Crouzet GN0 Series Catalog Page

GN0 Series 3 Phase Solid State Relay - DC Input
t
p
( , y )
g
(
)
e
)
Three-phase motor-reversing solid-state relay Ratings up to 50 amps @ 530Vac DBC substrate for superior thermal performance Epoxy-free design reduces internal component stress Back-to-Back dual SCR output for heavy industrial loads 100k-cycle UL508 endurance rating for enhanced reliability No external transient protection required (internal TVS)
UL/CSA/TUV Approved, CE & RoHS Complian
ut Specifications Part Numbers
Out
Output Current (40°C) Voltage range (Vrms) 48-530Vac 48-530Vac Rating Output Input Part Number Peak Voltage (Vpk , t = I min.) 1100 1100 25 Amp 48-530Vac 4-32Vdc GN025DSR Max off-state leakage (mArms) 3 3 50 Amp 48-530Vac 4-32Vdc GN050DSR Minimum Current (mArms) 100 100 Max. 1 cycle surge current 500 800 (Apk, Ta = 25ºC) Max. 1 second surge current 100 160 (Apk, Ta = 25ºC) Forward voltage drop 1.35 1.35 (Vpk @ Imax, Ta = 40ºC) I2T
60Hz ½ c cle Rjb (thermal res. Junction to baseplate, °C/W) 0.26 0.25 Static off-state dv/dt 500 500 (Vµs, Ta = 25ºC) HP Ratings at 120V 0.75 1.5 HP Ratings at 240V HP Ratings at 480V 3 7.5 Min/Max wire size 16/8 AWG 16/8 AWG Torque (N-m)
25 50
1040
2600
1
3
2.4
Input Specifications Equivalent Circuit
Input voltage Drop out volta Min. input current (for on-state) Maximum input current Input Resistance Maximum Turn-on time Maximum Turn-off time Min/Max stranded/solid wir Torque (N-m Interlocking Time
e
Ohms
4-32Vdc
1Vdc 17mA 25mA
Current Regulated
150 msec
8.33msec
24/14 AWG
1.9
100msec
General Characteristics
Operating Temperature (ºC) Storage Temperature (ºC) -40 to + 100 Input to output isolation 4000Vrms Input/output to ground isolation 2500Vrms Input to output capacitance 8pF (typical) Operating Frequency 47 to 63 Hz Housing Material Weight (grams) 370
-40 to + 80
UL 94V0 (self extinguishing)
Standards of Compliance
CE Compliant with the LVD 73/23/EEC UL Recognized per UL 508 and CSA C22.2 no. 14-95 TUV Certified per EN 60950 IEC 62314 IEC 60068-2-6 35mm/10-55Hz IEC 60068-2-27 15G / 11ms IEC 61000-4-2 Level 3 Electrostatic Discharge IEC 61000-4-3 Level 3 Radiated Electromagnetic Noise IEC 61000-4-4 Level 3 Immunity to Electrically Fast Transients IEC 61000-4-5 Level 3 Immunity to Electrical Surges IEC 61000-4-6 Level 3 Conducted Electromagnetic Noise CISPR 11 Class A Conducted and Radiated Noise for Industrial Enviroments
Products and specifications subject to change without notice
Order/Technical Support - Tel: (800) 677-5311 / Fax: (800) 677-3865 / www.crouzet-usa.com
Dimensional Drawings For GN0
Dimensions mm (inches)
GN0 Derating Curves
DERATING CURVES:
GN0 - 25AMP
30
25
20
15
10
Load Current (Amperes Per Ph ase)
5
0
20 30 40 50 60 70 80
Ambient Temperature (°C)
2.5°C/W 2°C/W
1.5°C/W 1°C/W
0.7°C/W
50 45 40 35 30 25 20 15 10
Load Current (Amperes Per Phase)
5 0
20 30 40 50 60 70 80
Ambient Temperature (°C)
DERATING CURVES:
GN0 - 50AMPS
1.5°C/W 1°C/W
0.7°C/W
0.5°C/W
0.25°C/W
Products and specifications subject to change without notice