FunctionA:ON-DelayC: OFF-DelayL:Repeat CycleU: Multifuction U
OutputTypeR: Relay
Power SupplyMV1:12-240V AC/DC
OutputQuantity1: 1 Output2:2 Outputs
Output Power10: 10 A
Type
O:Plug-in 8-PinsP:Plug-in 11-Pins
PART NUMBERING SYSTEM
Plug-In Timer
11 pins
› Multifunction or monofunction› Compact body for space saving› Wide time range (from 0.5 seconds to
10 days delay)
› Universal power supply (12-240 Vz)› 1 or 2 relay outputs
(SPDT / Changeover)
› Protective cover› LED status indicator› 3-wire PNP sensor compatible
PU2R10MV1
Multifunctions U -
Monofunction Ad -
Instantaneous
› 11-pins connections
Product selection
FunctionOutputSupply VoltagePart Number
Multifunction U: (A, At, B, C, H,
Ht, D, Di, Ac, Bw)
Ad - Instantaneous
A, At2 relays
C2 relays
L, Li2 relays
2 relays
PA2R10MV1
Monofunction A, At
12 to 240 Vz
12 to 240 Vz
12 to 240 Vz
12 to 240 Vz
PC2R10MV1
Monofunction C
PU2R10MV1
PA2R10MV1
PC2R10MV1
PL2R10MV1
11/2018
PL2R10MV1
Monofunction L, Li
You have a project? Contact us on www.crouzet.com
Description:
Syr-line, the new specialized range at Crouzet, aimed to satisfy the most unique requirements of your applications by innovating in design,
engineering and development.
The Plug in Analog Timers, a new family of 11 timers with multifuction or monofunction, universal power supply, wide time range, with all the classic
functions.
2 11/2018 Plug-In Timer
PU2R10MV1PA2R10MV1PC2R10MV1PL2R10MV1
Power Supply
Rated supply voltage Un
Voltage supply tolerance-15 %, +10 %
AC supply voltage frequency50 / 60 Hz ± 5%
Galvanic isolation of supply / inputsNo
Power consumption @ Un
Immunity to power micro cuts10 ms
Timing Control
Specied time ranges (7) (IEC 1812-1)0.5..10 s, 0.05..1 min, 0.5..10 min, 0.05..1 h, 0.5..10 h, 0.05..1 day, 0.5..10 days
Minimum control pulse duration
(IEC 1812-1)
Recovery time (after by de-energisation)
(IEC 1812-1)
Repeatability (IEC 1812-1)≤ ± 0.5 %
Setting Accuracy (IEC 1812-1)≤ ± 10 %
Temperature drift≤ ± 0.05 % / °C
Voltage drift≤ ± 0.2 % / V
Relay output
Contact arrangement2 CO (SPDT)
Maximum switching voltage
Switching current rate (resistive)
Minimum switching contact
Maximum switching power (resistive)2500 VA / 300 W
Electrical life
Maximum rate (at max switching power)360 cycles /hour
Mechanical life10 x 10
Rated impulse voltage4 kV (1.2/50 µs)
Dielectric strength between coil / contacts
(IEC 60664-1)
Dielectric strength between open contacts1 kV / 1 min / 1 mA / 50 Hz
Insulation
Rated Insulation voltage (IEC 60664-1)250 V
Insulation coordination (IEC 60664-1)Overvoltage category III; pollution degree 2; up to 2000 m above sea level
Rated impulse voltage (IEC 60664-1)4 kV (1.2/50 µs)
Clearance / Creepage distances
(IEC 60664-1)
Dielectric strength (EN-61812-1)2.5 kV / 1 min / 1 mA / 50 Hz
Insulation Resistance (NFC 93 050)
General specications
Status indication (LED)Un: green LED blinks when count, ash when waiting Y1, continuous ON when supplied
Casing35 mm
MountingMounting base-mounted on socket
Housing material (UL94)Enclosure plastic type V0
Degree of protection (IEC 60529)IP40
Operating temperature (IEC 60068-2)-20 °C to +60 °C
12 to 240 Vz
Approx. 3 VA (Va) 1.5 W (Vc)
40 ms
100 ms with load
120 ms
2 CO (SPDT) (ChangeOver -Single Pole Double Throw-)
(ChangeOver -Single
Pole Double Throw-)
R1: Follow timing
function
R2: Follow timing
function / Instantenous
250 Va / 10 A resistive / 125 Vc / 0.3 A resistive
NO / NC: 10 A 250 Va / 10 A 30 Vc @ 25 °C
NO / NC: 5 A 250 Va / 5 A 30 Vc @ 60 °C
10 mA / 5 Vc
5
cycles min at 250 Va/ 10 A resistive (NO only)
10
6
cycles
2.5 kV / 1 min / 1 mA / 50 Hz
3 mm / 3.2 mm
> 500 MOhms / 250 Vc / 1 min
R: yellow LED blink when only R2 is ON (instantaneous), continuous ON when the 2 relays are ON.
