P210 MV1
U
R
Function
A: ON-Delay
C: OFF-Delay
L: Repeat Cycle
U: Multifuction U
Output Type
R: Relay
Power Supply
MV1: 12-240V AC/DC
Output Quantity
1: 1 Output
2: 2 Outputs
Output Power
10: 10 A
Type
O: Plug-in 8-Pins
P: Plug-in 11-Pins
Plug-In Timer
11 pins
› Multifunction or monofunction
› Compact body for space saving
› Wide time range (from 0.5 seconds to
10 days delay)
› Universal power supply (12-240 Vz)
› 1 or 2 relay outputs
(SPDT / Changeover)
› Protective cover
› LED status indicator
› 3-wire PNP sensor compatible
PU2R10MV1
Multifunctions U -
Monofunction Ad -
Instantaneous
› 11-pins connections
Product selection
Function Output Supply Voltage Part Number
Multifunction U: (A, At, B, C, H,
Ht, D, Di, Ac, Bw)
Ad - Instantaneous
A, At 2 relays
C 2 relays
L, Li 2 relays
2 relays
PA2R10MV1
Monofunction A, At
12 to 240 Vz
12 to 240 Vz
12 to 240 Vz
12 to 240 Vz
PC2R10MV1
Monofunction C
PU2R10MV1
PA2R10MV1
PC2R10MV1
PL2R10MV1
11/2018
PL2R10MV1
Monofunction L, Li
You have a project? Contact us on www.crouzet.com
Description:
Syr-line, the new specialized range at Crouzet, aimed to satisfy the most unique requirements of your applications by innovating in design,
engineering and development.
The Plug in Analog Timers, a new family of 11 timers with multifuction or monofunction, universal power supply, wide time range, with all the classic
functions.

2 11/2018 Plug-In Timer
PU2R10MV1 PA2R10MV1 PC2R10MV1 PL2R10MV1
Power Supply
Rated supply voltage Un
Voltage supply tolerance -15 %, +10 %
AC supply voltage frequency 50 / 60 Hz ± 5%
Galvanic isolation of supply / inputs No
Power consumption @ Un
Immunity to power micro cuts 10 ms
Timing Control
Specied time ranges (7) (IEC 1812-1) 0.5..10 s, 0.05..1 min, 0.5..10 min, 0.05..1 h, 0.5..10 h, 0.05..1 day, 0.5..10 days
Minimum control pulse duration
(IEC 1812-1)
Recovery time (after by de-energisation)
(IEC 1812-1)
Repeatability (IEC 1812-1) ≤ ± 0.5 %
Setting Accuracy (IEC 1812-1) ≤ ± 10 %
Temperature drift ≤ ± 0.05 % / °C
Voltage drift ≤ ± 0.2 % / V
Relay output
Contact arrangement 2 CO (SPDT)
Maximum switching voltage
Switching current rate (resistive)
Minimum switching contact
Maximum switching power (resistive) 2500 VA / 300 W
Electrical life
Maximum rate (at max switching power) 360 cycles /hour
Mechanical life 10 x 10
Rated impulse voltage 4 kV (1.2/50 µs)
Dielectric strength between coil / contacts
(IEC 60664-1)
Dielectric strength between open contacts 1 kV / 1 min / 1 mA / 50 Hz
Insulation
Rated Insulation voltage (IEC 60664-1) 250 V
Insulation coordination (IEC 60664-1) Overvoltage category III; pollution degree 2; up to 2000 m above sea level
Rated impulse voltage (IEC 60664-1) 4 kV (1.2/50 µs)
Clearance / Creepage distances
(IEC 60664-1)
Dielectric strength (EN-61812-1) 2.5 kV / 1 min / 1 mA / 50 Hz
Insulation Resistance (NFC 93 050)
General specications
Status indication (LED) Un: green LED blinks when count, ash when waiting Y1, continuous ON when supplied
Casing 35 mm
Mounting Mounting base-mounted on socket
Housing material (UL94) Enclosure plastic type V0
Degree of protection (IEC 60529) IP40
Operating temperature (IEC 60068-2) -20 °C to +60 °C
12 to 240 Vz
Approx. 3 VA (Va) 1.5 W (Vc)
40 ms
100 ms with load
120 ms
2 CO (SPDT) (ChangeOver -Single Pole Double Throw-)
(ChangeOver -Single
Pole Double Throw-)
R1: Follow timing
function
R2: Follow timing
function / Instantenous
250 Va / 10 A resistive / 125 Vc / 0.3 A resistive
NO / NC: 10 A 250 Va / 10 A 30 Vc @ 25 °C
NO / NC: 5 A 250 Va / 5 A 30 Vc @ 60 °C
10 mA / 5 Vc
5
cycles min at 250 Va/ 10 A resistive (NO only)
10
6
cycles
2.5 kV / 1 min / 1 mA / 50 Hz
3 mm / 3.2 mm
> 500 MOhms / 250 Vc / 1 min
R: yellow LED blink when only R2 is ON (instantaneous), continuous ON when the 2 relays are ON.