Phase control
➜ EWS2
■ Space savings, accurate measurement and optimized
functions all improve the efficiency of your electrical
installation
■ Control : You simply install your EWS2 phase control
relay and without any adjustment you can monitor the
loss or inversion of one of the phases
■ Safety : The EWS2 range enables you to choose the
level of safety for your installation by using versions
with 1, 2 or 3 output changeovers
■ Self-powered : Simple to install, EWS2 control relays
use the controlled mains supply for their own power
supply voltage
Part numbers
Type Output relay Code
EWS2 2 changeovers
General characteristics
Input
Operating range
Operating range
Frequency 50 / 60 Hz
Maximum consumption 28 VA
Output
Output relay 2 changeovers
Type of contacts No cadmium
Nominal rating 8 A
Maximum breaking voltage
Nominal breaking capacity 2 000 VA
Min. breaking current
Electrical life (number of operations)
Maximum rate (at full load) 360 operations / hour
Mechanical life (operations)
Pick-up delay T1 ≤ 650 ms
Turn-off delay T2 < 300 ms
Connection capacity - without ferrule
Connection capacity - with ferrule
Max. tightening torque (IEC/EN 60947-1) 0.6
Environment
Operating temperature range (
Storage temperature (
Housing material Self-extinguishing
Protection (IEC/EN 60529) - Casing IP40
Protection (IEC/EN 60529) - Term. block IP20
Dielectric strength (IEC/EN 60255-5) 2.5 KV / 1 mn / 1 mA / 50 Hz
Insulation coordination (IEC/EN 60664-1) Overvoltage category III, degree of pollution 3 : 4 KV / 3
Weight (g) 86
o
0
C)
C)
➞ 3 x 400 V
3 x 230
3 x 200
➞ 3 x 484 V
a
250 V
10 mA / 5 V
5
at 8A/250 V
10
6
10 x 10
➞ 4 mm
1 x 0.5
➞ 2.5 mm
2 x 0.5
➞ 2.5 mm
1 x 0.5
➞ 1.5 mm
2 x 0.5
➞ 1 Nm / 5.3 ➞8.8 lbf.in
-20 ➞ +50
-40
➞ +70
a
a
c
a
2
(AWG 20 ➞ AWG 11)
2
(AWG 20 ➞ AWG 14)
2
(AWG 20 ➞ AWG 14)
2
(AWG 20 ➞ AWG 16)
84 873 034
1
Dimensions (mm)
EWS / EWS2
68
44
23.2
22.5
45
67.5
Connections
EWS2
L1
L2
L3
L1 L2 L3
3
Principles
Timing diagrams EWS2
100%
L1
0%
100%
L2
0%
100%
L3
0%
Tr Tr Tr
On
R
Off
Td Td Td Td
Td Td Td Td
5.5
11
R
12 14
90
2.6
21
R
22 24
Td : Power on delay
Tr : Responsable time after a fault has occurred
R : Output relay
L3
L2
Tr
2