Crouzet 84872021 Data Sheet

Page 1
DIN Rail Mount 22.5 mm EUL Part number 84872021
Voltage monitoring 2 relays to cover 6 ranges of measurement : 0.2V to 600V Automatic recognition AC/DC Frequency up to 500 Hz
Part numbers
Specifications
Type
Measurement range
Supply voltage
84 872 021
EUL
0,2→60V
24 V AC
Supply voltage Un
24 V, 120 V, 230 V, 50/60 Hz (galvanic isolation via transformer) 24 V (no galvanic isolation). In this case, the product power supply and measuring circuit power supply must be electrically isolated.
Operating range
0,85 1,15 Un
Maximum power consumption
3 VA
/ 1 W
Frequency of measured signal
40 500 Hz
Threshold Ue
Adjustment from 10 to 100 % of the measurement range
Hysteresis
Adjustment from 5 to 50 % of the displayed threshold
Display precision
±
10 % of the full scale
Delay on thresold crossing Tt
0,1 3 s ±10 %
Output relay
1 AgNi changeover, 8 A
max
Temperature Use (°C)
-
20→+60
Storage temperature (0C)
-
30→+70
InputsE1-M
E2-M E3-M
Sensitivity
E1-M : 0,2 to 2V E2-M : 1 to 10V E3-M : 6 to 60V
Input resistance
E1-M : 2kΩ E2-M : 10k
Ω
E3-M : 60k
Ω
Principles
05/09/2014 www.crouzet.com
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
Page 2
When the value of the controlled voltage, AC or DC, reaches the treshold Ue displayed on the front face, the output relay changes state at the end of a time delay T1, which can be set on the front face at between 0.1 and 3s. Once the voltage drops below 5 to 50 % of the treshold (hysteresis), the output relay changes state again instantly. Changing the hysteresis onthe front face does not therefore modify the value of the preset treshold.
When the value of the controlled voltage, AC or DC, reaches the treshold Ue displayed on the front face, the output relay changes state at the end of a time delay T1, which can be set on the front face at between 0.1 and 3s and remains latched in this position.
N
o
Legend
Treshold Ue
Hysteresis
UPPER function
UNDER function
Unit power-up
Controlled voltage
Principles
N
o
Legend
Treshold Ue
Hysteresis
UPPER function
UNDER function
Unit power-up
Controlled voltage
*** TRADUCTION MANQUANTE ***
Dimensions (mm)
EUL / EUH
05/09/2014 www.crouzet.com
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
Page 3
Connections
EUL
Legend
A1 - A2 : Supply voltage
Connections
EUL / EUH
05/09/2014 www.crouzet.com
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
Page 4
N
o
Legend
Supply voltage to be monitored
05/09/2014 www.crouzet.com
Unless otherwise specified, the characteristics given are applicable to all or part of the product range selected
Loading...