Crouzet 88970524 Installation Instructions

6051
Environmental Considerations
NEMA Rating
Electrical Environment
Environmental Considerations
Type
A(mm)
B(mm)
CT104
119
93
CT104 series 88 970 524
Installation Instruction
Unpack and check the delivery. If damage is found, notify the supplier.
NOTE:
Place the operator panel on a stable surface during installation. Dropping it or letting it fall may cause damage.
3
5
Go to the Security tab, the default password is 111111, click the buttons to set your own passwords.
4
NOTE:
1. Connect positive DC line to the ‘+’ terminal
and the DC ground to the ‘-’ terminal.
2. Please do not connect HMI with PLC and PC simultaneously to prevent potential difference from destroying USB ports of HMI and PC.
(A)
(B)
Cutout
(1) Installation Instruction, 2-sided A4 *1
(2) Human Machine Interface *1
(3) Power Connector *1
(4) Brackets & Screws *1 pack
(1)
(2)
(4)
(3)
1
2
Installation and Startup Guide
This document covers the installation of CT104 Series HMI, for the detailed specifications and operation, please refer to Brochure and Crouzet Touch Soft User Manual.
Handling and Storage:
Install Environment:
Installation Instructions
Secure the operator panel in position, using all the fastening holes and the provided brackets and screws. Screw Torque: 0.29 ~ 0.44 N.m (For reaching waterproof effect and preventing the panel from being deformed.)
Power Connections
Unpacking the Unit
System Settings
When HMI is powered up and displays image, click the system setting button. (Default System Password: 111111)
Crouzet Touch Soft Settings
Power
The unit can be powered by DC power only, voltage range: 24±20% Volts DC, compatible with most controller DC systems. The power conditioning circuitry inside the unit is accomplished by a switching power supply. The peak starting current can be as high as 2A.
Fusing Require­ments
If the display does not come on within 5 seconds of power up, remove power. An internal fuse will prevent damage if the polarity of the DC power is incorrect. Check wiring for proper connections and try to power up again.
6
7
1-2
3-4
Mode
Short
Open
Touch Screen Calibration Mode
Open
Short
Boot Loader Mode
Open
Open
Normal
8
PIN#
COM1 [RS485]
COM1
[RS232]
COM3
[RS485]
4 wire
2 wire
1
Rx-
Data- 2 Rx+
Data+ 3 Tx- 4 TX+
5
GND
6
TxD 7 Data-
8
Data+
9
RxD
CAUTION
NOTE: Make sure that all local and national electrical standards are met when
installing the unit. Contact your local authorities to determine which codes apply.
Limited Warranty
This product is limited warranted against defects in design and manufacture. The proven defective product will either be repaired or replaced, at Crouzet’s discretion. This warranty shall not cover any product which is
(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products. (b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse. (c) Product has been repaired or taken apart by unauthorized technicians. (d) Products whose identification markings have been removed or damaged.
High Voltage
An Internal fuse will prevent damage for overcurrent condition however it isn’t guaranteed. DC voltage sources should provide proper isolation from main AC power and similar hazards.
Emergency Stop
Safety Recommendations.
Supply Voltage Condition
Do not power the unit and inductive DC loads, or input circuitry to the controller, with the same power supply. Note: The 24 VDC output from some controllers may not have enough current to power the unit.
Wire Routing
a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded). b. Please use twisted pair cables for power wire and signal wire and conform to the impedance
matching. c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression devices. d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires. e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power
supply and the frame ground. This provides a path for static and high frequency dissipation.
Typical values to use are 1M Ohm and 4700pF.
Hardware Considerations
The system designer should be aware that devices in Controller systems could fail and thereby create an unsafe condition. Furthermore, electrical interference in an operator interface can lead to equipment start-up, which could result in property damage and/or physical injury to the operator. If you use any programmable control systems that require an operator, be aware that this potential safety hazard exists and take appropriate precautions. Although the specific design steps depend on your particular application, the following precautions generally apply to installation of solid-state programmable control devices, and conform to the guidelines for installation of Controllers recommended in NEMA ICS 3-304 Control Standards.
Programming Considerations
To conform with ICS Safety Recommendations, checks should be placed in the controller to ensure that all writable registers that control critical parts of plant or machinery have limit checks built into the program, with an out-of-limit safe shut down procedure to ensure safety of personnel.
Disposal Considerations
This product is an electronic device (EEE) and as such, must be sent to approved authorized treatment facility (*) after service life for proper disposal.
This product includes a lithium battery. Do not open it by force; do not throw it in fire. In compliance with Directive 2006/66/UE requirements, we inform you that batteries must not be discarded in household waste, and must also be sent to approved authorized treatment facility (*) after service life for proper disposal.
(*) visit http://www.crouzet-automation.fr/assistance/valorisation-des-dechets/
GMECT14P0_CT104_Installation_161006
DANGER
Launch Crouzet Touch Soft software, select your project file, press F7 shortcut key to open the download dialog box:
Select USB cable > Click Download to download this project file to HMI.
( Please refer to Crouzet Touch Soft User Manual for software operation details )
Communication Connections
9 Pin, Male, D-sub COM1 [RS232] COM1 [RS485] COM3 [RS485]
Jumper Settings
Please prepare a jumper cap for setting the jumpers. Another way to enter touch screen calibration mode is: Press and hold anywhere on the screen for more than 2 seconds when HMI starts.