6051
Environmental
Considerations
(1) Storage temperature -20°C/+60°C.
(2) Do not let water penetrate into packaging boxes during their storage and
transportation.
(3) Do not store the product in places of high temperature or under direct
sunlight.
(4) Please also avoid the places of high humidity. Be sure not to expose the
product to condensation, rain or frozen condition.
CT104 Series HMI is NEMA 4 rated (Indoor Only).
CT104 Series has been tested to conform to European CE requirements. This
means that the circuitry is designed to resist the effects of electrical noise. This
does not guarantee noise immunity in severe cases. Proper wire routing and
grounding will insure proper operation.
Environmental
Considerations
(1) Make sure that the displays are installed correctly and that the operating
limits are followed. Avoid installing units in environments where severe
mechanical vibration or shocks are present.
(2) Do not operate the unit in areas subject to explosion hazards due to
flammable gases, vapors or dusts.
(3) Do not install the unit where acid gas, such as SO2 exists.
(4) This device should be mounted in the vertical position and for use on the flat
surface enclosure.
(5) Conform to UL508 (ISBN 0-7629-0404-6) machine safety for use in
Pollution Degree 2 Environment.
CT104 series 88 970 524
Installation Instruction
Unpack and check the delivery. If damage
is found, notify the supplier.
NOTE:
Place the operator panel on a stable
surface during installation. Dropping it or
letting it fall may cause damage.
Go to the Security tab, the default
password is 111111, click the buttons to
set your own passwords.
NOTE:
1. Connect positive DC line to the ‘+’ terminal
and the DC ground to the ‘-’ terminal.
2. Please do not connect HMI with PLC and PC
simultaneously to prevent potential difference
from destroying USB ports of HMI and PC.
(1) Installation Instruction, 2-sided A4 *1
(2) Human Machine Interface *1
(4) Brackets & Screws *1 pack
Installation and Startup Guide
This document covers the installation of CT104 Series HMI, for the detailed specifications and
operation, please refer to Brochure and Crouzet Touch Soft User Manual.
Handling and Storage:
Install Environment:
Installation Instructions
Secure the operator panel in position, using all the fastening holes and the provided brackets
and screws. Screw Torque: 0.29 ~ 0.44 N.m (For reaching waterproof effect and preventing the panel from
being deformed.)
Power Connections
Unpacking the Unit
System Settings
When HMI is powered up and displays image,
click the system setting button.
(Default System Password: 111111)

Crouzet Touch Soft Settings
The unit can be powered by DC power only, voltage range: 24±20% Volts DC, compatible with
most controller DC systems. The power conditioning circuitry inside the unit is accomplished by a
switching power supply. The peak starting current can be as high as 2A.
If the display does not come on within 5 seconds of power up, remove power. An internal fuse will
prevent damage if the polarity of the DC power is incorrect. Check wiring for proper connections
and try to power up again.
Touch Screen Calibration Mode
NOTE: Make sure that all local and national electrical standards are met when
installing the unit. Contact your local authorities to determine which codes apply.
Limited Warranty
This product is limited warranted against defects in design and manufacture.
The proven defective product will either be repaired or replaced, at Crouzet’s discretion.
This warranty shall not cover any product which is
(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products.
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.
(c) Product has been repaired or taken apart by unauthorized technicians.
(d) Products whose identification markings have been removed or damaged.
An Internal fuse will prevent damage for overcurrent condition however it isn’t guaranteed. DC
voltage sources should provide proper isolation from main AC power and similar hazards.
Do not power the unit and inductive DC loads, or input circuitry to the controller, with the same
power supply. Note: The 24 VDC output from some controllers may not have enough current to
power the unit.
a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded).
b. Please use twisted pair cables for power wire and signal wire and conform to the impedance
matching.
c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression devices.
d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.
e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power
supply and the frame ground. This provides a path for static and high frequency dissipation.
Typical values to use are 1M Ohm and 4700pF.
The system designer should be aware that devices in Controller systems could fail and thereby
create an unsafe condition. Furthermore, electrical interference in an operator interface can lead to
equipment start-up, which could result in property damage and/or physical injury to the operator.
If you use any programmable control systems that require an operator, be aware that this potential
safety hazard exists and take appropriate precautions. Although the specific design steps depend on
your particular application, the following precautions generally apply to installation of solid-state
programmable control devices, and conform to the guidelines for installation of Controllers
recommended in NEMA ICS 3-304 Control Standards.
Programming
Considerations
To conform with ICS Safety Recommendations, checks should be placed in the controller to ensure
that all writable registers that control critical parts of plant or machinery have limit checks built into
the program, with an out-of-limit safe shut down procedure to ensure safety of personnel.
This product is an electronic device (EEE) and as such, must be sent to approved authorized
treatment facility (*) after service life for proper disposal.
This product includes a lithium battery.
Do not open it by force; do not throw it in fire.
In compliance with Directive 2006/66/UE requirements, we inform you that batteries must not be
discarded in household waste, and must also be sent to approved authorized treatment facility (*)
after service life for proper disposal.
(*) visit http://www.crouzet-automation.fr/assistance/valorisation-des-dechets/
GMECT14P0_CT104_Installation_161006
Launch Crouzet Touch Soft software, select your project file,
press F7 shortcut key to open the download dialog box:
Select USB cable > Click Download to download this project file to
HMI.
( Please refer to Crouzet Touch Soft User Manual
for software operation details )
Communication Connections
9 Pin, Male, D-sub
COM1 [RS232]
COM1 [RS485]
COM3 [RS485]
Jumper Settings
Please prepare a jumper cap for setting the jumpers.
Another way to enter touch screen calibration mode is: Press and hold anywhere on the screen for more
than 2 seconds when HMI starts.