■ H3US and M3US relays control, on 3-phase networks:
- overvoltage between phases,
- undervoltage between phases
■ The H3USN relay controls, on 3-phase networks:
- overvoltage between phases and neutral,
- undervoltage between phases and neutral,
- loss of neutral
■ Multi-voltage Products
■ Controls its own supply voltage
■ True RMS measurement
■ LED status indication
M3USH3USH3USN
FunctionUnder/overvoltage
Nominal voltage (V)
Output1 single pole changeover
Part numbers
between phases
3 x 208
➞ 3 x 480 V
relay
848732228487322084873221
Under/overvoltage
between phases
a
3 x 220 ➞ 3 x 480 V
2 single changeover
relays / one per threshold
Over and undervoltage
between phases and
neutral / loss of neutral
a
3 x 120 ➞ 3 x 277 V
2 single changeover
relays / one per threshold
a
■ Customisable colours and labels
■ Single voltage in the generic range
■ Fixed or adjustable time delay
■ Adjustable fixed hysteresis
Adaptations dedicated to M3US:
■ Fixed threshold in the generic range
Adaptations dedicated to H3US:
■ Fixed threshold in the generic range
Adaptations dedicated to H3USN:
■ Fixed overvoltage threshold in the generic range
■ Fixed undervoltage threshold in the generic range
DescriptionCode
Removable sealable cover for 17.5 mm casing84800000
Removable sealable cover for 35 mm casing84800001
M3USH3USH3USN
Supply
Supply voltage Un
Voltage supply tolerance-12% / +10%-12% / +10%-20% / +20%
Operating range
Power consumption at Un
Inputs and measuring cicuit
Selection of phase-phase nominal voltage Un208-220-380-400-415-
Selection of phase-neutral voltage--120-127-220-230-240-260-277
Output
Electrical life (number of operations)
General characteristics
Casing17.5 mm35 mm35 mm
Weight80 g130 g130 g
Comments
3 x 208
➞ 3 x 480 V
183
➞ 528 V
1.8 VA in
440-480 V
1 x 10
* 3-phase mains with earth* 3-phase mains with earth* 3-phase mains with earth
a
a
5
a
a
*3 x 220 ➞ 3 x 480 V a *3 x120 ➞ 3 x 277 V a *
194 ➞ 528 V
2.9 VA in
220-380-400-415-440480 V
1 x 10
a
a
a
4
96 ➞ 332 V
3.9 VA in
-
1 x 10
a
a
4
26
www.crouzet.com
General characteristics
Supply
a
supply voltage frequency
Galvanic isolation of power supply/measurementNo
Inputs and measuring cicuit
Frequency of measured signal50
Max. measuring cycle time150 ms/True RMS measurement
Voltage threshold adjustment
Fixed hysteresis2% of Un (M3US, H3US)
Display precision± 3% of the displayed value
Repetition accuracy with constant parameters± 0.5%
Measuring error with voltage drift< 1% across the whole range
Measuring error with temperature drift0.05% / °C
Timing
Delay on threshold crossing0.3
Repetition accuracy with constant parameters± 3%
Reset time1500 ms
Delay on pick-up500 ms
Alarm on delay time max.200 ms
Output
Type of contactsNo cadmium
Maximum breaking voltage
Max. breaking current
Min. breaking current
Breaking capacity (resistive)
Maximum rate360 operations/hour at full load
Operating categories acc. to IEC 60947-5-1AC 12, AC 13, AC 14, AC 15, DC 12, DC 13, DC 14
Mechanical life (operations)
Insulation
Nominal insulation voltage IEC 60664-1400 V
Insulation coordination (IEC 60664-1 / 60255-5)Overvoltage category III: degree of pollution 3
Rated impulse withstand voltage IEC 60664-1/60255-54 KV (1.2 / 50 µs)
Dielectric strength IEC 60664-1/60255-52 kV AC 50 Hz 1 min
Insulation resistance IEC 60664-1 / 60255-5
General characteristics
Display power supplyGreen LED
Display relayYellow LED (1 for M3US, 2 for H3US and H3USN)
MountingOn 35 mm symmetrical DIN rail, IEC/EN 60715
Mounting positionAll positions
Material: enclosure plastic type VO to UL94 standardIncandescent wire test according to IEC 60695-2-11 & NF EN 60695-2-11
Protection (IEC 60529)Terminal block: IP 20
Connecting capacity IEC 60947-1
Max. tightening torques IEC 60947-10.6
Operating temperature IEC 60068-2-20
Storage temperature IEC 60068-2-40
Humidity IEC 60068-2-302 x 24 hr cycle 95% RH max. without condensation 55°C
Vibrations according to IEC/EN60068-2-610
Shocks IEC 60068-2-65 g
Standards
MarkingCE (LVD) 73/23/EEC - EMC 89/336/EEC
Product standardNF EN 60255-6 / CEI 60255-6 / UL 508 / CSA C22.2 N°14
Electromagnetic compatibilityImmunity EN 61000-6-2/IEC 61000-6-2
CertificationsUL, CSA, GL
Conformity with environmental directivesRoHS, WEEE
