Flamgard-Plus Operation
15
4.4 Changing Alarm Levels (Relay Version Only)
WARNING
This work should be carried out by Crowcon or an approved
service centre unless suitable training has been received. Before
attempting to change alarm levels ensure the detector is in fresh
air and no flammable gas is present.
As standard the AL1 and AL2 alarm levels are factory set at 20% LEL
and 40% LEL respectively. To change either alarm level:
a Switch off and isolate power to the detector requiring attention.
b Open the junction box of the detector by loosening the tamper proof
grub screw and removing the lid by rotating it anti-clockwise.
c Remove the amplifier from the terminal board.
d Ensure that the ‘INHIBIT’ link is set to ‘N’.
e Re-fit the amplifier to the terminal board ensuring that all screws
have been secured correctly.
f Apply power to the detector and allow the detector to stabilise.
g Place the end of “CRO-Mag’ over the “MENU’ pad. The decimal
point above the word ‘ZERO’ will illuminate.
hWithnoammablegaspresentatthedetector,placetheendofthe
‘CRO-Mag’keyoverthe‘UP’or‘DOWN’arrowpadstomakethe
display read the desired alarm level.
i Using a long instrument screwdriver, turn the relevant ALARM SET
pot mounted on the terminal board (see Diagrams 1 & 2) to adjust
the alarm level. Tripping of the ALARM 1 level relay is confirmed by
the status LED turning a steady red. Tripping of the ALARM 2 level
relay is confirmed by the Status LED flashing red.
j Once the alarm level has been set, place end of ‘CRO-Mag’ over the
‘UP’or‘DOWN’arrowpadsandresetthedisplaytoreadzero.
k Place the end of the ‘CRO-Mag’ over the ‘MENU’ pad to return
the detector to normal operation, ie. No decimal points displayed,
backlight off and the Status LED indicating steady green.