3
PU2R10MV1PA2R10MV1PC2R10MV1PL2R10MV1
Storage temperature (IEC 60068-2)-40 °C to +70 °C
Humidity (IEC 60068-2-30)93 % without condensation
Vibration resistance (IEC 60068-2-6)±0.15mm from 10 Hz…60 Hz 2 g from 60 Hz..150 Hz
Shock resistance (IEC60068-2-27)10 gn - 11 ms; 3 X 6 axis (Output non-energized) 5 gn - 11 ms; 3 X 6 axis (Output energized)
Drop to concrete oor (IEC 60068-2-32)High: 0.75 m
Weight90 g
110 g with packaging
Standards
CEE Directive: 2014/30/EU
2014/35/EU
Approvals / MarkingCE
Security standard (IEC 60664-1)Insulation coordination for equipment within low-voltage systems
Conformity with environmental directives:
2015/863/UE
1907/2006
2012/19/UE
Product standard
(IEC 61812-1 / UL 60947-4-1)
Electromagnetic compatibility:
IEC 61000-6-2
IEC 61000-6-3
IEC 61000-6-4
Immunity to electrostatic discharges
(IEC61000-4-2)
Immunity to radiated, radio-frequency,
electromagnetic eld (IEC61000-4-3)
Immunity to rapid transient bursts (IEC
61000-4-4)
Immunity to shock waves on power supply
(IEC 61000-4-5)
Immunity to radiofrequency in common
mode (IEC 61000-4-6)
Immunity to voltage dips and breaks
(IEC 61000-4-11)
AC/DC main port emissions
(IEC 61000-6-3 IEC 61000-6-4)
Radiated emissions
(IEC 61000-6-3 IEC 61000-6-4)
EMC
Low voltage
cULus Listed Industrial Control Equipment
RoHS
Reach
WEEE
Specied time relays for industrial use
Industrial Control Equipment (NRNT- Industrial Control Switches)
Refer to UL840 Insulation Coordination for Electrical Equipment
230 MHz – 1 000 MHz, 37 dB(μV/m) Quasi-peak at 10 m
Or: 30 MHz – 230 MHz, 40 dB(μV/m) Quasi-peak at 3 m in a semi-anechoic chamber
230 MHz – 1 000 MHz, 47 dB(μV/m) Quasi-peak at 3 m in a semi-anechoic chamber
11/2018 | Plug-In Timer
4 11/2018 Plug-In Timer
unctio
PU2R10MV1PA2R10MV1PC2R10MV1PL2R10MV1
Function Diagrams
Basic Time Chart
Function A - On-Delay (Delay on make)
U
R2 TIMED
A2 f
A1 function
R1/R2
n
R2
T
Function Ad - Delay on Start Function At - Summation time relay
Function B - One-Shot Function Bw
Function Ac - On/Off Delay (Delay on make/break)
Function C - Off-Delay (Delay on break) Function D - Symmetrical ashing (OFF Start)
Function Di - Symmetrical ashing (ON Start) Function H - Interval
Function Ht - Interval summation time relay Function L - Recycler (OFF Start)
5
11/2018 | Plug-In Timer
Function Li - Recycler (ON Start)
PU2R10MV1PA2R10MV1PC2R10MV1PL2R10MV1
Connections
PU2R10MV1 - PA2R10MV1 - PC2R10MV1
+
U
6
5
2
R1Y1R2
1
11
7
8
9
10
4
3
–
PL2R10MV1
+
U
Y1
6
5
2
R1 R2
1
11
7
8
9
10
4
3
–
2 5
PU2R10MV1PA2R10MV1PC2R10MV1PL2R10MV1
Outline dimensions (mm)
±0.2
35
±0.2
45.01
±0.2
53
7.81
±0.3
PU2R10MV1PA2R10MV1PC2R10MV1PL2R10MV1
Socket
RECOMENDED SOCKET
11 Pins for DIN Rail or Panel Mount (P/N: 25 622 080)
62.56
±0.3
11.94
±0.2
13.3
±0.2
Warning:
The product information contained in this catalogue is given purely as information and does not constitute a representation, warrantly or any form of contractual commitment. Crouzet Automatismes SAS and its subsidiaries
reserve the right to modify their products without notice. It is imperative that we should be consulted over any particular use or application of our products and it is the responsability of the buyer to establish, particularly through
all the appropriate tests, that the product is suitable for the use or application. Under no circumstances will our warranty apply, nor shall we be held responsible for any application (such as any modication, addition, deletion,
use in conjunction with other electrical or electronic components, circuits or assemblies, or any other unsuitable material or substance) which has not been expressly agreed by us prior to the sale of our products.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.