BM2R
Timers
Syrline
17.5 mm - 2 Relay 8A
› Multi-function or mono-function
› Multi-range (12 function)
› Multi-voltage 12 →240 V AC/DC
› LED status indicator (relay version)
› Possibility of external load connection in parallel to the
control input
› 3-wire PNP sensor compatible
Specifications
Functions Delay Output Nominal rating Connections Supply voltage Code
A - Ac - At - B - C - D - Di -
H - Ht -N - TL - Tt
Output relay
Contact arrangement 2 CO (SPDT) (ChangeOver -Simple Pole Double Throw-)
Maximum switching voltage 250 VAC/ 8 A resistive / 250 VDC / 0.3 A resistive
Switching current rate (resistive) NO / NC : 8A 250 V AC / 8 A 30 VDC @ 25°C
Minimum switching contact 10 mA / 5 VDC
Maximum switching power (resistive) 2000 VA / 80 W @ 25°C
Electrical life 105 cycles min at 250 VAC/ 8 A resistive
Maximum rate (at max switching power) 360 cycles /hour
Mechanical life 10 x 106 cycles
Rated impulse voltage 5 kV (1.2/50µs)
Dielectric strength between coil / contacts IEC 60664-1: 5 kV /1 min / 1 mA / 50 Hz
Dielectric strength between open contacts 2.5 kV /1 min / 1 mA / 50 Hz
0,5 s →10 days 2 changeover
relays
2 x 8 A Screw terminals 12 →240 V ∿/⎓ BM2R08MV1
R1: Follow timing function
R2: Follow timing function / Instantaneous
NO / NC : 5A 250 V AC / 5 A 30 VDC @ 60°C
Timing
Timing ranges (7 ranges) 0.5→10s, 0.05→1min, 0.5→10min, 0.05→1h, 0.5→10h, 0.05→1day,
Minimum pulse duration typically (relay version) IEC 1812-1: 30 ms
Maximum reset time by de-energisation typically (relay version) IEC 1812-1: 120 ms
Repeatability IEC 1812-1: ≤ ± 0,5 %
Repetition accuracy with constant parameters IEC 1812-1: ≤ ± 10 %
Drift Temperature ≤ ± 0.05 % / °C
Voltage-dependent drift ≤ ± 0.2 % / V
0.5→10days
100 ms with load

Supply
Multi-voltage power supply 12→240 V∿/⎓
Operating range 15 %, +10 %
Operating frequency (Hz) 50 / 60 Hz ± 5 %
Galvanic isolation No
Max. absorbed power Approx. 3 VA (V∿) 1.5 W (V⎓)
Immunity from micro power cuts 10 ms
General characteristics
Insulation voltage, IEC 60664-1 300 V
Installation category (acc. to IEC/EN 60664-1) Overvoltage category III ; pollution degree 2
Impulse voltage CEI/EN 60664-1 4 kV (1,2 / 50 µs)
Clearance / Creepage distances IEC 60664-1: 3 mm / 3.2 mm
Breakdown voltage EN-61812-1: 2,5 kV / 1 min / 1 mA / 50 Hz
Insulation resistance NFC 93 050: > 500 MΩ / 250 V⎓ / 1min
Status indication Un: green LED blinks when count, continuous ON when supplied
R: yellow LED continuous ON when the relay is ON
Casing DIN 43880: 17,5 mm
Fixing: Symmetrical DIN rail EN 50022: 35 mm
Mounting position All positions
Housing material Enclosure plastic type UL94 - V0
Protection (IEC/EN 60529) Housing: IP40 / Terminal block: IP20
Terminal capacity Single-wire without ferrule IEC 60947-1
1 x 0.5 →3.3 mm² (AWG 20 →AWG 12)
2 x 0.5 →1.5 mm² (AWG 20 →AWG 16)
Max. tightening torque (Nm) IEC 60947-1: 0,5 N.m / 4,4 lbf.in
Operating temperature range (°C) IEC 60068-2: -20 °C →+60 °C
Storage temperature range (°C) IEC 60068-2: -40 °C →+70 °C
Relative humidity no condensation acc. to IEC/EN 60068-2-30 93 % without condensation
Vibration resistance according to IEC/EN 60068-2-6 ± 0.15 mm from 10 Hz →60 Hz 2g from 60 Hz →150 Hz
Impact resistance IEC 60068-2-27
15gn - 11ms ; 3 x 6 axis (output OFF)
5gn - 11ms ; 3 x 6 axis (Output ON)
Drop to concrete floor IEC 60068-2-32
High: 0.75m
Weight: casing 17,5 mm 70 g
80 g with packaging
Directives 2014/30/EU: EMC
2014/35/EU: low voltage
Certifications CE - cULus Listed Industrial Control Equipment - CCC
Conformity to standards CEI 60664-1: Insulation coordination for equipment within low-voltage
Conformity with environmental directives 2015/863/UE: RoHS
Electromagnetic compatibility IEC 61000-6-2, IEC 61000-6-3,
IEC 61000-6-4
Electromagnetic compatibility - Immunity to electrostatic discharges
acc to IEC/EN 61000-4-2
systems
CEI 61812-1/ Specified time relays for industrial use
UL 60947-4-1/ Industrial Control Equipment (NRNT- Industrial Control
Switches)
1907/2006: Reach
2012/19/UE: WEEE
Immunity for industrial environment
Emission residential environment
Emission industrial environment
Level III Air ± 8 KV / Contact ± 6 KV