Crouzet EU SERIES Catalog Page

CONTROLS CONTROLS
Un
T1
T1
Un
T1
T1
A1
A21214
E3E2E1
11 M
11
1412
A1 & A2 power supply
3.10˝ (78.5)
3.53˝ (89.7)
3.92˝ (99.3)
(22.5)
.89˝
.17˝ (4.2)
2.25˝ (57)
.20˝
(5)
.14˝
(3.5)
3.94˝ (100)
2.84˝ (72)
EU SERIES
VOLTAGE CONTROL RELAY
UL cUL listed
• Selectable Under or Over Voltage Modes
• Space Saving 22.5mm Wide Enclosure
• DIN-Rail / Surface Mount
TWO PRODUCT TYPES: EUL (.2 TO 60V) AND EUH (10 TO 600V) PROVIDE SELECTABLE OVER OR UNDER VOLTAGE CONTROL.
MODE OF OPERATION
VOLTAGE CONTROL WITHOUT MEMORY
Control of AC / DC voltage without memory
When the value of the controlled voltage, AC or DC, reaches the threshold Ue displayed on the front face, the output relay changes state at the end of a time delay T which can be set on the front face at between 0.1 and 3 s.
Once the voltage drops below 5 to 50% of the threshold (hysteresis), the output relay changes state again instantly. Changing the hysteresis on the front face does not therefore modify the value of the preset
Threshold Ue
Hysteresis
UPPER function
Hysteresis
threshold.
Control of AC / DC voltage with memory
When the value of the controlled voltage, AC or DC, reaches the threshold Ue displayed on the front face, the output relay changes
UNDER function
VOLTAGE CONTROL WITH MEMORY
state at the end of a time delay T which can be set on the front face at between 0.1 and 3 s, and stays locked in this position.
SPECIFICATIONS
Input power........................
Max. power consumption ............
Frequency of measured signal........
Threshold value ....................
Hysteresis.........................
Display Accuracy ...................
Delay on threshold overun ...........
Output ............................
Contact material....................
Maximum loading...................
Maximum switching voltage ..........
Operating temperature ..............
Storage temperature ................
Weight ............................
24 VDC, 24, 120, 230 VAC ±15%, 50/60 Hz 3 VA 40 to 500 Hz 1 to 100% of measurement range 5 to 50% of displayed threshold ±10% of full scale .1 to 3 sec. SPDT relay AgCdO 8 Amp resistive 250 VAC
-4°F to 140°F, (-20°C to 60°C)
-22°F to 158°F, (-30°C to 70°C)
4.9 oz. (140g)
Threshold Ue
Hysteresis
UPPER function
Hysteresis
Threshold Ue
UNDER function
WIRING
MEASUREMENT RANGE
TYPES EUL EUH
Input E1-M E2-M E3-M E1-M E2-M E3-M
Sensitivity
Input resistance
*Important: For 24 VDC Input power models, the supply voltage and the measured
0.2 to 1 to 6 to 15 to 30 to 60 to 2 V 10 V 60 V 150 V 300 V 600 V
2 k 10 k 60 k 100 k 300 k 600 k
voltage must be from separate sources. The “negative” poles of the auxiliary power and the measurement circuit are connected inside the unit.
DIMENSIONS inches (mm)
ORDERING INFORMATION:
Part Number Type Supply Voltage Measurement Range
84 872 020 EUL *24 VDC* .2 to 60 V 84 872 021 EUL 24 VAC .2 to 60 V 84 872 023 EUL 120 VAC1 .2 to 60 V 84 872 024 EUL 230 VAC2 .2 to 60 V 84 872 030 EUH *24 VDC* 10 to 600 V 84 872 031 EUH 24 VAC 10 to 600 V 84 872 033 EUH 120 VAC1 10 to 600 V 84 872 034 EUH 230 VAC2 10 to 600 V
*See “Important” in Specifications
5-24
204 Airline Drive, Suite 300, Coppell, Texas 75019 / Tel: (800) 677-5311 / FAX: (800) 677-3865 / www.crouzet-usa.com
Products and specifications subject to change without notice.
Consult factory for application assistance.
Unit power-up
Controlled voltage
Controlled voltage
Unit power-up
Controlled voltage
Controlled voltage
Loading...