers covered by this supplement which are not equipped with a tankless heater are supplied with a Honeywell L8148E limit control installed in Tapping “C” (Figure 29) using the 1/2” well and 1/2 x 1-1/2” bushing supplied. Boilers equipped with a tankless heater are supplied with a Honeywell L8124E, which is installed using a 3/4” well in the tankless heater. The L4006A shown in the installation manual is not used.
X Gas Piping - Refer to installation manual
2
XI Control System Wiring
WARNING
All wiring and grounding must be done in accordance with the authority having jurisdiction or, in the absence of such
Wire the boiler in accordance with the following instructions rather than those in the installation manual. Provide the boiler with a dedicated branch circuit with a fused disconnect. The minimum rating of this circuit must be 15A. Wire the boiler using the appropriate wiring diagram shown in Figures A-C in this supplement. In addition, note the following:
1) Steam boiler wiring is shown in Figure A. The junction box, transformer, and thermostat relay are prewired with all low voltage wire harnesses, except the damper harness (if used).
a) Mount the junction box assembly to the side jacket panel as shown in Figure D using two #10 x 1/2” sheet metal
screws. b) Connect the gray limit harness to terminals R and B on the L404 pressure limit. c) Mount the blocked vent switch (BVS) to the draft hood as shown in Figure E using two #10 x 1/2” sheet metal
screws. Route the red BVS harness along the side of the boiler as shown in Figure D and connect the pair of fully
insulated quick connects to the BVS. d) Route the other end of the BVS harness to the ignition module . Connect the fully insulted quick connect to the
“24 Volt” terminal. Connect the uninsulated connector to the “24 V Ground” piggy back terminal. Secure the BVS
harness to the jacket with the nylon clips provided as shown in Figure D. e) If a damper is installed, remove the red jumper wire inside the junction box that is indicated by Note #2 in Figure A.
Connect the damper harness to the wiring in the junction box as shown in Figure A. Route the damper harness to the
damper as shown in Figure D, using care to make sure that it does not come in contact with the draft hood or steam
piping. f) If a redundant LWCO and/or pressure limit are used, wire them so that they interrupt 120VAC power to the boiler.
2) Water Boiler wiring is shown in Figure B for boilers without a tankless heater and in Figure C for boilers with a tankless heater. The blocked vent switch (BVS) wire harness is factory wired to B1 and B2 on the “aquastat” (L8148E or L8124E).
a) Mount the aquastat to the control well. b) Mount the blocked vent switch (BVS) to the draft hood as shown in Figure E using two #10 x 1/2” sheet metal
screws. Route the red BVS harness along the side of the boiler as shown in Figure F and connect the pair of fully insulated quick connects to the BVS.
c) Route the other end of the BVS harness to the ignition module . Connect the fully insulated quick connect to the
“24 Volt” terminal. Connect the uninsulated connector to the “24 V Ground” piggy back terminal. Secure the BVS harness to the jacket with the nylon clips provided as shown in Figure F.
d) A vent damper cannot be used on boilers equipped with tankless heater. If a damper is installed on a boiler without
the tankless heater, remove the jumper plug inside the L8148E aquastat. Plug the 6-pole end of the damper harness into the aquastat. Plug the 4-pole end of the harness into the damper. Route the damper harness to the damper as shown in Figure F, using care to make sure that it does not come in contact with the draft hood.
e) If a LWCO and/or redundant temperature limit are used, wire them so that they interrupt 120VAC power to the
boiler.
3) Provide a Class II circuit between the boiler and the thermostat. Make thermostat connections to the boiler in accordance with Figure A-C.
4) Make 120VAC connections to the boiler in accordance with Figure A-C.
CAUTION
Make sure that damper and BVS harnesses are secured so that they do not come in contact with draft hood or steam piping.
3