50 / 60 Hz ±10%
➞ 60 Hz ± 10%
b
Undervoltage -2 to -20% of selected Un
for M3US:
(-2 to -12% across the 3 x 208 V range)
(-2 to -17% across the 3 x 220 V range)
for H3US:
(-2 to -12% across the 3 x 220 V range)
b
Overvoltage 2➞ 20% of selected Un
For M3US and H3US:
(+2
➞ +10% across the 3 x 480 V
➞ 30 s (0, +10%)
z
250 V
z
5 A
10 mA / 5 V
1250 VA
30 x 10
> 500 MΩ / 500 V
Casing: IP30
Rigid: 1 x 4
1 x 11 AWG - 2 x 14 AWG
Flexible with ferrules: 1 x 2.5
1 x 14 AWG - 2 x 16 AWG
➞ 150 Hz, A = 0.035 mm
Emission EN 61000-6-4/EN 61000-6-3
IEC 61000-6-4/IEC 61000-6-3
Emission EN 55022 class B
c
a
6
c
2
- 2 x 2.52 mm2
➞ 1 Nm / 5.3 ➞ 8.8 Lbf.Ft
➞ +50°C
➞ +70°C
a
range)
2
- 2 x 1.52 mm
pending
2
27
Overview
Phase control
Principles
3-phase voltage controllers which monitor:
- Undervoltage, adjustable from -20 to -2% of Un
- Overvoltage, adjustable from 2 to 20% of Un
- Presence of the neutral (H3USN only)
Measurements are taken between Phases for the H3US - M3US and between Phases and Neutral for the H3USN
Faults are signalled via LEDs, distinguishing the origin of the fault (one LED for the upper threshold, one LED for the lower threshold).
Voltage selector switch: Set the selector switch to the 3-phase network voltage Un.
The position of this selector switch is only taken into account when the unit is powered up.
If the switch position changes while the unit is operating, all the LEDs flash but the product continues to work normally with the voltage selected on
energisation prior to the change of position.
The LEDs return to their normal state if the switch is reset to its initial position defined before the last energisation.
The relay monitors its own supply voltage. It controls:
- Undervoltage, adjustable from -20 to -2% of Un (-12 to -2% over the 3 x 208 V
17% to -2% for the 3 x 220 V
- Overvoltage, adjustable from +2
maximum voltage 528 V
An adjustable time delay from 0.3 to 30s can be used to disable the output relay during a
transient fault.
In the event of a voltage fault, the relay opens at the end of the time delay set by the user.
In the event of phase failure, the relay opens instantaneously, without waiting for the end of the
time delay.
When the unit is powered up with a measured fault, the relay stays open.
H3US
The relay monitors its own supply voltage.
It controls:
- Undervoltage, adjustable from - 2 to - 20% of Un (-2 to -12% over the 3 x 220 V
the minimum voltage 194 V
- Overvoltage, adjustable from + 2 to +20% (+2 to +10% over the 3 x 480 V
maximum voltage 528 V
Each threshold has its own time delay with independent setting between 0.3 and 30 s.
In the event of a voltage fault, the corresponding relay (one undervoltage output/one overvoltage
output) opens at the end of the time delay set by the user.
In the event of phase failure, both relays open instantaneously, without waiting for the end of the
time delay. The two relay LEDs go out.
H3USN
The relay monitors its own supply voltage.
It controls:
- Presence of the neutral,
- Undervoltage, adjustable from -2 to -20% of Un,
- Overvoltage, adjustable from +2 to +20%.
Each threshold has its own time delay with independent setting between 0.3 and 30 s.
In the event of a voltage fault, the corresponding relay (one undervoltage output/one overvoltage
output) opens at the end of the time delay set by the user.
If neutral is lost, both relays open instantaneously and the corresponding LED is extinguished,
without waiting for the end of the time delay. The two relay LEDs are extinguished.
a
range due to the minimum voltage 183 V a)
a
a
➞ +20% (+2 ➞ +10% over the 3 x 480 V
).
a
)
).
a
range and -
a
range due to the
a
range due to
a
range due to the
28
Dimensions (mm)
www.crouzet.com
M3US
60
3,5
45
67,5
Connections
M3US
L1
L2
L3
1
F1
L1L2RL3
L2
L3
L1
12
111214
100 mA fast-blow fuse or cut-out
B
H3US
H3US - H3USN
44
23,2
5,5
17,5
3,5
90
2,6
67,5
45
60
44
23,2
5,5
35
90
2,6
H3US - H3USN
– KM1
11
14
U1
V1
W1
M1
3
L1
L2
L3
1
F1
L1L2
L2
L3
L1
12
111214
22 21 24
100 mA fast-blow fuse or cut-out
B
11
R1R2
22
14
– KM1
L3
21
24
U1
W1
V1
M1
3
L1
L2
L3
N
1
F1
L1L2
L2
L3
(N)
L1
12
111214
22 21 24
100 mA fast-blow fuse or cut-out
B
L3
11
R1R2
22
14
W1
U1
V1
M1
3
– KM1
(N)
21
24